The Network Management Card & Modbus/Jbus (66103) is recommended for central UPSs
protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS
has its own IP address and uses the local computer capabilities to:
● Supply web pages (http or https (SSL)) with information on status conditions and measurements/
settings/alarms,
● Integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates
Unicenter,
● Communicate with shutdown modules installed on the protected servers (Network Shutdown
Module),
● Send e-mail and SMS messages,
● Control the ON/OFF function of the UPS and the outlets,
● Monitor the Environment Sensor (optional, cat. no. 66846).
UNPACKING AND CHECKS
● One Network Management Card & Modbus/Jbus (66103)
● One serial cable for configuration (34003918),
● One installation manual (34003906).
CHECK ON UPS VERSION
Pulsar
The Network Management Card & Modbus/Jbus (66103) is compatible with the
available since 2006.Note.
Important. Before installing the card, check that the UPS technical level (NT) is at least
equal to that indicated in the table below.
UPSTypeTechnical level (NT)
Pulsar 700/1000/150002
Pulsar M2200/300003
Pulsar MX4000/5000/1000004
Pulsar MX Frame15/20 kVA01
● If the technical level of the UPS is lower than that indicated in the table, contact EATON.
range UPSs
34003906EN/AE - 3
Page 4
.
Settings/Sensor
6
6
1
0
3
U
P
S
data R
S
232
1
00M
10
M
000623001C07
ETHERNET 10/100BT port
Service port (Settings/Sensor)
Orange LED: RS232 activity
Green LED: communication
with the UPS
Catalogue number
Orange LED: 10/100M
Green LED: connection +
activity
MAC address
Jbus/modbus port
OVERVIEW
INDICATIONS
ETHERNET port
LEDColourStatusDescription
ACTGreen●OFF
●
ON
●
Flashing
100MOrange●
●
OFFON
Service port (Settings/Sensor)
Card not connected to network
●
●
Card connected to network, but no activity
●
Port is sending/receiving
Port operating at 10 Mbits/s
●
●
Port operating at 100 Mbits/s
LEDColourStatusDescription
UPS DataGreen● OFF
●
ON
●
Flashing
RS232Orange●
OFF
●
ON
●
Flashing
Card starting
●
●
Communicating with UPS
●
Normal operation
Communication with UPS is operational
Configuration menu activated
●
●
Normal operation
Configuration menu not activated
●
Communication with Environment Sensor (option)
4 - 34003906EN/AE
Page 5
The Network Management Card & Modbus/Jbus (66103) can be hot-plugged on all UPSs from
ETHERNET
ASI
S
e
t
t
i
n
g
s
/
S
e
n
s
o
r
6
6
1
0
3
U
P
S
d
a
t
a
R
S
2
3
2
1
0
0
M
1
0
M
EATON equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart
the UPS.
● Remove the plastic cover of the Minislot.
● Note the MAC address of the card before inserting it.
● Insert and secure the card with the screws.
● Connect the ETHERNET cable.
● Check the ETHERNET port indications.
● Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has
terminated correctly.
Note. Connection detection continues until the card has been connected to the network. Once
connection is made, card start-up continues.
IP SETTINGS
Once the card has started, proceed as indicated below.
● Connect the serial cable to card’s service port and PC’s COM port
● Use a terminal emulator such as HyperTerminal
TM
with these settings
Bits per secondData bitsStop bitsParityFlow control
960081nonenone
Your network is equipped with a BOOTP/DHCP server (default)
The card is configured by default with this service enabled. No manual configuration is required.The IP
parameters are automatically collected by the card.
From the main configuration menu: (see above)
● Press the 2 key (Network configuration).
● Press the 1 key(Read Network settings).
The settings supplied by the server are displayed:
Network configuration :
MAC address : 00:06:23:00:1C:07
Mode : DHCP
IP address : 172.17.23.18
Subnet mask : 255.255.248.0
Gateway : 172.17.17
● Note the IP address.
● Press the 0 key (Exit).
● Press the 0 key (Exit).
You can also use NMC Tool software utility to view the card IP adress
Provided on the Solution-Pac 2 CD-ROM or at www.eaton.com. It must be installed on a network
connected PC.
Your network is not equipped with a BOOTP/DHCP server
Manual configuration is required.
To set the network configuration, use terminal emulation (see above)
From the main configuration menu:
● Press the 2 key (Network configuration).
● Press the 2 key (Modify Network settings).
● Follow the instructions and enter the IP parameters:
0 : Exit
For each of the following questions, you can press "Return" to
select
the value shown in braces, or you can enter a new value
Should this target obtain IP settings from the network?[N] N
Static IP address [172.17.16.16]?172.16.1.82
Subnet mask IP address [255.255.0.0]? 255.255.255.0
Gateway address IP address [0.0.0.0]? 172.17.17.1
Done
Wait until "Done" is displayed, indicating that the IP parameters have been saved.
● Press the 0 key (Exit).
● Press the 1 key (Reset).
● Press the 2 key (Restart).
The card restarts with the new IP settings (after approx. one minute).
6 - 34003906EN/AE
Page 7
ACCESS TO SUPERVISION
To check whether the
installation and configuration, proceed as follows.
● Run a browser
● Enter in the address bar:
http://IP address/ (e.g. http://172.16.1.82/)
● The home page is displayed
Network Management Card
& Modbus/Jbus (66103)
is operational after
● Set the time by clicking the Time command.
● Continue configuration via the sections in the Settings menu.
USER MANUAL
This manual provides all the information required to install and configure the
Card
& Modbus/Jbus
For more information on the supervision, control and configuration functions offered by the
Management Card
in the Products/Power Management section of the
(66103).
& Modbus/Jbus
(66103), see the user manual on the
www.eaton.com/powerquality
Network Management
Solution-Pac 2
site.
34003906EN/AE - 7
Network
CD-ROM or
Page 8
6
6
1
0
2
S
e
ttin
g
s
/S
e
n
s
o
r
E
T
H
E
R
N
E
T
10
0M
10
M
U
P
S
dat
a
R
S2
32
O
n
=
Li
nk
B
l
i
n
k
=
Ac
t
ETHERNET
6
6
1
0
3
U
P
S d
a
ta R
S
23
2
10
0
M
10
M
SENSOR CONNECTION (option)
The Environment sensor is a Network Management Card & Modbus/Jbus option. It is available
from EATON (cat. no 66846).
The sensor remotely monitors the UPS environment by regularly measuring the temperature and
humidity, and checking the states of two external contacts. It can also send alarms (e-mail, SNMP trap)
tripped by pre-set thresholds.
Connection is made via the Service port (Settings/Sensor) on the Network Management Card & Modbus/Jbus. The sensor is detected automatically. Configuration and supervision use a menu that
may be accessed directly from the home page. For more information, see the user manual of the
Network Management Card & Modbus/Jbus.
8 - 34003906EN/AE
Page 9
JBUS/MODBUS
5
TxdRxdSG
43 2 1
SA1
SA2
SA2
Pin Function
1 Received data (input)
2Not connected
3Transmitted data (output)
4Not connected
5Signal ground
SA2
OFF
ON
1
8
RD = (A')
TD = (B)
TD = (A)
0 V
1
2
3
4
5
RS485
RD = (B')
R-
R+
T-
T+
0 V
SA1
SA2
SA1
OFF
ON
1
8
SA2
OFF
ON
1
8
SA2
SA2
SA2
SA1
SA1
SA1
RS232 link configuration and connection
RS485 link configuration and connection
For proper operation, the polarity of EIA RS485 2-wire and 4-wire lines must be set at only one point
and the lines terminated at the end.
Polarity
Normally, the master of the network sets the polarity of the line. The receiver inputs have a true failsafe
feature wich eliminates the need for external bias resistors and ensures a logic high output level when
the inputs are open or shorted. This guarantees that the receiver outputs are in a known state before
communication begins and when communication ceases.
Termination
Termination is used to match impedance of a node to the impedance of the transmission line being
used. When impedance are mismatched, the transmitted signal is not completely absorbed by the load
and a portion is reflected back into the transmission line. The termination line is not necessary if the
speed on the line is much less than 115Kbauds
The default setting of the RS485 is a 4 wires configuration without polarity and without termination.
SA1 switches are used to make the termination and the topology of the line (2 or 4 wires). The
termination resistance value is 166 Ω.
SA1 description:
1 : reserved
2 : reserved
3 : link termination between T- to R- (2 wires configuration) if set to ON
4 : connection T- to R- (2 wires configuration ) if set to ON
5 : connection T+ to R+ (2 wires configuration ) if set to ON
6 : reserved
7 : reserved
8 : link termination between R+ and R- if set to ON
34003906EN/AE - 9
Page 10
2 wires connection
SA1
SA2
SA1
OFF
ON
1
8
SA2
OFF
ON
1
8
SA2
SA2
SA2
SA1
SA1
SA1
5
L +
43 2 1
L -
5V
Rp
Ra
Rp
0V
Ra
0V
Ra
0V
L-L-
L+L+
L-L-
L+L+
3
7
24
13
24
13
polarity
connection
if end
of the line
polarity
transmit/receive
data
transmit/receive
data
transmit/receive
data
termination
termination
Master unitCard of an end-of-line cubicle
connection
if end
of the line
3V3
SA1-3
3V3
SA1-3
Card of an intermediate cubicle
SA2
OFF
ON
8 76 5 4 3 2 1
SA1
SA1
OFF
ON
8 7 6 5 4 3 2 1
SA1
Link without polarity and without termination.
SA2
OFF
ON
8 76 5 4 3 2 1
SA1
SA1
OFF
ON
8 7 6 5 4 3 2 1
SA1
Link with termination.
Card settings of an intermediate cubicle
Others settings
10 - 34003906EN/AE
Page 11
4 wires connection
SA1
SA2
5R-43 2 1
R +T -T +
SA1
OFF
ON
1
8
SA2
OFF
ON
1
8
SA2
SA2
SA2
SA1
SA1
SA1
5V
Rp
Rp
0V
RaRa
T-R-
T+R+
R-R-
R+R+
2
1
2
1
5V
Rp
Ra
Rp
0V
R-T-
R+T+
T-T-
T+T+
4
3
4
3
master
transmitt
slave
receiver
slave
receiver
termination
termination
receive data
slave
transmitt
receive data
slave
transmitt
transmit datatransmit data
transmit data
slave
receiver
receive data
polarity
connection if
end of the line
polarity
connection if
end of the line
Master unitCard of an intermediate cubicleCard of an end-of-line cubicle
SA2
OFF
ON
8 76 5 4 3 2 1
SA1
SA1
OFF
ON
8 7 6 5 4 3 2 1
SA1
Link without polarity and without termination.
SA2
OFF
ON
8 76 5 4 3 2 1
SA1
SA1
OFF
ON
8 7 6 5 4 3 2 1
SA1
Link with termination.
Card settings of an intermediate cubicle
Others settings
34003906EN/AE - 11
Page 12
Configuration of the JBUS/MODBUS communication parameters
6
6
1
0
2
Settings/Sensor
ETHERNET
10
0M
10
M
UP
Sda
ta
RS
2
32
O
n
=
Lin
k
B
l
i
n
k
=
Ac
t
ETHERNET
6
6
1
0
3
UP
S
data
R
S2
32
1
00M
1
0
M
Connect the RS232 link to a
terminal
(Microsoft Hyper terminal)
Through settings port
● Use the cord supplied with the card
● Connect the card to a computer
● Use a terminal emulator such as HyperTerminal
TM
with these settings
Bits per secondData bitsStop bitsParityFlow control
960081nonenone
● EMC: EN 61000-6-2 (2002), EN 61000-6-3 (2002), IEC/EN 62040-2 (2002)
In compliance with European directives:
● Low voltage: 73/23/EEC and 93/68/EEC.
● EMC: 89/336/EEC and 93/68/EEC.
Federal Communication Commission (FCC) statement
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment.
WEB SITE
The information presented in this manual is also available in other languages in the download section
of the EATON site (www.eaton.com/powerquality)
.
34003906EN/AE - 15
Page 16
www.eaton.com
34003906EN/AE
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.