Eaton Electrical SPI9000 User Manual

SPI9000 Inverter Unit FI9 – FI14
User Manual
MN04004002E For more information visit: www.EatonElectrical.com
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Important Notice – Please Read
The product discussed in this literature is subject to terms and conditions outlined in Eaton Electrical Inc. selling policies. The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton Electrical Inc. selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton Electrical Inc. be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.
The information contained in this manual is subject to change without notice.
®
Cover Photo: Cutler-Hammer
SPI9000 Inverter Unit.
MN04004002E For more information visit: www.EatonElectrical.com
i
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table of Contents
LIST OF FIGURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
LIST OF TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Definitions and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Hazardous High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Warnings, Cautions and Notices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
CHAPTER 1 — OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Receiving and Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
CHAPTER 2 — MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Fan Cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
CHAPTER 3 — POWER WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Frame Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Cable Installation and the UL Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Cable and Motor Insulation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
CHAPTER 4 — CONTROL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Control Wiring Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Control Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Galvanic Isolation Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Digital Input Signal Inversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Jumper Selections on Option Board A9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
CHAPTER 5 — MENU INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Keypad Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Indicators on the Keypad Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Keypad Pushbuttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Further Keypad Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
CHAPTER 6 — START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
APPENDIX A — FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
September 2006
ii
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
List of Figures
Figure 1-1: SPI9000 Inverter Unit Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Figure 2-1: SPI9000 FI9 Inverter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Figure 2-2: SPI9000 FI10 Inverter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Figure 2-3: SPI9000 FI12 Inverter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Figure 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13) . . . . . . . . . . . . . . . 2-4
Figure 2-5: Installation Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Figure 3-1: FI9/FI10 Basic Wiring Diagram with Charging . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Figure 3-2: FI9/FI10 Basic Wiring Diagram without Charging . . . . . . . . . . . . . . . . . . . . . . 3-2
Figure 3-3: FI12 Basic Wiring Diagram with Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-4: FI12 Basic Wiring Diagram without Charging . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-5: FI13 Basic Wiring Diagram with Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Figure 3-6: FI13 Basic Wiring Diagram without Charging . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Figure 3-7: FI14 Basic Wiring Diagram with Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-8: FI14 Basic Wiring Diagram without Charging . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Figure 4-1: Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Figure 4-2: Basic and Option BoardConnections of the Control Board . . . . . . . . . . . . . . 4-1
Figure 4-3: Inverters Connected in Parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 4-4: I/O Terminals of the Two Basic Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 4-5: Option Board A9 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Figure 4-6: Option Board A2 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Figure 4-7: Option Board A3 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Figure 4-8: Galvanic Isolation Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Figure 4-9: Positive/Negative Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Figure 4-10: Jumper Blocks on Option Board A9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Figure 4-11: Jumper Selection for Option Board A9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Figure 5-1: Control Keypad and Drive Status Indications . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Figure 5-2: Keypad Pushbuttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Figure 5-3: Keypad Display Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Figure 5-4: Keypad Navigation Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Figure 5-5: Monitoring Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Figure 5-6: Parameter Value Change Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Figure 5-7: Selection of Control Place . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Figure 5-8: Normal State, No Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Figure 5-9: Fault Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Figure 5-10: Fault History Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Figure 5-11: Selection of Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
Figure 5-12: Change of Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
Figure 5-13: Storing and Loading of Parameter Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
Figure 5-14: Parameter Copy to Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
Figure 5-15: Parameter Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
Figure 5-16: Password Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
Figure 5-17: Parameter Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Figure 5-18: Activation of Start-Up Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Figure 5-19: Disabling the Change of Multimonitoring Items . . . . . . . . . . . . . . . . . . . . . . 5-23
Figure 5-20: Keypad Settings Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Figure 5-21: Default Page Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Figure 5-22: Timeout Time Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
Figure 5-23: Internal Brake Resistor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25
Figure 5-24: Fan Control Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E For more information visit: www.EatonElectrical.com
iii
SPI9000 Inverter Unit FI9 – FI14 User Manual
Figure 5-25: HMI Acknowledge Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27
Figure 5-26: Counter Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Figure 5-27: Applications Info Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Figure 5-28: Expander Board Information Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
Figure 5-29: Expander Board Information Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
List of Tables
Table 1-1: FI9 – FI14 Inverter Unit Catalog Numbering System . . . . . . . . . . . . . . . . . . . . 1-1
Table 1-2: 380 – 500V AC, 50/60 Hz, Three-Phase Inverters Ratings . . . . . . . . . . . . . . . . . 1-4
Table 1-3: 525 – 690V AC, 50/60 Hz, Three-Phase Inverters Ratings . . . . . . . . . . . . . . . . . 1-5
Table 1-4: Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Table 1-5: DC Currents for 465 – 800V DC Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Table 1-6: DC Currents for 640 – 1100V DC Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . 1-8
Table 2-1: SPI9000 FI9 Inverter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Table 2-2: SPI9000 FI10 Inverter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Table 2-3: SPI9000 FI12 Inverter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Table 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13) . . . . . . . . . . . . . . . . 2-4
Table 2-5: Mounting Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Table 2-6: Required Cooling Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Table 3-1: Cable Types Required to Meet Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Table 3-2: Fuses Used in 465 – 800V DC Inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Table 3-3: Fuses Used in 640 – 1100V DC Inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Table 3-4: Cable Sizes for 380 – 500V AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Table 3-5: Terminal Sizes for 380 – 500V AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Table 3-6: Cable Sizes for 525 – 690V AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Table 3-7: Terminal Sizes for 525 – 690V AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Table 3-8: Cable Distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Table 3-9: Terminal Tightening Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Table 4-1: Tightening Torques of Option Board Terminals . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Table 4-2: Control I/O Terminal Signals on Option Board A9 . . . . . . . . . . . . . . . . . . . . . . 4-6
Table 4-3: Control I/O Terminal Signals on Option Board A2 . . . . . . . . . . . . . . . . . . . . . . 4-7
Table 4-4: Control I/O Terminal Signals on Option Board A3 . . . . . . . . . . . . . . . . . . . . . . 4-7
Table 5-1: Drive Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Table 5-2: Control Place Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Table 5-3: Status LEDs (Green – Green – Red) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Table 5-4: Text Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Table 5-5: Button Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Table 5-6: Monitored Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Table 5-7: Fault Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
Table 5-8: Fault Time Recorded Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Table 5-9: Real Time Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Table 5-10: System Menu Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Table 5-11: Counter Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27
Table 5-12: Resettable Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Table 5-13: Software Information Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Table 5-14: Applications Information Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Table 5-15: Hardware Information Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Table 5-16: Expander Board Parameters (Board OPTA9). . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
Table A-1: Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
September 2006
iv
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Safety
Definitions and Symbols
This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with either of two signal words: CAUTION or WARNING, as described below.
SPI9000 Inverter Unit FI9 – FI14 User Manual
WARNING
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death.
Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results. Important safety measures are described in CAUTION (as well as WARNING).
Hazardous High Voltage
Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.
WARNING
CAUTION
WARNING
MN04004002E For more information visit: www.EatonElectrical.com
v
SPI9000 Inverter Unit FI9 – FI14 User Manual
Warnings, Cautions and Notices
September 2006
Warnings
Read this manual thoroughly and make sure you understand the procedures before you attempt to install, set up, or operate this Cutler-Hammer electrical business.
®
SPI9000 Inverter Unit from Eaton’s
WARNING
Only a competent electrician may carry out the electrical installation.
WARNING
The components of the power unit of the inverter are live when the SPI9000 inverter is connected to DC supply. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is isolated from mains potential.
WARNING
The supply and motor terminals are live when the inverter is connected to DC supply, even if the motor is not running.
WARNING
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have dangerous control voltage present even when the inverter unit is disconnected from the DC supply.
WARNING
The inverter has a large capacitive leakage current.
WARNING
If the inverter is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1).
WARNING
Only spare parts delivered by Eaton can be used.
vi
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Cautions
SPI9000 Inverter Unit FI9 – FI14 User Manual
CAUTION
The SPI9000 inverter is meant for fixed installations only.
CAUTION
Do not perform any measurements when the inverter is connected to the DC supply.
CAUTION
After having disconnected the inverter from the DC supply, wait until the fan stops and the indicators on the keypad go out (if no keypad is attached see the indicator through the keypad base). Wait 5 more minutes before doing any work on inverter connections. Do not even open the cover before this time has expired.
CAUTION
Do not perform any voltage withstand tests on any part of inverter. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
CAUTION
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the inverter.
CAUTION
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
CAUTION
Before connecting the inverter to DC supply, make sure that the inverter front and cable covers are closed.
CAUTION
Ensure that the jumper positions are correct. Running the motor with signal settings that differ from the jumper positions will not harm the inverter but may harm the motor.
MN04004002E For more information visit: www.EatonElectrical.com
vii
SPI9000 Inverter Unit FI9 – FI14 User Manual
Grounding and ground fault protection
The SPI9000 inverter must always be grounded with a ground conductor connected to the ground terminal.
The ground fault protection inside the inverter only protects the inverter against ground faults in the motor or the motor cable.
Due to the high capacity currents present in the inverter, fault current protective switches may not function properly. If fault current protective switches are used, they need to be tested with ground fault currents present during possible fault situations.
Motor and Equipment Safety
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
CAUTION
September 2006
CAUTION
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
CAUTION
Before reversing the motor, make sure that this can be done safely.
CAUTION
Make sure that no power correction capacitors are connected to the motor cable.
CAUTION
Make sure that the motor terminals are not connected to mains potential.
viii
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
Chapter 1 — Overview
Receiving and Inspection
Cutler-Hammer scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no sign of transportation damage is to be found on the product and that the delivery is complete (compare the type designation of the product to the code below, see Table 1-1 ).
If the drive has been damaged during shipping, please contact the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.
Table 1-1: FI9 – FI14 Inverter Unit Catalog Numbering System
®
SPI9000 Inverter Units from Eaton’s electrical business have undergone
SPI9000 Inverter Unit FI9 – FI14 User Manual
Product Family
SPI = Inverter Unit
Current Rating
380 – 500V
140 = 140A 170 = 170A 205 = 205A 245 = 245A 300 = 300A 385 = 385A 460 = 460A 520 = 520A 590 = 590A 650 = 650A
525 – 690V
100 = 100A 125 = 125A 144 = 144A 170 = 170A 208 = 208A 261 = 261A 325 = 325A 385 = 385A 460 = 460A
S P I 0 1 6 A 0 –4A 1 N 1
N = No Brake Chopper Circuit
730 = 730A 820 = 820A
920 = 920A H10 = 1030A H11 = 1150A H13 = 1300A H16 = 1600A H19 = 1940A H23 = 2300A
502 = 502A
590 = 590A
650 = 650A
820 = 820A
920 = 920A H10 = 1030A H13 = 1300A H15 = 1500A H19 = 1900A
A = Alphanumeric
Voltage Rating
4 = 380 – 500V AC 5 = 525 – 690V AC
Enclosure Rating
0 = Chassis
Software Series
A = Standard
Input Options
1 = Three-Phase
Keypad
Board Modifications
1 = Standard Boards
Brake Chopper Options
MN04004002E
For more information visit: www.EatonElectrical.com
1-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Standard Features of SPI Inverter Units
Air cooling
Standard board
Alphanumeric control panel with fiber connection
EMC Class T (EN 61800-3 for IT networks)
Safety CE / UL
External charging required
I/O Modules A1 and A2
IP00
Storage
If the inverter is to be stored before use, make sure that the ambient conditions are acceptable.
September 2006
Storage temperature: -40 to 158°F (-40 to 70°C)
Relative humidity: <95%, no condensation
If the inverter is stored for over 12 months, contact Eaton before connecting the inverter to the power supply.
Maintenance
In normal conditions, Cutler-Hammer inverters are maintenance-free. However, we recommend cleaning the heatsink with compressed air whenever necessary. The cooling fan can easily be changed if required.
It may also be necessary to check the tightening torques of terminals at certain intervals.
Technical Data
Figure 1-1 presents the block diagram of the SPI9000 inverter. The inverter mechanically
consists of two units, the Power Unit and the Control Unit.
The Power Unit contains an inverter bridge which consists of IGBT switches and produces symmetrical, three-phase PWM-modulated AC voltage to the motor.
The Motor and Application Control Block is based on microprocessor software. The microprocessor controls the motor based on the information it receives through measurements, parameter settings, control I/O and the control keypad. The motor and application control block control the motor control ASIC which, in turn, calculates the IGBT positions. Gate drivers amplify these signals for driving the IGBT inverter bridge.
1-2
For more information visit: www.EatonElectrical.com
MN04004002E
September 2006
+
B
SPI9000 Inverter Unit FI9 – FI14 User Manual
Power Module
U
IGBT
Bridge
B
Keypad
Power
Supply
Fan
Control Module
RS-232
I/O
Slot A
Measurements
I/O
Slot B
ASIC
Control
I/O
Slot C
Driver
I/O
Slot D
I/O
Slot E
V
W
MN04004002E
Figure 1-1: SPI9000 Inverter Unit Block Diagram
The control keypad constitutes a link between the user and the inverter. The control keypad is used for parameter setting, reading status data and giving control commands. It is detachable and can be operated externally and is connected via a cable to the inverter. Instead of the control keypad, a PC can be used to control the inverter if connected through a similar cable.
The basic control interface and the parameters (the Basic Application) are easy to use. If a more versatile interface or parameters are required, a more suitable application can be chosen. See the application manual for more information on the different applications.
Optional I/O expander boards that increase the number of inputs and outputs to be used are also available. For more information, contact Eaton.
For more information visit: www.EatonElectrical.com 1-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
Power Ratings
Supply Voltage 465 – 800V DC, Motor Voltage 380 – 500V AC
High overload = Maximum current IS, 2 sec./20 sec., 150% overloadability, 1 min./10 min.
Following continuous operation at rated output current, 150% rated output current (IH) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Maximum current IS, 2 sec./20 sec., 110% overloadability, 1 min./10 min.
Following continuous operation at rated output current, 110% rated output current (IL) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
Table 1-2: 380 – 500V AC, 50/60 Hz, Three-Phase Inverters Ratings
Motor Shaft Power
675V DC Supply
10% Over­load 40°C P (kW)
110 132 160 200
250 315 355
400 450 500
560 630 710
800 900
1000
1200 1500 1800
Nominal Current
140 170 205 245
300 385 460
520 590 650
730 820 920
1030 1150 1300
1600 1940 2300
Loadability
Low High
10% Rated Cont. Current
(A)
I
L
170 205 261 300
385 460 520
590 650 730
820 920
1030
1150 1300 1450
1770 2150 2700
Over-
load
Current
(A)
187 226 287 330
424 506 572
649 715 803
902 1012 1133
1265 1430 1595
1947 2365 2970
Rated Cont. Current IH (A)
140 170 205 245
300 385 460
520 590 650
730 820 920
1030 1150 1300
1600 1940 2300
50% Over­load Current (A)
210 255 308 368
450 578 690
780 885 975
1095 1230 1380
1545 1725 1950
2400 2910 3287
Max Current I
S
280 336 349 444
540 693 828
936 1062 1170
1314 1476 1656
1854 2070 2340
2880 3492 3933
50% Over­load 50°C P (kW)
90 110 132 160
200 250 315
355 400 450
500 560 630
710 800 900
— — —
September 2006
Dimensions and Weight
Frame
FI9 9.4 x 40.6 x 14.6/143
FI10 9.4 x 40.6 x 21.7/220
FI12 2x9.4 x 40.6 x 21.7/440
FI12 2x9.4 x 40.6 x 21.7/440
FI13 27.9 x 40.6 x 21.8/665
FI14 2x27.9 x 40.6 x 21.8/665
W x H x D/Wt. in in./lbs. (mm/kg)
(239 x 1030 x 372/65)
(239 x 1030 x 552/100)
(2x239 x 1030 x 552/200)
(2x239 x 1030 x 552/200)
(708 x 1030 x 553/302)
(2x708 x 1030 x 553/302)
Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is
equal to or less than the factory default.
1-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Supply Voltage 640 – 1100V DC, Motor Voltage 525 – 690V AC
High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min
Following continuous operation at rated output current, 150% rated output current (IH) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min
Following continuous operation at rated output current, 110% rated output current (IL) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
All frames are available as IP21 and IP54.
Table 1-3: 525 – 690V AC, 50/60 Hz, Three-Phase Inverters Ratings
Motor Shaft Power
930V DC Supply
10% Over­load 40°C P (kW)
110 132 160 200
250 315 355 400
450 500 560
630 710 800
900
1000 1200
1500 1800 2000
Nominal Current
100 125 144 170
208 261 325 325
385 460 502
590 650 650
820 920
1030
1300 1500 1900
Loadability
Low High
Rated Cont. Current IL (A)
125 144 170 208
261 325 385 416
460 502 590
650 750 820
920 1030 1180
1500 1900 2250
10% Over­load Current (A)
138 158 187 229
287 358 424 458
506 552 649
715 825 902
1012 1133 1298
1650 2090 2475
Rated Cont. Current IH (A)
100 125 144 170
208 261 325 325
385 460 502
590 650 650
820 920
1030
1300 1500 1900
50% Over­load Current (A)
150 188 216 255
312 392 488 488
578 690 753
885 975 975
1230 1380 1464
1950 2250 2782
Max Current I
S
200 213 245 289
375 470 585 585
693 828 904
1062 1170 1170
1476 1656 1755
2340 2700 3335
SPI9000 Inverter Unit FI9 – FI14 User Manual
50% Over­load 50°C P(kW)
90 110 132 160
200 250 315 355
400 450 500
560 630 710
800 900
1000
1300 1500 1800
Frame
FI9 9.4 x 40.6 x 14.6/143
FI10 9.4 x 40.6 x 21.7/220
FI12 2x9.4 x 40.6 x 21.7/441
FI12 2x9.4 x 40.6 x 21.7/441
FI13 27.9 x 40.6 x 21.8/665
FI14 2x27.9 x 40.6 x 21.8/665
Dimensions and Weight W x H x D/Wt. in in./lbs. (mm/kg)
(239 x 1030 x 372/65)
(239 x 1030 x 552/100)
(2x239 x 1030 x 552/200)
(2x239 x 1030 x 552/200)
(708 x 1030 x 553/302)
(2x708 x 1030 x 553/302)
Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is
equal to or less than the factory default.
MN04004002E
For more information visit: www.EatonElectrical.com 1-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 1-4: Technical Information
Description Specification
Supply Connection
Input Voltage V
Input Current I
DC Bank Capacitance FI9 380 – 500V: 4950 μF; FI9 525 – 690V: 3733 μF
Starting Delay 5 seconds (FI9 and greater)
Motor Connection
Output Voltage 3 ~ 0 – V
Continuous Output Current I
Starting Torque I
Peak Current I
Output Frequency 0 – 320 Hz; 7200 Hz (special)
Frequency Resolution Application dependent
Control Characteristics
Control Method Frequency control V/f
Switching Frequency (See Parameter 2.6.9)
Frequency Reference Analog Input Panel Reference
Field Weakening Point 30 – 320 Hz
Acceleration Time 0 – 3000 sec
Deceleration Time 0 – 3000 sec
Braking Torque DC brake: 30% * T
Ambient Conditions
Ambient Operating Temperature -10°C (no frost) to +40°C: I
Storage Temperature -40 to 158°F (-40 to 70°C)
Relative Humidity 0 – 95% RH, non-condensing, non-corrosive,
Air Quality: – Chemical Vapors – Mechanical Particles
Altitude 100% load capacity (no derating) up to 1,000m
in
in
September 2006
465 – 800V DC; 380 – 500V AC (-0%. to +0%) 640 – 1100V DC; 525 – 690V AC (-0% to +0%) The waviness of the inverter supply voltage, which is formed in rectification of the electric network’s alternating voltage in basic frequency, must be less than 50V peak-to-peak.
(sqrt3 x U
mot
x I
x cosϕ) / (Vin x 0.98)
mot
FI10 380 – 500V: 9900 μF; FI10 525 – 690V: 7467 μF FI12 380 – 500V: 19800 μF; FI12 525 – 690V: 14933 μF FI13 380 – 500V: 29700 μF; FI13 525 – 690V: 22400 μF
/ 1.4
in
: Ambient temperature max. +50°C,
H
overload 1.5 x I I
: Ambient temperature max. +40°C,
L
overload 1.1 x I
for two seconds (torque motor dependent)
S
for 2 seconds every 20 seconds
S
(1 min./10 min.)
H
(1 min./10 min.)
L
Open loop: Sensorless vector control Closed loop: Frequency control Closed loop: Vector control
380 – 500V, 1 – 10 kHz; Factory default 3.6 kHz 525 – 690V, 1 – 6 kHz; Factory default 1.5 kHz
Resolution 0.1% (10 bits); Accuracy ±1% Resolution 0.01 Hz
(without brake)
N
-10°C (no frost) to +40°C: I
H L
no dripping water
IEC 721-3-3, unit in operation, Class 3C2 IEC 721-3-3, unit in operation, Class 3S2
1% derating for each 100m above 1000 (maximum, 3000m)
1-6 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 1-4: Technical Information, continued
Description Specification
Ambient Conditions, continued
Vibration EN 50178/EN 60068-2-6
Shock EN 50178, EN 60068-2-27
Cooling Capacity Required P
Cooling Air Required FI9, 677 cfm; FI10, 824 cfm;
Unit Enclosure Class IP00
EMC (at Default Settings)
Immunity Fulfill all EMC immunity requirements
Safety
Control Connections
Analog input voltage 0 to +10V, R
Analog input current 0(4) – 20 mA, R
Digital inputs (6) Positive or negative logic; 18 – 30V DC
Auxiliary voltage +24V, ±15%, max. 250 mA
Output reference voltage +10V, +3%, max. load 10 mA
Analog output 0(4) – 20mA; R
Digital outputs Open collector output, 50 mA/48V
Relay outputs 2 programmable change-over relay outputs
Protections
Overvoltage Protection Undervoltage Protection
Ground Fault Protection In case of ground fault in motor or motor cable, only the inverter is
Motor Phase Supervision Trips if any of the output phases are missing.
Overcurrent Protection Yes
Unit Overtemperature Protection Yes
Motor Overload Protection Yes
Motor Stall Protection Yes
Motor Underload Protection Yes
Short Circuit Protection of +24V and +10V Reference Voltages
5 – 150 Hz Displacement amplitude: 1 mm (peak) at 3 – 15.8 Hz Maximum acceleration amplitude: 1G at 15.8 – 150 Hz
UPS Drop Test (for applicable UPS weights) Storage and shipping: Maximum 15G, 11 ms (in package)
[kW] approx. P
loss
[kW] x 0,025
mat
FI12, 1648 cfm; FI13, 2472 cfm
CE, UL, CUL EN 61800-5-1 (2003) See unit nameplate for more detailed approvals.
= 200kΩΩΩΩ, (–10V to +10V joystick control)
Resolution 0.1%; Accuracy ±1%
Resolution 10 bits; Accuracy ±2%
i
= 250ΩΩΩΩ differential
i
max. 500ΩΩ
L
ΩΩ
Switching capacity: 24V DC/8A, 250V AC/8A, 125V DC/0.4A Minimum switching load: 5V/10 mA
500V inverters: 911V DC; 690V inverters: 1200V DC 500V inverters: 333V DC; 690V inverters: 460V DC
protected.
Ye s
MN04004002E
For more information visit: www.EatonElectrical.com 1-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 1-5: DC Currents for 465 – 800V DC Supply Voltage
Structure Inom (Output) Motor COS IDC (Input)
FI9 261 .89 304
FI10 385 .9 454
FI12 590 .9 695
FI13 1150 .91 1370
FI14 1770 .92 2132
Table 1-6: DC Currents for 640 – 1100V DC Supply Voltage
Structure Inom (Output) Motor COS IDC (Input)
September 2006
300 .89 350
460 .9 542
520 .9 613
650 .9 766
730 .91 870
820 .91 977
920 .91 1096
1030 .91 1227
1300 .91 1549
1450 .91 1727
2150 .92 2590
2700 .92 3252
FI9 125 .89 146
144 .89 168
170 .89 198
208 .9 245
FI10 261 .9 308
325 .9 383
385 .9 454
416 .9 490
F12 460 .91 548
502 .91 598
590 .91 703
650 .91 774
750 .91 894
820 .91 977
FI13 920 .91 1096
1030 .91 1227
1180 .92 1421
FI14 1500 .92 1807
1900 .93 2313
2250 .93 2739
1-8 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Chapter 2 — Mounting
Dimensions
The inverter can be mounted in a vertical position on the back plane of a cubicle. Enough space must be reserved around the inverter to ensure sufficient cooling, see Figure 2-5. You must follow the minimum dimensions for installation, see Tables 2-5 and 2-6. Also make sure that the mounting plane is relatively even. The inverter is fixed with four screws (or bolts, depending on the unit size). The following pages show the dimensions for the IP00 power module.
SPI9000 Inverter Unit FI9 – FI14 User Manual
W1D1
H2
H1
Dia. 1
Dia. 2
D3 D3
D4
D3
D2
W2 W2
FrontSide
TopBottom
H3
Figure 2-1: SPI9000 FI9 Inverter Dimensions
MN04004002E
Table 2-1: SPI9000 FI9 Inverter Dimensions
Approximate Dimensions in Inches (mm)
Inverters Voltage
SPI100 – 170 480V/575V 9.41
W1 W2 H1 H2 H3 D1 D2 D3 D4 Dia. 1 Dia. 2
3.94
(239)
(100)
For more information visit: www.EatonElectrical.com 2-1
40.63 (1032)
37.40 (950)
2.46 (62.5)
15.20 (386)
2.12 (53.9)
5.51 (140)
6.03 (153.1)
.18 (4.6)
.37 (9.5)
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
W1D1
W2
H1
H2
Dia.
Figure 2-2: SPI9000 FI10 Inverter Dimensions
Table 2-2: SPI9000 FI10 Inverter Dimensions
Approximate Dimensions in Inches (mm)
Inverters Voltage
SPI208 – 325 480V/575V 9.4
W1 W2 H1 H2 H3 D1 D2 D3 Dia.
(239)
7.9 (200)
41.3 (1050)
D3
D2
D2
37.5 (952)
TopBottom
H3
2.4 (60.5)
22.3 (566)
9.1 (230)
1.6 (41)
.37 (9.5)
FrontSide
2-2 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Dia.
D1
D2
D3
W3
W1
W2W2
H1
H2
FrontSide
H3
MN04004002E
Figure 2-3: SPI9000 FI12 Inverter Dimensions
Table 2-3: SPI9000 FI12 Inverter Dimensions
Approximate Dimensions in Inches (mm)
Inverters Voltage
SPI385 – 650 480V 18.8
W1 W2 W3 H1 H2 H3 D1 D2 D3 Dia.
7.9
(478)
For more information visit: www.EatonElectrical.com 2-3
(200)
1.1 (28)
D2
41.3 (1050)
37.5 (952)
TopBottom
2.4 (60.5)
22.3 (566)
9.1 (230)
1.6 (41)
.37 (9.5)
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Dia.
D1
D2
W1 W2
H1
H2
H3
FrontSide
D3
D5
Fan Cooling
Frames FI9 to FI14
D4
D3
TopBottom
Figure 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13)
Table 2-4: SPI9000 FI13 Inverter Dimensions (FI14 Is a Double FI13)
Approximate Dimensions in Inches (mm)
Inverters Voltage
SPI820 – H10 480V 27.9
W1 W2 H1 H2 H3 D1 D2 D3 D4 D5 Dia.
(708)
26.7 (677)
41.5 (1055)
37.4 (950)
2.46 (62.5)
22.3 (566)
1.1 (27)
1.6 (40)
9.6 (245)
5.9 (150)
.37 (9.5)
Enough free space must be left around the inverter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space Table 2-5.
If several units are mounted on top of each other, the required free space equals 2 * C (see Figure 2-5). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit. When planning the cooling for the space, take into consideration that the inverter’s heat loss is 2.5% of the nominal capacity.
2-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
B
FI9/FI10
SPI9000 Inverter Unit FI9 – FI14 User Manual
A
2
FI12
FI13
B
C
Figure 2-5: Installation Space
MN04004002E
For more information visit: www.EatonElectrical.com 2-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 2-5: Mounting Space Requirements
Frame Voltage
September 2006
Approximate Dimensions in Inches (mm)
ABB2C
FI9 380 – 500V
FI10 380 – 500V
FI12 380 – 500V
FI13 380 – 500V
FI14 380 – 500V
A = free space above the inverter B = distance between inverter and cabinet wall
= distance between two inverters
B
2
C = free space underneath of the inverter
525 – 690V
525 – 690V
525 – 690V
525 – 690V
525 – 690V
7.9 (200) .79 (20) 3.9 (100)
7.9 (200) .79 (20) 3.9 (100)
7.9 (200) .79 (20) 0 3.9 (100)
7.9 (200) .79 (20) 0 3.9 (100)
7.9 (200) .79 (20) 0 3.9 (100)
Table 2-6: Required Cooling Air
Frame Voltage
FI9 380 – 500V
525 – 690V
FI10 380 – 500V
525 – 690V
FI12 380 – 500V
525 – 690V
FI13 380 – 500V
525 – 690V
FI14 380 – 500V
525 – 690V
Greatest Possible Heat Loss (kW)
4.8
4.6
8.3
9.1
16.5
18.0
23.0
26.0
46.0
52.0
Cooling Air Required (cfm)
677 77.5
824 93
1648 186
2472 279
2 x 2472 2 x 279
Minimum Air Exhausting Hole on Switchgear (in
2
)
Power Losses
Raising the switching frequency of the drive, to reduce motor noise for example, inevitably affects the power losses and cooling requirements. For more information, contact Eaton.
2-6 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Chapter 3 — Power Wiring
The following wiring diagrams show the supply and motor connections.
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
+
B
FI 9/10
X10 X15X9
H
1...H7
DC
B
Fan
Cooling
External
Supply
MN04004002E
UVMW
PE
Figure 3-1: FI9/FI10 Basic Wiring Diagram with Charging
For more information visit: www.EatonElectrical.com 3-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
+
B
FI 9/10
X10 X15X9
H
1...H7
DC
B
Cooling
Fan
UVMW
PE
Figure 3-2: FI9/FI10 Basic Wiring Diagram without Charging
3-2 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
FI 10 Module 1
DC
+
B
B
+
DC
FI 10 Module 2
DC
+
B
B
External
Supply
X10
H1-7
U VMW
Note: Min. Cable Length (131.2í) 40m
H903
H900
X9
Cooling
PE
X15
Fan
X10
U V W
H1-7
H903
H900
X9
X15
Fan
Cooling
PE
Figure 3-3: FI12 Basic Wiring Diagram with Charging
MN04004002E
For more information visit: www.EatonElectrical.com 3-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
DC
+
B
B
FI 10 Module 1
X10
H1-7
H903
H900
X9
X15
Fan
Cooling
+
DC
DC
+
B
FI 10 Module 2
X10
H1-7
H903
B
H900
X9
X15
Fan
Cooling
U VMW
Note: Min. Cable Length (131.2) 40m
PE
U V W
PE
Figure 3-4: FI12 Basic Wiring Diagram without Charging
3-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
DC
+
B
B
FI 10 Module U
+
DC
DC
+
B
FI 10 Module V
B
+
DC
FI 10 Module W
DC
+
B
B
External
Supply
H1-7
H903
H900
X9
X15
X10
Fan
Cooling
W
X10
Fan
Cooling
U
V
M
H1-7
H903
H900
X9
X15
Fan
Cooling
PE
Figure 3-5: FI13 Basic Wiring Diagram with Charging
MN04004002E
For more information visit: www.EatonElectrical.com 3-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
DC
+
B
FI 10 Module U
B
Fan
Cooling
+
DC
FI 10 Module V
X10
B
+
H1-7
DC
B
X9
X15
Fan
Cooling
+
DC
FI 10 Module W
DC
+
B
B
Fan
Cooling
U
V
M
W
PE
Figure 3-6: FI13 Basic Wiring Diagram without Charging
3-6 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Controller
+
DC
FI 10 Module U
DC
+
B
B
FI 10 Module V
DC
+
+
B
DC
B
+
DC
B
DC
+
B
FI 10 Module W
External
Supply
+
DC
FI 10 Module U
DC
+
B
B
FI 10 Module V
DC
+
DC
+
B
B
+
DC
+
B
FI 10 Module W
DC
B
External
Supply
U
Note: Min. Cable Length (131.2) 40m
H1-7
V
H903
H900
X9
X15
Fan
Cooling
W
PE
Fan
Cooling
U
M
X10
Fan
Cooling
X10
Fan
Cooling
H1-7
V
H903
H900
X9
X15
Fan
Cooling
W
PE
Fan
Cooling
Figure 3-7: FI14 Basic Wiring Diagram with Charging
MN04004002E
For more information visit: www.EatonElectrical.com 3-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Controller
+
DC
FI 10 Module U
DC
+
B
B
Fan
Cooling
+
DC
FI 10 Module V
X10
B
+
H1-7
H903
DC
B
H900
X9
X15
Fan
Cooling
+
DC
FI 10 Module W
DC
+
B
B
Fan
Cooling
+
DC
DC
+
B
FI 10 Module U
B
Fan
Cooling
+
DC
FI 10 Module V
0 X1
B
+
H1-7
H903
DC
B
H900
X9
X15
Fan
Cooling
+
DC
FI 10 Module W
DC
+
B
B
Fan
Cooling
U
Note: Min. Cable Length (131.2) 40m
V
W
PE
U
M
Figure 3-8: FI14 Basic Wiring Diagram without Charging
V
W
PE
3-8 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Power Connections
DC Supply and Motor Cables
The power cables are connected to terminals DC+ and DC- (R+/B+ and DC terminals when using an external charging circuit) and the motor cables to terminals U, V and W. A cable entry gland should be used at the motor cable end to reach the EMC levels, see Table 3-2.
Use cables with a heat resistance of at least +60C. The cables and the fuses must be sized according to the inverter nominal output current which you can find on the rating plate. Installation of cables according to UL regulations is presented on Page 3-17 and aR fuse sizes in Tables 3-2 and 3-3 below.
If the motor temperature protection of the drive is used as an overload protection, the cable shall be chosen accordingly. If three or more cables are used in parallel for bigger units, each cable requires a separate overload protection.
These instructions apply only to installations with one motor and one cable connection from the inverter to the motor. In any other case, ask the factory for more information.
Table 3-1: Cable Types Required to Meet Standards
Cable Type EMC Level T
SPI9000 Inverter Unit FI9 – FI14 User Manual
Supply Cable Power cable intended for fixed installation and the specific DC voltage.
Motor Cable Power cable equipped with concentric protection wire and intended for the
Control Cable Screened cable equipped with compact low-impedance shield.
Fuses, 465 – 800V DC Inverters
Table 3-2: Fuses Used in 465 – 800V DC Inverters
Nominal Current Frame
140 FI9 170M3819 DIN1 690 400 2
170 FI9 170M3819 DIN1 690 400 2
205 FI9 170M6812 DIN3 690 800 2
245 FI9 170M6812 DIN3 690 800 2
300 FI10 170M8547 3SHT 690 1250 2
385 FI10 170M8547 3SHT 690 1250 2
460 FI10 170M8547 3SHT 690 1250 2
520 FI12 170M8547 3SHT 690 1250 4
590 FI12 170M8547 3SHT 690 1250 4
650 FI12 170M8547 3SHT 690 1250 4
730 FI12 170M8547 3SHT 690 1250 4
820 FI12 170M8547 3SHT 690 1250 4
920 FI12 170M8547 3SHT 690 1250 4
1030 FI13 170M8547 3SHT 690 1250 6
1150 FI13 170M8547 3SHT 690 1250 6
1300 FI13 170M8547 3SHT 690 1250 6
1600 FI14 170M8547 3SHT 690 1250 2 x 6
1940 FI14 170M8547 3SHT 690 1250 2 x 6
2300 FI14 170M8547 3SHT 690 1250 2 x 6
Shielded cable not required.
specific mains voltage.
Bussman aR Fuse Type Fuse Size Fuse Un (V) Fuse In (A) No. of Fuses
MN04004002E
For more information visit: www.EatonElectrical.com 3-9
SPI9000 Inverter Unit FI9 – FI14 User Manual
Fuses, 640 – 1100V DC Inverters
Table 3-3: Fuses Used in 640 – 1100V DC Inverters
Nominal Current Frame
100 FI9 170M4199 1SHT 1250 400 2
125 FI9 170M4199 3SHT 1250 400 2
144 FI9 170M4199 3SHT 1250 400 2
170 FI9 170M4199 3SHT 1250 400 2
208 FI10 170M6305 3SHT 1250 700 2
261 FI10 170M6305 3SHT 1250 700 2
325 FI10 170M6277 3SHT 1250 1000 2
325 FI10 170M6277 3SHT 1250 1000 4
385 FI12 170M6305 3SHT 1250 700 4
460 FI12 170M6305 3SHT 1250 700 4
502 FI12 170M6305 3SHT 1250 700 4
590 FI12 170M6277 3SHT 1250 1000 4
650 FI12 170M6277 3SHT 1250 1000 4
650 FI12 170M6277 3SHT 1250 1000 4
820 FI13 170M6305 3SHT 1250 700 6
920 FI13 170M6277 3SHT 1250 1000 6
1030 FI13 170M6277 3SHT 1250 1000 6
1300 FI14 170M6277 3SHT 1250 1000 2 x 6
1500 FI14 170M6277 3SHT 1250 1000 2 x 6
1900 FI14 170M6277 3SHT 1250 1000 2 x 6
September 2006
Bussman aR Fuse Type Fuse Size Fuse Un (V) Fuse In (A) No. of Fuses
Information about fuses:
gR fuses are designed to protect the device against both overcurrent and short circuits.
aR fuses protect the cables of the device against short circuits.
gG fuses are generally used to protect cables against overcurrent and short circuits.
3-10 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Inverter Supply and Motor Cables — 380 – 500V AC
Table 3-4: Cable Sizes for 380 – 500V AC
Nominal Current Frame IL [A]
140 FI9 170 2x(1x24)
170 205 2x(1x24)
205 261 3x(1x24)
245 300 6x(1x24)
300 FI10 385 5x40
385 460 5x40
460 520 6x40
520 FI12
590 650 5x40
650 730 5x40
730 820 5x40
820 920 5x40
920 1030 6x40
1030 FI13 1150 5x40
1150 1300 5x40
1300 1450 6x40
1600 FI14
1940 2150 5x40
2300 2700 6x40
Flexible conductor. Minimum temperature endurance for isolation 70°C.
Copper busbar.
The modules require symmetrical parallel cable with minimum length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets. Motor cables — EN 60204-1, IEC 60364-5-2/2001
PVC insulation40°C ambient temperature70°C surface temperature
590 5x40
1770 5x40
SPI9000 Inverter Unit FI9 – FI14 User Manual
Module Supply (DC) (per terminal Cu [mm2]
Motor Cable [mm2]
Cu: 3x95+50 Al: 3x120+70
Cu: 3x150+70 Al: 3x240Al+72Cu
Cu: 3x185+95 Al: 2x(3x120+70)
Cu: 2x(3x120+70) Al: 2x(3x185Al+57Cu)
Cu: 2x(3x120+70) Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70) Al: 2x(3x240Al+72Cu)
Cu: 2x(3x185+95) Al: 2x(3x300Al+88Cu)
Cu: 2x(3x240+120) Al: 4x(3x120Al+41Cu)
Cu: 4x(3x95+50) Al: 4x(3x150Al+41Cu)
Cu: 4x(3x120+70) Al: 4x(3x185Al+57Cu)
Cu: 4x(3x150+70) Al: 4x(3x185Al+57Cu)
Cu: 4x(3x150+70) Al: 4x(3x240Al+72Cu)
Cu: 4x(3x185+95) Al: 4x(3x300Al+88Cu)
Cu: 4x(3x240+170) Al: 6x (3x185Al+57Cu)
Cu: 6x(3x150+70) Al: 6x (3x240Al+70Cu)
Cu: 6x(3x185+95) Al: 6x (3x240Al+70Cu)
Cu: 2x 4x(3x240+170) Al: 2x 6x (3x185Al+57Cu)
Cu: 2x 6x(3x150+70) Al: 2x 6x (3x240Al+70Cu)
Cu: 2x 6x(3x185+95) Al: 2x 6x (3x240Al+70Cu)
MN04004002E
For more information visit: www.EatonElectrical.com 3-11
SPI9000 Inverter Unit FI9 – FI14 User Manual
Terminal Sizes — 380 – 500V AC
Table 3-5: Terminal Sizes for 380 – 500V AC
Nominal Current Frame IL [A]
140 FI9 170 PE: M8 x 25
170 205
205 261
245 300
300 FI10 385 PE: M8 x 25
385 460
460 520
520 FI12 590 PE: M8 x 25
590 650
650 730
730 820
820 920
920 1030
1030 FI13 1150
September 2006
Approximate Dimensions in Inches (mm) DC Supply Terminal Motor Cable Terminal
.51
(13)
.51
(13)
1150 1300
1300 1450
1.97 (50)
.63
(16)
1.57 (40)
1.50 (38)
.67
(17)
1.57 (40)
3-12 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Inverter Supply and Motor Cables — 525 – 690V AC
Table 3-6: Cable Sizes for 525 – 690V AC
Nominal Current Frame IL [A]
100 FI9 125 2x(1x24)
125 144 2x(1x24)
144 170 2x(1x24)
170 208 2x(1x24)
208 FI10 261 3x(1x24)
261 325 5x40
325 385 5x40
325 416 5x40
385 FI12
460 502 5x40
502 590 5x40
590 650 5x40
650 750 5x40
650 820 5x40
820 FI13 920 5x40
920 1030 5x40
1030 1180 5x40
1300 FI14
1500 1900 5x40
1900 2250 5x40
Flexible conductor. Minimum temperature endurance for isolation 70°C.
Copper busbar.
The modules require symmetrical parallel cable with minimum length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets. Motor cables — EN 60204-1, IEC 60364-5-2/2001
PVC insulation40°C ambient temperature70°C surface temperature
460 5x40
1500 5x40
SPI9000 Inverter Unit FI9 – FI14 User Manual
Module Supply (DC) (per terminal Cu [mm2]
Motor Cable [mm2]
Cu: 3x95+50 Al: 3x120+70
Cu: 3x95+50 Al: 3x120+70
Cu: 3x95+50 Al: 3x120+70
Cu: 3150+70 Al: 3x240Al+72Cu
Cu: 3x185+95 Al: 2x(3x95Al+29Cu)
Cu: 2x(3x95+50) Al: 2x(3x150Al+41Cu)
Cu: 2x(3x120+70) Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70) Al: 2x(3x185Al+57Cu)
Cu: 2x(3x150+70) Al: 2x(3x240Al+72Cu)
Cu: 2x(3x185+95) Al: 2x(3x300Al+88 Cu)
Cu: 2x(3x240+120) Al: 4x(3x120Al+41Cu)
Cu: 4x(3x95+50) Al: 4x(3x150Al+41Cu)
Cu: 4x(3x120+70) Al: 4x(3x150Al+41Cu)
Cu: 4x(3x150+70) Al: 4x(3x185Al+57Cu)
Cu:4x(3x150+70) Al:4x(3x2405+72Cu)
Cu:4x(3x185+95) Al:5x(3x185+57Cu)
Cu:5x(3x185+95) Al:6x(3x185+72Cu)
Cu: 2x4x(3x120+70) Al: 2x4x(3x150Al+41Cu)
Cu: 2x4x(3x185+95) Al: 2x5x(3x185+57Cu)
Cu: 2x5x(3x185+95) Al: 2x6x(3x185+72Cu)
MN04004002E
For more information visit: www.EatonElectrical.com 3-13
SPI9000 Inverter Unit FI9 – FI14 User Manual
Terminal Sizes — 525 – 690V AC
Table 3-7: Terminal Sizes for 525 – 690V AC
Nominal Current Frame IL [A]
100 FI9 125
125 144
144 170
September 2006
Approximate Dimensions in Inches (mm) DC Supply Terminal Motor Cable Terminal
.51
(13)
1.57 (40)
.51
(13)
1.57 (40)
170 208
208 FI10 261
261 325
325 385
325 416
385 FI12 460
460 502
502 590
590 650
650 750
650 820
820 FI13 920
1.38 (35)
1.97 (50)
1.97 (50)
.63
(16)
.63
(16)
.63
(16)
.51
(13)
.51
(13)
.51
(13)
1.57 (40)
1.57 (40)
1.50 (38)
1.50 (38)
1.50 (38)
.67
(17)
.67
(17)
.67
(17)
.51
(13)
.51
(13)
.51
(13)
1.57 (40)
1.57 (40)
920 1030
1030 1180
1.97 (50)
.63
(16)
1.57 (40)
1.50 (38)
.67
(17)
1.57 (40)
3-14 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Installation Instructions
1. Before starting the installation, check that none of the components of the inverter are live.
2. If the inverter is installed outside the cubicle, cabinet or device space, you need to install a separate inverter cover in accordance with protection class IP21 requirements (see Page 3-16. There is no need to install the inverter cover if the inverter is installed in a cubicle, separate cabinet or device space.
3. Place the motor cables sufficiently far from other cables:
Avoid placing the motor cables in long parallel lines with other cablesIf the motor cables runs in parallel with other cables, note the minimum distances
between the motor cables and other cables given in Table 3-8.
The given distances also apply between the motor cables and signal cables of other
systems.
– The maximum length of the motor cables is 984 feet (300m) (units with power
greater than 1.5 kW) and 328 feet (100m) (units with power from 0.75 to 1.5 kW).
The motor cables should cross other cables at an angle of 90 degrees.
Table 3-8: Cable Distances
Distance Between Cables in Inches (m)
SPI9000 Inverter Unit FI9 – FI14 User Manual
Shielded Cable in Feet (m)
11.8 (.3)
39.4 (1.0)
193 (59) 656 (200)
4. If cable insulation checks are needed, see Page 3-17.
5. Connect the cables:
Strip the motor and DC supply cables.Remove the screws of the cable protection plate. Do not open the cover of the power unit!Make holes into and pass the cables through the rubber grommets on the bottom of
the power unit. The rubber grommets are delivered in a separate bag.
Connect the DC supply, motor and control cables into their respective terminals.For information on the installation of greater units, please contact Eaton or your
local distributor.
– For Information on cable installation according to UL regulations, see Page 3-17. – For information on cable installation according to EMC regulations, see Table 3-1. – Make sure that the control cable wires do not come in contact with the electronic
components of the unit.
– If an external brake resistor (optional) is used, connect its cable to the appropriate
terminal.
– Check the connection of the ground cable to the motor and the inverter terminals
marked with .
– Connect the separate shield of the power cable to the ground terminals of the
inverter, motor and the supply center.
Attach the cable protection plate with the screws.Ensure that the control cables or the cables of the unit are not trapped between the
frame and the protection plate.
MN04004002E
For more information visit: www.EatonElectrical.com 3-15
SPI9000 Inverter Unit FI9 – FI14 User Manual
Frame Sizes
September 2006
Inverter Frame FI9, Protection Class IP00 Inverter Frame FI10, Protection Class IP00
Inverter Frame FI13, Protection Class IP00Inverter Frame FI12, Protection Class IP00
3-16 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Cable Installation and the UL Standards
To meet the UL (Underwriters Laboratories) regulations, a UL approved copper cable with a minimum heat-resistance of +60/75°C must be used.
The tightening torques of the terminals are given below in Table 3-9.
Table 3-9: Terminal Tightening Torques
Nominal Current Voltage Frame
SPI9000 Inverter Unit FI9 – FI14 User Manual
Tightening Torque in in-lb (Nm)
140 – 245 100 – 170
300 – 460 208 – 325
520 – 920 385 – 650
1030 – 1300 920 – 1030
1600 – 2300 1300 – 1900
Tightening torque of terminal connection to the isolative base.
380 – 500V 525 – 690V
380 – 500V 525 – 690V
380 – 500V 525 – 690V
380 – 500V 525 – 690V
380 – 500V 525 – 690V
Note: Apply counter torque to the nut on the other side of the terminal when tightening/
loosening the terminal screw in order to avoid damage to the terminal.
Cable and Motor Insulation Checks
1. Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the inverter and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor.
The insulation resistance must be >1MΩ.
FI9 340 (40)
FI10 340 (40)
FI12 340 (40)
FI13 340 (40)
FI14 340 (40)
MN04004002E
2. DC supply cable insulation checks
Disconnect the DC supply cable from terminals B- and B+ of the inverter and from DC supply. Measure the insulation resistance between each conductor and ground.
The insulation resistance must be >1MΩ.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1,000V.
The insulation resistance must be >1MΩ.
For more information visit: www.EatonElectrical.com 3-17
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
3-18 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Chapter 4 — Control Wiring
The control unit of the inverter consists of the control board and option boards (see Figures 4-1 and 4-2) connected to the five slot connectors (A to E) on the control board. The control board is connected to the power unit through a D connector (1).
SPI9000 Inverter Unit FI9 – FI14 User Manual
Figure 4-1: Control Board
E
D
C
B
A
Figure 4-2: Basic and Option Board
Connections of the Control Board
MN04004002E
For more information visit: www.EatonElectrical.com 4-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
When the inverter is delivered from the factory, the control unit usually includes two basic boards (I/O board and relay board), which are normally installed in slots A and B. On the next pages you will find the arrangement of the control I/O and the relay terminals of the two basic boards, the general wiring diagram and the control signal descriptions. The I/O boards mounted at the factory are indicated in the type code. For more information on the option boards, see the option board user manual.
The control board can be powered externally (+24V) by connecting the external power source to bidirectional terminal #6 (see Figure 4-5). This voltage is sufficient for parameter setting and for keeping the fieldbus active.
Note: If the +24V input of several inverters are connected in parallel, we recommend to use a
diode in terminal #6 to avoid the current flowing in opposite direction, which might damage the control board.
#
September 2006
External
+
24V
+
#
6
7
+
#
#
6
7
+
#
#
6
7
+
#
#
6
7
Control Wiring Details
The basic control connections for boards A2 and A3 are shown in Figures 4-6 and 4-7.
You can find the signal descriptions for applications in the application manual.
Figure 4-3: Inverters Connected in Parallel
1 2 3 4 5 6 7 8 9
10
Board OPT-A9 in Slot A Boards OPT-A2 and OPT-A3 in Slot B
11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26
OPT-A2
21 22 23 25 26 28 29
OPT-A3
Figure 4-4: I/O Terminals of the Two Basic Boards
4-2 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Basic I/O Board A9
+10Vref
AIA1
GND
AIA2
AIA2
24Vout
GND
DIA1
DIA2
DIA3
CMA
24Vout
GND
DIB4
DIB5
DIB6
CMB
Iout
Iout
DO1
1
+
2
3
+
4
-
5
6
7
8
9
10
11
12
13
14
15
16
17
+
18
-
19
20
Input Reference (Voltage)
Input Reference (Current)
Control Voltage Output
24V
GND
24V
GND
0 (4)/20 mA
Ω
RL<500
V<+48V
+
I<50 mA
Figure 4-5: Option Board A9 Wiring Diagram
Basic Relay Board A2
Figure 4-6: Option Board A2 Wiring Diagram
Indicates Connections for Inverted Signals
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
21
22
23
24
25
26
R
L
Switching: <8A / 24V DC <0.4A / 125V DC <2kVA / 250V AC Continuously <2 Arms
AC / DC
MN04004002E
For more information visit: www.EatonElectrical.com 4-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Control Cables
The control cables shall be at least 20 AWG screened multicore cables, see Table 4-1. The maximum terminal wire size is 14 AWG for the relay terminals and 16 AWG for other terminals.
You can find the tightening torques of the option board terminals in Table 4-1.
Table 4-1: Tightening Torques of Option Board Terminals
Terminal Screw
Basic Relay Board A3
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
TL1+
TL1
21
22
23
25
26
28
29
R
L
AC / DC
+t
Figure 4-7: Option Board A3 Wiring Diagram
Tightening Torque
lb-in.
Switching: <8A / 24V DC <0.4A / 125V DC <2kVA / 250V AC Continuously <2 Arms
Relay and thermistor terminals (screw M3) 4.5
Other terminals (screw M2.6) 1.8
4-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Galvanic Isolation Barriers
The control connections are isolated from the mains potential and the GND terminals are permanently connected to ground. See Figure 4-8.
The digital inputs are galvanically isolated from the I/O ground. the relay outputs are also double-isolated from each other at 300V AC (EN-50178).
SPI9000 Inverter Unit FI9 – FI14 User Manual
+
10Vref
AO1
AO2
RO1/1 RO1/2 RO1/3
RO2/1 RO2/2 RO2/3
GND +
24V
GND
AI1
+
AI2
-
AI2
DIN1... DIN3 CMA
DIN4... DIN6 CMB
+
-
DO1
+
TI1
TI1
Control to Ground
Digital Input Group A
Digital Input Group A
Analog Output
Digital Output
Control
Panel
Control
Board
Gate Drivers
L1 L2 L3
Power
Board
UVW
MN04004002E
Figure 4-8: Galvanic Isolation Barriers
For more information visit: www.EatonElectrical.com 4-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 4-2: Control I/O Terminal Signals on Option Board A9
Terminal Signal Technical Information
1 +10 Vref Reference voltage Maximum current 10 mA
2 AI1+ Analog input,
3 GND/AI1– Analog input common
4 AI2+ Analog input,
5 GND/AI2– Analog input common
6 24 Vout
(bidirectional)
7 GND I/O ground Ground for reference and controls
8 DIN1 Digital input 1 R
9 DIN2 Digital input 2
10 DIN3 Digital input 3
11 CMA Digital input common A for
12 24 Vout
(bidirectional)
13 GND I/O ground Same as terminal #7
14 DIN4 Digital input 4 R
15 DIN5 Digital input 5
16 DIN6 Digital input 6
17 CMB Digital input common B for
18 AO1+ Analog signal (+output) Output signal range:
19 AO1- Analog output common
20 DO1 Open collector output Maximum U
September 2006
Selection V or mA with jumper block X1 (see
voltage or current
Page 4-8) Default: 0 to +10V (Ri = 200 kΩ) (-10V to +10V Joy-stick control, selected with a jumper) 0 to 20 mA (Ri = 250 Ω) Differential input if not connected to ground; Allows ±20V differential mode voltage to GND
Selection V or mA with jumper block X1 (see
voltage or current
Page 4-8): Default: 0 to 20 mA (Ri = 250 Ω) 0 to +10V (Ri = 200 kΩ) (10V to +10V Joy-stick control, selected with a jumper) Differential input if not connected to ground; Allows ±20V differential mode voltage to GND
24V auxiliary voltage ±15%; maximum current 250 mA all boards
total; 150 mA from single board. Can also be used as external power backup for the control unit (and fieldbus).
= min. 5kΩ
i
18 – 30V = “1”
Must be connected to GND or 24V of I/O
DIN1, DIN2 and DIN3.
terminal or to external 24V or GND Selection with jumper block X3 (see Page 4-8)
24V auxiliary voltage Same as terminal #6
= min. 5kΩ
i
18 – 30V = “1”
Must be connected to GND or 24V of I/O
DIN4, DIN5 and DIN6
terminal or to external 24V or GND Selection with jumper block X3 (see Page 4-8)
Current 0(4) – 20 mA, R Voltage 0 – 10V, R Selection with jumper block X3 (see
>1kΩ
L
max. 500Ω or
L
Page 4-8)
= 48V DC
Maximum current = 50 mA
in
4-6 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 4-3: Control I/O Terminal Signals on Option Board A2
OPTA2
21 RO1/1 Relay output 1 Switching capacity 24V DC/8A
22 RO1/2
23 RO1/3 Min. switching load
24 RO2/1 Relay output 2 Switching capacity 24V DC/8A
25 RO2/2
26 RO2/3 Min. switching load
Table 4-4: Control I/O Terminal Signals on Option Board A3
OPTA3
21 RO1/1 Relay output 1 Switching capacity 24V DC/8A
22 RO1/2
23 RO1/3 Min. switching load
24 RO2/1 Relay output 2 Switching capacity 24V DC/8A
25 RO2/2
26 RO2/3 Min. switching load
28 TI1+ Thermistor input
29 TI1-
Digital Input Signal Inversions
The active signal level depends on which potential the common inputs CMA and CMB (terminals 11 and 17) are connected to. The alternatives are either +24V or ground (0V). See Figure 4-9.
250V AC/8A 125V DC/0.4A 5V/10 mA
250V AC/8A 125V DC/0.4A 5V/10 mA
250V AC/8A 125V DC/0.4A 5V/10 mA
250V AC/8A 125V DC/0.4A 5V/10 mA
We recommend the use of positive logic in all control connections of the inverter. If negative logic is used, additional appropriate measures are needed to meet the safety regulation requirements.
The 24 volt control voltage and the ground for the digital inputs and the common inputs (CMA, CMB) can be either internal or external.
 
+
24V
Ground
DIN1
DIN2
DIN3
CMA
Ground
+
24V
DIN1
DIN2
DIN3
CMA
Figure 4-9: Positive/Negative Logic
Positive logic (+24V is the active signal) = Input is active when the switch is closed.
Negative logic (0V is the active signal) = Input is active when the switch is closed.
Requires setting of jumper X3 to position “CMA/CMB isolated from ground.”
MN04004002E
For more information visit: www.EatonElectrical.com 4-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
Jumper Selections on Option Board A9
The user can customize the functions of the inverter to better suit his needs by selecting certain positions for the jumpers on the OPTA9 board. The positions of the jumpers determine the signal type of analogue and digital inputs.
On the A9 basic board, there are four jumper blocks (X1, X2, X3 and X6), each containing eight pins and two jumpers. The selection possibilities of the jumpers are shown in Figure 4-11.
September 2006
X1 X2
X6
X3
Figure 4-10: Jumper Blocks on Option Board A9
4-8 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Jumper Block X1:
AI1 Mode
A B C D
AI1 Mode: 0...20mA; Current Input
A B C D
AI1 Mode: Voltage Input; 0...10V
A B C D
AI1 Mode: Voltage Input; 0...10V (Differential)
A B C D
AI1 Mode: Voltage Input; -10...10V
Jumper Block X6:
AO1 Mode
A B C D
AI1 Mode: 0...20mA; Current Output
A B C D
Jumper Block X2:
AI2 Mode
A B C D
AI2 Mode: 0...20mA; Current Input
A B C D
AI2 Mode: Voltage Input; 0...10V
A B C D
AI2 Mode: Voltage Input; 0...10V (Differential)
A B C D
AI2 Mode: Voltage Input; -10...10V
Jumper Block X3:
CMA and CMB Grounding
CMB Connected to GND
CMA Connected to GND
CMB Isolated from GND
CMA Isolated from GND
CMB and CMA Internally Connected Together, Isolated from GND
MN04004002E
AO1 Mode: Voltage Output; 0...10V
= Factory Default
Figure 4-11: Jumper Selection for Option Board A9
CAUTION
Ensure that the jumper positions are correct. Running the motor with signal settings that differ from the jumper positions will not harm the inverter, but may harm the motor.
Note: If you change the AI/AO signal content, remember to change the corresponding board
parameter in Menu M7.
For more information visit: www.EatonElectrical.com 4-9
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
4-10 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Chapter 5 — Menu Information
Keypad Operation
The control keypad is the link between the SPI9000 inverter and the user. The control keypad features an alphanumeric display with seven indicators for the Run status (RUN, counter­clockwise, clockwise, READY, STOP, ALARM, FAULT) and three indicators for the control place (I/O term/Keypad/BusComm). There are also three Status Indicator LEDs (green – green – red), see Page 5-3.
The control information, i.e. the menu number, description of the menu or the displayed value and the numeric information are presented on three text lines.
The inverter is operable through the nine pushbuttons of the control keypad. Furthermore, the buttons can be used in setting parameters and monitoring values.
The keypad is detachable and isolated from the input line potential.
Indicators on the Keypad Display
SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E
Figure 5-1: Control Keypad and Drive Status Indications
For more information visit: www.EatonElectrical.com 5-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Drive Status Indicators
The drive status symbols tell the user the status of the motor and the inverter. In addition, they tell about possible irregularities detected by the motor control software in motor or inverter functions.
Table 5-1: Drive Status Indicators
Indicator Description
September 2006
Motor is running. Blinks when the stop command is given, but the frequency is still ramping down.
Indicates the direction of motor rotation.
Indicates that the drive is not running.
Lights up when AC power is on. In case of a trip, the symbol will not light up.
Indicates that the drive is running outside a certain limit and a warning is given.
Indicates that unsafe operating conditions are encountered and the drive was stopped.
Control Place Indicators
The symbols I/O Term, Keypad and Bus/Comm (see Table 5-2) indicate the choice of control place made in the Keypad control menu (M3) (see Page 5-9).
Table 5-2: Control Place Indicators
Indicator Description
I/O terminals are selected as the control place, i.e., START/STOP commands or reference values, etc. are given through the I/O terminals.
Control keypad is selected as the control place, i.e., the motor can be started or stopped or its reference values, etc. altered from the keypad.
The inverter is controlled through a fieldbus.
5-2 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Status LEDs (Green – Green – Red)
The status LEDs light up in connection with the READY, RUN and FAULT drive status indicators.
Table 5-3: Status LEDs (Green – Green – Red)
Indicator Description
Text Lines
The three text lines provide the users with information on their present location in the keypad menu structure as well as with information related to the operation of the drive.
Table 5-4: Text Lines
Indicator Description
SPI9000 Inverter Unit FI9 – FI14 User Manual
Lights up when the AC power is connected to the drive. Simultaneously, the drive status indicator READY is lit up.
Lights up when the drive is running. Blinks when the STOP button is pushed and the drive is ramping down.
Lights up when unsafe operating conditions are encountered and the drive was stopped (Fault Trip). Simultaneously, the drive status indicator FAULT blinks on the display and a fault description appears (see Page 5-11, Active Faults Menu).
Keypad Pushbuttons
The alphanumeric control keypad has nine pushbuttons that are used for controlling the inverter (and motor), setting parameters and monitoring values.
Location indicator: Displays the symbol and number of the menu, parameter, etc. Example: M2 = Menu 2 (Parameters); P2.1.3 = Acceleration time.
Description line: Displays the description of the menu, value or fault.
Value line: Displays the numerical and textual values of references, parameters, etc. and the number of submenus available in each menu.
MN04004002E
Figure 5-2: Keypad Pushbuttons
For more information visit: www.EatonElectrical.com 5-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 5-5: Button Descriptions
Indicator Description
September 2006
This button is used to reset active faults (see Page 5-11, Active Faults Menu).
This button is used to switch between the two latest displays. This may be useful when you want to see how the changed (new) value influences some other value.
The ENTER button is used for:
Confirmation of selections
•Fault history reset (2 – 3 seconds)
This button is used to browse up through the main menu and pages of different submenus. Edit values.
This button is used to browse down through the main menu and pages of different submenus. Edit values.
This button is used to:
Move backward in the menu
Move cursor left (in parameter menu)
Exit edit mode
Press and hold for 2 to 3 seconds to return to main menu
This button is used to:
Move forward in the menu
Move cursor right (in parameter menu)
Enter edit mode
Pressing this button starts the motor if the keypad is in the active control place. See Page 5-10, Selection of Control Place.
Pressing this button stops the motor (unless disabled by parameter R3.4/ R3.6). See Page 5-10, Selection of Control Place.
5-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Menu Navigation
The data on the control keypad is arranged in menus and submenus. The menus are used for the display and editing of measurement and control signals, parameter settings and reference value and fault displays. Through the menus, you can also adjust the contrast of the display.
SPI9000 Inverter Unit FI9 – FI14 User Manual
Location
Description
Number of Items
Available
The first menu level consists of menus M1 to M7 and is called the Main menu. The user can navigate in the main menu with the Browser buttons up and down. The desired submenu can be entered from the main menu with the menu buttons. When there still are pages to enter under the currently displayed menu or page, you can see an arrow in the lower right corner of the display and can reach the next menu level by pressing Menu Button Right.
The control keypad navigation chart is shown in Figure 5-4. Please note that menu M1 is located in the lower left corner. From there you will be able to navigate your way up to the desired menu using the menu and browser buttons.
You will find more detailed descriptions of the menus later in this chapter.
Monitor
V1 V14
Figure 5-3: Keypad Display Data
MN04004002E
For more information visit: www.EatonElectrical.com 5-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Expander boards
G1 G5
System Menu
S1 S9
Fault history
H1 H3
Active faults
F0
A: OPTA1
Language
English
11 Output phase
11 Output phase
or:
G1 G1
Browse
T1 T7
T1FT7
A: Parameters
P1 P3
Change
value
Operation days
17
Operation days
17
Keypad control
P1 P3
Parameters
G1 G9
Monitor
V1 V15
Control Place
I/O Terminal
Basic parameters
P1 P15
Output frequency
13.95 Hz
Browse
Change
value
Min Frequency
13.95 Hz
No editing!
Figure 5-4: Keypad Navigation Chart
Browse
Change
value
5-6 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Monitoring Menu (M1)
You can enter the Monitoring menu from the Main menu by pressing Menu Button Right when the location indication M1 is visible on the first line of the display. Figure 5-5 shows how to browse through the monitored values.
The monitored signals carry the indication V#.# and they are listed in Table 5-6. The values are updated once every 0.3 seconds.
This menu is meant only for signal checking. The values cannot be altered here. For changing values of parameters, see Page 5-8.
SPI9000 Inverter Unit FI9 – FI14 User Manual
FreqReference
13.95 Hz
Monitor
Output frequency
V1 V14
13.95 Hz
Figure 5-5: Monitoring Menu
MN04004002E
For more information visit: www.EatonElectrical.com 5-7
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 5-6: Monitored Signals
Code Signal Name Unit Description
V7.1 Output frequency Hz Frequency to the motor
V7.2 Frequency reference Hz
V7.3 Motor speed rpm Calculated motor speed
V7.4 Motor current A Measured motor current
V7.5 Motor torque % Calculated torque based/nominal torque of the unit
V7.6 Motor power % Calculated actual power/nominal power of the unit
V7.7 Motor voltage V Calculated motor voltage
V7.8 DC-link voltage V Measured DC-link voltage
V7.9 Unit temperature °C Heatsink temperature
V7.10 Motor temperature % Calculated motor temperature
V7.11 Voltage input V AI1
V7.12 Current input mA AI2
V7.13 DIN1, DIN2, DIN3 Digital input statuses
V7.14 DIN4, DIN5,DIN6 Digital input statuses
V7.15 DO1, RO2, RO3 Digital and relay output statuses
V7.16 Analog output
current
M1.17 Multimonitoring
items
September 2006
mA AO1
Displays three selectable monitoring values. See
Page 5-23.
Note: Applications may embody more monitoring values.
Parameter Menu (M2)
Parameters are the way of conveying the commands of the user to the inverter. Parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication M2 is visible on the first line of the display. The value editing procedure is presented in Figure 5-6.
Pressing Menu Button Right once takes you to the Parameter Group Menu (G#). Locate the desired parameter group by using the Browser buttons and press Menu Button Right again to see the group and its parameters. Use the Browser buttons to find the parameter (P#) you want to edit. Pressing Menu Button right takes you to the edit mode. As a sign of this, the parameter value starts to blink. You can now change the value in two different ways:
Set the desired value with the Browser buttons and confirm the change with the ENTER
button. Consequently, the blinking stops and the new value is visible in the value field.
Press Menu Button Right once more. Now you will be able to edit the value digit by
digit. This may come in handy, when a relatively greater or smaller value than that on the display is desired. Confirm the change with the ENTER button.
The value will not change unless the ENTER button is pressed. Pressing Menu Button Left takes you back to the previous menu.
Several parameters are locked, i.e. cannot be edited, when the drive is in RUN status. If you try to change the value of such a parameter the text *Locked* will appear on the display. The inverter must be stopped to edit these parameters.
The parameter values can also be locked using the function in menu M6 (see Page 5-22).
5-8 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
You can return to the Main menu any time by pressing Menu Button Left for 1 to 2 seconds.
The basic application package includes seven applications with different sets of parameters. You will find the parameter lists in the application manual.
Once in the last parameter of a parameter group, you can move directly to the first parameter of that group by pressing Browser button up.
See the diagram for parameter value change procedure in Figure 5-6.
Note: You can connect power to the control board by connecting the external power source
to the bidirectional terminal #6 on the OPTA9 board (see Chapter 4). The external power source can also be connected to the corresponding +24V terminal on any option board. This voltage is sufficient for parameter setting and for keeping the fieldbus active.
Input signals
G1 G8
M2
Parameters
Min Frequency
Keypad Control Menu (M3)
In the Keypad Control Menu, you can choose the control place, edit the frequency reference and change the direction of the motor. You can enter the submenu level by pressing Menu Button Right.
Note: There are some special functions that can be performed in menu M3:
Select the keypad as the active control place by pressing start for 3 seconds when the motor is running. The keypad will become the active control place and the current frequency reference and direction will be copied to the keypad.
Select the keypad as the active control place by pressing stop for 3 seconds when the motor is stopped. The keypad will become the active control place and the current frequency reference and direction will be copied to the keypad.
Basic parameters
G1 G8
Min Frequency
13.95 Hz
P1 P18
14.45 Hz
Figure 5-6: Parameter Value Change Procedure
Min Frequency
13.95 Hz
MN04004002E
Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by pressing enter for 3 seconds.
Note: If you are in any other menu than menu M3, these functions will not work.
For more information visit: www.EatonElectrical.com 5-9
SPI9000 Inverter Unit FI9 – FI14 User Manual
If you are in some other menu than menu M3 and try to start the motor by pressing the START button when the keypad is not selected as the active control place, you will get an error message: Keypad Control NOT ACTIVE.
Selection of Control Place
There are three different places (sources) where the inverter can be controlled. For each control place, a different symbol will appear on the alphanumeric display:
I/O terminals
Keypad (panel)
Fieldbus
You can change the control place by entering the edit mode with Menu Button Right. The options can then be browsed with the Browser buttons. Select the desired control place with the ENTER button. See Figure 5-7.
September 2006
M3
Keypad control
P1 P4
Control Place
Keypad
Control Place
I/O Remote
Control Place
Keypad
Control Place
I/O Remote
Figure 5-7: Selection of Control Place
Keypad Reference
The keypad reference submenu (P3.2) displays and allows the operator to edit the frequency reference. The changes will take place immediately. This reference value will not, however, influence the rotation speed of the motor unless the keypad has been selected as the active control place.
Note: The maximum difference in RUN mode between the output frequency and the keypad
reference is 6 Hz. The program automatically monitors the keypad reference value.
You may edit the reference value (pressing the ENTER button is not necessary).
5-10 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Keypad Direction
The keypad direction submenu (P3.3) displays and allows the operator to change the rotating direction of the motor. This setting will not, however, influence the rotation direction of the motor unless the keypad has been selected as the active control place.
Note: For additional information on controlling the motor with the keypad, see Pages 5-3 and
STOP Button Activated
By default, pushing the STOP button will always stop the motor regardless of the selected control place. You can disable this function by giving parameter 3.4 the value 0. If the value of this parameter is 0, the STOP button will stop the motor only when the keypad has been selected as the active control place.
Active Faults Menu (M4)
You can enter the Active Faults menu from the Main menu by pressing Menu Button Right when the location indication M4 is visible on the first line of the keypad display.
When a fault brings the inverter to a stop, the location indication F1, the fault code, a short description of the fault, and the fault type symbol (see below) will appear on the display. In addition, the indication FAULT or ALARM (see Table 5-1) is displayed and, in case of a FAULT, the red LED on the keypad starts to blink. If several faults occur simultaneously, the list of active faults can be browsed with the Browser buttons.
SPI9000 Inverter Unit FI9 – FI14 User Manual
6-2.
The memory of active faults can store a maximum of 10 faults in the order of appearance. The display can be cleared with the RESET button and the read-out will return to the same state it was in before the fault trip. The fault remains active until it is cleared with the RESET button or with a reset signal from the I/O terminal.
Note: Remove external Start signal before resetting the fault to prevent unintentional restart
of the drive.
MH
Active faults
F0
Figure 5-8: Normal State, No Faults
Fault Types
The inverter has four types of faults. These types differ from each other on the basis of the subsequent behavior of the drive. See Table 5-7.
MN04004002E
For more information visit: www.EatonElectrical.com 5-11
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Operation hours
34:21:05
Fault Type Symbol
11 Output phase
T1F
T13
Operation days
17
Figure 5-9: Fault Display
Table 5-7: Fault Types
Fault Type Symbol Meaning
A (Alarm) This type of fault is a sign of an unusual operating condition. It does not cause
F (Fault) An “F fault” makes the drive stop. Actions need to be taken to restart the drive.
AR (Fault Autoreset) If an “AR fault” occurs the drive will stop immediately. The fault is reset
FT (Fault Trip) If the drive is unable to restart the motor after an AR fault an FT fault occurs.
the drive to stop, nor does it require any special actions. The “A fault” remains in the display for about 30 seconds.
automatically and the drive tries to restart the motor. Finally, if the restart is not successful, a fault trip (FT, see below) occurs.
The “FT fault” has basically the same effect as the F fault: the drive is stopped.
Note: Fault Codes are listed in Appendix A.
Fault Time Data Record
When a fault occurs, the information described in Figure 5-8 is displayed. By pressing Menu Button Right, you will enter the Fault time data record menu indicated by T.1➔T.#. In this menu, some selected important data valid at the time of the fault are recorded. This feature will help the user or the service person in determining the cause of the fault.
5-12 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
The data available are:
Table 5-8: Fault Time Recorded Data
Data Units Description
T.1 D Counted operation days (Fault 43: Additional code)
T.2 hh:mm:ss
(d)
T.3 H z
hh:mm:ss
T.4 T.5 T.6 T.7 T.8
T.9 T.10 T.11 T.12 T.13
Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
A V % % V
°C — — — —
Counted operation hours (Fault 43: Counted operation days)
Output frequency (Fault 43: Counted operation hours)
Motor current Motor voltage Motor power Motor torque DC bus voltage
Unit temperature Run status Direction Warnings Zero speed
Real Time Record
If real time is set to run on the inverter, the data items T1 and T2 will appear as follows:
Table 5-9: Real Time Record
Data Units Description
T.1 yyyy-mm-dd Counted operation days
T.2 hh:mm:SS,sss Counted operation hours
Fault History Menu (M5)
You can enter the Fault History menu from the Main menu by pressing Menu Button Right when the location indication M5 is visible on the first line of the keypad display.
All faults are stored in the Fault History menu where you can browse them with the Browser buttons. Additionally, the Fault Time Data Record pages (see Page 5-12) are accessible for each fault. You can return to the previous menu any time by pressing Menu Button Left.
The memory of the inverter can store a maximum of 30 faults in order of appearance. The number of faults currently in the fault history is shown on the value line of the main page (H1H#). The order of the faults is indicated by the location indication in the upper left corner of the display. The latest fault is indicated by F5.1, the one before that by F5.2 and so on. If there are 30 uncleared faults in the memory, the next fault will erase the oldest fault from the memory.
Pressing the ENTER button for about 2 to 3 seconds resets the whole fault history. The symbol H# will change to 0.
MN04004002E
For more information visit: www.EatonElectrical.com 5-13
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
System Menu (M6)
You can enter the System menu from the Main menu by pressing Menu Button Right when the location indication M6 is visible on the first line of the keypad display.
The controls associated with the general use of the inverter, such as application selection, customized parameter sets or information about the hardware and software are located under the System menu. The number of submenus and subpages is shown with the symbol S (or P) on the value line.
Table 5-10 has a list of the functions available in the System menu.
Fault history
H1
5 ChargeSwitch
11 Output phase
H3
T1 T7
PUSH to Reset
Figure 5-10: Fault History Menu
Operation hours
13:25:43
Operation days
17
5-14 For more information visit: www.EatonElectrical.com MN04004002E
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
Table 5-10: System Menu Functions
Code Function Min Max Unit Default Cust Selections
S6.1 Selection of
language
English English
Deutsch Suomi Svenska Italiano
S6.2 Application
selection
Basic Application
Basic Application Standard Application Local/Remote control Appl. Multi-Step Application PID Control Application Multi-Purpose Control Appl. Pump and Fan Control Appl.
S6.3 Copy parameters
S6.3.1 Parameter sets Load factory defaults
Store set 1 Load set 1 Store set 2 Load set 2
S6.3.2 Load to keypad All parameters
S6.3.3 Load from keypad All parameters
All but motor parameters Application parameters
P6.3.4 Parameter backup Yes No
Ye s
S6.4 Parameter
comparison
S6.5 Safety
S6.5.1 Password Not used 0=Not used
P6.5.2 Parameter locking Change
Enabled
Change Enabled Change Disabled
S6.5.3 Start-Up Wizard No
Ye s
S6.5.4 Multimonitoring
items
Change Enabled
Change Enabled Change Disabled
S6.6 Keypad settings
P6.6.1 Default page
P6.6.2 Default page/OM
P6.6.3 Timeout time 0 65535 s 30
P6.6.4 Contrast 0 31 18
P6.6.5 Backlight time Always 65535 min 10
S6.7 Hardware settings
P6.7.1 Internal brake
resistor
Connected Not connected
Connected
P6.7.2 Fan control function Continuous Continuous
Temperature
P6.7.3 HMI acknowledge. 200 5000 ms 200
P6.7.4 HMI: no. of retries 1 10 5
MN04004002E
For more information visit: www.EatonElectrical.com 5-15
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table 5-10: System Menu Functions, continued
Code Function Min Max Unit Default Cust Selections
S6.8 System information
S6.8.1 Total counters
C6.8.10.1. MWh counter kWh
C6.8.10.2. Operation day
counter
C6.8.1.3. Operation hour
counter
S6.8.2 Trip counters
T6.8.2.1 MWh counter kWh
T6.8.2.2 Clear MWh counter
T6.8.2.3 Operation day
counter
T6.8.2.4 Operation hour
counter
T6.8.2.5 Clear operation
hour counter
S6.8.3 Software
information
S6.8.3.1 Software package
S6.8.3.2 System software
version
S6.8.3.3 Firmware interface
S6.8.3.4 System load
S6.8.4 Applications
S6.8.4.# Name of
application
D6.8.4.#.1 Application ID
D6.8.4.#.2 Applications:
version
D6.8.4.#.3 Applications:
firmware interface
S6.8.5 Hardware
I6.8.5.1 Unit power
I6.8.5.2 Unit voltage
I6.8.5.3 Info: Brake chopper
I6.8.5.4 Info: Brake resistor
S6.8.6 Expander boards
September 2006
5-16 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Selection of Language
The control keypad offers you the possibility to control the inverter through the keypad in the language of your choice.
Locate the language selection page under the System menu. Its location indication is S6.1. Press Menu Button Right once to enter the edit mode. As the name of the language starts to blink you can select another language for the keypad texts. Confirm with the ENTER button. The blinking stops and all text information on the keypad is presented in the selected language.
You can return to the previous menu any time by pressing Menu Button Left.
M6
System Menu
S1 S11
Language
English
Language
English
Langue
Francais
Figure 5-11: Selection of Language
Application Selection
The user can select the desired application on the Application selection page (S6.2). To enter the page, press Menu Button Right on the first page of the System menu. To change the application, press Menu Button Right once more. The name of the application starts to blink. Now you can browse the applications with the Browser buttons and select the desired application with the ENTER button.
After application change, you will be asked if you want the parameters of the new application to be uploaded to the keypad. If you want to do this, press the ENTER button. Pressing any other button leaves the parameters of the previously used application saved in the keypad.
For more information about the application, see the application manual.
MN04004002E
M6 56.2
System Menu
S1 S11
56.2 56.2
Application
Standard
Application
Standard
Application
Multi-step
Figure 5-12: Change of Application
For more information visit: www.EatonElectrical.com 5-17
SPI9000 Inverter Unit FI9 – FI14 User Manual
Copy Parameters
The parameter copy function is used when the operator wants to copy one or all parameter groups from one drive to another. All the parameter groups are first uploaded to the keypad, then the keypad is connected to another drive and then the parameter groups are downloaded to it (or possibly back to the same drive).
Before any parameters can be successfully copied from one drive to another, the drive has to be stopped when the parameters are downloaded to it:
The parameter copy menu (S6.3) contains four functions:
Parameter Sets (S6.3.1)
The user can reload the factory default parameter values and store and load two customized parameter sets (all parameters included in the application).
On the Parameter Sets page (S6.3.1), press Menu Button Right to enter the edit mode. The text LoadFactDef begins to blink and you can confirm the loading of factory defaults by pressing the ENTER button. The drive resets automatically.
Alternatively, you can choose any other storing or loading functions with the Browser buttons. Confirm with the ENTER button. Wait until “OK” appears on the display.
September 2006
56.3.1
Parameter sets
Select
56.3.1
Parameter sets
Wait. . .
56.3.1
Parameter sets
LoadFactDef
56.3.1
Parameter sets
OK
Confirm
Cancel
Figure 5-13: Storing and Loading of Parameter Sets
Upload parameters to keypad (To keypad, S6.3.2)
This function uploads all existing parameter groups to the keypad provided that the drive is stopped.
Enter the To Keypad page (S6.3.2) from the Parameter Copy menu. Pressing Menu Button Right takes you to the edit mode. Use the Browser buttons to select the option All Parameters and press the ENTER button. Wait until “OK” appears on the display.
5-18 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
56.3
Copy Parameters
Select
56.3.2
Up to keypad
Wait. . .
P1 P4
56.3.2
Up to keypad
Select
56.3.2
Up to keypad
OK
56.3.2
Up to keypad
All param.
Confirm
Change Value
Cancel
Figure 5-14: Parameter Copy to Keypad
Download parameters to drive (From keypad, S6.3.3)
This function downloads one or all parameter groups uploaded to the keypad to a drive provided that the drive is in STOP status.
Enter the To Keypad page (S6.3.2) from the Parameter Copy menu. Pressing the Menu Button Right takes you to the edit mode. Use the Browser buttons to select either All Parameters, All but Motor Parameters or Application Parameters and press the ENTER button. Wait until “OK” appears on the display.
The procedure to download the parameters from keypad to drive is similar to that of from drive to keypad. See Figure 5-14.
Automatic Parameter Backup (P6.3.4)
On this page you can activate or inactivate the parameter backup function. Enter the edit mode by pressing Menu Button Right. Select Yes or No with the Browser buttons.
When the Parameter backup function is activated control keypad makes a copy of the parameters of the presently used application. When applications are changed, you will be asked if you wish the parameters of the new application to be uploaded to the keypad. If you want to do this, press the ENTER button. If you wish to keep the copy of the parameters of the previously used application saved in the keypad, press any other button. Now you will be able to download these parameters to the drive following the instructions given in Chapter Copy Parameters on Page 5-18.
If you want the parameters of the new application to be automatically uploaded to the keypad, you have to do this for the parameters of the new application once on page 6.3.2 as instructed. Otherwise the panel will always ask for the permission to upload the parameters.
Note: Parameters saved in the parameter settings on page S6.3.1 will be deleted when
applications are changed. If you want to transfer the parameters from one application to another, you have to upload them first to the keypad.
MN04004002E
For more information visit: www.EatonElectrical.com 5-19
SPI9000 Inverter Unit FI9 – FI14 User Manual
Parameter Comparison
In the Parameter Comparison submenu (S6.4), you can compare the actual parameter values to the values of your customized parameter sets and those loaded to the control keypad.
You can compare the parameter by pressing Menu Button Right in the Compare Parameters submenu. The actual parameter values are first compared to those of the customized parameter Set1. If no differences are detected, “0” is displayed on the lowermost line. If any of the parameter values differ from those of Set1, the number of the deviations is displayed together with symbol P (for example, P1P5 = five deviating values). By pressing Menu Button Right once more, you can enter pages where you can see both the actual value and the value it was compared to. In this display, the value on the description line (in the middle) is the default value and the one on the value line (lowermost) is the edited value. Furthermore, you can also edit the actual value with the Browser buttons in the edit mode which you can enter by pressing Menu Button Right once.
September 2006
56.4
ParamComparison
C1 C3
56.4.1
Set1
0
Or
56.4.1
Set1
P1 P6
56.4.1.1
P2.1.2= 50.0
20.0 Hz
56.4.1.1
P2.1.2= 50.0
Edit Value
Confirm Change
Figure 5-15: Parameter Comparison
20.0 Hz
5-20 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Safety
Note: The Security submenu is protected with a password. Store the password in a safe
place!
Password (S6.5.1)
The application selection can be protected against unauthorized changes with the Password function (S6.5.1).
By default, the Password function is not in use. If you want to activate the function, enter the edit mode by pressing Menu Button Right. A blinking zero appears in the display and you can set a password with the Browser buttons. The password can be any number between 1 and
65535.
Note: You can also set the password by digits. In the edit mode, push Menu Button Right
again and another zero appears on the display. Set ones first. To set the tens, press Menu Button Right, and so on. Confirm the password with the ENTER button. After this, you have to wait until the Timeout time (P6.6.3) (see Page 5-24) has expired before the password function is activated.
If you try to change applications or the password itself, you will be prompted for the current password. Enter the password with the Browser buttons.
You can deactivate the password function by entering the value 0.
56.5.1
Password
Not in use
56.5.1
Password
0
Or
56.5.1
Password
00
Figure 5-16: Password Setting
Note: Store the password in a safe place! No changes can be made unless a valid password
is entered.
MN04004002E
For more information visit: www.EatonElectrical.com 5-21
SPI9000 Inverter Unit FI9 – FI14 User Manual
Parameter Lock (P6.5.2)
This function allows the user to prohibit changes to the parameters.
If the parameter lock is activated, the text *locked* will appear on the display if you try to edit a parameter value.
Note: This function does not prevent unauthorized editing of parameter values.
Enter the edit mode by pressing Menu Button Right. Use the Browser buttons to change the parameter lock status. Confirm the change with the ENTER button or go back to the previous level by pressing Menu Button Left.
September 2006
M6
S1 S9 P1 P4
56.5.2
Parameter Lock
SecuritySystem Menu
56.5.2
Parameter Lock
ChangeDisablChangeEnable
56.5.2
Parameter Lock
ChangeEnable
Figure 5-17: Parameter Locking
Start-Up Wizard (P6.5.3)
The Start-Up Wizard facilitates the commissioning of the inverter. If active, the Start-Up Wizard prompts the operator for the language and application of his/her choice and then displays the first menu or page.
Activating the Start-Up Wizard: In the System Menu, find page P6.5.3. Press Menu Button Right once to enter the edit mode. Use the Browser buttons to select Yes and confirm the selection with the ENTER button. If you want to deactivate the function, follow the same procedure and give the parameter value “NO”.
P6.5.3
Startup wizard
No
P6.5.3
Startup wizard
No Ye s
P6.5.3
Startup wizard
Confirm
Cancel
Figure 5-18: Activation of Start-Up Wizard
5-22 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Multimonitoring Items (P6.5.4)
The alphanumeric keypad features a display where you can monitor up to three actual values at the same time — see Monitoring Menu (M1) on Page 5-7 and the manual of the application you are using. On page P6.5.4 of the System Menu, you can define whether the operator can replace the values monitored with other values. See below.
56.5.4
Multimon. items
ChangeEnable
56.5.4
Multimon. items
56.5.4
Multimon. items
ChangeDisableChangeEnable
Figure 5-19: Disabling the Change of Multimonitoring Items
Keypad Settings
In the Keypad Settings submenu under the System menu, you can further customize your inverter operator interface.
Locate the Keypad Setting submenu (S6.6). Under the submenu, there are four pages (P#) associated with the keypad operation:
5.6.6 P6.6.
Keypad settings
P1 P5
Default page
0.
Figure 5-20: Keypad Settings Submenu
Default Page (P6.6.1)
MN04004002E
Here you can set the location (page) to which the display automatically moves when the Timeout Time (see below) has expired or the power is switched on to the keypad.
If the default page is 0, the function is not activated, i.e. the latest displayed page remains on the keypad display. Pressing Menu Button Right takes you to the edit mode. Change the number of the Main menu with the Browser buttons. To edit the number of the submenu/ page, press Menu Button Right. If the page you want to move to by default is at the third level, repeat the procedure. Confirm the new default page with the ENTER button. You can return to the previous menu at any time by pressing Menu Button Left.
P6.6.
Default page
0.
P6.6.
Default page
0.
P6.6.
Default page
1.
Confirm Change
Repeat to Set Default Submenu/Page
Cancel
Figure 5-21: Default Page Function
For more information visit: www.EatonElectrical.com 5-23
SPI9000 Inverter Unit FI9 – FI14 User Manual
Default page in the operating menu (P6.6.2)
Here you can set the location (page) in the Operating menu (in special applications only) to which the display automatically moves to when the set Timeout Time (see below) has expired or the power is switched on to the keypad.
See how to set the Default page in Figure 5-21.
Timeout Time (P6.6.3)
The Timeout Time setting defines the time after which the keypad display returns to the Default page (P6.6.1).
Enter the edit mode by pressing Menu Button Right. Set the desired timeout time and confirm it with the ENTER button. You can return to the previous menu at any time by pressing Menu Button Left.
September 2006
P6.6.3
Timeout time
90 s
P6.6.3 P6.6.3
Timeout time
90 s.
Timeout time
60 s.
Confirm Change
Cancel
Figure 5-22: Timeout Time Setting
Note: If the Default page value is 0, the Timeout Time setting has no effect.
Contrast Adjustment (P6.6.4)
In case the display is unclear, you can adjust its contrast through the same procedure as for the timeout time setting (see above).
Backlight Time (P6.6.5)
By giving a value for the Backlight time, you can determine how long the backlight stays on before going out. You can select any time between 1 and 65535 minutes or “Forever.” For the value setting procedure, see Timeout Time above.
5-24 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Hardware Settings
Note: The Hardware settings submenu is protected with a password. Store the password in a
safe place!
In the Hardware Settings submenu (S6.7) under the System menu, you can further control some functions of the hardware in your inverter. The functions available in this menu are Internal brake resistor connection, Fan control, HMI acknowledge timeout and HMI retry.
Internal Brake Resistor Connection (P6.7.1)
This function tells the inverter, whether the internal brake resistor is connected or not. If you have ordered the inverter with an internal brake resistor, the default value of this parameter is Connected. However, if it is necessary to increase braking capacity by installing an external brake resistor, or if the internal brake resistor is disconnected for another reason, it is advisable to change the value of this function to Not conn. in order to avoid unnecessary fault trips.
Enter the edit mode by pressing Menu Button Right. You can change the brake resistor information with the Browser buttons. Confirm the change with the ENTER button or return to the previous level with Menu Button Left.
Note: The brake resistor is available as optional equipment for all classes. It can be installed
internally in classes FR4 to FR6.
M6
S1 S8 P1 P4
P6.7.
InternBrakeRes
56.7
HW SettingsSystem Menu
P6.7.
InternBrakeRes
Not conn.Connected
P6.7.
InternBrakeRes
Connected
Figure 5-23: Internal Brake Resistor Connection
MN04004002E
For more information visit: www.EatonElectrical.com 5-25
SPI9000 Inverter Unit FI9 – FI14 User Manual
Fan Control (P6.7.2)
This function allows you to control the cooling fan of the inverter. You can set the fan to run continuously when the power is switched on or depending on the temperature of the unit. If the latter function has been selected, the fan is switched on automatically when the heatsink temperature reaches 60°C. The fan receives a stop command when the heatsink temperature falls to 55°C. After the command, the fan runs for approximately 1 minute before stopping. The same happens after switching on the power and after changing the value from Continuous to Temperature.
Note: The fan runs always when the drive is in RUN state.
To change the value: Enter the edit mode by pressing Menu Button Right. The value starts blinking. Use the Browser buttons to change the fan mode and confirm the change with the ENTER button. If you do not want to change the value, return to the previous level with Menu Button Left. See Figure 5-24.
September 2006
P6.7.2
Fan control
Continuous
P6.7.2 P6.7.2
Fan control
Continuous
Fan control
Temperature
Figure 5-24: Fan Control Function
HMI Acknowledge Timeout (P6.7.3)
This function allows the user to change the timeout of the HMI acknowledgement time. The inverter waits for the HMI acknowledgment in accordance with the value of this parameter.
Note: If the inverter has been connected to the PC with a normal cable, the default values of
parameters 6.7.3 and 6.7.4 (200 and 5) must not be changed.
If the inverter has been connected to the PC via a modem and there is a delay in transferring messages, the value of parameter 6.7.3 must be set according to the delay as follows:
Example:
Transfer delay between the inverter and the PC = 600 ms
The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving delay)
The corresponding setting shall be entered in the [Misc] part of the file NCDrive.ini:
Retries = 5
AckTimeOut = 1200
TimeOut = 6000
It must also be considered that intervals shorter than the AckTimeOut time cannot be
used in NC-Drive monitoring.
Enter the edit mode by pressing Menu Button Right. The current value starts to blink. Use the Browser buttons to change the acknowledgement time. Confirm the change with the ENTER button or return to the previous level with Menu Button Left.
5-26 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
P6.7.3
HMI ACK timeout
200ms
P6.7.3
HMI ACK timeout
200ms
Figure 5-25: HMI Acknowledge Timeout
Number of retries to receive HMI acknowledgement (P6.7.4)
With this parameter you can set the number of times the drive will try to receive acknowledgement if it does not receive acknowledgement within the acknowledgement time (P6.7.3) or if the received acknowledgement is faulty.
You can change value through the same procedure as for P6.7.3 (see above).
Note: Changes to P6.7.3 and P6.7.4 become effective after the next start-up.
System info
In the System info submenu (S6.8) you can find inverter-related hardware and software information.
You can enter the System info submenu by pressing Menu Button Right. You can now browse the submenu pages with the Browser buttons.
Total Counters
The Total counters menu (S6.8.1) contains information on the inverter operation times i.e. the total number of MWh, operation days and operation hours. Unlike the counters in the Trip counters menu, these counters cannot be reset.
Note: The Power On time counter (days and hours) runs always when the power is on.
Table 5-11: Counter Pages
Page Counter
C6.8.10.1 MWh counter
C6.8.10.2 Operation day counter
C6.8.1.3. Operation hour counter
MN04004002E
For more information visit: www.EatonElectrical.com 5-27
SPI9000 Inverter Unit FI9 – FI14 User Manual
Trip Counters
Trip counters (menu S6.8.2) are counters the values of which can be reset i.e. restored to zero. You can use the following resettable counters:
Note: The trip counters run only when the motor is running.
Table 5-12: Resettable Counters
Page Counter
T6.8.2.1 MWh counter
T6.8.2.3 Operation day counter
T6.8.2.4 Operation hour counter
The counters can be reset on pages 6.8.2.2 (Clear MWh counter) and 6.8.2.5 (Clear Operation time counter).
Example: When you want to reset the operation counters, see Figure 5-26.
September 2006
56.8.2 P6.8.2.5
Trip counters
T1 T5
P6.8.2.5
Clr Optime cntr
Reset
Clr Optime cntr
Not reset
P6.8.2.5
Clr Optime cntr
Reset
P6.8.2.5
Clr Optime cntr
Not reset
P6.8.2.5
Clr Optime cntr
Not reset
Figure 5-26: Counter Reset
Software (S6.8.3)
The Software information page includes information on the following inverter software related topics:
Table 5-13: Software Information Pages
Page Counter
6.8.3.1 Software packages
6.8.3.2 System software version
6.8.3.3 Firmware interface
6.8.3.4 System load
5-28 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Applications (S6.8.4)
At location S6.8.4, you can find the Applications submenu containing information on the application currently in use and all other applications loaded into the inverter. The following information is available:
Table 5-14: Applications Information Pages
Page Counter
6.8.4.# Name of application
6.8.4.#.1 Application ID
6.8.4.#.2 Version
6.8.4.#.3 Firmware interface
In the Applications information page, press Menu Button Right to enter the Application pages of which there are as many as there are applications loaded into the inverter. Locate the desired application with the Browser buttons and then enter the Information pages with Menu Button Right. Use the Browser buttons to see the different pages.
56.8.4
Applications
A1 A7 D1 D3
Standard
D1 D3
R6.8.4.
Basic
Version
2.01
R6.8.4. .
Application id
FIFF01
Figure 5-27: Applications Info Submenu
Hardware (S6.8.5)
The Hardware information page provides information on the following hardware-related topics:
Table 5-15: Hardware Information Pages
Page Counter
6.8.5.1 Nominal power of the unit
6.8.5.2 Nominal voltage of the unit
6.8.5.3 Brake chopper
6.8.5.4 Brake resistor
MN04004002E
For more information visit: www.EatonElectrical.com 5-29
SPI9000 Inverter Unit FI9 – FI14 User Manual
Expander Boards (S6.8.6)
The Expander boards submenu contains information about the basic and option boards. (See Chapter Control unit)
You can check the status of each board slot by entering the Expander Boards page with Menu Button Right. Use the Browser buttons to view the status of each board slot. The description line of the keypad will display the type of the expansion board and the text “Run” is shown below it. If no board is connected to the slot the text “no board” will be shown. If a board is connected to a slot but the connection is lost for some reason, the text “no conn.” is displayed. For more information, see Chapter 4.
For more information on expander board related parameters, see Page 5-30.
September 2006
56.8.6
Expander boards
Expander Board Menu (M7)
In the Expander board menu the user can 1) see the expander boards connected to the control board and 2) see and edit the parameters associated with the expander boards.
Go to the next menu level (G#) with Menu Button Right. At this level, you can browse through slots A to E with the Browser buttons to see which expander boards are connected to the control board. On the lowermost line of the display, you will also see the number of parameters associated with the board. You can view and edit the parameter values as described on Page 5-8. See Table 5-16 and Figure 5-29.
B:OPTA2
E1 E2
E6.8.6.
A:OPTA1
E1 E5 E1 E2
Software version
10001.0
E6.8.6. .
State
Run
Figure 5-28: Expander Board Information Menus
5-30 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Expander Board Parameters
Table 5-16: Expander Board Parameters (Board OPTA9)
Code Parameter Min Max Default Cust Selections
P7.1.1.1 AI1 mode 1 5 3 1 = 0 to 20 mA
P7.1.1.2 AI2 mode 1 5 1 See P7.1.1.1
P7.1.1.3 AO1 mode 1 4 1 1 = 0 to 20 mA
D:OPTC2
Monitor
G1 G2
M7
Expander boards
G7.3
C:OPTC1
G1 G5 G1 G2 P1 P4
G7.3. . G7.3. .
Slave address Slave address
126 126
G7.3.
Parameters
Run
Change Value
Confirm Change
2 = 4 to 20 mA 3 = 0 to 10V 4 = 2 to 10V 5 = –10 to +10 V
2 = 4 to 20 mA 3 = 0 to 10V 4 = 2 to 10V
V1 V2
Baud rate
Auto
Further Keypad Functions
The control keypad contains additional application-related functions. See the application manual for more information.
MN04004002E
Figure 5-29: Expander Board Information Menu
For more information visit: www.EatonElectrical.com 5-31
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
5-32 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Chapter 6 — Start-Up
Safety Precautions
Before start-up, note the following directions and warnings:
SPI9000 Inverter Unit FI9 – FI14 User Manual
WARNING
1
2
3
4
5
6
Internal components and circuit boards of the inverter (except for the galvanically isolated I/O terminals) are live when the inverter is connected to mains potential. Coming
into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the DC-link/brake resistor terminals+/- are live when the inverter is connected to DC supply, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O­terminals may have a dangerous control voltage present even when the inverter is disconnected from DC supply.
Do not make any connections when the inverter is connected to the DC supply.
After having disconnected the inverter, wait until the fan stops and the indicators on the keypad go out (if no keypad is attached see the indicator through the keypad base). Wait 5 more minutes before doing any work on inverter connections. Do not open the cover before the time has expired.
Before connecting the inverter to DC supply, make sure that the inverter’s front cover is closed.
MN04004002E
7
8
When running, the side of inverter FR8 is burning hot. Do not touch it with bare hands!
When running, the back of inverter FR6 is burning hot. Therefore it MUST NOT be mounted onto a surface which is not fireproof.
For more information visit: www.EatonElectrical.com 6-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Sequence of Operation
1. Read the safety instructions in the front of this manual carefully and follow them.
2. After installation, make sure:
Both the inverter and the motor are grounded
DC supply and motor cables comply with the requirements given in Chapter 3
Control cables are located as far as possible from the power cables (see
Chapter 2), and the shields of the shielded cables are connected to protective ground. The wires must not touch the electrical components of the inverter.
Common inputs of digital input groups are connected to +24V or the ground of the
I/O terminal or the external supply.
3. Check the quality and quantity of cooling air. (See Chapter 2, Mounting Space
Dimensions.)
4. Check the inside of the inverter for condensation.
5. Check that all Start/Stop switches connected to the I/O terminals are in the Stop position.
September 2006
6. Connect the inverter to DC supply.
7. Set the parameters of group 1 according to the requirements of your application (see application manual). Set the following parameters at the least:
Motor nominal voltage
Motor nominal frequency
Motor nominal speed
Motor nominal current
You will find the values needed for the parameters on the motor rating plate.
8. Perform either Test A or B without the motor running:
Test A — Controls from the I/O terminals:
Turn the Start/Stop switch to ON position.
Change the frequency reference (potentiometer).
Check in the Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
Turn the Start/Stop switch to OFF position.
Test B— Control from the Control keypad:
Change the control from the I/O terminals to the keypad as advised on Page 5-10.
Press the START button on the keypad.
Move over to the Keypad Control Menu M3 and Keypad Reference submenu (see
Keypad Reference on Page 5-10) and change the frequency reference with the Browser buttons.
6-2 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Check in Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
Press the STOP button on the keypad.
9. Perform the start-up tests without the motor being connected to the process. If this is not possible, make sure that each test can be done safely prior to performing it. Inform your co-workers of the tests.
Switch off the DC supply voltage and wait until the drive has stopped as advised on
Page 6-1, Safety Precautions.
Connect the motor cable to the motor and to the motor cable terminals of the
inverter.
Make sure that all Start/Stop switches are in Stop positions.
Switch the supply voltage ON.
Repeat Test A or B in step 8.
10. Connect the motor to the process (if the start-up test was performed without the motor being connected). Inform our co-workers of the tests.
Before running the tests, make sure that this can be done safely.
Repeat Test A or B in step 8.
MN04004002E
For more information visit: www.EatonElectrical.com 6-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
6-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
Appendix A — Fault Codes
When a fault is detected by the inverter control electronics, the drive is stopped and the symbol F together with the ordinal number of the fault, the fault code and a short fault description appear on the display. The fault can be reset with the RESET button on the control keypad or via the I/O terminal. The faults are stored in the Fault History Menu M5, which can be browsed. Table A-1 contains all the fault codes.
Table A-1: Fault Codes
Fault Code Fault Possible Cause Solution
SPI9000 Inverter Unit FI9 – FI14 User Manual
1 Overcurrent Inverter detected too high a current
(>4 x I
) in the motor cable:
n
Sudden heavy load increase
Short circuit in the motor
Unsuitable motor
2 Overvoltage The DC link voltage exceeded the
defined limits:
Deceleration time too short
High overvoltage spikes in supply
3 Ground Fault
Current measurement has detected that the sum of motor phase currents is not zero.
Insulation failure in cables or
motor
5 Charging Switch Charging switch is open, when the
START command is given:
Faulty operation
Component failure
6 Emergency Stop Stop signal was given from the
option board.
7 Saturation Trip Various causes:
Component failure
Brake resistor is short circuited or
overloaded
8 System Fault Component failure
Faulty operation
Note: See exceptional fault data record on Page 5-12.
Programmable.
Check loading. Check motor. Check cables.
Set the deceleration time longer. Add a brake chopper or brake
resistor.
Check motor cable and motor.
Reset the fault and restart. Should the fault re-occur, contact
your Cutler-Hammer distributor.
Cannot be reset from the keypad. Switch off the power. DO NOT RE-CONNECT POWER. Contact Eaton. If this fault appears simultaneously
with Fault 1, check motor cables and motor.
Reset the fault and restart. Should the fault re-occur, contact
your Cutler-Hammer distributor.
MN04004002E
For more information visit: www.EatonElectrical.com A-1
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table A-1: Fault Codes (Continued)
Fault Code Fault Possible Cause Solution
9 Undervoltage
10 Input Line
Supervision
11 Output phase
supervision
12 Brake Chopper
Supervision
13 Inverter
Undertemperature
14 Inverter
Overtemperature
15 Motor Stalled
16 Motor
Overtemperature
17 Motor underload
22 EEPROM
checksum fault
24 Counter fault Values displayed on counters are
25 Microprocessor
watchdog fault
26 Startup prevented Start-up of the drive was prevented. Cancel prevention of start-up.
29 Thermistor fault
Programmable.
DC link voltage is below the defined voltage limits:
Supply voltage too low (most
probable cause)
Inverter internal fault
In case of temporary supply voltage break, reset the fault and restart the inverter. Check the supply voltage. If it is adequate, an internal failure has occurred. Contact your Cutler-Hammer distributor.
Input line phase is missing. Check supply voltage and cable.
Current measurement has detected
Check motor cable and motor. there is no current in one motor phase.
No brake resistor installed
Brake resistor is broken
Brake chopper failure
Check brake resistor.
If the resistor is OK, the chopper is
faulty.
Contact your Cutler-Hammer
distributor.
Heatsink temperature is under -10°C
Heatsink temperature is over 90°C.
Check the correct amount and flow of
cooling air. Overtemperature warning is issued when the heatsink temperature exceeds 85°C.
Check the heatsink for dust.
Check the ambient temperature.
Make sure that the switching
frequency is not too high in relation
to ambient temperature and motor
load.
Motor stall protection has tripped. Check motor.
Motor overheating was detected
by inverter motor temperature model
Decrease the motor load.
If no motor overload exists, check the
temperature model parameters.
Motor is overloaded
Motor underload protection tripped.
Parameter save fault
Faulty operation
Component failure
incorrect.
Faulty operation
Component failure
Reset the fault and restart.
Should the fault re-occur, contact
your Cutler-Hammer distributor.
The thermistor input of option board detected an increase in the motor temperature.
Check motor cooling and loading.
Check thermistor connection.
(If thermistor input of the option
board is not in use, it has to be short
circuited.)
September 2006
A-2 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table A-1: Fault Codes (Continued)
Fault Code Fault Possible Cause Solution
31 IGBT Temperature
(hardware)
IGBT inverter bridge overtemperature protection detected
Check loading.
Check motor size. a short term overload current that is too high.
32 Fan Cooling Cooling fan of the inverter does not
start, when ON command is given.
34 CAN Bus
Sent message not acknowledged. Ensure that there is another device
Communication
Contact your Cutler-Hammer
distributor.
on the bus with the same
configuration.
36 Control Unit Control unit cannot control power
Change control unit. unit and vice versa.
37 Device Change
(same type)
Option board or control unit
changed
Reset
Note: No fault time data record.
Option board of different type or
drive with different power rating
38 Device Added
(same type)
Option board or drive added
Drive with same power rating or
Reset
Note: No fault time data record.
same type of board added
39 Device Removed
Option board removed
Drive removed
Reset
Note: No fault time data record.
40 Device Unknown Unknown option board or drive. Contact your Cutler-Hammer
distributor.
41 IGBT Temperature IGBT Inverter Bridge
overtemperature protection has
Check loading.
Check motor size. detected a short term overload current that is too high.
42 Brake Resistor
Overtemperature
Brake resistor overtemperature
protection detected braking that is
Set the deceleration time longer.
Use external brake resistor. too heavy.
43 Encoder Fault Note: See the exceptional fault data
record on Page 5-12. Additional
Check encoder channel connections.
Check the encoder board. codes:
1 = Encoder 1 channel A is missing 2 = Encoder 1 channel B is missing 3 = Both encoder 1 channels are
missing
4 = Encoder reversed
44 Device Change
(different type)
Option board or control unit
changed
Option board of different type or
drive with different power rating
Reset.
Note: No fault time data record is
made.
Note: Application parameter values
restored to default.
45 Device Added
(different type)
Option board or device added
Option board of different type or
drive with different power rating added
Reset.
Note: No fault time data record is
made.
Note: Application parameter values
restored to default.
Programmable.
“A” faults only.
MN04004002E
For more information visit: www.EatonElectrical.com A-3
SPI9000 Inverter Unit FI9 – FI14 User Manual
Table A-1: Fault Codes (Continued)
Fault Code Fault Possible Cause Solution
September 2006
50 Analog Input
(signal range, 4 to 20 mA)
Current for analog input is < 4 mA:
Control cable is broken or loose
Signal source failed
Check the current loop, signal source and wiring.
51 External Fault Digital input failed. Check source of trigger.
52 Keypad
communication
There is no connection between the control keypad and the inverter.
Check the keypad connection and keypad cable.
Fault
53 Fieldbus Fault The data connection between the
fieldbus master and the fieldbus board is broken.
Check installation. If installation is correct, contact your
Cutler-Hammer distributor.
54 Slot Fault Defective option board or slot. Check that the board is properly
installed and seated in slot. If the installation is correct, contact your Cutler-Hammer distributor.
56 PT100 Board
Temperature Fault
Programmable.
Temperature limit values set for the PT100 board have been exceeded.
Determine the cause of the high temperature.
A-4 For more information visit: www.EatonElectrical.com MN04004002E
September 2006
SPI9000 Inverter Unit FI9 – FI14 User Manual
MN04004002E
For more information visit: www.EatonElectrical.com A-5
SPI9000 Inverter Unit FI9 – FI14 User Manual
September 2006
A-6 For more information visit: www.EatonElectrical.com MN04004002E
Company Information
Eaton’s electrical business is a global leader in electrical control, power distribution, and industrial automation products and services. Through advanced product development, world-class manufacturing methods, and global engineering services and support, Eaton’s electrical business provides customer-driven solutions under brand names such as Cutler-Hammer®, Powerware®, Durant®, Heinemann®, Holec® and MEM®, which globally serve the changing needs of the industrial, utility, light commercial, residential, and OEM markets. For more information, visit www.EatonElectrical.com.
Eaton Corporation is a diversified industrial manufacturer with 2005 sales of $11.1 billion. Eaton is a global leader in electrical systems and components for power quality, distribution and control; fluid power systems and services for industrial, mobile and aircraft equipment; intelligent truck drivetrain systems for safety and fuel economy; and automotive engine air management systems, powertrain solutions and specialty controls for performance, fuel economy and safety. Eaton has 60,000 employees and sells products to customers in more than 125 countries. For more information,
visit www.
eaton.com.
Eaton Electrical Inc. 1000 Cherrington Parkway Moon Township, PA 15108-4312 USA tel: 1-800-525-2000 www.EatonElectrical.com
© 2006 Eaton Corporation All Rights Reserved Printed in USA Publication No. MN04004002E/CPG September 2006
Loading...