Rack-Mount Installation
To install a 9- or 12-slot uninterruptible power system (UPS) cabinet into a rack, you must order a cabinet specifically designed for rack-mounting. Nine- and 12-slot battery cabinets ASY-0749 and ASY-0750 are also available for rack-mounting. These models can be installed in an EIA-standard 48.3 cm (19) equipment rack and include a rack-mounting kit with the brackets and required hardware.
To install the UPS or battery cabinet in the equipment rack:
NOTE The 9- and 12-slot cabinets are heavy [9-slot: 72 kg (158 lb); 12-slot: 89 kg (196 lb)]. This procedure requires two people to lift and position the cabinet into the equipment rack. Install the cabinet in the rack before installing power and battery modules and before making connections to the intended power source.
1. Remove the four screws (two on either side) securing the top cover
of the cabinet. Carefully lift the cover straight up and off to avoid stressing the front panel display. Set the cover aside.
2. Remove the cabinet side covers by lifting the top edge. No other
hardware must be detached. Store or discard the side covers.
3. Carefully replace the cabinet top cover and secure with the four
screws removed in Step 1. Position the cover lip to fit behind the front panel display.
EATON Powerware®9170+Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
www.powerware.com
1
Page 4
RACK-MOUNT INSTALLATION
4. Install six metal clip nuts (nine clip nuts for 12-slot cabinets) onto
NOTE DO NOT install metal clip nuts in the bottom cabinet section.
each side flange along the front of the cabinet (see Figure 1).
Metal Clip Nuts
Tab Slots
Tab Slots
Metal Clip Nuts
Tab Slots
Metal Clip Nuts
Figure 1. Metal Clip Nut and Tab Slot Locations
2
EATON Powerware®9170+Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B www.powerware.com
Page 5
RACK-MOUNT INSTALLATION
5. Install two rack-mount ears (three for 12-slot cabinets) on each side
of the cabinet (see Figure 2).
Insert the two offset tabs on the rear edge of the ear into the matching tab slots on the cabinet side frame (see Figure 1). Pivot the ear forward until it is flush against the cabinet side frame. Secure each ear with three 1/4-20
×1/2Phillips-head bolts; screw
the bolts into the metal clip nuts installed in Step 4.
NOTE DO NOT install rack-mount ears in the bottom cabinet section.
Rack-Mount Ear
Rack-Mount Ear
Rack-Mount Ear
Figure 2. Rack-Mount Ears Installed
EATON Powerware®9170+Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B
www.powerware.com
3
Page 6
RACK-MOUNT INSTALLATION
6. Select the proper holes in the rail that position the cabinet at the
7. Install one equipment rail on each side of the rack using four
8. With one person lifting each side of the cabinet, position the cabinet
desired location in the rack.
10-32
×1/2flat-head screws per rail.
onto the two equipment rails (see Figure 3).
Carefully slide the cabinet into the equipment rack until the rack-mount ears of the cabinet are flush with the front vertical rails of the rack. Verify that the holes in the ears align with the holes in the rack.
Equipment Rail
Figure 3. Rails Holding UPS Cabinet
4
EATON Powerware®9170+Rail Kit (9- and 12-Slot Cabinets) Installation Guide S 164201420 Rev B www.powerware.com
Page 7
9. Secure the cabinet in the rack using 10-32×1/2Torx®screws or
10. Follow the instructions in the UPS user’s guide to install the power
Service and Support
If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
RACK-MOUNT INSTALLATION
other appropriate customer-specified screws.
and battery modules.
United States:
1-800-356-5737 or 1-919-870-3149
Canada: 1-800-461-9166 ext 260 All other countries: Call your local service representative
Please have the following information ready when you call the Help Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the Help
for the dealer or distributor nearest you.