Rosemount™ 3051 Pressure Transmitter
and Rosemount 3051CF Series Flow
Meter
with PROFIBUS® PA Protocol
Page 2
Quick Start GuideFebruary 2019
NOTICE
This installation guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof,
Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051 Reference Manual for
more instruction. This manual is also available electronically on EmersonProcess.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices. Review the approvals section of the
Rosemount 3051 Reference Manual for any restrictions associated with a safe installation.
Do not remove the transmitter cover in explosive atmospheres when the circuit is live.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing enclosure use a ½–14 NPT form.
Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Contents
Mount the transmitter................................... 3
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 1-7: Mounting the Transmitter in Liquid Applications
CoplanarIn-line
1.2Mount the transmitter in gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 1-8: Mounting the Transmitter in Gas Applications
Coplanar
Quick Start Guide5
Inline
Page 6
Flow
Flow
Quick Start GuideFebruary 2019
1.3Mount the transmitter in steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 1-9: Mounting the Transmitter in Steam Applications
Coplanar
In-line
1.4Mounting options
Coplanar flange
Panel mount
6Emerson.com/Rosemount
(1)
Pipe mount
Page 7
February 2019Quick Start Guide
Traditional flange
Panel mount
(2)
Rosemount 3051T
Panel mount
(3)
Pipe mount
Pipe mount
(1)
Panel bolts are customer supplied.
(2) Panel bolts are customer supplied.
(3) Panel bolts are customer supplied.
Quick Start Guide7
Page 8
B
4 × 2.88-in. (73 mm)
A
4 × 1.75-in. (44 mm)
C
4 × 1.75-in.
(44 mm)
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in. (44 mm)
4 × 2.25-in. (57 mm)
Quick Start GuideFebruary 2019
1.5Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow these assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 1-10 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
Figure 1-10: Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing
Table 1-1. If bolt material is not shown in Table 1-1, contact a local Emerson
representative for more information.
Procedure
1. Carbon steel bolts do not require lubrication and the stainless steel
bolts are coated with a lubricant to ease installation. However, no
additional lubricant should be applied when installing either type of
bolt.
8Emerson.com/Rosemount
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern.
See Table 1-1 for initial torque value.
Page 9
B7M
316
316
316
SW
316
STM
316
R
B8M
February 2019Quick Start Guide
4. Torque the bolts to the final torque value using the same crossing
pattern. See Table 1-1 for final torque value.
5. Verify the flange bolts are protruding through the isolator plate before
applying pressure.
Example
Table 1-1: Torque Values for the Coplanar Flange and Flange Adapter
Bolts
Bolt materialHead markingsInitial
torque
CS
300 in-lb650 in-lb
SST
150 in-lb300 in-lb
Final
torque
Quick Start Guide9
Page 10
A
B
C
D
Rosemount 3051S/3051/2051
Quick Start GuideFebruary 2019
1.6O-rings with flange adapters
WARNING
Failure to install proper flange adapter O-rings may cause process leaks, which
can result in death or serious injury. The two flange adapters are distinguished
by unique O-ring grooves. Only use the O-ring that is designed for its specific
flange adapter, as shown below.
Figure 1-11: O-ring Location
A. Flange adapter
B. O-ring
C. PFTE-based profile (square)
D. Elastomer profile (round)
Whenever the flanges or adapters are removed, visually inspect the O-rings.
Replace them if there are any signs of damage, such as nicks or cuts. If you
replace the O-rings, re-torque the flange bolts and alignment screws after
installation to compensate for seating of the PTFE O-ring.
1.7
1.8
10Emerson.com/Rosemount
Environmental seal for housing
Thread sealing (PFTE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seals and meets requirements of NEMA
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are
required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
®
Page 11
A
February 2019Quick Start Guide
vent path is between the housing and sensor of the transmitter (see Figure
1-12).
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so that the process can
drain away.
Figure 1-12: In-line Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
Quick Start Guide11
Page 12
A
Quick Start GuideFebruary 2019
2Consider housing rotation
To improve visibility of optional LCD display:
Procedure
1. Loosen the housing rotation screw.
2. First rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to thread limit, rotate the housing
counter clockwise to the desired location (up to 360° from thread
limit).
3. Re-tighten the housing rotation screw (see Figure 2-1).
Figure 2-1: Housing Rotation
A. Housing rotation screw (5/64-in. hex wrench required)
12Emerson.com/Rosemount
Page 13
February 2019Quick Start Guide
3Set jumpers and switches
3.1Security
After the transmitter is configured, you may want to protect the configuration
data from unwarranted changes. Each transmitter is equipped with a security
jumper that can be positioned ON to prevent the accidental or deliberate
change of configuration data. The jumper is labeled “Security”. The security
jumper also prevents changes made using the Local Operator Interface.
3.2Simulate
The simulate jumper is used in conjunction with the analog input (AI) block.
This jumper is used to simulate the pressure measurement and is used as a
lock-out feature for the AI block. to enable the simulate feature, the jumper
must be moved to the “ON” position after power is applied. This feature
prevents the transmitter from being accidentally left in simulate mode.
Figure 3-1: Transmitter Jumper Locations
Quick Start Guide13
Page 14
Quick Start GuideFebruary 2019
4Connect wiring and power up
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the field terminals side.
2. Connect the power leads to the terminals indicated on the terminal
block label.
• Power terminals are polarity insensitive - connect positive or
negative to either terminal.
3. Ensure full contact with Terminal Block screw and washer. When using
a direct wiring method, wrap wire clockwise to ensure it is in place
when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration.
4. Ensure proper grounding. It is important that the instrument cable
shield:
• Be trimmed close and insulated from touching the transmitter
housing
• Be connected to the next shield if cable is routed through a
junction box
• Be connected to a good earth ground at the power supply end
5. Plug and seal unused conduit connections.
6. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and the
transmitter housing.
7. Replace the housing cover.
14Emerson.com/Rosemount
Page 15
A
B
February 2019Quick Start Guide
Example
Figure 4-1: Terminals
A. Power terminals
B. Ground terminal
Note
“NC” is a No Connect terminal (do not use)
Quick Start Guide15
Page 16
B
A
C
DE
G
F
I
I
J
H
Quick Start GuideFebruary 2019
Figure 4-2: Wiring
A. 6234 ft (1900 m) max (depending upon cable characteristics)
B. Integrated power conditioner and filter
C. Terminators
D. Power supply
E. DP/PA coupler/link
F. Trunk
G. DP network
H. Signal wiring
I. Spur
J. PROFIBUS PA device
4.1
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
outside of the electronics housing and inside the terminal compartment.
These grounds are used when transient protect terminal blocks are installed
or to fulfill local regulations. See Step 2 below for more information on how
the cable shield should be grounded.
Procedure
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 4-3. The
cable shield should:
3. Be trimmed close and insulated from touching the transmitter
housing.
4. Continuously connect to the termination point.
16Emerson.com/Rosemount
Page 17
DP
B
A
D
E
A
C
February 2019Quick Start Guide
5. Be connected to a good earth ground at the power supply end.
Figure 4-3: Wiring
A. Minimize distance
B. Trim shield and insulate
C. Ground for transient protection
D. Connect shield back to the power supply ground
E. Insulate shield
6. Replace the housing cover. It is recommended the cover be tightened
until there is no gap between the cover and the housing.
7. Plug and seal unused conduit connections.
4.1.1 Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic
safety and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide
complete functionality.
4.1.2 Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply
filter and decouple the segment from other segments attached to the same
power supply.
4.1.3 Grounding
Signal wiring of the Fieldbus segment cannot be grounded. Grounding out
one of the signal wires will shut down the entire Fieldbus segment.
4.1.4 Shield wire ground
To protect the Fieldbus segment from noise, grounding techniques for shield
wire require a single grounding point for shield wire to avoid creating a
ground loop. Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
Quick Start Guide17
Page 18
Quick Start GuideFebruary 2019
5Basic configuration
5.1Configuration tasks
The transmitter can be configured via either the local operator interface (LOI)
– option code M4, or via a Class 2 Master (DD or DTM™ based). The two basic
configuration tasks for the PROFIBUS PA Pressure transmitter are:
Procedure
1. Assign address.
2. Configure engineering units (scaling).
Note
Rosemount 3051 Profibus Profile 3.02 devices are set to identification
number adaptation mode when shipped from the factory. This mode
allows the transmitter to communicate with any Profibus control host
with either the generic Profile GSD (9700) or Rosemount 3051 specific
GSD (4444) loaded on the host; therefore, it is not required to change
the transmitter identification number at startup.
5.2Assign address
The Rosemount 3051 Pressure Transmitter is shipped with a temporary
address of 126. This must be changed to a unique value between 0 and 125 in
order to establish communication with the host. Usually, addresses 0–2 are
reserved for masters or couplers, therefore transmitter addresses between 3
and 125 are recommended.
Address can be set via either:
• LOI – see Table 5-1 and Figure 5-1
• Class 2 Master – see Class 2 Master manual for setting address
5.3
18Emerson.com/Rosemount
Configure engineering units
Unless otherwise requested, the Rosemount 3051 Pressure Transmitter ships
with the following settings:
• Measurement mode: Pressure
• Engineering units: inches H2O
• Scaling: None
Engineering units should be confirmed or configured before installation. Units
can be configured for Pressure, Flow or Level measurement.
Measurement type, Units, Scaling, and Low Flow Cutoff (when applicable) can
be set via either:
Page 19
February 2019Quick Start Guide
• LOI – see Table 5-1 and Figure 5-1
• Class 2 master – see Table 5-2 for parameter configuration
5.4Configuration tools
5.4.1 Local operator interface (LOI)
When ordered, the LOI can be used for commissioning the device. To activate
the LOI, push either configuration button located under the top tag of the
transmitter. See Table 5-1 and Figure 5-1 for operation and menu
information. The security jumper prevents changes made using the LOI.
Note
Buttons must be fully engaged ≈ 0.5 in. (10mm) of travel.
Table 5-1: LOI Button Operation
ButtonActionNavigationCharacter EntrySave?
ScrollMoves down menu
categories
EnterSelects menu
category
Changes character
(1)
value
Enters character
and advances
Changes between
Save and Cancel
Saves
(1) Characters blink when they can be changed.
Figure 5-1: LOI Menu
5.5
Class 2 Master
The Rosemount 3051 Profibus DD and DTM files are available at
EmersonProcess.com/Rosemount or by contacting your local salesperson.
See Table 5-2 for steps to configure the transmitter for Pressure
Quick Start Guide19
Page 20
Quick Start GuideFebruary 2019
measurement. See the Rosemount 3051 Reference Manual for Flow or Level
configuration instructions.
Table 5-2: Pressure Configuration via Class 2 Master
StepsActions
Set blocks to Out of Service Put Transducer Block into Out of Service mode
Put Analog Input Block into Out of Service mode
Select Measurement TypeSet Primary Value type to Pressure
Select UnitsSet Engineering Units
- Primary and secondary units must match
Enter ScalingSet Scale In in Transducer Block to 0 - 100
Set Scale Out in Transducer Block to 0 - 100
Set PV Scale in Analog Input Block to 0 - 100
Set Out Scale in Analog Input Block to 0 - 100
Set Linearization in Analog Input Block to No
Set blocks to AutoPut Transducer Block into Auto mode
Put Analog Input Block into Auto mode
Linearization
5.5.1 Host integration
Control host (Class 1)
The Rosemount 3051 device utilizes condensed status as recommended by
the Profile 3.02 specification and NE 107. See manual for condensed status bit
assignment information.
The appropriate GSD file must be loaded on the control host - Rosemount
3051 specific (rmt4444.gsd) or Profile 3.02 Generic (pa139700.gsd). These
files can be found on EmersonProcess.com/Rosemount or Profibus.com.
Configuration host (Class 2)
The appropriate DD or DTM file must be installed in the configuration host.
These files can be found at EmersonProcess.com/Rosemount.
20Emerson.com/Rosemount
Page 21
February 2019Quick Start Guide
6Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to
perform a zero trim on the sensor to eliminate error due to mounting position
or static pressure effects.
This can be done by performing a zero trim via:
• LOI – see Table 5-1 and Figure 5-1
• Class 2 master – see Table 5-2 for parameter configuration
6.1Zero trim via Class 2 Master
Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Device Basic Setup > Calibration and set the Lower Calibration
Point to 0.0.
4. Place the transducer block to AUTO mode.
Quick Start Guide21
Page 22
Quick Start GuideFebruary 2019
7Product Certifications
Rev 1.4
7.1European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
7.2Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
7.3North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate:
Standards:
Markings:
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is
0T2H0.AE
FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3810 –
2005, ANSI/NEMA 250 – 2003
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(–
50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
1Q4A4.AX
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 –
2004, FM Class 3810 – 2005
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1
when connected per Rosemount drawing 03031-1019; NI CL 1,
DIV 2, GP A, B, C, D; T4(-50 °C ≤ Ta ≤ +70 °C) [HART], T5(–50 °C
≤ Ta ≤ +40 °C) [HART]; T4(–50 °C ≤ Ta ≤ +60 °C) [Fieldbus/
PROFIBUS]; Type 4x
considered a potential risk of ignition by impact or friction. Care must
be taken into account during installation and use to prevent impact
and friction.
22Emerson.com/Rosemount
Page 23
February 2019Quick Start Guide
2. The Rosemount 3051 Transmitter with the transient terminal block
(Option code T1) will not pass the 500Vrms dielectric strength test
and this must be taken into account during installation.
IE USA FISCO
Certificate:
Standards:
1Q4A4.AX
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 2004, FM Class 3810 - 2005
Markings:
IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount
drawing 03031-1019 (–50 °C ≤ Ta ≤ +60 °C); Type 4x
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is
considered a potential risk of ignition by impact or friction. Care must
be taken into account during installation and use to prevent impact
and friction.
2. The Rosemount 3051 Transmitter with the transient terminal block
(Option code T1) will not pass the 500Vrms dielectric strength test
and this must be taken into account during installation.
C6 Canada Explosionproof, Dust-Ignitionproof, Intrinsic Safety and
Nonincendive
Explosionproof for Class I, Division 1, Groups B, C and D;
Suitable for Class I, Zone 1, Group IIB+H2, T5; DustIgnitionproof Class II, Division 1, Groups E, F, G; Class III
Division 1; Intrinsically Safe Class I, Division 1 Groups A, B, C, D
when connected in accordance with Rosemount drawing
03031-1024, Temperature Code T3C; Suitable for Class I, Zone
0; Class I Division 2 Groups A, B, C and D, T5; Suitable for Class I
Zone 2, Group IIC; Type 4X; Factory Sealed; Single Seal (See
drawing 03031-1053)
E6 Canada Explosionproof, Dust-Ignitionproof and Division 2
1. This device contains a thin wall diaphragm. Installation, maintenance
Explosionproof Class I, Division 1, Groups B, C and D; Suitable
for Class I, Zone 1, Group IIB+H2, T5; Dust-Ignitionproof for
Class II and Class III, Division 1, Groups E, F and G; Class I,
Division 2, Groups A, B, C and D; Suitable for Class I Zone 2,
Group IIC; Type 4X; Factory Sealed; Single Seal (See drawing
03031-1053)
II 1/2 G Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–
50 °C ≤ Ta ≤ +80 °C) II 1 D Ex ta IIIC T95 °C T
105 °C Da (–
500
20°C ≤ Ta ≤ +85°C)
and use shall take into account the environmental conditions to which
the diaphragm will be subjected. The manufacturer’s instructions for
installation and maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the
manufacturer shall be contacted.
3. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
I1 ATEX Intrinsic Safety and Dust
Certificate:
Standards:
Markings:
BAS97ATEX1089X; Baseefa11ATEX0275X
EN60079-0:2012, EN60079-11:2012, EN60079-31:2009
HART: II 1 G Ex ia IIC Ga T4(–60 °C ≤ Ta ≤ +60 °C)
Fieldbus/PROFIBUS: II 1 G Ex ia IIC Ga T4(–60 °C ≤ Ta ≤ +60
°C)
24Emerson.com/Rosemount
Page 25
February 2019Quick Start Guide
DUST: II 1 D Ex ta IIIC T95 °C T
105 °C Da (–20 °C ≤ Ta ≤
500
+85 °C)
Table 7-2: Input Parameters
ParameterHARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
i
i
i
Capacitance C
Inductance L
i
i
30 V30 V
200 mA300 mA
0.9 W1.3 W
0.012 µF0 µF
0 mH0 mH
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test
required by clause 6.3.12 of EN60079-11:2012. This must be taken
into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact or abrasion if located in Zone 0.
3. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
IA ATEX FISCO
Certificate:
Standards:
Markings:
BAS 98ATEX1355X
EN60079-0:2012, EN60079-11:2009
II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 7-3: Input Parameters
ParameterFISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
Quick Start Guide25
17.5 V
380 mA
5.32 W
< 5 nF
< 10 µH
Page 26
Quick Start GuideFebruary 2019
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test
required by clause 6.3.12 of EN60079-11:2012. This must be taken
into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact or abrasion if located in Zone 0.
N1 ATEX Type n and Dust
Certificate:
Standards:
BAS00ATEX3105X; Baseefa11ATEX0275X
EN60079-0:2012, EN60079-15:2010, EN60079-31:2009
Markings:
T95 °C T
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test
that is required by clause 6.8.1 of EN60079-15. This must be taken into
account when installing the apparatus.
2. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–50 °C ≤ Ta ≤
+80 °C); Ex ta IIIC T95 °C T
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C); II 1 D Ex ta IIIC
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
and use shall take into account the environmental conditions to which
the diaphragm will be subjected. The manufacturer’s instructions for
26Emerson.com/Rosemount
Page 27
February 2019Quick Start Guide
installation and maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the
manufacturer shall be contacted.
3. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 09.0076X
IEC60079-0:2011, IEC60079-11:2011
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–60 °C ≤
Ta ≤ +70 °C)
Fieldbus/PROFIBUS: Ex ia IIC T4(–60 °C ≤ Ta ≤ +60 °C)
Table 7-5: Input Parameters
ParameterHARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V30 V
200 mA300 mA
0.9 W1.3 W
0.012 µF0 µF
0 mH0 mH
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
clause 6.3.12 of IEC60079-11. This must be taken into account when
installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
IECEx Mining (Special A0259)
Certificate:
Standards:
Markings:
Quick Start Guide27
IECEx TSA 14.0001X
IEC60079-0:2011, IEC60079-11:2011
Ex ia I Ma (–60 °C ≤ Ta ≤ +70 °C)
Page 28
Quick Start GuideFebruary 2019
Table 7-6: Input Parameters
ParameterHARTFieldbus/
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
30 V30 V17.5 V
200 mA300 mA380 mA
0.9 W1.3 W5.32 W
0.012 µF0 µF< 5 nF
i
0 mH0 mH< 10 µH
PROFIBUS
FISCO
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
IEC60079-11. This must be taken into account when installing the
apparatus.
2. It is a condition of safe use that the above input parameters shall be
taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with
housing, covers and sensor module housing made out of stainless
steel are used in Group I applications
N7 IECEx Type n
Certificate:
Standards:
Markings:
IECEx BAS 09.0077X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test
required by IEC60079-15. This must be taken into account when
installing the apparatus.
Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–50 °C ≤ Ta ≤
+80 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
and use shall take into account the environmental conditions to which
the diaphragm will be subjected. The manufacturer’s instructions for
installation and maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the
dimensions of the flameproof joints.
3. The capacitance of the wrap around label, being 1.6nF, exceeds the
limit in Table 9 of ABNT NBR IEC 60079-0. The user shall determine
suitability for the specific application.
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–60 °C ≤
Ta ≤ +70 °C)
Fieldbus/PROFIBUS: Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 7-7: Input Parameters
ParameterHARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V30 V
200 mA300 mA
0.9 W1.3 W
0.012 µF0 µF
0 mH0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
ABNT NBR IRC 60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
1. If the equipment is fitted with an optional 90V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
ABNT NBR IEC 60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ Ta ≤ +65 °C), T5(-50 °C ≤ Ta ≤
+80 °C)
Special Conditions for Safe Use (X):
1. The relation between ambient temperature arrange and temperature
class is as follows: When used in a combustible dust environment, the
maximum ambient temperature is 80 °C.
30Emerson.com/Rosemount
Page 31
February 2019Quick Start Guide
T
a
–50 °C ≤ Ta ≤ +80 °CT5
–50 °C ≤ Ta ≤ +65 °CT6
Temperature class
When used in a combustible dust environment, the maximum
ambient temperature is 80 °C.
2. The earth connection facility in the enclosure should be connected
reliably.
3. Cable entry certified by notified body with type of protection Ex d IIC in
accordance with GB3836.1-2000 and GB3836.2-2000, should be
applied when installed in a hazardous location. When used in
combustible dust environment, cable entry in accordance with IP66 or
higher level should be applied.
4. Obey the warning “Keep tight when the circuit is alive.”
5. End users are not permitted to change any internal components.
6. During installation, use and maintenance of this product, observe the
following standards: GB3836.13-1997, GB3836.15-2000,
GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007.
1. Symbol “X” is used to denote specific conditions of use:
• If the apparatus is fitted with an optional 90 V transient suppressor,
it is not capable of withstanding the 500 V insulation test for 1
minute. This must be taken into account when installing the
apparatus.
• The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located in Zone 0.
2. The relation between T code and ambient temperature range is:
Model
HARTT5–60 °C ≤ Ta ≤ +40 °C
Quick Start Guide31
T codeTemperature range
Page 32
Quick Start GuideFebruary 2019
ModelT codeTemperature range
HARTT4–60 °C ≤ Ta ≤ +70 °C
Fieldbus/PROFIBUS/
FISCO
T4–60 °C ≤ Ta ≤ +60 °C
3. Intrinsically Safe parameters:
ParameterHARTFieldbus/
Voltage U
Current I
Power P
Capacitance Ci0.012 µF0 µF< 5 nF
Inductance L
i
i
i
30 V30 V17.5 V
200 mA300 mA380 mA
0.9 W1.3 W5.32 W
0 mH0 mH< 10 µH
i
PROFIBUS
FISCO
Note
FISCO parameters apply to both Group IIC and IIB.
Note
[For Flowmeters] When Rosemount 644 Temperature Transmitter is
used, the Rosemount 644 should be used with Ex-certified associated
apparatus to establish explosion protection system that can be used in
explosive gas atmospheres. Wiring and terminals should comply with
the instruction manual of both Rosemount 644 and associated
apparatus. The cables between Rosemount 644 and associated
apparatus should be shielded cables (the cables must have insulated
shield). The shielded cable has to be grounded reliably in a nonhazardous area.
4. Transmitters comply with the requirements for FISCO field devices
specified in IEC60079-27:2008. For the connection of an intrinsically
safe circuit in accordance with FISCO Model, FISCO parameters are
listed in the table above.
5. The product should be used with Ex-certified associated apparatus to
establish explosion protection system that can be used in explosive
gas atmospheres. Wiring and terminals should comply with the
instruction manual of the product and associated apparatus.
6. The cables between this product and associated apparatus should be
shielded cables (the cables must have insulated shield). The shielded
cable has to be grounded reliably in a non-hazardous area.
32Emerson.com/Rosemount
Page 33
February 2019Quick Start Guide
7. End users are not permitted to change any intern components but to
settle the problem in conjunction with the manufacturer to avoid
damage to the product.
8. During installation, use and maintenance of this product, observe the
following standards: GB3836.13-1997, GB3836.15-2000,
GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007
N3 China Type n
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use: The apparatus
is not capable of withstanding the 500 V test to earth for one minute.
The must be taken into consideration during installation.
1. When the thread adapter or blanking plug is used with an enclosure in
type of protection increased safety “e” the entry thread shall be
suitably sealed in order to maintain the ingress protection rating (IP) of
the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric
thread forms. G1/2 thread forms are only acceptable for existing
(legacy) equipment installations.
7.12 Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate:
Intended Use:
09-HS446883A-5-PDA
Marine & Offshore Applications – Measurement of either
gauge or absolute pressure for liquid, gas, and vapor.
SBV Bureau Veritas (BV) Type Approval
Certificate:
BV Rules:
Requirements:
Application:
23155
Bureau Veritas Rules for the Classification of Steel Ships
Bureau Veritas Rules for the Classification of Steel Ships
Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUTIMS; Pressure transmitter type 3051 cannot be installed on
diesel engines
SDN Det Norske Veritas (DNV) Type Approval
Certificate:
Intended Use:
Quick Start Guide35
TAA000004F
DNV GL Rules for Classification – Ships and offshore units
Page 36
Quick Start GuideFebruary 2019
Application:
Location classes
TemperatureD
HumidityB
VibrationA
EMCB
EnclosureD
SLL Lloyds Register (LR) Type Approval
Certificate:
Application:
11/60002
Environmental categories ENV1, ENV2, ENV3, and ENV5
C5 Custody Transfer - Measurement Canada Accuracy Approval
Certificate:
AG-0226; AG-0454; AG-0477
36Emerson.com/Rosemount
Page 37
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 1 of 4
We,
Rosemount, Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
declare under our sole responsibility that the product,
Rosemount 3051 Pressure Transmitters
manufactured by,
Rosemount, Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
to which this declaration relates, is in conformity with the provisions of the European Union
Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Union notified body certification, as shown in the attached
schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
1-Feb-19; Shakopee, MN USA
(date of issue & place)
February 2019Quick Start Guide
7.13 Rosemount 3051 Declaration of Conformity
Figure 7-1: Rosemount 3051 Declaration of Conformity
Quick Start Guide37
Page 38
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 2 of 4
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
DNV GL Business Assurance Italia S.r.l. [Notified Body Number: 0496]
Via Energy Park, 14, N-20871
Vimercate (MB), Italy
Note – equipment manufactured prior to 20 October 2018 may be marked with the previous PED
Notified Body number; previous PED Notified Body information was as follows:
Det Norske Veritas (DNV) [Notified Body Number: 0575]
Veritasveien 1, N-1322
Hovik, Norway
ATEX Notified Bodies
DEKRA [Notified Body Number: 0344]
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Postbank 6794687
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
Quick Start GuideFebruary 2019
40Emerson.com/Rosemount
Page 41
February 2019Quick Start Guide
Quick Start Guide41
Page 42
Quick Start GuideFebruary 2019
42Emerson.com/Rosemount
Page 43
February 2019Quick Start Guide
Quick Start Guide43
Page 44
*00825-0100-4797*
00825-0100-4797, Rev. FD
Quick Start Guide
February 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.