MN04004002EFor more information visit: www.EatonElectrical.com
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Important Notice – Please Read
The product discussed in this literature is subject to terms and conditions outlined in Eaton
Electrical Inc. selling policies. The sole source governing the rights and remedies of any
purchaser of this equipment is the relevant Eaton Electrical Inc. selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION,
RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton
Electrical Inc. be responsible to the purchaser or user in contract, in tort (including
negligence), strict liability or otherwise for any special, indirect, incidental or consequential
damage or loss whatsoever, including but not limited to damage or loss of use of equipment,
plant or power system, cost of capital, loss of power, additional expenses in the use of
existing power facilities, or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations and descriptions contained herein.
The information contained in this manual is subject to change without notice.
®
Cover Photo: Cutler-Hammer
SPI9000 Inverter Unit.
MN04004002EFor more information visit: www.EatonElectrical.com
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Safety
Definitions and Symbols
This symbol indicates high voltage. It calls your attention to items
or operations that could be dangerous to you and other persons
operating this equipment. Read the message and follow the
instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with either of
two signal words: CAUTION or WARNING, as described below.
SPI9000 Inverter Unit FI9 – FI14 User Manual
WARNING
WARNING
Indicates a potentially hazardous situation which, if not avoided,
can result in serious injury or death.
Indicates a potentially hazardous situation which, if not avoided,
can result in minor to moderate injury, or serious damage to the
product. The situation described in the CAUTION may, if not
avoided, lead to serious results. Important safety measures are
described in CAUTION (as well as WARNING).
Hazardous High Voltage
Motor control equipment and electronic controllers are connected
to hazardous line voltages. When servicing drives and electronic
controllers, there may be exposed components with housings or
protrusions at or above line potential. Extreme care should be taken
to protect against shock.
Stand on an insulating pad and make it a habit to use only one
hand when checking components. Always work with another
person in case an emergency occurs. Disconnect power before
checking controllers or performing maintenance. Be sure
equipment is properly grounded. Wear safety glasses whenever
working on electronic controllers or rotating machinery.
WARNING
CAUTION
WARNING
MN04004002EFor more information visit: www.EatonElectrical.com
v
SPI9000 Inverter Unit FI9 – FI14 User Manual
Warnings, Cautions and Notices
September 2006
Warnings
Read this manual thoroughly and make sure you understand the procedures before you
attempt to install, set up, or operate this Cutler-Hammer
electrical business.
®
SPI9000 Inverter Unit from Eaton’s
WARNING
Only a competent electrician may carry out the electrical
installation.
WARNING
The components of the power unit of the inverter are live when the
SPI9000 inverter is connected to DC supply. Coming into contact
with this voltage is extremely dangerous and may cause death or
severe injury. The control unit is isolated from mains potential.
WARNING
The supply and motor terminals are live when the inverter is
connected to DC supply, even if the motor is not running.
WARNING
The control I/O-terminals are isolated from the mains potential.
However, the relay outputs and other I/O-terminals may have
dangerous control voltage present even when the inverter unit is
disconnected from the DC supply.
WARNING
The inverter has a large capacitive leakage current.
WARNING
If the inverter is used as a part of a machine, the machine
manufacturer is responsible for providing the machine with a main
switch (EN 60204-1).
WARNING
Only spare parts delivered by Eaton can be used.
vi
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Cautions
SPI9000 Inverter Unit FI9 – FI14 User Manual
CAUTION
The SPI9000 inverter is meant for fixed installations only.
CAUTION
Do not perform any measurements when the inverter is connected
to the DC supply.
CAUTION
After having disconnected the inverter from the DC supply, wait
until the fan stops and the indicators on the keypad go out (if no
keypad is attached see the indicator through the keypad base). Wait
5 more minutes before doing any work on inverter connections. Do
not even open the cover before this time has expired.
CAUTION
Do not perform any voltage withstand tests on any part of inverter.
There is a certain procedure according to which the tests shall be
performed. Ignoring this procedure may result in damaged
product.
CAUTION
Prior to measurements on the motor or the motor cable, disconnect
the motor cable from the inverter.
CAUTION
Do not touch the components on the circuit boards. Static voltage
discharge may damage the components.
CAUTION
Before connecting the inverter to DC supply, make sure that the
inverter front and cable covers are closed.
CAUTION
Ensure that the jumper positions are correct. Running the motor
with signal settings that differ from the jumper positions will not
harm the inverter but may harm the motor.
MN04004002EFor more information visit: www.EatonElectrical.com
vii
SPI9000 Inverter Unit FI9 – FI14 User Manual
Grounding and ground fault protection
The SPI9000 inverter must always be grounded with a ground conductor connected to the
ground terminal.
The ground fault protection inside the inverter only protects the inverter against ground
faults in the motor or the motor cable.
Due to the high capacity currents present in the inverter, fault current protective switches
may not function properly. If fault current protective switches are used, they need to be
tested with ground fault currents present during possible fault situations.
Motor and Equipment Safety
Before starting the motor, check that the motor is mounted properly
and ensure that the machine connected to the motor allows the
motor to be started.
CAUTION
September 2006
CAUTION
Set the maximum motor speed (frequency) according to the motor
and the machine connected to it.
CAUTION
Before reversing the motor, make sure that this can be done safely.
CAUTION
Make sure that no power correction capacitors are connected to the
motor cable.
CAUTION
Make sure that the motor terminals are not connected to mains
potential.
viii
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Chapter 1 — Overview
Receiving and Inspection
Cutler-Hammer
scrupulous tests and quality checks at the factory before they are delivered to the customer.
However, after unpacking the product, check that no sign of transportation damage is to be
found on the product and that the delivery is complete (compare the type designation of the
product to the code below, see Table 1-1).
If the drive has been damaged during shipping, please contact the cargo insurance company
or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
Table 1-1: FI9 – FI14 Inverter Unit Catalog Numbering System
®
SPI9000 Inverter Units from Eaton’s electrical business have undergone
For more information visit: www.EatonElectrical.com
1-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Standard Features of SPI Inverter Units
●
Air cooling
Standard board
●
●
Alphanumeric control panel with fiber connection
●
EMC Class T (EN 61800-3 for IT networks)
Safety CE / UL
●
●External charging required
●I/O Modules A1 and A2
●IP00
Storage
If the inverter is to be stored before use, make sure that the ambient conditions are
acceptable.
September 2006
Storage temperature: -40 to 158°F (-40 to 70°C)
Relative humidity:<95%, no condensation
If the inverter is stored for over 12 months, contact Eaton before connecting the inverter to
the power supply.
Maintenance
In normal conditions, Cutler-Hammer inverters are maintenance-free. However, we
recommend cleaning the heatsink with compressed air whenever necessary. The cooling fan
can easily be changed if required.
It may also be necessary to check the tightening torques of terminals at certain intervals.
Technical Data
Figure 1-1 presents the block diagram of the SPI9000 inverter. The inverter mechanically
consists of two units, the Power Unit and the Control Unit.
The Power Unit contains an inverter bridge which consists of IGBT switches and produces
symmetrical, three-phase PWM-modulated AC voltage to the motor.
The Motor and Application Control Block is based on microprocessor software. The
microprocessor controls the motor based on the information it receives through
measurements, parameter settings, control I/O and the control keypad. The motor and
application control block control the motor control ASIC which, in turn, calculates the IGBT
positions. Gate drivers amplify these signals for driving the IGBT inverter bridge.
1-2
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
+
B
SPI9000 Inverter Unit FI9 – FI14 User Manual
Power Module
U
IGBT
Bridge
–
B
Keypad
Power
Supply
Fan
Control Module
RS-232
I/O
Slot A
Measurements
I/O
Slot B
ASIC
Control
I/O
Slot C
Driver
I/O
Slot D
I/O
Slot E
V
W
MN04004002E
Figure 1-1: SPI9000 Inverter Unit Block Diagram
The control keypad constitutes a link between the user and the inverter. The control keypad is
used for parameter setting, reading status data and giving control commands. It is
detachable and can be operated externally and is connected via a cable to the inverter.
Instead of the control keypad, a PC can be used to control the inverter if connected through a
similar cable.
The basic control interface and the parameters (the Basic Application) are easy to use. If a
more versatile interface or parameters are required, a more suitable application can be
chosen. See the application manual for more information on the different applications.
Optional I/O expander boards that increase the number of inputs and outputs to be used are
also available. For more information, contact Eaton.
For more information visit: www.EatonElectrical.com1-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
Power Ratings
Supply Voltage 465 – 800V DC, Motor Voltage 380 – 500V AC
High overload = Maximum current IS, 2 sec./20 sec., 150% overloadability, 1 min./10 min.
Following continuous operation at rated output current, 150% rated output current (IH) for
1 min, followed by a period of load current less than rated current, and of such duration that
the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Maximum current IS, 2 sec./20 sec., 110% overloadability, 1 min./10 min.
Following continuous operation at rated output current, 110% rated output current (IL) for
1 min, followed by a period of load current less than rated current, and of such duration that
the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is
equal to or less than the factory default.
1-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Supply Voltage 640 – 1100V DC, Motor Voltage 525 – 690V AC
High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min
Following continuous operation at rated output current, 150% rated output current (IH) for 1
min, followed by a period of load current less than rated current, and of such duration that
the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min
Following continuous operation at rated output current, 110% rated output current (IL) for 1
min, followed by a period of load current less than rated current, and of such duration that
the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
Air Quality:
– Chemical Vapors
– Mechanical Particles
Altitude100% load capacity (no derating) up to 1,000m
in
in
September 2006
465 – 800V DC; 380 – 500V AC (-0%. to +0%)
640 – 1100V DC; 525 – 690V AC (-0% to +0%)
The waviness of the inverter supply voltage, which is formed in
rectification of the electric network’s alternating voltage in basic
frequency, must be less than 50V peak-to-peak.
500V inverters: 911V DC; 690V inverters: 1200V DC
500V inverters: 333V DC; 690V inverters: 460V DC
protected.
Ye s
MN04004002E
For more information visit: www.EatonElectrical.com1-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 1-5: DC Currents for 465 – 800V DC Supply Voltage
StructureInom (Output)Motor COSIDC (Input)
FI9261.89304
FI10385.9454
FI12590.9695
FI131150.911370
FI141770.922132
Table 1-6: DC Currents for 640 – 1100V DC Supply Voltage
StructureInom (Output)Motor COSIDC (Input)
September 2006
300.89350
460.9542
520.9613
650.9766
730.91870
820.91977
920.911096
1030.911227
1300.911549
1450.911727
2150.922590
2700.923252
FI9125.89 146
144.89 168
170.89 198
208.9 245
FI10261.9 308
325.9 383
385.9 454
416.9 490
F12460.91 548
502.91 598
590.91 703
650.91 774
750.91 894
820.91 977
FI13920.911096
1030.911227
1180.921421
FI141500.921807
1900.932313
2250.932739
1-8For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Chapter 2 — Mounting
Dimensions
The inverter can be mounted in a vertical position on the back plane of a cubicle. Enough
space must be reserved around the inverter to ensure sufficient cooling, see Figure 2-5. You
must follow the minimum dimensions for installation, see Tables 2-5 and 2-6. Also make sure
that the mounting plane is relatively even. The inverter is fixed with four screws (or bolts,
depending on the unit size). The following pages show the dimensions for the IP00 power
module.
SPI9000 Inverter Unit FI9 – FI14 User Manual
W1D1
H2
H1
Dia. 1
Dia. 2
D3D3
D4
D3
D2
W2 W2
FrontSide
TopBottom
H3
Figure 2-1: SPI9000 FI9 Inverter Dimensions
MN04004002E
Table 2-1: SPI9000 FI9 Inverter Dimensions
Approximate Dimensions in Inches (mm)
InvertersVoltage
SPI100 – 170 480V/575V 9.41
W1W2H1H2H3D1D2D3D4Dia. 1 Dia. 2
3.94
(239)
(100)
For more information visit: www.EatonElectrical.com2-1
40.63
(1032)
37.40
(950)
2.46
(62.5)
15.20
(386)
2.12
(53.9)
5.51
(140)
6.03
(153.1)
.18
(4.6)
.37
(9.5)
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
W1D1
W2
H1
H2
Dia.
Figure 2-2: SPI9000 FI10 Inverter Dimensions
Table 2-2: SPI9000 FI10 Inverter Dimensions
Approximate Dimensions in Inches (mm)
InvertersVoltage
SPI208 – 325 480V/575V 9.4
W1W2H1H2H3D1D2D3Dia.
(239)
7.9
(200)
41.3
(1050)
D3
D2
D2
37.5
(952)
TopBottom
H3
2.4
(60.5)
22.3
(566)
9.1
(230)
1.6
(41)
.37
(9.5)
FrontSide
2-2For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Dia.
D1
D2
D3
W3
W1
W2W2
H1
H2
FrontSide
H3
MN04004002E
Figure 2-3: SPI9000 FI12 Inverter Dimensions
Table 2-3: SPI9000 FI12 Inverter Dimensions
Approximate Dimensions in Inches (mm)
InvertersVoltage
SPI385 – 650 480V18.8
W1W2W3H1H2H3D1D2D3Dia.
7.9
(478)
For more information visit: www.EatonElectrical.com2-3
(200)
1.1
(28)
D2
41.3
(1050)
37.5
(952)
TopBottom
2.4
(60.5)
22.3
(566)
9.1
(230)
1.6
(41)
.37
(9.5)
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Dia.
D1
D2
W1
W2
H1
H2
H3
FrontSide
D3
D5
Fan Cooling
Frames FI9 to FI14
D4
D3
TopBottom
Figure 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13)
Table 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13)
Approximate Dimensions in Inches (mm)
InvertersVoltage
SPI820 – H10 480V27.9
W1W2H1H2H3D1D2D3D4D5Dia.
(708)
26.7
(677)
41.5
(1055)
37.4
(950)
2.46
(62.5)
22.3
(566)
1.1
(27)
1.6
(40)
9.6
(245)
5.9
(150)
.37
(9.5)
Enough free space must be left around the inverter to ensure sufficient air circulation and
cooling. You will find the required dimensions for free space Table 2-5.
If several units are mounted on top of each other, the required free space equals 2 * C (see
Figure 2-5). Moreover, the outlet air used for cooling by the lower unit must be directed away
from the air intake of the upper unit. When planning the cooling for the space, take into
consideration that the inverter’s heat loss is 2.5% of the nominal capacity.
2-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
B
FI9/FI10
SPI9000 Inverter Unit FI9 – FI14 User Manual
A
2
FI12
FI13
B
C
Figure 2-5: Installation Space
MN04004002E
For more information visit: www.EatonElectrical.com2-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 2-5: Mounting Space Requirements
FrameVoltage
September 2006
Approximate Dimensions in Inches (mm)
ABB2C
FI9380 – 500V
FI10380 – 500V
FI12380 – 500V
FI13380 – 500V
FI14380 – 500V
A = free space above the inverter
B = distance between inverter and cabinet wall
= distance between two inverters
B
2
C = free space underneath of the inverter
525 – 690V
525 – 690V
525 – 690V
525 – 690V
525 – 690V
7.9 (200).79 (20)3.9 (100)
7.9 (200).79 (20)3.9 (100)
7.9 (200).79 (20)03.9 (100)
7.9 (200).79 (20)03.9 (100)
7.9 (200).79 (20)03.9 (100)
Table 2-6: Required Cooling Air
FrameVoltage
FI9380 – 500V
525 – 690V
FI10380 – 500V
525 – 690V
FI12380 – 500V
525 – 690V
FI13380 – 500V
525 – 690V
FI14380 – 500V
525 – 690V
Greatest Possible
Heat Loss (kW)
4.8
4.6
8.3
9.1
16.5
18.0
23.0
26.0
46.0
52.0
Cooling Air
Required (cfm)
67777.5
82493
1648186
2472279
2 x 24722 x 279
Minimum Air
Exhausting Hole
on Switchgear (in
2
)
Power Losses
Raising the switching frequency of the drive, to reduce motor noise for example, inevitably
affects the power losses and cooling requirements. For more information, contact Eaton.
2-6For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Chapter 3 — Power Wiring
The following wiring diagrams show the supply and motor connections.
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
+
B
FI 9/10
X10X15X9
H
1...H7
DC
–
B
–
Fan
Cooling
External
Supply
MN04004002E
UVMW
PE
Figure 3-1: FI9/FI10 Basic Wiring Diagram with Charging
For more information visit: www.EatonElectrical.com3-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
+
B
FI 9/10
X10X15X9
H
1...H7
DC
–
B
Cooling
–
Fan
UVMW
PE
Figure 3-2: FI9/FI10 Basic Wiring Diagram without Charging
3-2For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
FI 10 Module 1
DC
+
B
B
–
–
+
DC
FI 10 Module 2
DC
+
B
B
–
External
Supply
–
X10
H1-7
U VMW
Note: Min. Cable Length
(131.2í) 40m
H903
H900
X9
Cooling
PE
X15
Fan
X10
U V W
H1-7
H903
H900
X9
X15
Fan
Cooling
PE
Figure 3-3: FI12 Basic Wiring Diagram with Charging
MN04004002E
For more information visit: www.EatonElectrical.com3-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
DC
+
B
B
FI 10 Module 1
X10
H1-7
H903
H900
–
–
X9
X15
Fan
Cooling
+
DC
DC
+
B
FI 10 Module 2
X10
H1-7
H903
B
H900
–
–
X9
X15
Fan
Cooling
U VMW
Note: Min. Cable Length
(131.2’) 40m
PE
U V W
PE
Figure 3-4: FI12 Basic Wiring Diagram without Charging
3-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
DC
+
B
B
FI 10 Module U
–
–
+
DC
DC
+
B
FI 10 Module V
B
–
–
+
DC
FI 10 Module W
DC
+
B
–
B
–
External
Supply
H1-7
H903
H900
X9
X15
X10
Fan
Cooling
W
X10
Fan
Cooling
U
V
M
H1-7
H903
H900
X9
X15
Fan
Cooling
PE
Figure 3-5: FI13 Basic Wiring Diagram with Charging
MN04004002E
For more information visit: www.EatonElectrical.com3-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
DC
+
B
FI 10 Module U
B
–
–
Fan
Cooling
+
DC
FI 10 Module V
X10
B
+
H1-7
DC
B
–
–
X9
X15
Fan
Cooling
+
DC
FI 10 Module W
DC
+
B
B
–
–
Fan
Cooling
U
V
M
W
PE
Figure 3-6: FI13 Basic Wiring Diagram without Charging
3-6For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
FI 10 Module U
DC
+
B
–
B
–
FI 10 Module V
DC
+
+
B
DC
–
–
B
+
DC
–
–
B
DC
+
B
FI 10 Module W
External
Supply
+
DC
FI 10 Module U
DC
+
B
–
B
–
FI 10 Module V
DC
+
–
DC
+
B
–
B
+
DC
+
B
FI 10 Module W
DC
–
–
B
External
Supply
U
Note: Min. Cable Length
(131.2’) 40m
H1-7
V
H903
H900
X9
X15
Fan
Cooling
W
PE
Fan
Cooling
U
M
X10
Fan
Cooling
X10
Fan
Cooling
H1-7
V
H903
H900
X9
X15
Fan
Cooling
W
PE
Fan
Cooling
Figure 3-7: FI14 Basic Wiring Diagram with Charging
MN04004002E
For more information visit: www.EatonElectrical.com3-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
FI 10 Module U
DC
+
B
–
B
–
Fan
Cooling
+
DC
FI 10 Module V
X10
B
+
H1-7
H903
DC
B
H900
–
–
X9
X15
Fan
Cooling
+
DC
FI 10 Module W
DC
+
B
–
B
–
Fan
Cooling
+
DC
DC
+
B
FI 10 Module U
B
–
–
Fan
Cooling
+
DC
FI 10 Module V
0
X1
B
+
H1-7
H903
DC
B
H900
–
–
X9
X15
Fan
Cooling
+
DC
FI 10 Module W
DC
+
B
–
B
–
Fan
Cooling
U
Note: Min. Cable Length
(131.2’) 40m
V
W
PE
U
M
Figure 3-8: FI14 Basic Wiring Diagram without Charging
V
W
PE
3-8For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Power Connections
DC Supply and Motor Cables
The power cables are connected to terminals DC+ and DC- (R+/B+ and DC terminals when
using an external charging circuit) and the motor cables to terminals U, V and W. A cable
entry gland should be used at the motor cable end to reach the EMC levels, see Table 3-2.
Use cables with a heat resistance of at least +60C. The cables and the fuses must be sized
according to the inverter nominal output current which you can find on the rating plate.
Installation of cables according to UL regulations is presented on Page 3-17 and aR fuse sizes
in Tables 3-2 and 3-3 below.
If the motor temperature protection of the drive is used as an overload protection, the cable
shall be chosen accordingly. If three or more cables are used in parallel for bigger units, each
cable requires a separate overload protection.
These instructions apply only to installations with one motor and one cable connection from
the inverter to the motor. In any other case, ask the factory for more information.
Table 3-1: Cable Types Required to Meet Standards
Cable TypeEMC Level T
SPI9000 Inverter Unit FI9 – FI14 User Manual
Supply CablePower cable intended for fixed installation and the specific DC voltage.
Motor CablePower cable equipped with concentric protection wire and intended for the
Control CableScreened cable equipped with compact low-impedance shield.
Fuses, 465 – 800V DC Inverters
Table 3-2: Fuses Used in 465 – 800V DC Inverters
Nominal
CurrentFrame
140FI9170M3819DIN16904002
170FI9170M3819DIN16904002
205FI9170M6812DIN36908002
245FI9170M6812DIN36908002
300FI10170M85473SHT69012502
385FI10170M85473SHT69012502
460FI10170M85473SHT69012502
520FI12170M85473SHT69012504
590FI12170M85473SHT69012504
650FI12170M85473SHT69012504
730FI12170M85473SHT69012504
820FI12170M85473SHT69012504
920FI12170M85473SHT69012504
1030FI13170M85473SHT69012506
1150FI13170M85473SHT69012506
1300FI13170M85473SHT69012506
1600FI14170M85473SHT69012502 x 6
1940FI14170M85473SHT69012502 x 6
2300FI14170M85473SHT69012502 x 6
Shielded cable not required.
specific mains voltage.
Bussman aR
Fuse TypeFuse SizeFuse Un (V)Fuse In (A)No. of Fuses
MN04004002E
For more information visit: www.EatonElectrical.com3-9
SPI9000 Inverter Unit FI9 – FI14 User Manual
Fuses, 640 – 1100V DC Inverters
Table 3-3: Fuses Used in 640 – 1100V DC Inverters
Nominal
CurrentFrame
100FI9170M41991SHT12504002
125FI9170M41993SHT12504002
144FI9170M41993SHT12504002
170FI9170M41993SHT12504002
208FI10170M63053SHT12507002
261FI10170M63053SHT12507002
325FI10170M62773SHT125010002
325FI10170M62773SHT125010004
385FI12170M63053SHT12507004
460FI12170M63053SHT12507004
502FI12170M63053SHT12507004
590FI12170M62773SHT125010004
650FI12170M62773SHT125010004
650FI12170M62773SHT125010004
820FI13170M63053SHT12507006
920FI13170M62773SHT125010006
1030FI13170M62773SHT125010006
1300FI14170M62773SHT125010002 x 6
1500FI14170M62773SHT125010002 x 6
1900FI14170M62773SHT125010002 x 6
September 2006
Bussman aR
Fuse TypeFuse SizeFuse Un (V)Fuse In (A)No. of Fuses
Information about fuses:
gR fuses are designed to protect the device against both overcurrent and short circuits.
aR fuses protect the cables of the device against short circuits.
gG fuses are generally used to protect cables against overcurrent and short circuits.
3-10For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Inverter Supply and Motor Cables — 380 – 500V AC
Table 3-4: Cable Sizes for 380 – 500V AC
Nominal
CurrentFrameIL [A]
140FI91702x(1x24)
1702052x(1x24)
2052613x(1x24)
2453006x(1x24)
300FI103855x40
3854605x40
4605206x40
520FI12
5906505x40
6507305x40
7308205x40
8209205x40
92010306x40
1030FI1311505x40
115013005x40
130014506x40
1600FI14
194021505x40
230027006x40
Flexible conductor. Minimum temperature endurance for isolation 70°C.
Copper busbar.
The modules require symmetrical parallel cable with minimum length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets.
Motor cables — EN 60204-1, IEC 60364-5-2/2001
– PVC insulation
– 40°C ambient temperature
– 70°C surface temperature
5905x40
17705x40
SPI9000 Inverter Unit FI9 – FI14 User Manual
Module Supply (DC)
(per terminal Cu [mm2]
Motor Cable
[mm2]
Cu: 3x95+50
Al: 3x120+70
Cu: 3x150+70
Al: 3x240Al+72Cu
Cu: 3x185+95
Al: 2x(3x120+70)
Cu: 2x(3x120+70)
Al: 2x(3x185Al+57Cu)
Cu: 2x(3x120+70)
Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70)
Al: 2x(3x240Al+72Cu)
Cu: 2x(3x185+95)
Al: 2x(3x300Al+88Cu)
Cu: 2x(3x240+120)
Al: 4x(3x120Al+41Cu)
Cu: 4x(3x95+50)
Al: 4x(3x150Al+41Cu)
Cu: 4x(3x120+70)
Al: 4x(3x185Al+57Cu)
Cu: 4x(3x150+70)
Al: 4x(3x185Al+57Cu)
Cu: 4x(3x150+70)
Al: 4x(3x240Al+72Cu)
Cu: 4x(3x185+95)
Al: 4x(3x300Al+88Cu)
Cu: 4x(3x240+170)
Al: 6x (3x185Al+57Cu)
Cu: 6x(3x150+70)
Al: 6x (3x240Al+70Cu)
Cu: 6x(3x185+95)
Al: 6x (3x240Al+70Cu)
Cu: 2x 4x(3x240+170)
Al: 2x 6x (3x185Al+57Cu)
Cu: 2x 6x(3x150+70)
Al: 2x 6x (3x240Al+70Cu)
Cu: 2x 6x(3x185+95)
Al: 2x 6x (3x240Al+70Cu)
MN04004002E
For more information visit: www.EatonElectrical.com3-11
SPI9000 Inverter Unit FI9 – FI14 User Manual
Terminal Sizes — 380 – 500V AC
Table 3-5: Terminal Sizes for 380 – 500V AC
Nominal
CurrentFrameIL [A]
140FI9170PE: M8 x 25
170205
205261
245300
300FI10385PE: M8 x 25
385460
460520
520FI12590PE: M8 x 25
590650
650730
730820
820920
9201030
1030FI131150
September 2006
Approximate Dimensions in Inches (mm)
DC Supply TerminalMotor Cable Terminal
.51
(13)
.51
(13)
11501300
13001450
1.97
(50)
.63
(16)
1.57
(40)
1.50
(38)
.67
(17)
1.57
(40)
3-12For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Inverter Supply and Motor Cables — 525 – 690V AC
Table 3-6: Cable Sizes for 525 – 690V AC
Nominal
CurrentFrameIL [A]
100FI91252x(1x24)
1251442x(1x24)
1441702x(1x24)
1702082x(1x24)
208FI102613x(1x24)
2613255x40
3253855x40
3254165x40
385FI12
4605025x40
5025905x40
5906505x40
6507505x40
6508205x40
820FI139205x40
92010305x40
103011805x40
1300FI14
150019005x40
190022505x40
Flexible conductor. Minimum temperature endurance for isolation 70°C.
Copper busbar.
The modules require symmetrical parallel cable with minimum length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets.
Motor cables — EN 60204-1, IEC 60364-5-2/2001
– PVC insulation
– 40°C ambient temperature
– 70°C surface temperature
4605x40
15005x40
SPI9000 Inverter Unit FI9 – FI14 User Manual
Module Supply (DC)
(per terminal Cu [mm2]
Motor Cable
[mm2]
Cu: 3x95+50
Al: 3x120+70
Cu: 3x95+50
Al: 3x120+70
Cu: 3x95+50
Al: 3x120+70
Cu: 3150+70
Al: 3x240Al+72Cu
Cu: 3x185+95
Al: 2x(3x95Al+29Cu)
Cu: 2x(3x95+50)
Al: 2x(3x150Al+41Cu)
Cu: 2x(3x120+70)
Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70)
Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70)
Al: 2x(3x240Al+72Cu)
Cu: 2x(3x185+95)
Al: 2x(3x300Al+88 Cu)
Cu: 2x(3x240+120)
Al: 4x(3x120Al+41Cu)
Cu: 4x(3x95+50)
Al: 4x(3x150Al+41Cu)
Cu: 4x(3x120+70)
Al: 4x(3x150Al+41Cu)
Cu: 4x(3x150+70)
Al: 4x(3x185Al+57Cu)
Cu:4x(3x150+70)
Al:4x(3x2405+72Cu)
Cu:4x(3x185+95)
Al:5x(3x185+57Cu)
Cu:5x(3x185+95)
Al:6x(3x185+72Cu)
Cu: 2x4x(3x120+70)
Al: 2x4x(3x150Al+41Cu)
Cu: 2x4x(3x185+95)
Al: 2x5x(3x185+57Cu)
Cu: 2x5x(3x185+95)
Al: 2x6x(3x185+72Cu)
MN04004002E
For more information visit: www.EatonElectrical.com3-13
SPI9000 Inverter Unit FI9 – FI14 User Manual
Terminal Sizes — 525 – 690V AC
Table 3-7: Terminal Sizes for 525 – 690V AC
Nominal
CurrentFrameIL [A]
100FI9125
125144
144170
September 2006
Approximate Dimensions in Inches (mm)
DC Supply TerminalMotor Cable Terminal
.51
(13)
1.57
(40)
.51
(13)
1.57
(40)
170208
208FI10261
261325
325385
325416
385FI12460
460502
502590
590650
650750
650820
820FI13920
1.38
(35)
1.97
(50)
1.97
(50)
.63
(16)
.63
(16)
.63
(16)
.51
(13)
.51
(13)
.51
(13)
1.57
(40)
1.57
(40)
1.50
(38)
1.50
(38)
1.50
(38)
.67
(17)
.67
(17)
.67
(17)
.51
(13)
.51
(13)
.51
(13)
1.57
(40)
1.57
(40)
9201030
10301180
1.97
(50)
.63
(16)
1.57
(40)
1.50
(38)
.67
(17)
1.57
(40)
3-14For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Installation Instructions
1. Before starting the installation, check that none of the components of the inverter are live.
2. If the inverter is installed outside the cubicle, cabinet or device space, you need to install
a separate inverter cover in accordance with protection class IP21 requirements (see
Page 3-16. There is no need to install the inverter cover if the inverter is installed in a
cubicle, separate cabinet or device space.
3. Place the motor cables sufficiently far from other cables:
– Avoid placing the motor cables in long parallel lines with other cables
– If the motor cables runs in parallel with other cables, note the minimum distances
between the motor cables and other cables given in Table 3-8.
– The given distances also apply between the motor cables and signal cables of other
systems.
– The maximum length of the motor cables is 984 feet (300m) (units with power
greater than 1.5 kW) and 328 feet (100m) (units with power from 0.75 to 1.5 kW).
– The motor cables should cross other cables at an angle of 90 degrees.
Table 3-8: Cable Distances
Distance Between Cables in
Inches (m)
SPI9000 Inverter Unit FI9 – FI14 User Manual
Shielded
Cable in Feet (m)
11.8 (.3)
39.4 (1.0)
≥ 193 (59)
≤ 656 (200)
4. If cable insulation checks are needed, see Page 3-17.
5. Connect the cables:
– Strip the motor and DC supply cables.
– Remove the screws of the cable protection plate. Do not open the cover of the power unit!
– Make holes into and pass the cables through the rubber grommets on the bottom of
the power unit. The rubber grommets are delivered in a separate bag.
– Connect the DC supply, motor and control cables into their respective terminals.
– For information on the installation of greater units, please contact Eaton or your
local distributor.
– For Information on cable installation according to UL regulations, see Page 3-17.
– For information on cable installation according to EMC regulations, see Table 3-1.
– Make sure that the control cable wires do not come in contact with the electronic
components of the unit.
– If an external brake resistor (optional) is used, connect its cable to the appropriate
terminal.
– Check the connection of the ground cable to the motor and the inverter terminals
marked with.
– Connect the separate shield of the power cable to the ground terminals of the
inverter, motor and the supply center.
– Attach the cable protection plate with the screws.
– Ensure that the control cables or the cables of the unit are not trapped between the
frame and the protection plate.
MN04004002E
For more information visit: www.EatonElectrical.com3-15
SPI9000 Inverter Unit FI9 – FI14 User Manual
Frame Sizes
September 2006
Inverter Frame FI9, Protection Class IP00Inverter Frame FI10, Protection Class IP00
Inverter Frame FI13, Protection Class IP00Inverter Frame FI12, Protection Class IP00
3-16For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Cable Installation and the UL Standards
To meet the UL (Underwriters Laboratories) regulations, a UL approved copper cable with a
minimum heat-resistance of +60/75°C must be used.
The tightening torques of the terminals are given below in Table 3-9.
Table 3-9: Terminal Tightening Torques
Nominal CurrentVoltageFrame
SPI9000 Inverter Unit FI9 – FI14 User Manual
Tightening Torque in
in-lb (Nm)
140 – 245
100 – 170
300 – 460
208 – 325
520 – 920
385 – 650
1030 – 1300
920 – 1030
1600 – 2300
1300 – 1900
Tightening torque of terminal connection to the isolative base.
380 – 500V
525 – 690V
380 – 500V
525 – 690V
380 – 500V
525 – 690V
380 – 500V
525 – 690V
380 – 500V
525 – 690V
Note: Apply counter torque to the nut on the other side of the terminal when tightening/
loosening the terminal screw in order to avoid damage to the terminal.
Cable and Motor Insulation Checks
1. Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the inverter and from the
motor. Measure the insulation resistance of the motor cable between each phase
conductor as well as between each phase conductor and the protective ground
conductor.
The insulation resistance must be >1MΩ.
FI9340 (40)
FI10340 (40)
FI12340 (40)
FI13340 (40)
FI14340 (40)
MN04004002E
2. DC supply cable insulation checks
Disconnect the DC supply cable from terminals B- and B+ of the inverter and from DC
supply. Measure the insulation resistance between each conductor and ground.
The insulation resistance must be >1MΩ.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the
motor connection box. Measure the insulation resistance of each motor winding. The
measurement voltage must equal at least the motor nominal voltage but not exceed
1,000V.
The insulation resistance must be >1MΩ.
For more information visit: www.EatonElectrical.com3-17
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
3-18For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Chapter 4 — Control Wiring
The control unit of the inverter consists of the control board and option boards (see
Figures 4-1 and 4-2) connected to the five slot connectors (A to E) on the control board. The
control board is connected to the power unit through a D connector (1).
SPI9000 Inverter Unit FI9 – FI14 User Manual
Figure 4-1: Control Board
E
D
C
B
A
Figure 4-2: Basic and Option Board
Connections of the Control Board
MN04004002E
For more information visit: www.EatonElectrical.com4-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
When the inverter is delivered from the factory, the control unit usually includes two basic
boards (I/O board and relay board), which are normally installed in slots A and B. On the next
pages you will find the arrangement of the control I/O and the relay terminals of the two basic
boards, the general wiring diagram and the control signal descriptions. The I/O boards
mounted at the factory are indicated in the type code. For more information on the option
boards, see the option board user manual.
The control board can be powered externally (+24V) by connecting the external power source
to bidirectional terminal #6 (see Figure 4-5). This voltage is sufficient for parameter setting
and for keeping the fieldbus active.
Note: If the +24V input of several inverters are connected in parallel, we recommend to use a
diode in terminal #6 to avoid the current flowing in opposite direction, which might
damage the control board.
#
September 2006
External
+
24V
+
–
#
6
7
+
–
#
#
6
7
+
–
#
#
6
7
+
–
#
#
6
7
Control Wiring Details
The basic control connections for boards A2 and A3 are shown in Figures 4-6 and 4-7.
You can find the signal descriptions for applications in the application manual.
Figure 4-3: Inverters Connected in Parallel
123456789
10
Board OPT-A9 in Slot ABoards OPT-A2 and OPT-A3 in Slot B
11 12 13 14 15 16 17 18 19 20
21 22 2324 25 26
OPT-A2
21 22 2325 2628 29
OPT-A3
Figure 4-4: I/O Terminals of the Two Basic Boards
4-2For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Basic I/O Board A9
+10Vref
AIA1
GND
AIA2
AIA2
24Vout
GND
DIA1
DIA2
DIA3
CMA
24Vout
GND
DIB4
DIB5
DIB6
CMB
Iout
Iout
DO1
1
+
2
3
+
4
-
5
6
7
8
9
10
11
12
13
14
15
16
17
+
18
-
19
20
Input Reference
(Voltage)
Input Reference
(Current)
Control Voltage Output
24V
GND
24V
GND
0 (4)/20 mA
Ω
RL<500
V<+48V
+
I<50 mA
Figure 4-5: Option Board A9 Wiring Diagram
Basic Relay Board A2
Figure 4-6: Option Board A2 Wiring Diagram
Indicates Connections for Inverted Signals
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
21
22
23
24
25
26
R
L
Switching:
<8A / 24V DC
<0.4A / 125V DC
<2kVA / 250V AC
Continuously
<2 Arms
AC / DC
MN04004002E
For more information visit: www.EatonElectrical.com4-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Control Cables
The control cables shall be at least 20 AWG screened multicore cables, see Table 4-1. The
maximum terminal wire size is 14 AWG for the relay terminals and 16 AWG for other
terminals.
You can find the tightening torques of the option board terminals in Table 4-1.
Table 4-1: Tightening Torques of Option Board Terminals
Terminal Screw
Basic Relay Board A3
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
TL1+
TL1
21
22
23
25
26
28
–
29
R
L
AC / DC
+t
Figure 4-7: Option Board A3 Wiring Diagram
Tightening Torque
lb-in.
Switching:
<8A / 24V DC
<0.4A / 125V DC
<2kVA / 250V AC
Continuously
<2 Arms
Relay and thermistor terminals (screw M3)4.5
Other terminals (screw M2.6)1.8
4-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Galvanic Isolation Barriers
The control connections are isolated from the mains potential and the GND terminals are
permanently connected to ground. See Figure 4-8.
The digital inputs are galvanically isolated from the I/O ground. the relay outputs are also
double-isolated from each other at 300V AC (EN-50178).
SPI9000 Inverter Unit FI9 – FI14 User Manual
+
10Vref
AO1
AO2
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
GND
+
24V
GND
AI1
+
AI2
-
AI2
DIN1...
DIN3
CMA
DIN4...
DIN6
CMB
+
-
DO1
+
TI1
–
TI1
Control to
Ground
Digital Input
Group A
Digital Input
Group A
Analog
Output
Digital
Output
Control
Panel
Control
Board
Gate Drivers
L1 L2 L3
Power
Board
UVW
MN04004002E
Figure 4-8: Galvanic Isolation Barriers
For more information visit: www.EatonElectrical.com4-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 4-2: Control I/O Terminal Signals on Option Board A9
TerminalSignalTechnical Information
1+10 VrefReference voltageMaximum current 10 mA
2AI1+Analog input,
3GND/AI1–Analog input common
4AI2+Analog input,
5GND/AI2–Analog input common
624 Vout
(bidirectional)
7GNDI/O groundGround for reference and controls
8DIN1Digital input 1R
9DIN2Digital input 2
10DIN3Digital input 3
11CMADigital input common A for
1224 Vout
(bidirectional)
13GNDI/O groundSame as terminal #7
14DIN4Digital input 4R
15DIN5Digital input 5
16DIN6Digital input 6
17CMBDigital input common B for
18AO1+Analog signal (+output)Output signal range:
19AO1-Analog output common
20DO1Open collector outputMaximum U
September 2006
Selection V or mA with jumper block X1 (see
voltage or current
Page 4-8)
Default: 0 to +10V (Ri = 200 kΩ)
(-10V to +10V Joy-stick control, selected
with a jumper)
0 to 20 mA (Ri = 250 Ω)
Differential input if not connected to ground;
Allows ±20V differential mode voltage to
GND
Selection V or mA with jumper block X1 (see
voltage or current
Page 4-8):
Default: 0 to 20 mA (Ri = 250 Ω)
0 to +10V (Ri = 200 kΩ)
(10V to +10V Joy-stick control, selected with
a jumper)
Differential input if not connected to ground;
Allows ±20V differential mode voltage to
GND
24V auxiliary voltage±15%; maximum current 250 mA all boards
total; 150 mA from single board. Can also be
used as external power backup for the
control unit (and fieldbus).
= min. 5kΩ
i
18 – 30V = “1”
Must be connected to GND or 24V of I/O
DIN1, DIN2 and DIN3.
terminal or to external 24V or GND
Selection with jumper block X3 (see
Page 4-8)
24V auxiliary voltageSame as terminal #6
= min. 5kΩ
i
18 – 30V = “1”
Must be connected to GND or 24V of I/O
DIN4, DIN5 and DIN6
terminal or to external 24V or GND
Selection with jumper block X3 (see
Page 4-8)
Current 0(4) – 20 mA, R
Voltage 0 – 10V, R
Selection with jumper block X3 (see
>1kΩ
L
max. 500Ω or
L
Page 4-8)
= 48V DC
Maximum current = 50 mA
in
4-6For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 4-3: Control I/O Terminal Signals on Option Board A2
OPTA2
21RO1/1Relay output 1Switching capacity24V DC/8A
22RO1/2
23RO1/3Min. switching load
24RO2/1Relay output 2Switching capacity24V DC/8A
25RO2/2
26RO2/3Min. switching load
Table 4-4: Control I/O Terminal Signals on Option Board A3
OPTA3
21RO1/1Relay output 1Switching capacity24V DC/8A
22RO1/2
23RO1/3Min. switching load
24RO2/1Relay output 2Switching capacity24V DC/8A
25RO2/2
26RO2/3Min. switching load
28TI1+Thermistor input
29TI1-
Digital Input Signal Inversions
The active signal level depends on which potential the common inputs CMA and CMB
(terminals 11 and 17) are connected to. The alternatives are either +24V or ground (0V). See
Figure 4-9.
250V AC/8A
125V DC/0.4A
5V/10 mA
250V AC/8A
125V DC/0.4A
5V/10 mA
250V AC/8A
125V DC/0.4A
5V/10 mA
250V AC/8A
125V DC/0.4A
5V/10 mA
We recommend the use of positive logic in all control connections of the inverter. If negative
logic is used, additional appropriate measures are needed to meet the safety regulation
requirements.
The 24 volt control voltage and the ground for the digital inputs and the common inputs
(CMA, CMB) can be either internal or external.
+
24V
Ground
DIN1
DIN2
DIN3
CMA
Ground
+
24V
DIN1
DIN2
DIN3
CMA
Figure 4-9: Positive/Negative Logic
Positive logic (+24V is the active signal) = Input is active when the switch is closed.
Negative logic (0V is the active signal) = Input is active when the switch is closed.
Requires setting of jumper X3 to position “CMA/CMB isolated from ground.”
MN04004002E
For more information visit: www.EatonElectrical.com4-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
Jumper Selections on Option Board A9
The user can customize the functions of the inverter to better suit his needs by selecting
certain positions for the jumpers on the OPTA9 board. The positions of the jumpers
determine the signal type of analogue and digital inputs.
On the A9 basic board, there are four jumper blocks (X1, X2, X3 and X6), each containing
eight pins and two jumpers. The selection possibilities of the jumpers are shown in
Figure 4-11.
September 2006
X1X2
X6
X3
Figure 4-10: Jumper Blocks on Option Board A9
4-8For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Jumper Block X1:
AI1 Mode
A B C D
AI1 Mode: 0...20mA; Current Input
A B C D
AI1 Mode: Voltage Input; 0...10V
A B C D
AI1 Mode: Voltage Input; 0...10V (Differential)
A B C D
AI1 Mode: Voltage Input; -10...10V
Jumper Block X6:
AO1 Mode
A B C D
AI1 Mode: 0...20mA; Current Output
A B C D
Jumper Block X2:
AI2 Mode
A B C D
AI2 Mode: 0...20mA; Current Input
A B C D
AI2 Mode: Voltage Input; 0...10V
A B C D
AI2 Mode: Voltage Input; 0...10V (Differential)
A B C D
AI2 Mode: Voltage Input; -10...10V
Jumper Block X3:
CMA and CMB Grounding
CMB Connected to GND
CMA Connected to GND
CMB Isolated from GND
CMA Isolated from GND
CMB and CMA
Internally Connected Together,
Isolated from GND
MN04004002E
AO1 Mode: Voltage Output; 0...10V
= Factory Default
Figure 4-11: Jumper Selection for Option Board A9
CAUTION
Ensure that the jumper positions are correct. Running the motor
with signal settings that differ from the jumper positions will not
harm the inverter, but may harm the motor.
Note: If you change the AI/AO signal content, remember to change the corresponding board
parameter in Menu M7.
For more information visit: www.EatonElectrical.com4-9
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
4-10For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Chapter 5 — Menu Information
Keypad Operation
The control keypad is the link between the SPI9000 inverter and the user. The control keypad
features an alphanumeric display with seven indicators for the Run status (RUN, counterclockwise, clockwise, READY, STOP, ALARM, FAULT) and three indicators for the control
place (I/O term/Keypad/BusComm). There are also three Status Indicator LEDs (green – green
– red), see Page 5-3.
The control information, i.e. the menu number, description of the menu or the displayed
value and the numeric information are presented on three text lines.
The inverter is operable through the nine pushbuttons of the control keypad. Furthermore,
the buttons can be used in setting parameters and monitoring values.
The keypad is detachable and isolated from the input line potential.
Indicators on the Keypad Display
SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E
Figure 5-1: Control Keypad and Drive Status Indications
For more information visit: www.EatonElectrical.com5-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Drive Status Indicators
The drive status symbols tell the user the status of the motor and the inverter. In addition,
they tell about possible irregularities detected by the motor control software in motor or
inverter functions.
Table 5-1: Drive Status Indicators
IndicatorDescription
September 2006
Motor is running. Blinks when the stop command is given, but the frequency
is still ramping down.
Indicates the direction of motor rotation.
Indicates that the drive is not running.
Lights up when AC power is on. In case of a trip, the symbol will not light up.
Indicates that the drive is running outside a certain limit and a warning is
given.
Indicates that unsafe operating conditions are encountered and the drive was
stopped.
Control Place Indicators
The symbols I/O Term, Keypad and Bus/Comm (see Table 5-2) indicate the choice of control
place made in the Keypad control menu (M3) (see Page 5-9).
Table 5-2: Control Place Indicators
IndicatorDescription
I/O terminals are selected as the control place, i.e., START/STOP commands
or reference values, etc. are given through the I/O terminals.
Control keypad is selected as the control place, i.e., the motor can be started
or stopped or its reference values, etc. altered from the keypad.
The inverter is controlled through a fieldbus.
5-2For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Status LEDs (Green – Green – Red)
The status LEDs light up in connection with the READY, RUN and FAULT drive status
indicators.
Table 5-3: Status LEDs (Green – Green – Red)
IndicatorDescription
Text Lines
The three text lines provide the users with information on their present location in the keypad
menu structure as well as with information related to the operation of the drive.
Table 5-4: Text Lines
IndicatorDescription
SPI9000 Inverter Unit FI9 – FI14 User Manual
Lights up when the AC power is connected to the drive. Simultaneously, the
drive status indicator READY is lit up.
Lights up when the drive is running. Blinks when the STOP button is pushed
and the drive is ramping down.
Lights up when unsafe operating conditions are encountered and the drive
was stopped (Fault Trip). Simultaneously, the drive status indicator FAULT
blinks on the display and a fault description appears (see Page 5-11, Active
Faults Menu).
Keypad Pushbuttons
The alphanumeric control keypad has nine pushbuttons that are used for controlling the
inverter (and motor), setting parameters and monitoring values.
Location indicator: Displays the symbol and number of the menu, parameter,
etc. Example: M2 = Menu 2 (Parameters); P2.1.3 = Acceleration time.
Description line: Displays the description of the menu, value or fault.
Value line: Displays the numerical and textual values of references,
parameters, etc. and the number of submenus available in each menu.
MN04004002E
Figure 5-2: Keypad Pushbuttons
For more information visit: www.EatonElectrical.com5-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 5-5: Button Descriptions
IndicatorDescription
September 2006
This button is used to reset active faults (see Page 5-11, Active Faults Menu).
This button is used to switch between the two latest displays. This may be
useful when you want to see how the changed (new) value influences some
other value.
The ENTER button is used for:
• Confirmation of selections
•Fault history reset (2 – 3 seconds)
This button is used to browse up through the main menu and pages of
different submenus.
Edit values.
This button is used to browse down through the main menu and pages of
different submenus.
Edit values.
This button is used to:
• Move backward in the menu
• Move cursor left (in parameter menu)
• Exit edit mode
• Press and hold for 2 to 3 seconds to return to main menu
This button is used to:
• Move forward in the menu
• Move cursor right (in parameter menu)
• Enter edit mode
Pressing this button starts the motor if the keypad is in the active control
place. See Page 5-10, Selection of Control Place.
Pressing this button stops the motor (unless disabled by parameter R3.4/
R3.6). See Page 5-10, Selection of Control Place.
5-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Menu Navigation
The data on the control keypad is arranged in menus and submenus. The menus are used for
the display and editing of measurement and control signals, parameter settings and
reference value and fault displays. Through the menus, you can also adjust the contrast of
the display.
SPI9000 Inverter Unit FI9 – FI14 User Manual
Location
Description
Number of Items
Available
The first menu level consists of menus M1 to M7 and is called the Main menu. The user can
navigate in the main menu with the Browser buttons up and down. The desired submenu can
be entered from the main menu with the menu buttons. When there still are pages to enter
under the currently displayed menu or page, you can see an arrow in the lower right corner
of the display and can reach the next menu level by pressing Menu Button Right.
The control keypad navigation chart is shown in Figure 5-4. Please note that menu M1 is
located in the lower left corner. From there you will be able to navigate your way up to the
desired menu using the menu and browser buttons.
You will find more detailed descriptions of the menus later in this chapter.
Monitor
V1V14
Figure 5-3: Keypad Display Data
MN04004002E
For more information visit: www.EatonElectrical.com5-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Expander boards
G1G5
System Menu
S1S9
Fault history
H1H3
Active faults
F0
A: OPTA1
Language
English
11 Output phase
11 Output phase
or:
G1G1
Browse
T1T7
T1FT7
A: Parameters
P1P3
Change
value
Operation days
17
Operation days
17
Keypad control
P1P3
Parameters
G1G9
Monitor
V1V15
Control Place
I/O Terminal
Basic parameters
P1P15
Output frequency
13.95 Hz
Browse
Change
value
Min Frequency
13.95 Hz
No editing!
Figure 5-4: Keypad Navigation Chart
Browse
Change
value
5-6For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Monitoring Menu (M1)
You can enter the Monitoring menu from the Main menu by pressing Menu Button Right
when the location indication M1 is visible on the first line of the display. Figure 5-5 shows
how to browse through the monitored values.
The monitored signals carry the indication V#.# and they are listed in Table 5-6. The values
are updated once every 0.3 seconds.
This menu is meant only for signal checking. The values cannot be altered here. For changing
values of parameters, see Page 5-8.
SPI9000 Inverter Unit FI9 – FI14 User Manual
FreqReference
13.95 Hz
Monitor
Output frequency
V1V14
13.95 Hz
Figure 5-5: Monitoring Menu
MN04004002E
For more information visit: www.EatonElectrical.com5-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 5-6: Monitored Signals
CodeSignal NameUnitDescription
V7.1Output frequencyHzFrequency to the motor
V7.2Frequency reference Hz
V7.3Motor speedrpmCalculated motor speed
V7.4Motor currentAMeasured motor current
V7.5Motor torque%Calculated torque based/nominal torque of the unit
V7.6Motor power%Calculated actual power/nominal power of the unit
V7.7Motor voltageVCalculated motor voltage
V7.8DC-link voltageVMeasured DC-link voltage
V7.9Unit temperature°CHeatsink temperature
V7.10Motor temperature%Calculated motor temperature
V7.11Voltage inputVAI1
V7.12Current inputmAAI2
V7.13DIN1, DIN2, DIN3—Digital input statuses
V7.14DIN4, DIN5,DIN6—Digital input statuses
V7.15DO1, RO2, RO3—Digital and relay output statuses
V7.16Analog output
current
M1.17Multimonitoring
items
September 2006
mA AO1
Displays three selectable monitoring values. See
Page 5-23.
Note: Applications may embody more monitoring values.
Parameter Menu (M2)
Parameters are the way of conveying the commands of the user to the inverter. Parameter
values can be edited by entering the Parameter Menu from the Main Menu when the location
indication M2 is visible on the first line of the display. The value editing procedure is
presented in Figure 5-6.
Pressing Menu Button Right once takes you to the Parameter Group Menu (G#). Locate the
desired parameter group by using the Browser buttons and press Menu Button Right again
to see the group and its parameters. Use the Browser buttons to find the parameter (P#) you
want to edit. Pressing Menu Button right takes you to the edit mode. As a sign of this, the
parameter value starts to blink. You can now change the value in two different ways:
●Set the desired value with the Browser buttons and confirm the change with the ENTER
button. Consequently, the blinking stops and the new value is visible in the value field.
●Press Menu Button Right once more. Now you will be able to edit the value digit by
digit. This may come in handy, when a relatively greater or smaller value than that on
the display is desired. Confirm the change with the ENTER button.
The value will not change unless the ENTER button is pressed. Pressing Menu Button Left
takes you back to the previous menu.
Several parameters are locked, i.e. cannot be edited, when the drive is in RUN status. If you
try to change the value of such a parameter the text *Locked* will appear on the display. The
inverter must be stopped to edit these parameters.
The parameter values can also be locked using the function in menu M6 (see Page 5-22).
5-8For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
You can return to the Main menu any time by pressing Menu Button Left for 1 to 2 seconds.
The basic application package includes seven applications with different sets of parameters.
You will find the parameter lists in the application manual.
Once in the last parameter of a parameter group, you can move directly to the first parameter
of that group by pressing Browser button up.
See the diagram for parameter value change procedure in Figure 5-6.
Note: You can connect power to the control board by connecting the external power source
to the bidirectional terminal #6 on the OPTA9 board (see Chapter 4). The external
power source can also be connected to the corresponding +24V terminal on any option
board. This voltage is sufficient for parameter setting and for keeping the fieldbus
active.
Input signals
G1G8
M2
Parameters
Min Frequency
Keypad Control Menu (M3)
In the Keypad Control Menu, you can choose the control place, edit the frequency reference
and change the direction of the motor. You can enter the submenu level by pressing Menu
Button Right.
Note: There are some special functions that can be performed in menu M3:
Select the keypad as the active control place by pressing start for 3 seconds when the motor
is running. The keypad will become the active control place and the current frequency
reference and direction will be copied to the keypad.
Select the keypad as the active control place by pressing stop for 3 seconds when the motor
is stopped. The keypad will become the active control place and the current frequency
reference and direction will be copied to the keypad.
Basic parameters
G1G8
Min Frequency
13.95 Hz
P1P18
14.45 Hz
Figure 5-6: Parameter Value Change Procedure
Min Frequency
13.95 Hz
MN04004002E
Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by pressing enter for 3
seconds.
Note: If you are in any other menu than menu M3, these functions will not work.
For more information visit: www.EatonElectrical.com5-9
SPI9000 Inverter Unit FI9 – FI14 User Manual
If you are in some other menu than menu M3 and try to start the motor by pressing the
START button when the keypad is not selected as the active control place, you will get an
error message: Keypad Control NOT ACTIVE.
Selection of Control Place
There are three different places (sources) where the inverter can be controlled. For each
control place, a different symbol will appear on the alphanumeric display:
●I/O terminals
●Keypad (panel)
●Fieldbus
You can change the control place by entering the edit mode with Menu Button Right. The
options can then be browsed with the Browser buttons. Select the desired control place with
the ENTER button. See Figure 5-7.
September 2006
M3
Keypad control
P1P4
Control Place
Keypad
Control Place
I/O Remote
Control Place
Keypad
Control Place
I/O Remote
Figure 5-7: Selection of Control Place
Keypad Reference
The keypad reference submenu (P3.2) displays and allows the operator to edit the frequency
reference. The changes will take place immediately. This reference value will not, however,
influence the rotation speed of the motor unless the keypad has been selected as the active
control place.
Note: The maximum difference in RUN mode between the output frequency and the keypad
reference is 6 Hz. The program automatically monitors the keypad reference value.
You may edit the reference value (pressing the ENTER button is not necessary).
5-10For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Keypad Direction
The keypad direction submenu (P3.3) displays and allows the operator to change the rotating
direction of the motor. This setting will not, however, influence the rotation direction of the
motor unless the keypad has been selected as the active control place.
Note: For additional information on controlling the motor with the keypad, see Pages 5-3 and
STOP Button Activated
By default, pushing the STOP button will always stop the motor regardless of the selected
control place. You can disable this function by giving parameter 3.4 the value 0. If the value of
this parameter is 0, the STOP button will stop the motor only when the keypad has been
selected as the active control place.
Active Faults Menu (M4)
You can enter the Active Faults menu from the Main menu by pressing Menu Button Right
when the location indication M4 is visible on the first line of the keypad display.
When a fault brings the inverter to a stop, the location indication F1, the fault code, a short
description of the fault, and the fault type symbol (see below) will appear on the display. In
addition, the indication FAULT or ALARM (see Table 5-1) is displayed and, in case of a FAULT,
the red LED on the keypad starts to blink. If several faults occur simultaneously, the list of
active faults can be browsed with the Browser buttons.
SPI9000 Inverter Unit FI9 – FI14 User Manual
6-2.
The memory of active faults can store a maximum of 10 faults in the order of appearance.
The display can be cleared with the RESET button and the read-out will return to the same
state it was in before the fault trip. The fault remains active until it is cleared with the RESET
button or with a reset signal from the I/O terminal.
Note: Remove external Start signal before resetting the fault to prevent unintentional restart
of the drive.
MH
Active faults
F0
Figure 5-8: Normal State, No Faults
Fault Types
The inverter has four types of faults. These types differ from each other on the basis of the
subsequent behavior of the drive. See Table 5-7.
MN04004002E
For more information visit: www.EatonElectrical.com5-11
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Operation hours
34:21:05
Fault Type
Symbol
11 Output phase
T1F
T13
Operation days
17
Figure 5-9: Fault Display
Table 5-7: Fault Types
Fault Type SymbolMeaning
A (Alarm)This type of fault is a sign of an unusual operating condition. It does not cause
F (Fault)An “F fault” makes the drive stop. Actions need to be taken to restart the drive.
AR (Fault Autoreset)If an “AR fault” occurs the drive will stop immediately. The fault is reset
FT (Fault Trip)If the drive is unable to restart the motor after an AR fault an FT fault occurs.
the drive to stop, nor does it require any special actions. The “A fault” remains
in the display for about 30 seconds.
automatically and the drive tries to restart the motor. Finally, if the restart is not
successful, a fault trip (FT, see below) occurs.
The “FT fault” has basically the same effect as the F fault: the drive is stopped.
Note: Fault Codes are listed in Appendix A.
Fault Time Data Record
When a fault occurs, the information described in Figure 5-8 is displayed. By pressing Menu
Button Right, you will enter the Fault time data record menu indicated by T.1➔T.#. In this
menu, some selected important data valid at the time of the fault are recorded. This feature
will help the user or the service person in determining the cause of the fault.
5-12For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
The data available are:
Table 5-8: Fault Time Recorded Data
DataUnitsDescription
T.1DCounted operation days (Fault 43: Additional code)
T.2hh:mm:ss
(d)
T.3H z
hh:mm:ss
T.4
T.5
T.6
T.7
T.8
T.9
T.10
T.11
T.12
T.13
Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
Output frequency
(Fault 43: Counted operation hours)
Motor current
Motor voltage
Motor power
Motor torque
DC bus voltage
Unit temperature
Run status
Direction
Warnings
Zero speed
Real Time Record
If real time is set to run on the inverter, the data items T1 and T2 will appear as follows:
Table 5-9: Real Time Record
DataUnitsDescription
T.1yyyy-mm-ddCounted operation days
T.2hh:mm:SS,sssCounted operation hours
Fault History Menu (M5)
You can enter the Fault History menu from the Main menu by pressing Menu Button Right
when the location indication M5 is visible on the first line of the keypad display.
All faults are stored in the Fault History menu where you can browse them with the Browser
buttons. Additionally, the Fault Time Data Record pages (see Page 5-12) are accessible for
each fault. You can return to the previous menu any time by pressing Menu Button Left.
The memory of the inverter can store a maximum of 30 faults in order of appearance. The
number of faults currently in the fault history is shown on the value line of the main page
(H1➔H#). The order of the faults is indicated by the location indication in the upper left corner
of the display. The latest fault is indicated by F5.1, the one before that by F5.2 and so on. If
there are 30 uncleared faults in the memory, the next fault will erase the oldest fault from the
memory.
Pressing the ENTER button for about 2 to 3 seconds resets the whole fault history. The
symbol H# will change to 0.
MN04004002E
For more information visit: www.EatonElectrical.com5-13
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
System Menu (M6)
You can enter the System menu from the Main menu by pressing Menu Button Right when
the location indication M6 is visible on the first line of the keypad display.
The controls associated with the general use of the inverter, such as application selection,
customized parameter sets or information about the hardware and software are located
under the System menu. The number of submenus and subpages is shown with the symbol
S (or P) on the value line.
Table 5-10 has a list of the functions available in the System menu.
Fault history
H1
5 ChargeSwitch
11 Output phase
H3
T1T7
PUSH to Reset
Figure 5-10: Fault History Menu
Operation hours
13:25:43
Operation days
17
5-14For more information visit: www.EatonElectrical.comMN04004002E
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Table 5-10: System Menu Functions
CodeFunctionMinMaxUnitDefaultCustSelections
S6.1Selection of
language
EnglishEnglish
Deutsch
Suomi
Svenska
Italiano
S6.2Application
selection
Basic
Application
Basic Application
Standard Application
Local/Remote control Appl.
Multi-Step Application
PID Control Application
Multi-Purpose Control Appl.
Pump and Fan Control Appl.
S6.3Copy parameters
S6.3.1Parameter setsLoad factory defaults
Store set 1
Load set 1
Store set 2
Load set 2
S6.3.2Load to keypadAll parameters
S6.3.3Load from keypadAll parameters
All but motor parameters
Application parameters
P6.3.4Parameter backupYesNo
Ye s
S6.4Parameter
comparison
S6.5Safety
S6.5.1PasswordNot used0=Not used
P6.5.2Parameter lockingChange
Enabled
Change Enabled
Change Disabled
S6.5.3Start-Up WizardNo
Ye s
S6.5.4Multimonitoring
items
Change
Enabled
Change Enabled
Change Disabled
S6.6Keypad settings
P6.6.1Default page
P6.6.2Default page/OM
P6.6.3Timeout time065535s30
P6.6.4Contrast03118
P6.6.5Backlight timeAlways65535min10
S6.7Hardware settings
P6.7.1Internal brake
resistor
ConnectedNot connected
Connected
P6.7.2Fan control functionContinuousContinuous
Temperature
P6.7.3HMI acknowledge.2005000ms200
P6.7.4HMI: no. of retries1105
MN04004002E
For more information visit: www.EatonElectrical.com5-15
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 5-10: System Menu Functions, continued
CodeFunctionMinMaxUnitDefaultCustSelections
S6.8System information
S6.8.1Total counters
C6.8.10.1.MWh counterkWh
C6.8.10.2.Operation day
counter
C6.8.1.3.Operation hour
counter
S6.8.2Trip counters
T6.8.2.1MWh counterkWh
T6.8.2.2Clear MWh counter
T6.8.2.3Operation day
counter
T6.8.2.4Operation hour
counter
T6.8.2.5Clear operation
hour counter
S6.8.3Software
information
S6.8.3.1Software package
S6.8.3.2System software
version
S6.8.3.3Firmware interface
S6.8.3.4System load
S6.8.4Applications
S6.8.4.#Name of
application
D6.8.4.#.1Application ID
D6.8.4.#.2Applications:
version
D6.8.4.#.3Applications:
firmware interface
S6.8.5Hardware
I6.8.5.1Unit power
I6.8.5.2Unit voltage
I6.8.5.3Info: Brake chopper
I6.8.5.4Info: Brake resistor
S6.8.6Expander boards
September 2006
5-16For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Selection of Language
The control keypad offers you the possibility to control the inverter through the keypad in the
language of your choice.
Locate the language selection page under the System menu. Its location indication is S6.1.
Press Menu Button Right once to enter the edit mode. As the name of the language starts to
blink you can select another language for the keypad texts. Confirm with the ENTER button.
The blinking stops and all text information on the keypad is presented in the selected
language.
You can return to the previous menu any time by pressing Menu Button Left.
M6
System Menu
S1S11
Language
English
Language
English
Langue
Francais
Figure 5-11: Selection of Language
Application Selection
The user can select the desired application on the Application selection page (S6.2). To enter
the page, press Menu Button Right on the first page of the System menu. To change the
application, press Menu Button Right once more. The name of the application starts to blink.
Now you can browse the applications with the Browser buttons and select the desired
application with the ENTER button.
After application change, you will be asked if you want the parameters of the new application
to be uploaded to the keypad. If you want to do this, press the ENTER button. Pressing any
other button leaves the parameters of the previously used application saved in the keypad.
For more information about the application, see the application manual.
MN04004002E
M656.2
System Menu
S1S11
56.256.2
Application
Standard
Application
Standard
Application
Multi-step
Figure 5-12: Change of Application
For more information visit: www.EatonElectrical.com5-17
SPI9000 Inverter Unit FI9 – FI14 User Manual
Copy Parameters
The parameter copy function is used when the operator wants to copy one or all parameter
groups from one drive to another. All the parameter groups are first uploaded to the keypad,
then the keypad is connected to another drive and then the parameter groups are
downloaded to it (or possibly back to the same drive).
Before any parameters can be successfully copied from one drive to another, the drive has to
be stopped when the parameters are downloaded to it:
The parameter copy menu (S6.3) contains four functions:
Parameter Sets (S6.3.1)
The user can reload the factory default parameter values and store and load two customized
parameter sets (all parameters included in the application).
On the Parameter Sets page (S6.3.1), press Menu Button Right to enter the edit mode. The
text LoadFactDef begins to blink and you can confirm the loading of factory defaults by
pressing the ENTER button. The drive resets automatically.
Alternatively, you can choose any other storing or loading functions with the Browser
buttons. Confirm with the ENTER button. Wait until “OK” appears on the display.
September 2006
56.3.1
Parameter sets
Select
56.3.1
Parameter sets
Wait. . .
56.3.1
Parameter sets
LoadFactDef
56.3.1
Parameter sets
OK
Confirm
Cancel
Figure 5-13: Storing and Loading of Parameter Sets
Upload parameters to keypad (To keypad, S6.3.2)
This function uploads all existing parameter groups to the keypad provided that the drive is
stopped.
Enter the To Keypad page (S6.3.2) from the Parameter Copy menu. Pressing Menu Button
Right takes you to the edit mode. Use the Browser buttons to select the option All Parameters
and press the ENTER button. Wait until “OK” appears on the display.
5-18For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
56.3
Copy Parameters
Select
56.3.2
Up to keypad
Wait. . .
P1P4
56.3.2
Up to keypad
Select
56.3.2
Up to keypad
OK
56.3.2
Up to keypad
All param.
Confirm
Change Value
Cancel
Figure 5-14: Parameter Copy to Keypad
Download parameters to drive (From keypad, S6.3.3)
This function downloads one or all parameter groups uploaded to the keypad to a drive
provided that the drive is in STOP status.
Enter the To Keypad page (S6.3.2) from the Parameter Copy menu. Pressing the Menu Button
Right takes you to the edit mode. Use the Browser buttons to select either All Parameters, All
but Motor Parameters or Application Parameters and press the ENTER button. Wait until
“OK” appears on the display.
The procedure to download the parameters from keypad to drive is similar to that of from
drive to keypad. See Figure 5-14.
Automatic Parameter Backup (P6.3.4)
On this page you can activate or inactivate the parameter backup function. Enter the edit
mode by pressing Menu Button Right. Select Yes or No with the Browser buttons.
When the Parameter backup function is activated control keypad makes a copy of the
parameters of the presently used application. When applications are changed, you will be
asked if you wish the parameters of the new application to be uploaded to the keypad. If you
want to do this, press the ENTER button. If you wish to keep the copy of the parameters of the
previously used application saved in the keypad, press any other button. Now you will be
able to download these parameters to the drive following the instructions given in Chapter
Copy Parameters on Page 5-18.
If you want the parameters of the new application to be automatically uploaded to the
keypad, you have to do this for the parameters of the new application once on page 6.3.2 as
instructed. Otherwise the panel will always ask for the permission to upload the parameters.
Note: Parameters saved in the parameter settings on page S6.3.1 will be deleted when
applications are changed. If you want to transfer the parameters from one application
to another, you have to upload them first to the keypad.
MN04004002E
For more information visit: www.EatonElectrical.com5-19
SPI9000 Inverter Unit FI9 – FI14 User Manual
Parameter Comparison
In the Parameter Comparison submenu (S6.4), you can compare the actual parameter values
to the values of your customized parameter sets and those loaded to the control keypad.
You can compare the parameter by pressing Menu Button Right in the Compare Parameters
submenu. The actual parameter values are first compared to those of the customized
parameter Set1. If no differences are detected, “0” is displayed on the lowermost line. If any
of the parameter values differ from those of Set1, the number of the deviations is displayed
together with symbol P (for example, P1➔P5 = five deviating values). By pressing Menu
Button Right once more, you can enter pages where you can see both the actual value and
the value it was compared to. In this display, the value on the description line (in the middle)
is the default value and the one on the value line (lowermost) is the edited value.
Furthermore, you can also edit the actual value with the Browser buttons in the edit mode
which you can enter by pressing Menu Button Right once.
September 2006
56.4
ParamComparison
C1C3
56.4.1
Set1
0
Or
56.4.1
Set1
P1P6
56.4.1.1
P2.1.2= 50.0
20.0 Hz
56.4.1.1
P2.1.2= 50.0
Edit Value
Confirm Change
Figure 5-15: Parameter Comparison
20.0 Hz
5-20For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Safety
Note: The Security submenu is protected with a password. Store the password in a safe
place!
Password (S6.5.1)
The application selection can be protected against unauthorized changes with the Password
function (S6.5.1).
By default, the Password function is not in use. If you want to activate the function, enter the
edit mode by pressing Menu Button Right. A blinking zero appears in the display and you can
set a password with the Browser buttons. The password can be any number between 1 and
65535.
Note: You can also set the password by digits. In the edit mode, push Menu Button Right
again and another zero appears on the display. Set ones first. To set the tens, press
Menu Button Right, and so on. Confirm the password with the ENTER button. After
this, you have to wait until the Timeout time (P6.6.3) (see Page 5-24) has expired before
the password function is activated.
If you try to change applications or the password itself, you will be prompted for the current
password. Enter the password with the Browser buttons.
You can deactivate the password function by entering the value 0.
56.5.1
Password
Not in use
56.5.1
Password
0
Or
56.5.1
Password
00
Figure 5-16: Password Setting
Note: Store the password in a safe place! No changes can be made unless a valid password
is entered.
MN04004002E
For more information visit: www.EatonElectrical.com5-21
SPI9000 Inverter Unit FI9 – FI14 User Manual
Parameter Lock (P6.5.2)
This function allows the user to prohibit changes to the parameters.
If the parameter lock is activated, the text *locked* will appear on the display if you try to edit
a parameter value.
Note: This function does not prevent unauthorized editing of parameter values.
Enter the edit mode by pressing Menu Button Right. Use the Browser buttons to change the
parameter lock status. Confirm the change with the ENTER button or go back to the previous
level by pressing Menu Button Left.
September 2006
M6
S1S9P1P4
56.5.2
Parameter Lock
SecuritySystem Menu
56.5.2
Parameter Lock
ChangeDisablChangeEnable
56.5.2
Parameter Lock
ChangeEnable
Figure 5-17: Parameter Locking
Start-Up Wizard (P6.5.3)
The Start-Up Wizard facilitates the commissioning of the inverter. If active, the Start-Up
Wizard prompts the operator for the language and application of his/her choice and then
displays the first menu or page.
Activating the Start-Up Wizard: In the System Menu, find page P6.5.3. Press Menu Button
Right once to enter the edit mode. Use the Browser buttons to select Yes and confirm the
selection with the ENTER button. If you want to deactivate the function, follow the same
procedure and give the parameter value “NO”.
P6.5.3
Startup wizard
No
P6.5.3
Startup wizard
NoYe s
P6.5.3
Startup wizard
Confirm
Cancel
Figure 5-18: Activation of Start-Up Wizard
5-22For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Multimonitoring Items (P6.5.4)
The alphanumeric keypad features a display where you can monitor up to three actual values
at the same time — see Monitoring Menu (M1) on Page 5-7 and the manual of the application
you are using. On page P6.5.4 of the System Menu, you can define whether the operator can
replace the values monitored with other values. See below.
56.5.4
Multimon. items
ChangeEnable
56.5.4
Multimon. items
56.5.4
Multimon. items
ChangeDisableChangeEnable
Figure 5-19: Disabling the Change of Multimonitoring Items
Keypad Settings
In the Keypad Settings submenu under the System menu, you can further customize your
inverter operator interface.
Locate the Keypad Setting submenu (S6.6). Under the submenu, there are four pages (P#)
associated with the keypad operation:
5.6.6P6.6.
Keypad settings
P1P5
Default page
0.
Figure 5-20: Keypad Settings Submenu
Default Page (P6.6.1)
MN04004002E
Here you can set the location (page) to which the display automatically moves when the
Timeout Time (see below) has expired or the power is switched on to the keypad.
If the default page is 0, the function is not activated, i.e. the latest displayed page remains on
the keypad display. Pressing Menu Button Right takes you to the edit mode. Change the
number of the Main menu with the Browser buttons. To edit the number of the submenu/
page, press Menu Button Right. If the page you want to move to by default is at the third
level, repeat the procedure. Confirm the new default page with the ENTER button. You can
return to the previous menu at any time by pressing Menu Button Left.
P6.6.
Default page
0.
P6.6.
Default page
0.
P6.6.
Default page
1.
Confirm Change
Repeat to Set
Default Submenu/Page
Cancel
Figure 5-21: Default Page Function
For more information visit: www.EatonElectrical.com5-23
SPI9000 Inverter Unit FI9 – FI14 User Manual
Default page in the operating menu (P6.6.2)
Here you can set the location (page) in the Operating menu (in special applications only) to
which the display automatically moves to when the set Timeout Time (see below) has expired
or the power is switched on to the keypad.
See how to set the Default page in Figure 5-21.
Timeout Time (P6.6.3)
The Timeout Time setting defines the time after which the keypad display returns to the
Default page (P6.6.1).
Enter the edit mode by pressing Menu Button Right. Set the desired timeout time and
confirm it with the ENTER button. You can return to the previous menu at any time by
pressing Menu Button Left.
September 2006
P6.6.3
Timeout time
90 s
P6.6.3P6.6.3
Timeout time
90 s.
Timeout time
60 s.
Confirm Change
Cancel
Figure 5-22: Timeout Time Setting
Note: If the Default page value is 0, the Timeout Time setting has no effect.
Contrast Adjustment (P6.6.4)
In case the display is unclear, you can adjust its contrast through the same procedure as for
the timeout time setting (see above).
Backlight Time (P6.6.5)
By giving a value for the Backlight time, you can determine how long the backlight stays on
before going out. You can select any time between 1 and 65535 minutes or “Forever.” For the
value setting procedure, see Timeout Time above.
5-24For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Hardware Settings
Note: The Hardware settings submenu is protected with a password. Store the password in a
safe place!
In the Hardware Settings submenu (S6.7) under the System menu, you can further control
some functions of the hardware in your inverter. The functions available in this menu are
Internal brake resistor connection, Fan control, HMI acknowledge timeout and HMI retry.
Internal Brake Resistor Connection (P6.7.1)
This function tells the inverter, whether the internal brake resistor is connected or not. If you
have ordered the inverter with an internal brake resistor, the default value of this parameter is
Connected. However, if it is necessary to increase braking capacity by installing an external
brake resistor, or if the internal brake resistor is disconnected for another reason, it is
advisable to change the value of this function to Not conn. in order to avoid unnecessary
fault trips.
Enter the edit mode by pressing Menu Button Right. You can change the brake resistor
information with the Browser buttons. Confirm the change with the ENTER button or return
to the previous level with Menu Button Left.
Note: The brake resistor is available as optional equipment for all classes. It can be installed
internally in classes FR4 to FR6.
M6
S1S8P1P4
P6.7.
InternBrakeRes
56.7
HW SettingsSystem Menu
P6.7.
InternBrakeRes
Not conn.Connected
P6.7.
InternBrakeRes
Connected
Figure 5-23: Internal Brake Resistor Connection
MN04004002E
For more information visit: www.EatonElectrical.com5-25
SPI9000 Inverter Unit FI9 – FI14 User Manual
Fan Control (P6.7.2)
This function allows you to control the cooling fan of the inverter. You can set the fan to run
continuously when the power is switched on or depending on the temperature of the unit. If
the latter function has been selected, the fan is switched on automatically when the heatsink
temperature reaches 60°C. The fan receives a stop command when the heatsink temperature
falls to 55°C. After the command, the fan runs for approximately 1 minute before stopping.
The same happens after switching on the power and after changing the value from
Continuous to Temperature.
Note: The fan runs always when the drive is in RUN state.
To change the value: Enter the edit mode by pressing Menu Button Right. The value starts
blinking. Use the Browser buttons to change the fan mode and confirm the change with the
ENTER button. If you do not want to change the value, return to the previous level with Menu
Button Left. See Figure 5-24.
September 2006
P6.7.2
Fan control
Continuous
P6.7.2P6.7.2
Fan control
Continuous
Fan control
Temperature
Figure 5-24: Fan Control Function
HMI Acknowledge Timeout (P6.7.3)
This function allows the user to change the timeout of the HMI acknowledgement time. The
inverter waits for the HMI acknowledgment in accordance with the value of this parameter.
Note: If the inverter has been connected to the PC with a normal cable, the default values of
parameters 6.7.3 and 6.7.4 (200 and 5) must not be changed.
If the inverter has been connected to the PC via a modem and there is a delay in transferring
messages, the value of parameter 6.7.3 must be set according to the delay as follows:
Example:
●Transfer delay between the inverter and the PC = 600 ms
●The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving delay)
●The corresponding setting shall be entered in the [Misc] part of the file NCDrive.ini:
– Retries = 5
– AckTimeOut = 1200
– TimeOut = 6000
●It must also be considered that intervals shorter than the AckTimeOut time cannot be
used in NC-Drive monitoring.
Enter the edit mode by pressing Menu Button Right. The current value starts to blink. Use the
Browser buttons to change the acknowledgement time. Confirm the change with the ENTER
button or return to the previous level with Menu Button Left.
5-26For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
P6.7.3
HMI ACK timeout
200ms
P6.7.3
HMI ACK timeout
200ms
Figure 5-25: HMI Acknowledge Timeout
Number of retries to receive HMI acknowledgement (P6.7.4)
With this parameter you can set the number of times the drive will try to receive
acknowledgement if it does not receive acknowledgement within the acknowledgement time
(P6.7.3) or if the received acknowledgement is faulty.
You can change value through the same procedure as for P6.7.3 (see above).
Note: Changes to P6.7.3 and P6.7.4 become effective after the next start-up.
System info
In the System info submenu (S6.8) you can find inverter-related hardware and software
information.
You can enter the System info submenu by pressing Menu Button Right. You can now
browse the submenu pages with the Browser buttons.
Total Counters
The Total counters menu (S6.8.1) contains information on the inverter operation times i.e. the
total number of MWh, operation days and operation hours. Unlike the counters in the Trip
counters menu, these counters cannot be reset.
Note: The Power On time counter (days and hours) runs always when the power is on.
Table 5-11: Counter Pages
PageCounter
C6.8.10.1MWh counter
C6.8.10.2Operation day counter
C6.8.1.3.Operation hour counter
MN04004002E
For more information visit: www.EatonElectrical.com5-27
SPI9000 Inverter Unit FI9 – FI14 User Manual
Trip Counters
Trip counters (menu S6.8.2) are counters the values of which can be reset i.e. restored to
zero. You can use the following resettable counters:
Note: The trip counters run only when the motor is running.
Table 5-12: Resettable Counters
PageCounter
T6.8.2.1MWh counter
T6.8.2.3Operation day counter
T6.8.2.4Operation hour counter
The counters can be reset on pages 6.8.2.2 (Clear MWh counter) and 6.8.2.5 (Clear Operation
time counter).
Example: When you want to reset the operation counters, see Figure 5-26.
September 2006
56.8.2P6.8.2.5
Trip counters
T1T5
P6.8.2.5
Clr Optime cntr
Reset
Clr Optime cntr
Not reset
P6.8.2.5
Clr Optime cntr
Reset
P6.8.2.5
Clr Optime cntr
Not reset
P6.8.2.5
Clr Optime cntr
Not reset
Figure 5-26: Counter Reset
Software (S6.8.3)
The Software information page includes information on the following inverter software
related topics:
Table 5-13: Software Information Pages
PageCounter
6.8.3.1Software packages
6.8.3.2System software version
6.8.3.3Firmware interface
6.8.3.4System load
5-28For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Applications (S6.8.4)
At location S6.8.4, you can find the Applications submenu containing information on the
application currently in use and all other applications loaded into the inverter. The following
information is available:
Table 5-14: Applications Information Pages
PageCounter
6.8.4.#Name of application
6.8.4.#.1Application ID
6.8.4.#.2Version
6.8.4.#.3Firmware interface
In the Applications information page, press Menu Button Right to enter the Application pages
of which there are as many as there are applications loaded into the inverter. Locate the
desired application with the Browser buttons and then enter the Information pages with
Menu Button Right. Use the Browser buttons to see the different pages.
56.8.4
Applications
A1A7D1D3
Standard
D1D3
R6.8.4.
Basic
Version
2.01
R6.8.4. .
Application id
FIFF01
Figure 5-27: Applications Info Submenu
Hardware (S6.8.5)
The Hardware information page provides information on the following hardware-related
topics:
Table 5-15: Hardware Information Pages
PageCounter
6.8.5.1Nominal power of the unit
6.8.5.2Nominal voltage of the unit
6.8.5.3Brake chopper
6.8.5.4Brake resistor
MN04004002E
For more information visit: www.EatonElectrical.com5-29
SPI9000 Inverter Unit FI9 – FI14 User Manual
Expander Boards (S6.8.6)
The Expander boards submenu contains information about the basic and option boards. (See
Chapter Control unit)
You can check the status of each board slot by entering the Expander Boards page with Menu
Button Right. Use the Browser buttons to view the status of each board slot. The description
line of the keypad will display the type of the expansion board and the text “Run” is shown
below it. If no board is connected to the slot the text “no board” will be shown. If a board is
connected to a slot but the connection is lost for some reason, the text “no conn.” is
displayed. For more information, see Chapter 4.
For more information on expander board related parameters, see Page 5-30.
September 2006
56.8.6
Expander boards
Expander Board Menu (M7)
In the Expander board menu the user can 1) see the expander boards connected to the
control board and 2) see and edit the parameters associated with the expander boards.
Go to the next menu level (G#) with Menu Button Right. At this level, you can browse through
slots A to E with the Browser buttons to see which expander boards are connected to the
control board. On the lowermost line of the display, you will also see the number of
parameters associated with the board. You can view and edit the parameter values as
described on Page 5-8. See Table 5-16 and Figure 5-29.
B:OPTA2
E1E2
E6.8.6.
A:OPTA1
E1E5E1E2
Software version
10001.0
E6.8.6. .
State
Run
Figure 5-28: Expander Board Information Menus
5-30For more information visit: www.EatonElectrical.comMN04004002E
2 = 4 to 20 mA
3 = 0 to 10V
4 = 2 to 10V
5 = –10 to +10 V
2 = 4 to 20 mA
3 = 0 to 10V
4 = 2 to 10V
V1V2
Baud rate
Auto
Further Keypad Functions
The control keypad contains additional application-related functions. See the application
manual for more information.
MN04004002E
Figure 5-29: Expander Board Information Menu
For more information visit: www.EatonElectrical.com5-31
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
5-32For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Chapter 6 — Start-Up
Safety Precautions
Before start-up, note the following directions and warnings:
SPI9000 Inverter Unit FI9 – FI14 User Manual
WARNING
1
2
3
4
5
6
Internal components and circuit boards of the inverter
(except for the galvanically isolated I/O terminals) are live
when the inverter is connected to mains potential. Coming
into contact with this voltage is extremely dangerous and
may cause death or severe injury.
The motor terminals U, V, W and the DC-link/brake resistor
terminals+/- are live when the inverter is connected to DC
supply, even if the motor is not running.
The control I/O-terminals are isolated from the mains
potential. However, the relay outputs and other I/Oterminals may have a dangerous control voltage present
even when the inverter is disconnected from DC supply.
Do not make any connections when the inverter is
connected to the DC supply.
After having disconnected the inverter, wait until the fan
stops and the indicators on the keypad go out (if no keypad
is attached see the indicator through the keypad base). Wait
5 more minutes before doing any work on inverter
connections. Do not open the cover before the time has
expired.
Before connecting the inverter to DC supply, make sure that
the inverter’s front cover is closed.
MN04004002E
7
8
When running, the side of inverter FR8 is burning hot. Do
not touch it with bare hands!
When running, the back of inverter FR6 is burning hot.
Therefore it MUST NOT be mounted onto a surface which is
not fireproof.
For more information visit: www.EatonElectrical.com6-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Sequence of Operation
1. Read the safety instructions in the front of this manual carefully and follow them.
2. After installation, make sure:
●Both the inverter and the motor are grounded
●DC supply and motor cables comply with the requirements given in Chapter 3
●Control cables are located as far as possible from the power cables (see
Chapter 2), and the shields of the shielded cables are connected to protective
ground. The wires must not touch the electrical components of the inverter.
●Common inputs of digital input groups are connected to +24V or the ground of the
I/O terminal or the external supply.
3. Check the quality and quantity of cooling air. (See Chapter 2, Mounting Space
Dimensions.)
4. Check the inside of the inverter for condensation.
5. Check that all Start/Stop switches connected to the I/O terminals are in the Stop
position.
September 2006
6. Connect the inverter to DC supply.
7. Set the parameters of group 1 according to the requirements of your application (see
application manual). Set the following parameters at the least:
●Motor nominal voltage
●Motor nominal frequency
●Motor nominal speed
●Motor nominal current
You will find the values needed for the parameters on the motor rating plate.
8. Perform either Test A or B without the motor running:
Test A — Controls from the I/O terminals:
●Turn the Start/Stop switch to ON position.
●Change the frequency reference (potentiometer).
●Check in the Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
●Turn the Start/Stop switch to OFF position.
Test B— Control from the Control keypad:
●Change the control from the I/O terminals to the keypad as advised on Page 5-10.
●Press the START button on the keypad.
●Move over to the Keypad Control Menu M3 and Keypad Reference submenu (see
Keypad Reference on Page 5-10) and change the frequency reference with the
Browser buttons.
6-2For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
●Check in Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
●Press the STOP button on the keypad.
9. Perform the start-up tests without the motor being connected to the process. If this is
not possible, make sure that each test can be done safely prior to performing it. Inform
your co-workers of the tests.
●Switch off the DC supply voltage and wait until the drive has stopped as advised on
Page 6-1, Safety Precautions.
●Connect the motor cable to the motor and to the motor cable terminals of the
inverter.
●Make sure that all Start/Stop switches are in Stop positions.
●Switch the supply voltage ON.
●Repeat Test A or B in step 8.
10. Connect the motor to the process (if the start-up test was performed without the motor
being connected). Inform our co-workers of the tests.
●Before running the tests, make sure that this can be done safely.
●Repeat Test A or B in step 8.
MN04004002E
For more information visit: www.EatonElectrical.com6-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
6-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
Appendix A — Fault Codes
When a fault is detected by the inverter control electronics, the drive is stopped and the
symbol F together with the ordinal number of the fault, the fault code and a short fault
description appear on the display. The fault can be reset with the RESET button on the
control keypad or via the I/O terminal. The faults are stored in the Fault History Menu M5,
which can be browsed. Table A-1 contains all the fault codes.
Table A-1: Fault Codes
Fault
Code FaultPossible CauseSolution
SPI9000 Inverter Unit FI9 – FI14 User Manual
1OvercurrentInverter detected too high a current
(>4 x I
) in the motor cable:
n
• Sudden heavy load increase
• Short circuit in the motor
• Unsuitable motor
2OvervoltageThe DC link voltage exceeded the
defined limits:
• Deceleration time too short
• High overvoltage spikes in supply
3Ground Fault
Current measurement has detected
that the sum of motor phase currents
is not zero.
• Insulation failure in cables or
motor
5Charging SwitchCharging switch is open, when the
START command is given:
• Faulty operation
• Component failure
6Emergency StopStop signal was given from the
option board.
7Saturation TripVarious causes:
• Component failure
• Brake resistor is short circuited or
overloaded
8System Fault• Component failure
• Faulty operation
Note: See exceptional fault data
record on Page 5-12.
Programmable.
Check loading.
Check motor.
Check cables.
Set the deceleration time longer.
Add a brake chopper or brake
resistor.
Check motor cable and motor.
Reset the fault and restart.
Should the fault re-occur, contact
your Cutler-Hammer distributor.
Cannot be reset from the keypad.
Switch off the power.
DO NOT RE-CONNECT POWER.
Contact Eaton.
If this fault appears simultaneously
with Fault 1, check motor cables and
motor.
Reset the fault and restart.
Should the fault re-occur, contact
your Cutler-Hammer distributor.
MN04004002E
For more information visit: www.EatonElectrical.comA-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table A-1: Fault Codes (Continued)
Fault
Code FaultPossible CauseSolution
9Undervoltage
10Input Line
Supervision
11Output phase
supervision
12Brake Chopper
Supervision
13Inverter
Undertemperature
14Inverter
Overtemperature
15Motor Stalled
16Motor
Overtemperature
17Motor underload
22EEPROM
checksum fault
24Counter faultValues displayed on counters are
25Microprocessor
watchdog fault
26Startup prevented Start-up of the drive was prevented. Cancel prevention of start-up.
29Thermistor fault
Programmable.
DC link voltage is below the defined
voltage limits:
• Supply voltage too low (most
probable cause)
• Inverter internal fault
In case of temporary supply voltage
break, reset the fault and restart the
inverter. Check the supply voltage. If
it is adequate, an internal failure has
occurred.
Contact your Cutler-Hammer
distributor.
Input line phase is missing.Check supply voltage and cable.
Current measurement has detected
Check motor cable and motor.
there is no current in one motor
phase.
• No brake resistor installed
• Brake resistor is broken
• Brake chopper failure
Check brake resistor.
If the resistor is OK, the chopper is
faulty.
Contact your Cutler-Hammer
distributor.
Heatsink temperature is under -10°C
Heatsink temperature is over 90°C.
Check the correct amount and flow of
cooling air.
Overtemperature warning is issued
when the heatsink temperature
exceeds 85°C.
Check the heatsink for dust.
Check the ambient temperature.
Make sure that the switching
frequency is not too high in relation
to ambient temperature and motor
load.
Motor stall protection has tripped.Check motor.
• Motor overheating was detected
by inverter motor temperature
model
Decrease the motor load.
If no motor overload exists, check the
temperature model parameters.
• Motor is overloaded
Motor underload protection tripped.
Parameter save fault
• Faulty operation
• Component failure
incorrect.
• Faulty operation
• Component failure
Reset the fault and restart.
Should the fault re-occur, contact
your Cutler-Hammer distributor.
The thermistor input of option board
detected an increase in the motor
temperature.
Check motor cooling and loading.
Check thermistor connection.
(If thermistor input of the option
board is not in use, it has to be short
circuited.)
September 2006
A-2For more information visit: www.EatonElectrical.comMN04004002E
Check motor size.
a short term overload current that is
too high.
32Fan CoolingCooling fan of the inverter does not
start, when ON command is given.
34CAN Bus
Sent message not acknowledged.Ensure that there is another device
Communication
Contact your Cutler-Hammer
distributor.
on the bus with the same
configuration.
36Control UnitControl unit cannot control power
Change control unit.
unit and vice versa.
37Device Change
(same type)
• Option board or control unit
changed
Reset
Note: No fault time data record.
• Option board of different type or
drive with different power rating
38Device Added
(same type)
• Option board or drive added
• Drive with same power rating or
Reset
Note: No fault time data record.
same type of board added
39Device Removed
• Option board removed
• Drive removed
Reset
Note: No fault time data record.
40Device UnknownUnknown option board or drive.Contact your Cutler-Hammer
distributor.
41IGBT Temperature IGBT Inverter Bridge
overtemperature protection has
Check loading.
Check motor size.
detected a short term overload
current that is too high.
42Brake Resistor
Overtemperature
Brake resistor overtemperature
protection detected braking that is
Set the deceleration time longer.
Use external brake resistor.
too heavy.
43Encoder FaultNote: See the exceptional fault data
record on Page 5-12. Additional
Check encoder channel connections.
Check the encoder board.
codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are
missing
4 = Encoder reversed
44Device Change
(different type)
• Option board or control unit
changed
• Option board of different type or
drive with different power rating
Reset.
Note: No fault time data record is
made.
Note: Application parameter values
restored to default.
45Device Added
(different type)
• Option board or device added
• Option board of different type or
drive with different power rating
added
Reset.
Note: No fault time data record is
made.
Note: Application parameter values
restored to default.
Programmable.
“A” faults only.
MN04004002E
For more information visit: www.EatonElectrical.comA-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table A-1: Fault Codes (Continued)
Fault
Code FaultPossible CauseSolution
September 2006
50Analog Input
(signal range,
4 to 20 mA)
Current for analog input is < 4 mA:
• Control cable is broken or loose
• Signal source failed
Check the current loop, signal source
and wiring.
51External FaultDigital input failed.Check source of trigger.
52Keypad
communication
There is no connection between the
control keypad and the inverter.
Check the keypad connection and
keypad cable.
Fault
53Fieldbus FaultThe data connection between the
fieldbus master and the fieldbus
board is broken.
Check installation.
If installation is correct, contact your
Cutler-Hammer distributor.
54Slot FaultDefective option board or slot.Check that the board is properly
installed and seated in slot. If the
installation is correct, contact your
Cutler-Hammer distributor.
56PT100 Board
Temperature Fault
Programmable.
Temperature limit values set for the
PT100 board have been exceeded.
Determine the cause of the high
temperature.
A-4For more information visit: www.EatonElectrical.comMN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E
For more information visit: www.EatonElectrical.comA-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
A-6For more information visit: www.EatonElectrical.comMN04004002E
Company Information
Eaton’s electrical business is a global leader in electrical control, power distribution, and
industrial automation products and services. Through advanced product development,
world-class manufacturing methods, and global engineering services and support,
Eaton’s electrical business provides customer-driven solutions under brand names such
as Cutler-Hammer®, Powerware®, Durant®, Heinemann®, Holec® and MEM®, which
globally serve the changing needs of the industrial, utility, light commercial, residential,
and OEM markets. For more information, visit www.EatonElectrical.com.
Eaton Corporation is a diversified industrial manufacturer with 2005 sales of $11.1 billion.
Eaton is a global leader in electrical systems and components for power quality, distribution
and control; fluid power systems and services for industrial, mobile and aircraft equipment;
intelligent truck drivetrain systems for safety and fuel economy; and automotive engine air
management systems, powertrain solutions and specialty controls for performance, fuel
economy and safety. Eaton has 60,000 employees and sells products to customers in more
than 125 countries. For more information,
visit www.
eaton.com.
Eaton Electrical Inc.
1000 Cherrington Parkway
Moon Township, PA 15108-4312
USA
tel: 1-800-525-2000
www.EatonElectrical.com