Emerson Rosemount 3051 Series, Rosemount 3051CF Series, 3051T, 3051S Quick Start Manual

Page 1
Quick Start Guide
00825-0100-4797, Rev FD
February 2019
Rosemount™ 3051 Pressure Transmitter and Rosemount 3051CF Series Flow Meter
with PROFIBUS® PA Protocol
Page 2
Quick Start Guide February 2019
NOTICE
This installation guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051 Reference Manual for more instruction. This manual is also available electronically on EmersonProcess.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the
Rosemount 3051 Reference Manual for any restrictions associated with a safe installation.
Do not remove the transmitter cover in explosive atmospheres when the circuit is live.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
Contents
Mount the transmitter................................... 3
Consider housing rotation............................12
Set jumpers and switches.............................13
Connect wiring and power up...................... 14
2 Emerson.com/Rosemount
Basic configuration...................................... 18
Trim the transmitter.................................... 21
Product Certifications.................................. 22
Page 3
February 2019 Quick Start Guide

1 Mount the transmitter

Figure 1-1: Panel Mount Coplanar Flange
5/16 x 1½ panel bolts are customer supplied.
Figure 1-2: Pipe Mount Coplanar Flange
Quick Start Guide 3
Page 4
Quick Start Guide February 2019
Figure 1-3: Panel Mount Traditional Flange
Figure 1-4: Pipe Mount Traditional Flange
Figure 1-5: Panel Mount Rosemount™ 3051T
4 Emerson.com/Rosemount
Page 5
Flow
February 2019 Quick Start Guide
Figure 1-6: Pipe Mount Rosemount 3051T

1.1 Mount the transmitter in liquid applications

Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 1-7: Mounting the Transmitter in Liquid Applications
Coplanar In-line

1.2 Mount the transmitter in gas applications

Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 1-8: Mounting the Transmitter in Gas Applications
Coplanar
Quick Start Guide 5
Inline
Page 6
Flow
Flow
Quick Start Guide February 2019

1.3 Mount the transmitter in steam applications

Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 1-9: Mounting the Transmitter in Steam Applications
Coplanar
In-line

1.4 Mounting options

Coplanar flange
Panel mount
6 Emerson.com/Rosemount
(1)
Pipe mount
Page 7
February 2019 Quick Start Guide
Traditional flange
Panel mount
(2)
Rosemount 3051T
Panel mount
(3)
Pipe mount
Pipe mount
(1)
Panel bolts are customer supplied.
(2) Panel bolts are customer supplied. (3) Panel bolts are customer supplied.
Quick Start Guide 7
Page 8
B
4 × 2.88-in. (73 mm)
A
4 × 1.75-in. (44 mm)
C
4 × 1.75-in.
(44 mm)
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in. (44 mm)
4 × 2.25-in. (57 mm)
Quick Start Guide February 2019

1.5 Bolting considerations

If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 1-10 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
Figure 1-10: Common Transmitter Assemblies
A. Transmitter with coplanar flange B. Transmitter with coplanar flange and optional flange adapters C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the material by viewing the markings on the head of the bolt and referencing
Table 1-1. If bolt material is not shown in Table 1-1, contact a local Emerson
representative for more information.
Procedure
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
8 Emerson.com/Rosemount
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See Table 1-1 for initial torque value.
Page 9
B7M
316
316
316
SW
316
STM
316
R
B8M
February 2019 Quick Start Guide
4. Torque the bolts to the final torque value using the same crossing pattern. See Table 1-1 for final torque value.
5. Verify the flange bolts are protruding through the isolator plate before applying pressure.
Example
Table 1-1: Torque Values for the Coplanar Flange and Flange Adapter Bolts
Bolt material Head markings Initial
torque
CS
300 in-lb 650 in-lb
SST
150 in-lb 300 in-lb
Final torque
Quick Start Guide 9
Page 10
A
B
C D
Rosemount 3051S/3051/2051
Quick Start Guide February 2019

1.6 O-rings with flange adapters

WARNING
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adapter, as shown below.
Figure 1-11: O-ring Location
A. Flange adapter B. O-ring C. PFTE-based profile (square)
D. Elastomer profile (round)
Whenever the flanges or adapters are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the O-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE O-ring.
1.7
1.8
10 Emerson.com/Rosemount

Environmental seal for housing

Thread sealing (PFTE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seals and meets requirements of NEMA Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.

In-line gage transmitter orientation

The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing. The
®
Page 11
A
February 2019 Quick Start Guide
vent path is between the housing and sensor of the transmitter (see Figure
1-12).
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away.
Figure 1-12: In-line Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
Quick Start Guide 11
Page 12
A
Quick Start Guide February 2019

2 Consider housing rotation

To improve visibility of optional LCD display:
Procedure
1. Loosen the housing rotation screw.
2. First rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit).
3. Re-tighten the housing rotation screw (see Figure 2-1).
Figure 2-1: Housing Rotation
A. Housing rotation screw (5/64-in. hex wrench required)
12 Emerson.com/Rosemount
Page 13
February 2019 Quick Start Guide

3 Set jumpers and switches

3.1 Security

After the transmitter is configured, you may want to protect the configuration data from unwarranted changes. Each transmitter is equipped with a security jumper that can be positioned ON to prevent the accidental or deliberate change of configuration data. The jumper is labeled “Security”. The security jumper also prevents changes made using the Local Operator Interface.

3.2 Simulate

The simulate jumper is used in conjunction with the analog input (AI) block. This jumper is used to simulate the pressure measurement and is used as a lock-out feature for the AI block. to enable the simulate feature, the jumper must be moved to the “ON” position after power is applied. This feature prevents the transmitter from being accidentally left in simulate mode.
Figure 3-1: Transmitter Jumper Locations
Quick Start Guide 13
Page 14
Quick Start Guide February 2019

4 Connect wiring and power up

Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the field terminals side.
2. Connect the power leads to the terminals indicated on the terminal block label.
Power terminals are polarity insensitive - connect positive or
negative to either terminal.
3. Ensure full contact with Terminal Block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
4. Ensure proper grounding. It is important that the instrument cable shield:
Be trimmed close and insulated from touching the transmitter
housing
Be connected to the next shield if cable is routed through a
junction box
Be connected to a good earth ground at the power supply end
5. Plug and seal unused conduit connections.
6. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
7. Replace the housing cover.
14 Emerson.com/Rosemount
Page 15
A
B
February 2019 Quick Start Guide
Example
Figure 4-1: Terminals
A. Power terminals B. Ground terminal
Note
“NC” is a No Connect terminal (do not use)
Quick Start Guide 15
Page 16
B
A
C
D E
G
F
I
I
J
H
Quick Start Guide February 2019
Figure 4-2: Wiring
A. 6234 ft (1900 m) max (depending upon cable characteristics) B. Integrated power conditioner and filter C. Terminators
D. Power supply
E. DP/PA coupler/link
F. Trunk G. DP network H. Signal wiring
I. Spur J. PROFIBUS PA device
4.1

Signal wiring grounding

Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations. See Step 2 below for more information on how the cable shield should be grounded.
Procedure
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 4-3. The cable shield should:
3. Be trimmed close and insulated from touching the transmitter housing.
4. Continuously connect to the termination point.
16 Emerson.com/Rosemount
Page 17
DP
B
A
D
E
A
C
February 2019 Quick Start Guide
5. Be connected to a good earth ground at the power supply end.
Figure 4-3: Wiring
A. Minimize distance B. Trim shield and insulate C. Ground for transient protection D. Connect shield back to the power supply ground
E. Insulate shield
6. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing.
7. Plug and seal unused conduit connections.

4.1.1 Power supply

The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide complete functionality.

4.1.2 Power conditioner

A Fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply.

4.1.3 Grounding

Signal wiring of the Fieldbus segment cannot be grounded. Grounding out one of the signal wires will shut down the entire Fieldbus segment.

4.1.4 Shield wire ground

To protect the Fieldbus segment from noise, grounding techniques for shield wire require a single grounding point for shield wire to avoid creating a ground loop. Connect the cable shields for the entire segment to a single good earth ground at the power supply.
Quick Start Guide 17
Page 18
Quick Start Guide February 2019

5 Basic configuration

5.1 Configuration tasks

The transmitter can be configured via either the local operator interface (LOI) – option code M4, or via a Class 2 Master (DD or DTM™ based). The two basic configuration tasks for the PROFIBUS PA Pressure transmitter are:
Procedure
1. Assign address.
2. Configure engineering units (scaling).
Note
Rosemount 3051 Profibus Profile 3.02 devices are set to identification number adaptation mode when shipped from the factory. This mode allows the transmitter to communicate with any Profibus control host with either the generic Profile GSD (9700) or Rosemount 3051 specific GSD (4444) loaded on the host; therefore, it is not required to change the transmitter identification number at startup.

5.2 Assign address

The Rosemount 3051 Pressure Transmitter is shipped with a temporary address of 126. This must be changed to a unique value between 0 and 125 in order to establish communication with the host. Usually, addresses 0–2 are reserved for masters or couplers, therefore transmitter addresses between 3 and 125 are recommended.
Address can be set via either:
LOI – see Table 5-1 and Figure 5-1
Class 2 Master – see Class 2 Master manual for setting address
5.3
18 Emerson.com/Rosemount

Configure engineering units

Unless otherwise requested, the Rosemount 3051 Pressure Transmitter ships with the following settings:
Measurement mode: Pressure
Engineering units: inches H2O
Scaling: None
Engineering units should be confirmed or configured before installation. Units can be configured for Pressure, Flow or Level measurement.
Measurement type, Units, Scaling, and Low Flow Cutoff (when applicable) can be set via either:
Page 19
February 2019 Quick Start Guide
LOI – see Table 5-1 and Figure 5-1
Class 2 master – see Table 5-2 for parameter configuration

5.4 Configuration tools

5.4.1 Local operator interface (LOI)

When ordered, the LOI can be used for commissioning the device. To activate the LOI, push either configuration button located under the top tag of the transmitter. See Table 5-1 and Figure 5-1 for operation and menu information. The security jumper prevents changes made using the LOI.
Note
Buttons must be fully engaged ≈ 0.5 in. (10mm) of travel.
Table 5-1: LOI Button Operation
Button Action Navigation Character Entry Save?
Scroll Moves down menu
categories
Enter Selects menu
category
Changes character
(1)
value
Enters character and advances
Changes between Save and Cancel
Saves
(1) Characters blink when they can be changed.
Figure 5-1: LOI Menu
5.5

Class 2 Master

The Rosemount 3051 Profibus DD and DTM files are available at
EmersonProcess.com/Rosemount or by contacting your local salesperson.
See Table 5-2 for steps to configure the transmitter for Pressure
Quick Start Guide 19
Page 20
Quick Start Guide February 2019
measurement. See the Rosemount 3051 Reference Manual for Flow or Level configuration instructions.
Table 5-2: Pressure Configuration via Class 2 Master
Steps Actions
Set blocks to Out of Service Put Transducer Block into Out of Service mode
Put Analog Input Block into Out of Service mode
Select Measurement Type Set Primary Value type to Pressure
Select Units Set Engineering Units
- Primary and secondary units must match
Enter Scaling Set Scale In in Transducer Block to 0 - 100
Set Scale Out in Transducer Block to 0 - 100
Set PV Scale in Analog Input Block to 0 - 100
Set Out Scale in Analog Input Block to 0 - 100
Set Linearization in Analog Input Block to No
Set blocks to Auto Put Transducer Block into Auto mode
Put Analog Input Block into Auto mode
Linearization

5.5.1 Host integration

Control host (Class 1)
The Rosemount 3051 device utilizes condensed status as recommended by the Profile 3.02 specification and NE 107. See manual for condensed status bit assignment information.
The appropriate GSD file must be loaded on the control host - Rosemount 3051 specific (rmt4444.gsd) or Profile 3.02 Generic (pa139700.gsd). These files can be found on EmersonProcess.com/Rosemount or Profibus.com.
Configuration host (Class 2)
The appropriate DD or DTM file must be installed in the configuration host. These files can be found at EmersonProcess.com/Rosemount.
20 Emerson.com/Rosemount
Page 21
February 2019 Quick Start Guide

6 Trim the transmitter

Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on the sensor to eliminate error due to mounting position or static pressure effects.
This can be done by performing a zero trim via:
LOI – see Table 5-1 and Figure 5-1
Class 2 master – see Table 5-2 for parameter configuration

6.1 Zero trim via Class 2 Master

Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Device Basic Setup > Calibration and set the Lower Calibration Point to 0.0.
4. Place the transducer block to AUTO mode.
Quick Start Guide 21
Page 22
Quick Start Guide February 2019

7 Product Certifications

Rev 1.4

7.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.

7.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

7.3 North America

E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate:
Standards:
Markings:
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is
0T2H0.AE
FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3810 – 2005, ANSI/NEMA 250 – 2003
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(– 50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
1Q4A4.AX
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount drawing 03031-1019; NI CL 1, DIV 2, GP A, B, C, D; T4(-50 °C ≤ Ta ≤ +70 °C) [HART], T5(–50 °C ≤ Ta ≤ +40 °C) [HART]; T4(–50 °C ≤ Ta ≤ +60 °C) [Fieldbus/ PROFIBUS]; Type 4x
considered a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
22 Emerson.com/Rosemount
Page 23
February 2019 Quick Start Guide
2. The Rosemount 3051 Transmitter with the transient terminal block (Option code T1) will not pass the 500Vrms dielectric strength test and this must be taken into account during installation.
IE USA FISCO
Certificate:
Standards:
1Q4A4.AX
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 ­2004, FM Class 3810 - 2005
Markings:
IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 03031-1019 (–50 °C ≤ Ta ≤ +60 °C); Type 4x
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is considered a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
2. The Rosemount 3051 Transmitter with the transient terminal block (Option code T1) will not pass the 500Vrms dielectric strength test and this must be taken into account during installation.
C6 Canada Explosionproof, Dust-Ignitionproof, Intrinsic Safety and Nonincendive
Certificate:
Standards:
1053834
ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987
Markings:
Explosionproof for Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone 1, Group IIB+H2, T5; Dust­Ignitionproof Class II, Division 1, Groups E, F, G; Class III Division 1; Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T3C; Suitable for Class I, Zone 0; Class I Division 2 Groups A, B, C and D, T5; Suitable for Class I Zone 2, Group IIC; Type 4X; Factory Sealed; Single Seal (See drawing 03031-1053)
E6 Canada Explosionproof, Dust-Ignitionproof and Division 2
Certificate:
Standards:
1053834
ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2 No. 213 - M1987
Quick Start Guide 23
Page 24
Quick Start Guide February 2019
Markings:

7.4 Europe

E8 ATEX Flameproof and Dust
Certificate:
Standards:
Markings:
Table 7-1: Process Temperature
Temperature class Process temperature
T6 –50 °C to +65 °C
T5 –50 °C to +80 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
Explosionproof Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone 1, Group IIB+H2, T5; Dust-Ignitionproof for Class II and Class III, Division 1, Groups E, F and G; Class I, Division 2, Groups A, B, C and D; Suitable for Class I Zone 2, Group IIC; Type 4X; Factory Sealed; Single Seal (See drawing 03031-1053)
KEMA00ATEX2013X; Baseefa11ATEX0275X
EN60079-0:2012 + A11:2013, EN60079-1:2007, EN60079-26:2007, EN60079-31:2009
II 1/2 G Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–
50 °C ≤ Ta ≤ +80 °C) II 1 D Ex ta IIIC T95 °C T
105 °C Da (–
500
20°C ≤ Ta ≤ +85°C)
and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
3. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
I1 ATEX Intrinsic Safety and Dust
Certificate:
Standards:
Markings:
BAS97ATEX1089X; Baseefa11ATEX0275X
EN60079-0:2012, EN60079-11:2012, EN60079-31:2009
HART: II 1 G Ex ia IIC Ga T4(–60 °C ≤ Ta ≤ +60 °C) Fieldbus/PROFIBUS: II 1 G Ex ia IIC Ga T4(–60 °C ≤ Ta ≤ +60
°C)
24 Emerson.com/Rosemount
Page 25
February 2019 Quick Start Guide
DUST: II 1 D Ex ta IIIC T95 °C T
105 °C Da (–20 °C ≤ Ta ≤
500
+85 °C)
Table 7-2: Input Parameters
Parameter HART Fieldbus/PROFIBUS
Voltage U
Current I
Power P
i
i
i
Capacitance C
Inductance L
i
i
30 V 30 V
200 mA 300 mA
0.9 W 1.3 W
0.012 µF 0 µF
0 mH 0 mH
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.
3. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
IA ATEX FISCO
Certificate:
Standards:
Markings:
BAS 98ATEX1355X
EN60079-0:2012, EN60079-11:2009
II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 7-3: Input Parameters
Parameter FISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
Quick Start Guide 25
17.5 V
380 mA
5.32 W
< 5 nF
< 10 µH
Page 26
Quick Start Guide February 2019
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.
N1 ATEX Type n and Dust
Certificate:
Standards:
BAS00ATEX3105X; Baseefa11ATEX0275X
EN60079-0:2012, EN60079-15:2010, EN60079-31:2009
Markings:
T95 °C T
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test that is required by clause 6.8.1 of EN60079-15. This must be taken into account when installing the apparatus.
2. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.

7.5 International

E7 IECEx Flameproof and Dust
Certificate:
Standards:
Markings:
Table 7-4: Process Temperature
Temperature class Process temperature
T6 –50 °C to +65 °C
T5 –50 °C to +80 °C
IECEx KEM 09.0034X; IECEx BAS 10.0034X
IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-26:2006, IEC60079-31:2008
Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–50 °C ≤ Ta ≤ +80 °C); Ex ta IIIC T95 °C T
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C); II 1 D Ex ta IIIC
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for
26 Emerson.com/Rosemount
Page 27
February 2019 Quick Start Guide
installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
3. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 09.0076X
IEC60079-0:2011, IEC60079-11:2011
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–60 °C ≤ Ta ≤ +70 °C)
Fieldbus/PROFIBUS: Ex ia IIC T4(–60 °C ≤ Ta ≤ +60 °C)
Table 7-5: Input Parameters
Parameter HART Fieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V 30 V
200 mA 300 mA
0.9 W 1.3 W
0.012 µF 0 µF
0 mH 0 mH
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of IEC60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
IECEx Mining (Special A0259)
Certificate:
Standards:
Markings:
Quick Start Guide 27
IECEx TSA 14.0001X
IEC60079-0:2011, IEC60079-11:2011
Ex ia I Ma (–60 °C ≤ Ta ≤ +70 °C)
Page 28
Quick Start Guide February 2019
Table 7-6: Input Parameters
Parameter HART Fieldbus/
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
30 V 30 V 17.5 V
200 mA 300 mA 380 mA
0.9 W 1.3 W 5.32 W
0.012 µF 0 µF < 5 nF
i
0 mH 0 mH < 10 µH
PROFIBUS
FISCO
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by IEC60079-11. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications
N7 IECEx Type n
Certificate:
Standards:
Markings:
IECEx BAS 09.0077X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by IEC60079-15. This must be taken into account when installing the apparatus.
7.6

Brazil

E2 INMETRO Flameproof
Certificate:
Standards:
UL-BR 13.0643X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-1:2009 + Errata 1:2011, ABNT NBR IEC60079-26:2008 + Errata 1:2008
28 Emerson.com/Rosemount
Page 29
February 2019 Quick Start Guide
Markings:
Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–50 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the dimensions of the flameproof joints.
3. The capacitance of the wrap around label, being 1.6nF, exceeds the limit in Table 9 of ABNT NBR IEC 60079-0. The user shall determine suitability for the specific application.
I2 INMETRO Intrinsic Safety
Certificate:
Standards:
UL-BR 13.0584X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings:
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–60 °C ≤ Ta ≤ +70 °C)
Fieldbus/PROFIBUS: Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 7-7: Input Parameters
Parameter HART Fieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V 30 V
200 mA 300 mA
0.9 W 1.3 W
0.012 µF 0 µF
0 mH 0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by ABNT NBR IRC 60079-11. This must be taken into account when installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
Quick Start Guide 29
Page 30
Quick Start Guide February 2019
IB INMETRO FISCO
Certificate:
Standards:
UL-BR 13.0584X
ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings:
Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 ° C)
Table 7-8: Input Parameters
Parameter FISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
17.5 V
380 mA
5.32 W
< 5 nF
< 10 µH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor, it is not capable of withstanding the 500 V insulation test required by ABNT NBR IEC 60079-11. This must be taken into account when installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
7.7

China

E3 China Flameproof
Certificate:
Standards:
GYJ14.1041X; GYJ15.1368X [Flowmeters]
GB12476-2000; GB3836.1-2010, GB3836.2-2010, GB3836.20-2010
Markings:
Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ Ta ≤ +65 °C), T5(-50 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
1. The relation between ambient temperature arrange and temperature class is as follows: When used in a combustible dust environment, the maximum ambient temperature is 80 °C.
30 Emerson.com/Rosemount
Page 31
February 2019 Quick Start Guide
T
a
–50 °C ≤ Ta ≤ +80 °C T5
–50 °C ≤ Ta ≤ +65 °C T6
Temperature class
When used in a combustible dust environment, the maximum ambient temperature is 80 °C.
2. The earth connection facility in the enclosure should be connected reliably.
3. Cable entry certified by notified body with type of protection Ex d IIC in accordance with GB3836.1-2000 and GB3836.2-2000, should be applied when installed in a hazardous location. When used in combustible dust environment, cable entry in accordance with IP66 or higher level should be applied.
4. Obey the warning “Keep tight when the circuit is alive.”
5. End users are not permitted to change any internal components.
6. During installation, use and maintenance of this product, observe the following standards: GB3836.13-1997, GB3836.15-2000, GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007.
I3 China Intrinsic Safety
Certificate:
Standards:
GYJ13.1362X; GYJ15.1367X [Flowmeters]
GB3836.1-2010, GB3836.4-2010, GB3836.20-2010, GB12476.1-2000
Markings:
Ex ia IIC Ga T4/T5
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use:
If the apparatus is fitted with an optional 90 V transient suppressor,
it is not capable of withstanding the 500 V insulation test for 1 minute. This must be taken into account when installing the apparatus.
The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
2. The relation between T code and ambient temperature range is:
Model
HART T5 –60 °C ≤ Ta ≤ +40 °C
Quick Start Guide 31
T code Temperature range
Page 32
Quick Start Guide February 2019
Model T code Temperature range
HART T4 –60 °C ≤ Ta ≤ +70 °C
Fieldbus/PROFIBUS/ FISCO
T4 –60 °C ≤ Ta ≤ +60 °C
3. Intrinsically Safe parameters:
Parameter HART Fieldbus/
Voltage U
Current I
Power P
Capacitance Ci0.012 µF 0 µF < 5 nF
Inductance L
i
i
i
30 V 30 V 17.5 V
200 mA 300 mA 380 mA
0.9 W 1.3 W 5.32 W
0 mH 0 mH < 10 µH
i
PROFIBUS
FISCO
Note
FISCO parameters apply to both Group IIC and IIB.
Note
[For Flowmeters] When Rosemount 644 Temperature Transmitter is used, the Rosemount 644 should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of both Rosemount 644 and associated apparatus. The cables between Rosemount 644 and associated apparatus should be shielded cables (the cables must have insulated shield). The shielded cable has to be grounded reliably in a non­hazardous area.
4. Transmitters comply with the requirements for FISCO field devices specified in IEC60079-27:2008. For the connection of an intrinsically safe circuit in accordance with FISCO Model, FISCO parameters are listed in the table above.
5. The product should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.
6. The cables between this product and associated apparatus should be shielded cables (the cables must have insulated shield). The shielded cable has to be grounded reliably in a non-hazardous area.
32 Emerson.com/Rosemount
Page 33
February 2019 Quick Start Guide
7. End users are not permitted to change any intern components but to settle the problem in conjunction with the manufacturer to avoid damage to the product.
8. During installation, use and maintenance of this product, observe the following standards: GB3836.13-1997, GB3836.15-2000, GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007
N3 China Type n
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use: The apparatus is not capable of withstanding the 500 V test to earth for one minute. The must be taken into consideration during installation.
GYJ15.1105X
GB3836.1-2010, GB3836.8-2003
Ex nA nL IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)

7.8 Japan

E4 Japan Flameproof
Certificate:
Markings:
TC20577, TC20578, TC20583, TC20584 [HART]; TC20579, TC20580, TC20581, TC20582 [Fieldbus]
Ex d IIC T5

7.9 Technical Regulations Customs Union (EAC)

EM EAC Flameproof
Certificate:
Markings:
RU C-US.GB05.B.01197
Ga/Gb Ex d IIC T5/T6 X, T5(–60 °C ≤ Ta ≤ +80 °C), T6(–60 °C ≤ T ≤ +65 °C)
a
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate:
Markings:
Quick Start Guide 33
RU C-US.GB05.B.01197
HART: 0Ex ia IIC T4/T5 Ga X, T4(–60 °C ≤ Ta ≤ +70 °C), T5(–60 °C ≤ Ta ≤ +40 °C)
Fieldbus/PROFIBUS: 0Ex ia IIC T4 Ga X (–60 °C ≤ Ta ≤ +60 °C)
Page 34
Quick Start Guide February 2019
Special Conditions for Safe Use (X):
1. See certificate for special conditions.

7.10 Combinations

K2 Combination of E2 and I2
K5 Combination of E5 and I5
K6 Combination of C6, E8, and I1
K7 Combination of E7, I7, and N7
K8 Combination of E8, I1, and N1
KB Combination of E5, I5, and C6
KD Combination of E8, I1, E5, I5, and C6
KM Combination of EM and IM

7.11 Conduit Plugs and Adapters

IECEx Flameproof and Increased Safety
Certificate:
Standards:
Markings:
IECEx FMG 13.0032X
IEC60079-0:2011, IEC60079-1:2007, IEC60079-7:2006-2007
Ex de IIC Gb
ATEX Flameproof and Increased Safety
Certificate:
Standards:
Markings:
FM13ATEX0076X
EN60079-0:2012, EN60079-1:2007, IEC60079-7:2007
II 2 G Ex de IIC Gb
Table 7-9: Conduit Plug Thread Sizes
Thread Identification mark
M20 × 1.5 M20
1/2–14 NPT 1/2 NPT
Table 7-10: Thread Adapter Thread Sizes
Male thread Identification mark
M20 × 1.5– 6H M20
1/2–14 NPT 1/2–14 NPT
34 Emerson.com/Rosemount
Page 35
February 2019 Quick Start Guide
Table 7-10: Thread Adapter Thread Sizes (continued)
Male thread Identification mark
3/4–14 NPT 3/4–14 NPT
Female thread Identification mark
M20 × 1.5–6H M20
1/2–14 NPT 1/2–14 NPT
G1/2 G1/2
Special Conditions for Safe Use (X):
1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G1/2 thread forms are only acceptable for existing (legacy) equipment installations.

7.12 Additional Certifications

SBS American Bureau of Shipping (ABS) Type Approval
Certificate:
Intended Use:
09-HS446883A-5-PDA
Marine & Offshore Applications – Measurement of either gauge or absolute pressure for liquid, gas, and vapor.
SBV Bureau Veritas (BV) Type Approval
Certificate:
BV Rules:
Requirements:
Application:
23155
Bureau Veritas Rules for the Classification of Steel Ships
Bureau Veritas Rules for the Classification of Steel Ships
Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT­IMS; Pressure transmitter type 3051 cannot be installed on diesel engines
SDN Det Norske Veritas (DNV) Type Approval
Certificate:
Intended Use:
Quick Start Guide 35
TAA000004F
DNV GL Rules for Classification – Ships and offshore units
Page 36
Quick Start Guide February 2019
Application:
Location classes
Temperature D
Humidity B
Vibration A
EMC B
Enclosure D
SLL Lloyds Register (LR) Type Approval
Certificate:
Application:
11/60002
Environmental categories ENV1, ENV2, ENV3, and ENV5
C5 Custody Transfer - Measurement Canada Accuracy Approval
Certificate:
AG-0226; AG-0454; AG-0477
36 Emerson.com/Rosemount
Page 37
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 1 of 4
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount 3051 Pressure Transmitters
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
1-Feb-19; Shakopee, MN USA
(date of issue & place)
February 2019 Quick Start Guide

7.13 Rosemount 3051 Declaration of Conformity

Figure 7-1: Rosemount 3051 Declaration of Conformity
Quick Start Guide 37
Page 38
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 2 of 4
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
PED Directive (2014/68/EU)
Rosemount 3051CA4; 3051CD2, 3, 4, 5; 3051HD2, 3, 4, 5; (also with P9 option)
QS Certificate of Assessment - Certificate No. 12698-2018-CE-USA-ACCREDIA Module H Conformity Assessment Other Standards Used: ANSI/ISA61010-1:2004
Note – previous PED Certificate No. 59552-2009-CE-HOU-DNV
All other Rosemount 3051 Pressure Transmitters
Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal, Process Flange, or Manifold
Sound Engineering Practice
Rosemount 3051CFx DP Flowmeters
See DSI 1000 Declaration of Conformity
Quick Start Guide February 2019
38 Emerson.com/Rosemount
Page 39
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 3 of 4
ATEX Directive (2014/34/EU)
BAS97ATEX1089X - Intrinsic Safety
Equipment Group II Category 1 G
Ex ia IIC T5/T4 Ga
Harmonized Standards Used:
EN60079-0:2012 + A11:2013, EN60079-11:2012
BAS00ATEX3105X - Type n
Equipment Group II Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards Used:
EN60079-0:2012 + A11:2013, EN60079-15:2010
Baseefa11ATEX0275X - Dust
Equipment Group II Category 1 D
Ex ta IIIC T95°C T
500
105°C Da
Harmonized Standards Used:
EN60079-0:2012 + A11:2013, EN60079-31:2014
KEMA00ATEX2013X - Flameproof
Equipment Group II Category 1/2 G
Ex db IIC T6…T4 Ga/Gb
Harmonized Standards Used:
EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-26:2015
February 2019 Quick Start Guide
Quick Start Guide 39
Page 40
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 4 of 4
PED Notified Body
DNV GL Business Assurance Italia S.r.l. [Notified Body Number: 0496]
Via Energy Park, 14, N-20871 Vimercate (MB), Italy
Note – equipment manufactured prior to 20 October 2018 may be marked with the previous PED Notified Body number; previous PED Notified Body information was as follows: Det Norske Veritas (DNV) [Notified Body Number: 0575] Veritasveien 1, N-1322 Hovik, Norway
ATEX Notified Bodies
DEKRA [Notified Body Number: 0344]
Utrechtseweg 310, 6812 AR Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands Postbank 6794687
SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
Quick Start Guide February 2019
40 Emerson.com/Rosemount
Page 41
February 2019 Quick Start Guide
Quick Start Guide 41
Page 42
Quick Start Guide February 2019
42 Emerson.com/Rosemount
Page 43
February 2019 Quick Start Guide
Quick Start Guide 43
Page 44
*00825-0100-4797*
00825-0100-4797, Rev. FD
Quick Start Guide
February 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRF@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Google.com/+RosemountMeasurement
©
2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...