Installation manual
The Network Management Card & Modbus/Jbus (66103) is recommended for central UPSs
protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS
has its own IP address and uses the local computer capabilities to:
● Supply web pages (http or https (SSL)) with information on status conditions and measurements/
settings/alarms,
● Integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates
Unicenter,
● Communicate with shutdown modules installed on the protected servers (Network Shutdown
Module),
● Send e-mail and SMS messages,
● Control the ON/OFF function of the UPS and the outlets,
● Monitor the Environment Sensor (optional, cat. no. 66846).
UNPACKING AND CHECKS
● One Network Management Card & Modbus/Jbus (66103)
● One serial cable for configuration (34003918),
● One installation manual (34003906).
CHECK ON UPS VERSION
Pulsar
The Network Management Card & Modbus/Jbus (66103) is compatible with the
available since 2006.Note.
Important. Before installing the card, check that the UPS technical level (NT) is at least
equal to that indicated in the table below.
UPS Type Technical level (NT)
Pulsar 700/1000/1500 02
Pulsar M 2200/3000 03
Pulsar MX 4000/5000/10000 04
Pulsar MX Frame 15/20 kVA 01
● If the technical level of the UPS is lower than that indicated in the table, contact EATON.
range UPSs
34003906EN/AE - 3
.
Settings/Sensor
6
6
1
0
3
U
P
S
data R
S
232
1
00M
10
M
000623001C07
ETHERNET 10/100BT port
Service port (Settings/Sensor)
Orange LED: RS232 activity
Green LED: communication
with the UPS
Catalogue number
Orange LED: 10/100M
Green LED: connection +
activity
MAC address
Jbus/modbus port
OVERVIEW
INDICATIONS
ETHERNET port
LED Colour Status Description
ACT Green ● OFF
●
ON
●
Flashing
100M Orange ●
●
OFF
ON
Service port (Settings/Sensor)
Card not connected to network
●
●
Card connected to network, but no activity
●
Port is sending/receiving
Port operating at 10 Mbits/s
●
●
Port operating at 100 Mbits/s
LED Colour Status Description
UPS Data Green ● OFF
●
ON
●
Flashing
RS232 Orange ●
OFF
●
ON
●
Flashing
Card starting
●
●
Communicating with UPS
●
Normal operation
Communication with UPS is operational
Configuration menu activated
●
●
Normal operation
Configuration menu not activated
●
Communication with Environment Sensor (option)
4 - 34003906EN/AE
The Network Management Card & Modbus/Jbus (66103) can be hot-plugged on all UPSs from
ETHERNET
ASI
S
e
t
t
i
n
g
s
/
S
e
n
s
o
r
6
6
1
0
3
U
P
S
d
a
t
a
R
S
2
3
2
1
0
0
M
1
0
M
EATON equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart
the UPS.
● Remove the plastic cover of the Minislot.
● Note the MAC address of the card before inserting it.
● Insert and secure the card with the screws.
● Connect the ETHERNET cable.
● Check the ETHERNET port indications.
● Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has
terminated correctly.
Note. Connection detection continues until the card has been connected to the network. Once
connection is made, card start-up continues.
IP SETTINGS
Once the card has started, proceed as indicated below.
● Connect the serial cable to card’s service port and PC’s COM port
● Use a terminal emulator such as HyperTerminal
TM
with these settings
Bits per second Data bits Stop bits Parity Flow control
9600 8 1 none none
"Echo typed characters locally" option: disabled
● Type EATON (or eaton).
The main configuration menu is displayed:
EATON
NETWORK MANAGEMENT CARD
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
34003906EN/AE - 5