Powerware series
Eaton 9130 UPS
700 – 3000 VA
MultilingualLCD
Advanced power protection for:
• ITandnetworkingenvironments
• Servers,networkinggear
• Telecommunications,VoIP,securitysystems
• Medicalsystems
• Diagnosticsandmedicalscreening
• Patientrecordarchives
• Manufacturingsystems
• Chipfabrication
• Pharmaceuticalproduction
• Chemicalprocessing
Double conversion UPS
Highest power performance
Double conversion topology. The 9130 constantly monitors •
power conditions and regulates voltage and frequency. Even
when presented with the most severe power problems,
UPS’s output remains within 3% of nominal voltage.
More real power. High 0,9 output power factor enables the •
9130 to provide its full power capability to modern IT equipment.
Highest efficiency to reduce utility and cooling spending. •
When power conditions are within acceptable limits, the
9130 can operate in a high-efficiency mode providing 95 percent efficiency.
Unmatched reliability
The int• ernal bypass allows service continuity in case of
internal fault, a maintenance bypass is also available (as
option) for easy replacement of the UPS without powering
down critical systems.
Stronger, longer battery life. Eaton ABM® battery manage-•
ment technology uses an innovative three-stage charging
technique, that only recharges the battery when necessary,
so the battery experiences less corrosion and service life is
prolonged by up to 50%.
Batteries can be hot-swapped without ever having to shut •
down connected equipment.
Possibility to add more runtime at any time with up to four •
external hot-swappable battery modules to run systems for
hours if necessary.
Enables prolonged runtime of essential equipment during •
power outages by allowing for orderly, remote shutdown of
non-critical systems and processes thanks to a capability to
control load segments.
Outstanding versatility
One p• latform, two factors, dozens of choices. Up to 3000
VA of UPS power is packed into only 2U of rack space. The
tower option is about the size of a modern, compact PC.
Enhanced configuration capability through easily navigated •
multilingual graphical display.
Remote monitoring. The 9130 comes complete with the •
Eaton Software Suite CD including SNMP-compatible power
management software providing control and visibility over all
your UPS systems.
Connectivity options are available for almost any network •
environment.
Eaton 9130 UPS
1
7
5
3
4
2
6
Technical specificaTions
General
User interface
LEDs Four status-indicating LEDs
Topology True online, double-conversion
Diagnostics Full system self-test
UPS bypass Automatic bypass
Rail kit Included with all rackmount units
Electrical Input
Nominal voltage 220–240V
Voltage range 160–276 Vac (with load PF of 0.7)
Frequency range 45–65 Hz (50/60 Hz)
Electrical Output
Power factor 0.9
Voltage ±3 % of nominal regulation (on utility and battery)
Frequency regulation ±3 Hz online
Load crest factor 3 to 1
Graphical LCD with blue backlight and text in
English, French, German, Russian and Spanish
1. Multilingual graphical LCD
display
2. Panel for replacing batteries
3. 1 USB port + 1 serial port
4.
1 Relay Output + 1 EPO
connector
5. EBM battery unit connector
6. Load segments
7. Communication card slot
2
6
Communications
Ports RS-232 and USB HID port as standard
Relay output Common alarm standard
SNMP/Web card for monitoring in SNMP-based
Optional communication
cards (BD Slot)
Environmental
Safety and EMC markings
Audible noise <50 dB
Ambient operating 0˚C to +40˚C
Storage temperature
Relative humidity 5–90% non-condensing
networks, monitoring through Web browser
interface. Relay card for integration to industrial
environment and BMS, remote shutdown for IBM
AS/400 systems
CE (per IEC/EN62040-2: Emissions, Category
C1; Immunity, Category C2), GS
-20˚C to +40˚C with batteries and
-25˚C to +55˚C without batteries
1
4
7
3
Description Part number Rating (VA/Watts) Input connection Output receptacles Dimensions H x W x D, mm Weight, kg
Tower Models
PW9130i700T 103006433-6591 700/630 C14 (6) C13 230 x 160 x 350 12.2
PW9130i1000T-XL 103006434-6591 1000/900 C14 (6) C13 230 x 160 x 380 14.5
PW9130i1500T-XL 103006435-6591 1500/1350 C14 (6) C13 230 x 160 x 430 19.0
PW9130i2000T-XL 103006436-6591 2000/1800 C14 (8) C13, (1) C19 325 x 214 x 410 34.5
PW9130i3000T-XL 103006437-6591 3000/2700 C20 (8) C13, (1) C19 325 x 214 x 410 34.5
Tower Extended Battery Modules
PW9130N1000T-EBM 103006438-6591 NA NA NA 230 x 160 x 380 18.5
PW9130N1500T-EBM 103006439-6591 NA NA NA 230 x 160 x 430 24.3
PW9130N3000T-EBM 103006440-6591 NA NA NA 325 x 214 x 410 50.0
Rack Models
PW9130i1000R-XL2U 103006455-6591 1000/900 C14 (6) C13 86.5 x 438 x 450 16
PW9130i1500R-XL2U 103006456-6591 1500/1350 C14 (6) C13 86.5 x 438 x 450 19
PW9130i2000R-XL2U 103006457-6591 2000/1800 C14 (8) C13, (1) C19 86.5 x 438 x 600 29
PW9130i3000R-XL2U 103006463-6591 3000/2700 C20 (8) C13, (1) C19 86.5 x 438 x 600 29.5
Rack Extended Battery Modules
PW9130N1000R-EBM2U 103006458-6591 NA NA NA 86.5 x 438 x 450 22.1
PW9130N1500R-EBM2U 103006459-6591 NA NA NA 86.5 x 438 x 450 28.1
PW9130N3000R-EBM2U 103006460-6591 NA NA NA 86.5 x 438 x 600 41.1
Internal batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
BATTERY RUNTIMES*
Rack models
PW9130i1000R-XL2U 13 22 55 82 103 186 151 250 223 312
PW9130i1500R-XL2U 11 18 47 81 83 143 126 208 195 262
PW9130i2000R-XL2U 13 24 63 95 118 190 170 242 221 345
PW9130i3000R-XL2U 8 14 34 62 70 92 96 156 130 211
Tower models
PW9130i700T-XL 12 19 N/A N/A N/A N/A N/A N/A N/A N/A
PW9130i1000T-XL 13 22 55 82 103 186 151 250 223 312
PW9130i1500T-XL 11 18 47 81 83 143 126 208 195 262
PW9130i2000T-XL 21 34 81 130 145 198 184 293 248 431
PW9130i3000T-XL 12 20 49 79 90 143 134 180 165 240
* Runtimes are shown at a 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
75% Load 50% Load 75% Load 50% Load 75% Load 50% Load 75% Load 50% Load 75% Load 50% Load
In the interests of continuous product improvement all specifications are subject to change without notice.
© 2009 Eaton Corporation, All Rights Reserved, 00DATA1018094 rev A, February 2009