Rosemount™ 3051 Pressure Transmitter
and Rosemount 3051CF Series
Flowmeters
with FOUNDATION™ Fieldbus Protocol
Page 2
Quick Start GuideFebruary 2019
Safety messages
NOTICE
This guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide instructions
for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or
intrinsically safe (I.S.) installations. Refer to the Rosemount 3051 FOUNDATION Fieldbus Reference
Manual for more instruction. This manual is also available electronically on Emerson.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of the transmitters in a hazardous environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review the
Product Certifications section for any restrictions associated with a safe installation.In Explosion-proof/
Flameproof and Non-Incendive/Type n installations, do not remove the transmitter covers when power
is applied to the unit.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a ½–14 NPT thread form.
Entries marked “M20” are M20 × 1.5 thread form. On devices with multiple conduit entries, all entries
will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread
form when closing these entries.
Contents
System readiness........................................... 3
• Verify the correct device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
• Download the correct device driver at your host vendor download site,
Emerson.com/Rosemount or Fieldbus.org.
1.1.1 Rosemount 3051 device revisions and drivers
Table 1-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1-1: Rosemount 3051 FOUNDATION Fieldbus Device Revisions and
Files
Device
Revision
8AllDD4: DD Rev 1Emerson.comRosemount
7AllDD4: DD Rev 3
HostDevice driver (DD)
(1)
AllDD5: DD Rev 1
EmersonAMS Device Manager
EmersonAMS Device Manager
EmersonField Communicator:
AllDD5: NA
EmersonAMS Device Manager
EmersonAMS Device Manager
EmersonField Communicator:
V 10.5 or higher: DD
Rev 2
V 8 to 10.5: DD Rev 1
DD Rev 2
V 10.5 or higher: DD
Rev 6
V 8 to 10.5: DD Rev 4
DD Rev 6
(2)
Device driver
(DTM)
Document
3051 Pressure
Transmitter
with FOUNDATION
Fieldbus
Reference
Manual
(1) FOUNDATION Fieldbus device revision can be read using a Foundation Fieldbus
capable configuration tool.
(2) Device driver file names use device and DD revision. To access functionality, the
correct device driver must be installed on your control and asset management
hosts, and on your configuration tools.
Quick Start Guide3
Page 4
Start
1. Transmitter
installation
(Section 3)
2. Commissioning
tag
(Section 3.4)
Done
Locate device
7. Zero trim the
transmitter
(Section 5.4)
3. Housing
rotation
(Section 3.5.1)
5. Grounding,
wiring and
power up
(Section 4.6)
6. Configuration
(Section 2.7.1, 2.8)
4. Set switches
and software
write lock
(Section 4.4)
Quick Start GuideFebruary 2019
Figure 1-1: Installation Flowchart
4Emerson.com/Rosemount
Page 5
February 2019Quick Start Guide
2Transmitter installation
2.1Mount the transmitter
For dimensional drawing information refer to the Dimensional Drawings
section of the Rosemount™ 3051 Product Data Sheet.
Figure 2-1: Panel Mount Coplanar Flange
5/16 x 1½ panel bolts are customer supplied.
Quick Start Guide5
Page 6
Quick Start GuideFebruary 2019
Figure 2-2: Pipe Mount Coplanar Flange
Figure 2-3: Panel Mount Traditional Flange
Figure 2-4: Pipe Mount Traditional Flange
6Emerson.com/Rosemount
Page 7
February 2019Quick Start Guide
Figure 2-5: Panel Mount Rosemount™ 3051T
Figure 2-6: Pipe Mount Rosemount 3051T
2.1.1 Mount the transmitter in liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 2-7: Mounting the Transmitter in Liquid Applications
Coplanar
Quick Start Guide7
In-line
Page 8
Flow
Flow
Quick Start GuideFebruary 2019
2.1.2 Mount the transmitter in gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 2-8: Mounting the Transmitter in Gas Applications
CoplanarInline
2.1.3 Mount the transmitter in steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
8Emerson.com/Rosemount
Page 9
Flow
B
4 × 2.88-in. (73 mm)
A
4 × 1.75-in. (44 mm)
C
4 × 1.75-in.
(44 mm)
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in. (44 mm)
4 × 2.25-in. (57 mm)
February 2019Quick Start Guide
Figure 2-9: Mounting the Transmitter in Steam Applications
CoplanarIn-line
2.1.4 Bolting considerations
If the transmitter installation requires assembly of the process flanges,
manifolds, or flange adapters, follow these assembly guidelines to ensure a
tight seal for optimal performance characteristics of the transmitters. Use
only bolts supplied with the transmitter or sold by Emerson as spare parts.
Figure 2-10 illustrates common transmitter assemblies with the bolt length
required for proper transmitter assembly.
Figure 2-10: Common Transmitter Assemblies
A. Transmitter with coplanar flange
B. Transmitter with coplanar flange and optional flange adapters
C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional manifold and flange
adapters
Bolts are typically carbon steel (CS) or stainless steel (SST). Confirm the
material by viewing the markings on the head of the bolt and referencing
Quick Start Guide9
Page 10
B7M
316
316
316
SW
316
STM
316
R
B8M
Quick Start GuideFebruary 2019
Table 2-1. If bolt material is not shown in Table 2-1, contact a local Emerson
representative for more information.
Procedure
1. Carbon steel bolts do not require lubrication and the stainless steel
bolts are coated with a lubricant to ease installation. However, no
additional lubricant should be applied when installing either type of
bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern.
See Table 2-1 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing
pattern. See Table 2-1 for final torque value.
5. Verify the flange bolts are protruding through the isolator plate before
applying pressure.
Example
Table 2-1: Torque Values for the Coplanar Flange and Flange Adapter
Bolts
Bolt materialHead markingsInitial
CS
SST
torque
300 in-lb650 in-lb
150 in-lb300 in-lb
Final
torque
10Emerson.com/Rosemount
Page 11
A
B
C
D
Rosemount 3051S/3051/2051
February 2019Quick Start Guide
2.1.5 O-rings with flange adapters
WARNING
Failure to install proper flange adapter O-rings may cause process leaks, which
can result in death or serious injury. The two flange adapters are distinguished
by unique O-ring grooves. Only use the O-ring that is designed for its specific
flange adapter, as shown below.
Figure 2-11: O-ring Location
A. Flange adapter
B. O-ring
C. PFTE-based profile (square)
D. Elastomer profile (round)
Whenever the flanges or adapters are removed, visually inspect the O-rings.
Replace them if there are any signs of damage, such as nicks or cuts. If you
replace the O-rings, re-torque the flange bolts and alignment screws after
installation to compensate for seating of the PTFE O-ring.
2.1.6 Environmental seal for housing
Thread sealing (PFTE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seals and meets requirements of NEMA
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are
required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
®
2.1.7 In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
Quick Start Guide11
Page 12
A
Quick Start GuideFebruary 2019
vent path is between the housing and sensor of the transmitter (see Figure
2-12).
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so that the process can
drain away.
Figure 2-12: In-line Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
2.1.8 Installing high pressure coned and threaded connection
The transmitter comes with an autoclave connection designed for high
pressure applications. Follow the steps below to properly connect the
transmitter to your process:
Procedure
1. Apply a process-compatible lubricant to the gland nut threads.
2. Slip the gland nut onto the tube, then thread the collar onto the tube
end (the collar is reverse threaded).
3. Apply a small amount of process-compatible lubricant applied to the
tube cone to help prevent galling and facilitate sealing. Insert the
tubing into the connection and tighten finger tight.
4. Tighten the gland nut to a torque of 25 ft-lb.
Note
A weep hole has been designed into the transmitter for safety and leak
detection. If fluid begins to leak from the weep hole, isolate the
process pressure, disconnect the transmitter, and reseal until the leak
is resolved.
12Emerson.com/Rosemount
Page 13
Commissioning Tag
DEVICE ID:
0011513051010001440-12169809172 5
DEVICE REVISION: 7.2
PHYSICAL DEVICE TAG
DEVICE ID:
0011513051010001440-12169809172 5
DEVICE REVISION: 7.2
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A
Commissioning Tag
DEVICE ID:
001151AC00010001440-1216980917 25
DEVICE REVISION: 8.1
PHYSICAL DEVICE TAG
DEVICE ID:
001151AC00010001440-121698091725
DEVICE REVISION: 8.1
S / N :
PHYSICAL DEVICE TAG
Device Barcode
February 2019Quick Start Guide
2.2Tagging
2.2.1 Commissioning (paper) tag
To identify which device is at a particular location, use the removable tag
provided with the transmitter. Ensure the physical device tag (PD tag field) is
properly entered in both places on the removable commissioning tag and tear
off the bottom portion for each transmitter.
Note
The device description loaded in the host system must be at the same revision
as this device; see System readiness.
Figure 2-13: Commissioning Tag
2.3
Quick Start Guide13
Consider housing rotation
A. Device revision
Note
The device description loaded in the host system must be at the same revision
as this device. You can download the device description from the host system
website or Emerson.com/Rosemount by selecting Device Drivers under
Resources. You can also visit Fieldbus.org and select End User Resources.
To improve visibility of optional LCD display:
Procedure
1. Loosen the housing rotation screw.
2. First rotate the housing clockwise to the desired location. If the desired
location cannot be achieved due to thread limit, rotate the housing
Page 14
A
Quick Start GuideFebruary 2019
counter clockwise to the desired location (up to 360° from thread
limit).
3. Re-tighten the housing rotation screw (see Figure 2-14).
Figure 2-14: Housing Rotation
A. Housing rotation screw (5/64-in. hex wrench required)
2.4Set the switches
Set simulate and security switch configuration before installation as shown in
Figure 2-15.
• The simulate switch enables or disables simulated alerts and simulated AI
Block status and values. The default simulate switch position is enabled.
• The security switch allows (unlocked symbol) or prevents (locked symbol)
any configuration of the transmitter.
• Default security is off (unlocked symbol).
• The security switch can be enabled or disabled in software.
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not
remove the instrument cover in explosive atmospheres when the
circuit is live.
3. Slide the security and simulate switches into the preferred position.
4. Replace the housing cover.
14Emerson.com/Rosemount
Page 15
C
A
B
D
E
F
February 2019Quick Start Guide
Note
It is recommended the cover be tightened until there is no gap between the
cover and the housing.
Figure 2-15: Simulate and Security Switches
A. Simulate disabled position
B. Simulate switch
C. Simulate enabled position
D. Security locked position
E. Security switch
F. Security unlocked position
2.5Wire, ground, and power up
Use copper wire of sufficient size to ensure that the voltage across the
transmitter power terminals does not drop below 9 Vdc. Power supply voltage
can be variable, especially under abnormal conditions, such as when
operating on battery backup. Emerson ™ recommends a minimum of 12 Vdc
under normal operating conditions and shielded twisted pair Type A cable.
Procedure
1. To power the transmitter, connect the power leads to the terminals
indicated on the terminal block label.
Quick Start Guide15
Page 16
DP
A
A
D
E
B
C
Quick Start GuideFebruary 2019
Figure 2-16: Wiring Terminals
A. Minimize distance
B. Trim shield and insulate
C. Protective grounding terminal (do not ground cable shield at the
transmitter)
D. Insulate shield
E. Connect shield back to the power supply ground
Note
The Rosemount™ 3051 power terminals are polarity insensitive, which
means the electrical polarity of the power leads does not matter when
connecting to the power terminals. If polarity sensitive devices are
connected to the segment, follow terminal polarity. When wiring to
the screw terminals, Emerson recommends using crimped legs.
2. Ensure full contact with terminal block screw and washer. When using
a direct wiring method, wrap wire clockwise to ensure it is in place
when tightening the terminal block screw.
Note
Emerson does not recommend using a pin or ferrule wire terminal, as
the connection may be more susceptible to loosening over time or
under vibration.
16Emerson.com/Rosemount
Page 17
February 2019Quick Start Guide
2.5.1 Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
outside of the electronics housing and inside the terminal compartment.
These grounds are used when transient protect terminal blocks are installed
or to fulfill local regulations.
Procedure
1. Remove the field terminals housing cover.
a) Trim the cable shield as short as practical and insulate from
touching the transmitter housing.
Note
Do NOT ground the cable shield at the transmitter; if the cable
shield touches the transmitter housing, it can create ground
loops and interfere with communications.
b) Continuously connect the cable shields to the power supply
ground.
c) Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
Note
Improper grounding is the most frequent cause of poor
segment communications.
2. Connect the wiring pair and ground as indicated in Figure 2-16.
3. Replace the housing cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
2.5.2 Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic
safety and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide
complete functionality.
2.5.3 Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply
filter and decouple the segment from other segments attached to the same
power supply.
Quick Start Guide17
Page 18
Quick Start GuideFebruary 2019
2.5.4 Grounding
Signal wiring of the Fieldbus segment cannot be grounded. Grounding out
one of the signal wires will shut down the entire Fieldbus segment.
2.5.5 Shield wire ground
To protect the Fieldbus segment from noise, grounding techniques for shield
wire require a single grounding point for shield wire to avoid creating a
ground loop. Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
2.5.6 Signal termination
For every Fieldbus segment a terminator should be installed at the beginning
and at the end of each segment.
2.5.7 Locating devices
Frequently, different personnel install, configure, and commission devices
over time. A Locate Device capability uses the LCD display (when installed) to
assist personnel in finding the desired device.
From the device Overview screen, select the Locate Device button. This
launches a method allowing you to display a Find me message or enter a
custom message to display on the device LCD display.
When you exit the Locate Device method, the device LCD display
automatically returns to normal operation.
Note
Some hosts do not support Locate Device in the DD.
2.6
Configure
Each Foundation Fieldbus host or configuration tool has a different way of
displaying and performing configurations. Some use device descriptions (DD)
or DD methods for configuration and to display data consistently across
platforms. There is no requirement that a host or configuration tool support
these features. Use the following block examples to do basic configuration to
the transmitter. For more advanced configurations, see the Rosemount 3051
Foundation Fieldbus Reference Manual.
Note
DeltaV™ users should use DeltaV Explorer for the resource and transducer
blocks and control studio for the function blocks.
2.6.1 Configure the AI block
Navigation instructions for each step are provided below. In addition, the
screens used for each step are shown in Figure 2-18.
18Emerson.com/Rosemount
Page 19
Start
Device Configuration
here
1. Verify device tag:
PD_TAG
7. Set damping:
PRIMARY_VALUE_
DAMPING
8. Set up LCD display
6. Set low cutoff:
LOW_CUT
9. Review transmitter
configuration
3. Set signal
conditioning:
L_TYPE
5. Set scaling
OUT_SCALE
2. Check switches and
software write lock
Done
10. Set switches and
software write lock
4. Set scaling
XD_SCALE
February 2019Quick Start Guide
Figure 2-17: Configuration Flowchart
Quick Start Guide19
Page 20
(Overview)
Pressure
Calibration
Device Information
Locate Device
Scale Gauges
(Calibration)
Primary Value
Sensor Trim
Sensor Limits
Restore Factory Calibration
Last Calibration Points
Calibration Details
(Device Information)
Identification
( 1)
Revisions
Materials of Construction
Security & Simulation
(Materials of Construction)
Sensor
Sensor Range
Flange
Remote Seal
(Configure)
Guided Setup
Manual Setup
Alert Setup
(Manual Setup)
Process Variable
Materials of Construction
Display
()
Display Options
Advanced Configuration
(Classic View)( 9 )
View All Parameters
Mode Summary
AI Blocks Channel Mapping
Zero Trim
Change Damping
Local Display Setup
Configure Analog Input Blocks (3, 4, 5, 9)
(8, 9)
(8, 9)
(7, 9)
Class
ic View
Display
(2, 10)
Quick Start GuideFebruary 2019
Figure 2-18: Basic Configuration Menu Tree
2.6.2 Before you begin
A. Standard text – navigation selections available
B. (Text) – name of selection used on parent menu screen to access this
screen
C. Bold text – automated methods
D. Underlined text – configuration task numbers from configuration flow
chart
See Figure 2-17 to graphically view the step by step process for basic device
configuration. Before beginning configuration, you may need to verify the
device tag or deactivate hardware and software write protection on the
transmitter. To do this follow Step 1 and Step 2 below. Otherwise continue at
“AI block configuration”.
Procedure
1. To verify the device tag:
20Emerson.com/Rosemount
Page 21
February 2019Quick Start Guide
a) Navigation: from the Overview screen, select Device
Information to verify the device tag.
2. To check the switches (see Figure 2-15):
a) The write lock switch must be in the unlocked position if the
switch has been enabled in software.
b) To disable the software write lock (devices ship from the
factory with the software write lock disabled):
• Navigation: from the Overview screen, select Device Information
and then select the Security and Simulation tab.
• Perform Write Lock Setup to disable software write lock.
Example
Note
Place the control loop in “Manual” mode before beginning analog input block
configuration.
2.6.3 AI block configuration
To use guided setup:
• Navigate to Configure > Guided Setup.
• Select AI Block Unit Setup.
Note
Guided setup will automatically go through each step in the proper order.
Note
For convenience, AI block 1 is pre-linked to the transmitter primary variable
and should be used for this purpose. AI block 2 is pre-linked to the transmitter
sensor temperature. The channel must be selected for AI blocks 3 and 4.
• Channel 1 is the primary variable.
• Channel 2 is the sensor temperature.
If the Foundation Fieldbus Diagnostics Suite Option Code D01 is enabled,
these additional channels are available.
• Channel 12 is the SPM mean.
• Channel 13 is the SPM standard deviation.
To configure SPM, refer to the Rosemount 3051 Foundation Fieldbus
Reference Manual.
Quick Start Guide21
Page 22
Quick Start GuideFebruary 2019
Note
Step 1 through Step 4 are all performed in a single step by step method under
guided setup, or on a single screen using manual setup.
Note
If the L_TYPE selected in Step 1 is “Direct”, Step 2, Step 3 and Step 4 are not
needed. If the L_TYPE selected is “Indirect”, Step 4 is not needed. Any
unneeded steps will automatically be skipped.
Procedure
1. To select the signal conditioning “L_TYPE” from the drop down menu:
a) Select L_TYPE: Direct for pressure measurements using the
device default units.
b) Select L_TYPE: Indirect for other pressure or level units.
c) Select L_TYPE: Indirect Square Root for flow units.
2. To set XD_SCALE to the 0% and 100% scale points (the transmitter
range):
a) Select the XD_SCALE_UNITS from the drop down menu.
b) Enter the XD_SCALE 0% point. This may be elevated or
suppressed for level applications.
c) Enter the XD_SCALE 100% point. This may be elevated or
suppressed for level applications.
d) If L_TYPE is “Direct”, the AI block may be placed in AUTO mode
to return the device to service. Guided setup does this
automatically.
3. If L_TYPE is “Indirect” or “Indirect Square Root”, set OUT_SCALE to
change engineering units.
a) Select the OUT_SCALE UNITS from the drop down menu.
b) Set the OUT_SCALE low value. This may be elevated or
suppressed for level applications.
c) Set the OUT_SCALE high value. This may be elevated or
suppressed for level applications.
d) If L_TYPE is “Indirect”, the AI Block may be placed in AUTO
mode to return the device to service. Guided setup does this
automatically.
4. If L_TYPE is “Indirect Square Root”, a LOW FLOW CUTOFF function is
available.
a) Enable LOW FLOW CUTOFF.
22Emerson.com/Rosemount
Page 23
February 2019Quick Start Guide
b) Set the LOW_CUT VALUE in XD_SCALE UNITS.
c) The AI block may be placed in AUTO mode to return the device
to service. Guided setup does this automatically.
5. Change damping.
a) To use guided setup:
• Navigate to Configure > Guided Setup.
• Select Change Damping.
Note
Guided setup will automatically go through each step in the
proper order.
• Enter the desired damping value in seconds. The permitted
range of values is 0.4 to 60 seconds.
b) To use manual setup:
• Navigate to Configure > Manual Setup > Process Variable.
• Select Change Damping.
• Enter the desired damping value in seconds. The permitted
range of values is 0.4 to 60 seconds.
6. Configure optional LCD display (if installed).
a) To use guided setup:
• Navigate to Configure > Guided Setup.
• Select Local Display Setup.
Note
Guided setup will automatically go through each step in the
proper order.
• Check the box next to each parameter to be displayed to a
maximum of four parameters. The LCD display will
continuously scroll through the selected parameters.
b) To use manual setup:
• Navigate to Configure > Guided Setup.
• Select Local Display Setup.
• Check each parameter to be displayed. The LCD display will
continuously scroll through the selected parameters.
Quick Start Guide23
Page 24
Quick Start GuideFebruary 2019
7. Review transmitter configuration and place in service.
a) To review the transmitter configuration, navigate using the
manual setup navigation sequences for “AI Block Unit Setup”,
“Change Damping”, and “Set up LCD Display”.
b) Change any values as necessary.
c) Return to the Overview screen.
d) If mode is “Not in Service”, select the Change button, and then
select Return All to Service.
Note
If hardware or software write protection is not needed, Step 8 can be
skipped.
8. Set switches and software write lock.
a) Check switches (see Figure 2-17).
Note
The write lock switch can be left in the locked or unlocked position.
The simulate enable/disable switch may be in either position for
normal device operation.
2.6.4 Enable software write lock
Procedure
1. Navigate from the Overview screen.
a) Select Device Information.
b) Select the Security and Simulation tab.
2. Perform Write Lock Setup to enable software write lock.
2.6.5 AI block configuration parameters
Use the pressure, DP flow, and DP level examples for guides.
Select only the units
that are supported by
the device.
Pabartorr at 0 °Cft H2O at 4°Cm H2O at 4 °C
kPambar kg/cm
2
ft H2O at 60°Fmm Hg at 0
°C
mPapsfkg/m
2
ft H2O at 68°Fcm Hg at 0 °C
hPaAtmin H2O at 4°Cmm H2O at 4°Cin Hg at 0 °C
°Cpsiin H2O at 60°Fmm H2O at
m Hg at 0 °C
68 °C
°Fg/cm2in H2O at 68°Fcm H2O at 4°C
Out_ScaleScale and engineering units
Pressure example
ParametersEnter data
Channel1
L_TypeDirect
XD_ScaleSee list of supported engineering units.
Note
Select only the units that are supported by the device.
Out_ScaleSet values outside operating range.
DP Flow example
Parameters
Channel1
L_TypeSquare root
XD_Scale0–100 inH2O at 68 °F
Enter data
Note
Select only the units that are supported by the device.
Out_Scale0–20 GPM
Low_CutinH2O at 68 °F
Quick Start Guide25
Page 26
Quick Start GuideFebruary 2019
DP Level example
ParametersEnter data
Channel1
L_TypeIndirect
XD_Scale0–300 inH2O at 68 °F
Note
Select only the units that are supported by the device.
Out_Scale0–25 ft.
2.6.6 Display pressure on the LCD display
Procedure
• Select the Pressure check box on the Display Configuration screen.
2.7Zero trim the transmitter
Note
Transmitters are shipped fully calibrated per request or by the factory default
of full scale (span = upper range limit).
A zero trim is a single-point adjustment used for compensating mounting
position and line pressure effects. When performing a zero trim, ensure the
equalizing valve is open and all wet legs are filled to the correct level.
The transmitter will only allow 3–5 percent URL zero error to be trimmed. For
greater zero errors, compensate for the offset by using the XD_Scaling,
Out_Scaling and Indirect L_Type which are part of the AI block.
Procedure
1. To use guided setup:
a) Navigate to Configure > Guided Setup.
b) Select Zero Trim.
c) The method will execute the zero trim.
2. To use manual setup:
a) Navigate to Overview > Calibration > Sensor Trim.
b) Select Zero Trim.
c) The method will execute the zero trim.
26Emerson.com/Rosemount
Page 27
February 2019Quick Start Guide
3Product Certifications
Rev 1.13
3.1European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
3.2Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
3.3North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Range 1–5
Certificate:
Standards:
Markings:
Range 6
Certificate:
Standards:
Markings:
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Range 1–5 (HART)
Certificate:
FM16US0121
FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3810 2005, ANSI/NEMA 250 - 2003
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(–
50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
XP Class I, Division 1, Groups B, C and D, T5, (–50 °C ≤ Ta ≤ +85
°C) Suitable for Class I, Zone 1, Group IIB+H2, T5; DIP Class II
and Class III, Division 1, Groups E, F and G, T5, (–50 °C ≤ Ta ≤
+85 °C); Type 4X; Factory Sealed; Single Seal (See drawing
03031-1053)
FM16US0120X
Quick Start Guide27
Page 28
Quick Start GuideFebruary 2019
Standards:
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008
Markings:
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1
when connected per Rosemount drawing 03031-1019; NI CL 1,
DIV 2, GP A, B, C, D; T4 (–50 °C ≤ Ta ≤ +70 °C) [HART], T5(–50 °C
≤ Ta ≤ +40 °C) [HART]; T4 (–50 °C ≤ Ta ≤ +60 °C) [Foundation
Fieldbus/PROFIBUS®]; Type 4x
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is
considered a potential risk of ignition by impact or friction. Care must
be taken into account during installation and use to prevent impact
and friction.
2. The Rosemount 3051 Transmitter with the transient terminal block
(option code T1) will not pass the 500 Vrms dielectric strength test
and this must be taken into account during installation.
IS Class I, II, III, Division 1 Groups A, B, C, D, E, F, and G when
connected in accordance with Rosemount drawing
03031-1024, Suitable for Class I, Zone 0 Group IIC; Class I,
Division 2, Groups A, B, C and D; NIFW; Suitable for Class I Zone
2, Group IIC; HART: T4 (–60 °C ≤ Ta ≤ +70 °C);T5 (–60 °C ≤ Ta ≤
+40 °C) Foundation Fieldbus/PROFIBUS: T4 (–60 °C ≤ Ta ≤ +60
°C) Type 4X; Factory Sealed; Single Seal (See drawing
03031-1053)
IE USA FISCO
Range 1–5 (HART)
Certificate:
Standards:
FM16US0120X
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 2004, FM Class 3810 - 2005
Markings:
IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount
drawing 03031-1019 (–50 °C ≤ Ta ≤ +60 °C); Type 4x
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Transmitter housing contains aluminum and is
considered a potential risk of ignition by impact or friction. Care must
28Emerson.com/Rosemount
Page 29
February 2019Quick Start Guide
be taken into account during installation and use to prevent impact
and friction.
2. The Rosemount 3051 Transmitter with the transient terminal block
(option code T1) will not pass the 500 Vrms dielectric strength test
and this must be taken into account during installation.
IS Class I, Division 1 Groups A, B, C, D, T4 (–60 °C ≤ Ta ≤ +60 °C)
when connected in accordance with Rosemount drawing
03031-1024, Suitable for Class I, Zone 0 Group IIC; Type 4X;
Factory Sealed; Single Seal (See drawing 03031-1053)
C6 Canada Explosionproof, Dust-Ignitionproof, Intrinsic Safety and
Nonincendive
Explosionproof for Class I, Division 1, Groups B, C and D;
Suitable for Class I, Zone 1, Group IIB+H2, T5 (–50 °C ≤ Ta ≤ +85
°C); Intrinsically Safe Class I, Division 1 Groups A, B, C, D when
connected in accordance with Rosemount drawing
03031-1024, Temperature Code T4; Suitable for Class I, Zone
0; Class I Division 2 Groups A, B, C and D, T5 (–50 °C ≤ Ta ≤ +85
°C); Intrinsically Safe Class I, Division 1 Groups A, B, C, D when
connected in accordance with Rosemount drawing
03031-1024, Temperature Code T4; Suitable for Class I, Zone
0; Class I Division 2 Groups A, B, C and D, T5 (–50 °C ≤ Ta ≤ +85
°C); Suitable for Class I Zone 2, Group IIC; Type 4X; Factory
Sealed; Single Seal (See drawing 03031-1053)
E6 Canada Explosionproof, Dust-Ignitionproof and Division 2
Explosionproof Class I, Division 1, Groups B, C and D; Suitable
for Class I, Zone 1, Group IIB+H2, T5 (–50 °C ≤ Ta ≤ +85 °C);
Dust-Ignitionproof for Class II and Class III, Division 1, Groups E,
Quick Start Guide29
Page 30
Quick Start GuideFebruary 2019
F and G; T5 (–50 °C ≤ Ta ≤ +85 °C); Class I, Division 2, Groups A,
B, C and D; T5 (–50 °C ≤ Ta ≤ +85 °C); Suitable for Class I Zone 2,
Group IIC; Type 4X; Factory Sealed; Single Seal (See drawing
03031-1053)
Ex II 1/2 G Ex db IIC T6…T4 Ga/Gb T6(–60 °C ≤ Ta ≤ +70 °C), T4/
T5(–60 °C ≤ Ta ≤ +80 °C); Ex II 1 D Ex ta IIIC T95 °C T500 105 °C
Da (–20 °C ≤ Ta ≤ +85 °C)
Table 3-1: Process Temperature
Temperature
class
T6–60 °C to +70 °C
T5–60 °C to +80 °C
T4–60 °C to +120 °C
Process
temperature
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
and use shall take into account the environmental conditions to which
the diaphragm will be subjected. The manufacturer's instructions for
installation and maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
HART: Ex II 1 G Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–
60 °C ≤ Ta ≤ +70 °C) Fieldbus/PROFIBUS: Ex II 1 G Ex ia IIC Ga
T4(–60 °C ≤ Ta ≤ +60 °C) DUST: Ex II 1 D Ex ta IIIC T95 °C T
°C Da (–20 °C ≤ Ta ≤ +85 °C)
Table 3-2: Input Parameters
ParameterHARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V30 V
200 mA300 mA
0.9 W1.3 W
0.012 μF0 μF
0 mH0 mH
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test
required by clause 6.3.12 of EN60079-11:2012. This must be taken
into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact or abrasion if located in Zone 0.
500
105
3. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
IA ATEX FISCO
Certificate:
Standards:
Markings:
BAS97ATEX1089X
EN60079-0:2012 + A11:2013, EN60079-11:2012
Ex II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C)
Table 3-3: Input Parameters
ParameterFISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
Quick Start Guide31
i
i
i
i
i
17.5 V
380 mA
5.32 W
≤ 5 nF
≤ 10 μH
Page 32
Quick Start GuideFebruary 2019
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test
required by EN60079-11. This must be taken into account when
installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however care should be taken to protect it
from impact or abrasion if located in Zone 0.
Ex II 3 G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C); Ex II 1 D Ex ta IIIC
T95 °C T
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test
that is required by clause 6.8.1 of EN60079-15. This must be taken into
account when installing the apparatus.
2. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
Ex db IIC T6…T4 Ga/Gb T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–60 °C
≤ Ta ≤ +80 °C); Ex ta IIIC T95 °C T
°C)
105 °C Da (–20 °C ≤ Ta ≤ +85 °C)
500
105 °C Da (–20 °C ≤ Ta ≤ +85
500
Temperature classProcess temperature
T6–60 °C to +70 °C
T5–60 °C to +80 °C
T4–60 °C to +80 °C
32Emerson.com/Rosemount
Page 33
February 2019Quick Start Guide
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance
and use shall take into account the environmental conditions to which
the diaphragm will be subjected. The manufacturer's instructions for
installation and maintenance shall be followed in detail to assure
safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 09.0076X
IEC60079-0:2011, IEC60079-11:2011
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–60 °C ≤
Ta ≤ +70 °C) Fieldbus/PROFIBUS: Ex ia IIC Ga T4(–60 °C ≤ Ta ≤
+60 °C)
Table 3-5: Input Parameter
ParameterHARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
30 V30 V
200 mA300 mA
0.9 W1.3 W
0.012 μF0 μF
i
0 mH0 mH
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
clause 6.3.12 of IEC60079-11. This must be taken into account when
installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
Quick Start Guide33
Page 34
Quick Start GuideFebruary 2019
IECEx Mining (Special A0259)
Certificate:
Standards:
Markings:
IECEx TSA 14.0001X
IEC60079-0:2011, IEC60079-11:2011
Ex ia I Ma (–60 °C ≤ Ta ≤ +70 °C)
Table 3-6: Input Parameter
ParameterHARTFieldbus/PROFIBUSFISCO
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V30 V17.5 V
200 mA300 mA380 mA
0.9 W1.3 W5.32 W
0.012 μF0 μF< 5 nF
0 mH0 mH< 10 μH
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is
not capable of withstanding the 500 V insulation test required by
IEC60079-11. This must be taken into account when installing the
apparatus.
2. It is a condition of safe use that the above input parameters shall be
taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with
housing, covers and sensor module housing made out of stainless
steel are used in Group I applications.
IG IECEx FISCO
Certificate:
Standards:
IECEx BAS 09.0076X
IEC60079-0:2011, IEC60079-11:2011
Special Conditions for Safe Use (X):
Table 3-7: Input Parameter
ParameterFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
34Emerson.com/Rosemount
i
i
i
i
i
17.5 V
380 mA
5.32 W
≤ 5 nF
≤ 10 μH
Page 35
February 2019Quick Start Guide
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with an optional 90V transient suppressor, it is
not capable of withstanding the 500V insulation test required by
clause 6.3.12 of IEC 60079-11. This must be taken into account when
installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
N7 IECEx Type n
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500V insulation test
3.6Brazil
E2 INMETRO Flameproof
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness
IECEx BAS 09.0077X
IEC60079-0:2011, IEC60079-15:2010
Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
required by clause 6.5.1 of IEC 60079-15. This must be taken into
account when installing the apparatus.
Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–60 °C
≤ Ta ≤ +80 °C)
that forms a boundary between zone 0 (process connection) and zone
1 (all other parts of the equipment). The model code and datasheet
are to be consulted for details of the diaphragm material. Installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragm will be subjected. The
manufacturer's instructions for installation and maintenance shall be
followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
Quick Start Guide35
Page 36
Quick Start GuideFebruary 2019
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
HART: Ex ia IIC T5/T4 Ga, T5(–60 °C ≤ Ta ≤ +40 °C), T4(–60 °C ≤
Ta ≤ +70 °C) Fieldbus/PROFIBUS: Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤
+60 °C)
Table 3-8: Input Parameter
ParameterHARTFieldbus/PROFIBUS
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
30 V30 V
200 mA300 mA
0.9 W1.3 W
0.012 μF0 μF
0 mH0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
ABNT NBR IRC 60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and given protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if equipment requires EPL Ga.
1. If the equipment is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test required by
ABNT NBR IEC 60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and given protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if equipment requires EPL Ga.
Ex d IIC T6/T5 Ga/Gb, T6(–50 °C ≤ Ta ≤ +65 °C), T5(–50 °C ≤ Ta ≤
+80 °C)
Special Conditions for Safe Use (X):
1. The relation between ambient temperature arrange and temperature
class is as follows: When used in a combustible dust environment, the
maximum ambient temperature is 80 °C.
T
a
–50 °C~+80 °CT5
–50 °C~+65 °CT6
Temperature class
2. The earth connection facility in the enclosure should be connected
reliably.
3. Cable entry certified by notified body with type of protection Ex d IIC in
accordance with GB3836.1-2000 and GB3836.2-2000, should be
applied when installed in a hazardous location. When used in
Quick Start Guide37
Page 38
Quick Start GuideFebruary 2019
combustible dust environment, cable entry in accordance with IP66 or
higher level should be applied.
4. Obey the warning “Keep tight when the circuit is alive.”
5. End users are not permitted to change any internal components.
6. During installation, use and maintenance of this product, observe the
following standards: GB3836.13-1997, GB3836.15-2000,
GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007
1. Symbol “X” is used to denote specific conditions of use:
2. If the apparatus is fitted with an optional 90 V transient suppressor, it
is not capable of withstanding the 500 V insulation test for 1 minute.
This must be taken into account when installing the apparatus.
3. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in Zone 0.
4. The relation between T code and ambient temperature range is:
Model
HARTT5–60 °C ≤ Ta ≤ +40 °C
HARTT4–60 °C ≤ Ta ≤ +70 °C
Fieldbus/PROFIBUS/FISCOT4–40 °C ≤ Ta ≤ +60 °C
T codeTemperature range
5. Intrinsically Safe parameters:
Parameter
Voltage U
Current I
Power P
Capacitance C
Inductance L
38Emerson.com/Rosemount
i
i
i
i
i
HARTFieldbus/PROFIBUSFISCO
30 V30 V17.5 V
200 mA300 mA380 mA
0.9 W1.3 W5.32 W
0.012 μF0 μF< 5 nF
0 mH0 mH< 10 μH
Page 39
February 2019Quick Start Guide
Note
FISCO parameters apply to both Group IIC and IIB. [For Flowmeters]
When Rosemount 644 Temperature Transmitter is used, the
transmitter should be used with Ex-certified associated apparatus to
establish explosion protection system that can be used in explosive
gas atmospheres. Wiring and terminals should comply with the
instruction manual of both Rosemount 644 and associated apparatus.
The cables between Rosemount 644 and associated apparatus should
be shielded cables (the cables must have insulated shield). The
shielded cable has to be grounded reliably in a non-hazardous area.
6. Transmitters comply with the requirements for FISCO field devices
specified in IEC60079-27:2008. For the connection of an intrinsically
safe circuit in accordance with FISCO Model, FISCO parameters are
listed in the table above.
7. The product should be used with Ex-certified associated apparatus to
establish explosion protection system that can be used in explosive
gas atmospheres. Wiring and terminals should comply with the
instruction manual of the product and associated apparatus.
8. The cables between this product and associated apparatus should be
shielded cables (the cables must have insulated shield). The shielded
cable has to be grounded reliably in a non-hazardous area.
9. End users are not permitted to change any intern components but to
settle the problem in conjunction with the manufacturer to avoid
damage to the product.
10. During installation, use and maintenance of this product, observe the
following standards: GB3836.13-1997, GB3836.15-2000,
GB3836.16-2006, GB50257-1996, GB12476.2-2006, GB15577-2007
N3 China Type n
Certificate:
Standards:
Markings:
GYJ15.1105X
GB3836.1-2010, GB3836.8-2003
Ex nA nL IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use: The apparatus
is not capable of withstanding the 500 V test to earth for one minute.
The must be taken into consideration during installation.
1. When the thread adapter or blanking plug is used with an enclosure in
type of protection increased safety “e” the entry thread shall be
suitably sealed in order to maintain the ingress protection rating (IP) of
the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric
thread forms. G1/2 thread forms are only acceptable for existing
(legacy) equipment installations.
3.13 Additional Certifications
SBS Americaan Bureau of Shipping (ABS) Type Approval
Certificate:
Intended:
09-HS446883A-5-PDA
Marine & Offshore Applications — Measurement of either
gauge or absolute pressure for liquid, gas, and vapor.
SBV Bureau Veritas (BV) Type Approval
Certificate:
Requirements:
Application:
23155
Bureau Veritas Rules for the Classification of Steel Ships
Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUTIMS; Pressure transmitter type 3051 cannot be installed on
diesel engines
SDN Det Norske Veritas (DNV) Type Approval
Certificate:
Intended Use:
Application:
42Emerson.com/Rosemount
TAA000004F
DNV GL Rules for Classification — Ships and offshore units
Location classes
TemperatureD
Page 43
February 2019Quick Start Guide
Location classes
HumidityB
VibrationA
EMCB
EnclosureD
SLL Lloyds Register (LR) Type Approval
Certificate:
Application:
11/60002
Environmental categories ENV1, ENV2, ENV3, and ENV5
C5 Custody Transfer - Measurement Canada Accuracy Approval
Certificate:
AG-0226; AG-0454; AG-0477
Quick Start Guide43
Page 44
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 1 of 4
We,
Rosemount, Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
declare under our sole responsibility that the product,
Rosemount 3051 Pressure Transmitters
manufactured by,
Rosemount, Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
to which this declaration relates, is in conformity with the provisions of the European Union
Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Union notified body certification, as shown in the attached
schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
1-Feb-19; Shakopee, MN USA
(date of issue & place)
Quick Start GuideFebruary 2019
3.14 Declaration of Conformity
44Emerson.com/Rosemount
Page 45
EU Declaration of Conformity
No: RMD 1017 Rev. AC
Page 2 of 4
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
DNV GL Business Assurance Italia S.r.l. [Notified Body Number: 0496]
Via Energy Park, 14, N-20871
Vimercate (MB), Italy
Note – equipment manufactured prior to 20 October 2018 may be marked with the previous PED
Notified Body number; previous PED Notified Body information was as follows:
Det Norske Veritas (DNV) [Notified Body Number: 0575]
Veritasveien 1, N-1322
Hovik, Norway
ATEX Notified Bodies
DEKRA [Notified Body Number: 0344]
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Postbank 6794687
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
ATEX Notified Bod y for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
February 2019Quick Start Guide
Quick Start Guide47
Page 48
Quick Start GuideFebruary 2019
48Emerson.com/Rosemount
Page 49
February 2019Quick Start Guide
Quick Start Guide49
Page 50
Quick Start GuideFebruary 2019
50Emerson.com/Rosemount
Page 51
February 2019Quick Start Guide
Quick Start Guide51
Page 52
*00825-0200-4774*
00825-0200-4774, Rev. CA
Quick Start Guide
February 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.