P/N 1838-065 REV U, 4/13
Copyright 2003 DoorKing, Inc. All rights reserved.
Page 2 1838-065-U-4-13
Use this manual with the following models only.
Model 1838 Access Controller, REV T or Higher
DoorKing, Inc. reserves the right to make changes in the products described in this manual
without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions
or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to
this manual. This manual is copyrighted, all rights reserved. No portion of this manual may be
copied, reproduced, translated, or reduced to any electronic medium without prior written consent
from DoorKing, Inc.
1838-065
-U-4-13 Page
3
TABLE OF CONTENTS
Prefac
Section 1 – Installation
Section 2 – Wiring
Section 3 – Programming
e
Important Notices......................................................................................................................................................6
Important Information................................................................................................................................................7
Features ..................................................................................................................................................................8
General Information..................................................................................................................................................13
This equipment has been tested and found to comply with the limits for a class A digital device,
pursuant to Part 15 of the FCC Rules and Regulations. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
FCC Registration Number: DUF6VT-12874-OT-T
DOC - CANADA
The Canadian Department of Communications label identifies certified equipment. This certification
means that the equipment meets certain telecommunications network protective, operational, and
safety requirements. The Department does not guarantee the equipment will operate to the users
satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the
facilities of the local telecommunications company. The equipment must also be installed using an
acceptable means of connection. The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility
designated by the supplier. Any repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications company cause to request the user to
disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power
utility, telephone lines, and internal metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
CAUTION: Users should not attempt to make such connections themselves, but should contact the
appropriate electric inspection authority, or electrician, as appropriate.
DOC Registration Number: 1736 4528 A
Notice:
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to
be connected to a telephone loop which is used by the device, to prevent overloading. The
termination on a loop may consist of any combination of devices subject only to the requirement that
the sum of the load numbers of all the devices does not exceed 100.
Notice:
DoorKing does not provide a power transformer on units sold into Canada. Use only transformers that
are CSA listed to power this entry system. The model 1838 requires a 16.5-volt, 20 VA transformer.
Listing:
This product has been tested to and found to be in compliance with the U.L 294 Safety Standard by
Intertek Testing Services NA Inc. (a Nationally Recognized Testing Laboratory) and is ETL listed.
Page 6 1838-065-U-4-13
IMPORTANT INFORMATION
Prior to beginning the installation of the access control system, we suggest that you become
familiar with the instructions, illustrations, and wiring guidelines in this manual. This will help
insure that you installation is performed in an efficient and professional manner.
The proper installation of the access controller is an extremely important and integral part of
the overall access control system. Check all local building ordinances and building codes
prior to installing this system. Be sure your installation is in compliance with local codes.
When used to control a door or pedestrian gate, try to locate the access controller as near as
possible to the entry point. The unit should be mounted on a rigid wall to prevent excessive
shock and vibration from closing doors or gates. Continuous vibration and shock from
slamming doors or spring-loaded pedestrian gates will damage the circuit board. Under no circumstances should the unit be mounted directly to a moving door or gate.
ADA mounting requirements for door control (Ref: ICC/ANSI A117.1-2009).
1. Unobstructed Forward Reach
. Where a clear floor or ground space allows only a
forward approach to an object and is unobstructed, mounting height shall be a
minimum of 15 inches (381 mm), and a maximum of 48 inches (1.22 m), above the
floor or ground to the operable controls.
2. Obstructed High Forward Reach
. If the high forward reach is over an obstruction
greater than 20 inches, but less than 25 inches, mounting height shall be a maximum
of 44 inches (1.12 m) above the floor or ground to the operable controls.
3. Unobstructed Side Reach
. Where a clear floor or ground space allows a parallel
approach to an object and the side reach is unobstructed, and the edge of the clear
floor space is 10 inches (255 mm) maximum from the object, mounting height shall
be a minimum of 15 inches (380 mm), and a maximum of 48 inches (1.22 m), above
the floor or ground to the operable controls.
4. Obstructed High Side Reach
. If the side reach is over an obstruction greater than 10
inches, but less than 24 inches, mounting height shall be a maximum of 46 inches
(1.17 m) above the floor or ground to the operable controls.
When used to control a vehicular gate with an automatic gate operator, the access
control device (card reader, keypad, etc.) must be mounted a minimum of ten (10) feet
away from the gate and gate operator, or in such a way that a person cannot operate
the device and/or touch the gate or gate operator at the same time.
Be sure that access control devices are installed so that they are not directly in the traffic
lane. Gooseneck mounting post and kiosks work well for these type systems. When
planning where to locate the access device, take into consideration traffic lane layouts, turn
around lanes for rejected access, conduit runs, power availability, etc.
This access system controller contains a number of static sensitive components that can be
damaged or destroyed by static discharges during installation or use. Discharge any static
prior to removing the circuit board by touching a proper ground device.
Instruct the end user to read and follow these instructions. Instruct the end user to
never let children play with or operate any access control device. This Owner’s
Manual is the property of the end user and must be left w ith them when installation is
complete.
1838-065
-U-4-13 Page
7
FEATURES
Can provide service for up to 3000 system users.
Can store up to 8000 card, transmitter or digital PIN codes.
Can interface with DKS Remote Call Stations to provide telephone communication and entry
control (P/N 1838-120, 1838-121).
System can be programmed with a PC by modem, RS-232, RS-422 (requires 1508-055
adapters), a LAN connection (requires 1830-175 TCP/IP kit) or via the internet using the
Internet Modem Server (use of the IM Server is fee based. Visit
http://www.doorking.com/IMServer
Transaction buffer stores the last 8000 events and has its own backup power source to retain
memory during power outages.
View LIVE Transactions.
31-security levels total (security level 00 always denies entry, security level 01 always admits
entry), with 29 programmable security levels, each with four time zones allows you to control
and restrict user access as needed.
Programmable holiday schedule.
Facility codes can be enabled or disabled. Store up to 10 different facility codes.
True Anti-Pass Back feature. Requires APB chip set.
Two internal relays allow the system to control two entry points.
for more information).
System can be expanded to control up to 16 entry points. Tracker expansion boards are
required (one for each additional entry point) and are not included with the system. Tracker
boards also provide output for door ajar and forced entry alarms.
Optional elevator control board(s) can control up to four elevators with each elevator serving
up to 64 floors.
System will interface with selected models of DKS DoorKing vehicular gate operators to
provide gate operator information and data (requires a Tracker board for each gate operator
that is to send data to the system).
Page 8 1838-065-U-4-13
SECTION 1 - INSTALLATION
If you are going to use a telephone line with this controller, order it at least two weeks prior to the
planned installation date. This will assure that a phone line is available when the unit is installed.
The telephone company will require the following information from you:
Type: Touch Tone, Loop Start
Ringer Equivalence: 0.0 A
Jack Type: RJ11C
FCC Registration (US): DUF6VT-12874-OT-T
DOC (Canada): 1736 4528 A
Electrical Listing: Complies with U.L. 294 - ETL Listed
.
1.1 Installation Guidelines
Open the cabinet of the access controller and disconnect the keypad ribbon cable from
1.
the main circuit board.
2. Remove the 6-32 x 1/2 round head screws from the right side of the circuit board.
3. Remove the circuit board by gently pulling it out of the main terminal edge connector.
CAUTION - the circuit board contains static sensitive components. Discharge any static
electricity from your hands by touching a proper ground device before removing the
circuit board. Place the circuit board where it will not be damaged.
4. Mount the access controller cabinet using 8-32 screws. The access controller has four 832 blind pems installed in each corner. See page 10. Make any necessary conduit
connections using the conduit knockouts provided on the bottom of the cabinet. DO NOT
make any other conduit holes in the cabinet.
5. Route wiring into the cabinet. Do not apply any power at this time.
6. Clean out the cabinet. Be sure that all dirt, metal and/or wood debris is removed from the
cabinet and that the terminal strip edge connector is clean and free of any loose particles.
7. Re-install the circuit board into the cabinet by gently pushing the circuit board terminals
into the edge connector. CAUTION - the circuit board contains static sensitive
components. Discharge any static electricity from your hands by touching a proper
ground device before removing the circuit board.
8. Secure the circuit board to the cabinet using the screws removed in step 2.
9. Plug the keypad ribbon cable into the circuit board. The cable points to the left.
WARNING! If this access control system is used to control a vehicular gate
with an automatic gate operator, the access control device must be mounted
a minimum of ten (10) feet away from the gate and gate operator, or in such a
way that a person cannot operate the access control device and touch the
gate or gate operator at the same time.
1838-065
-U-4-13 Page
9
1.1.1 Mount Information
If used to control a door or pedestrian gate, try to locate the access controller as near as possible to
the entry point. The unit should be mounted on a rigid wall to prevent excessive shock and vibration
from closing doors or gates. Continuous vibration and shock from slamming doors or spring-loaded
pedestrian gates will damage the circuit board. Under no circumstances should the unit be
mounted directly to a moving door or gate.
.625
10.0
.875 KO
3-Places
1.125 KO
2-Places
9.0
.5
text
10.75
12.25
3.75
6.0
12.0
10.25
4.0
2.0
1.5
DOORKING, INC., INGLEWOOD, CA 90301
Model 1838 Controller Mounting Dimensions
Title:
Date:Rev.Dwg. No.
7/03M1838-065-1
B
Page 10 1838-065-U-4-13
1.2 Memory Chip Information
The 18
chips with power to the system turned on. Doing this will irrevocably damage the memory
chips. Memory chips are static sensitive. Discharge any static electricity from your hands by
touching a proper ground device before removing the control board or memory chips. Handle
memory chips with care.
38 is shipped with memory chips pre-installed. Do not remove or re-install the memory
1. The large memory chip socket is colored black and is located in the center of the circuit
board. Be sure that the handle is in the un-locked position (pointing up). Be sure that
power to the telephone entry system is off.
2. Carefully insert the memory chip into the socket. The small half circular indentation on
the chip must be to the right. CAUTION: Installing the memory chip backwards will
cause permanent damage to the chip. Be sure that the memory chip is seated correctly
in the socket, then move the lever to the locked position.
3. Install the small memory chip in the socket located at the bottom of the circuit board. The
small circular indentation on the chip must be to the right. CAUTION: Installing the
memory chip backwards will cause permanent damage to the chip. Be sure that the
memory chip is seated correctly in the socket .
1838 Series Circuit Boards Memory Chip Location
Dimple on chip must be towards the right!
1
1
DOORKING, INC., INGLEWOOD, CA 90301
Title:
1838 Series Memory Chip Location
Date:Dwg. No.
4/03
M1838-065-2
1
Rev.
A
1838-065
-U-4-13 Page
11
Page 12 1838-065-U-4-13
SECTION 2 – WIRING
Prior to installing wiring to the access control system, we suggest that you become familiar with the
instructions, illustrations, and wiring guidelines in this manual. This will help insure that you
installation is performed in an efficient and professional manner.
The wiring of the access control panel is an extremely important and integral part of the
overall access control system. Use proper wire for the communication line, power wires, and
be sure that the system is properly grounded. Check all local building ordinances and
building codes prior to installing this system. Be sure your installation is in compliance with
local codes.
WARNING: If this access control system is used to control a vehicular gate with an automatic
gate operator, the access devices (card reader, keypad, etc.) must be mounted a minimum of
ten (10) feet away from the gate and gate operator, or in such a way that the user cannot come
into contact with the gate or gate operator when using the entry device. If the entry device
has been installed closer to the automated vehicular gate, do not proceed with any wiring until
the device has been moved and re-installed so that it is in compliance with these instructions.
Use only the supplied transformers (or U.L. listed equivalent) to power the access control system and
any wiegand input devices (16.5 VAC, 20 VA). Do not power any other devices (electric strikes,
magnetic locks, etc.) from these power transformers. For wire runs up to 100 feet, use 18 AWG, 600
volt insulated wire. For wire runs up to 200 feet, use 16 AWG, 600 volt insulated wire. Power wires
are susceptible to noise and hum pickup; therefore it is preferable that you keep power wire runs as
short as possible.
This access control system contains a number of static sensitive components that can be damaged or
destroyed by static discharges during installation or use. Discharge any static prior to removing the
circuit board from the lobby panel by touching a proper ground device.
If Tracker expansion boards are being used with this system, refer to the Tracker Installation and
Wiring manual that came with the Tracker expansion boards, for detailed information on wiring
Tracker boards to the PC programmable access control system.
If Elevator Control is used with this system, refer to the Elevator Control Installation and Wiring
manual for detailed information on wiring the elevator control boards to this system and to the
elevator push button control panel.
.
1838-065
-U-4-13 Page
13
2.1 WIRING GUIDELINES
Do not run hi
gh voltage (115 V) power lines and communication lines in the same conduit. These
should be in separate conduits at least six (6) inches apart. Be sure that all phone line wiring is twisted and completely isolated from ground.
Use only the supplied 16.5 VAC (or U.L. listed equivalent) to power the access control system. Do
not power any other devices (electric strikes, magnetic locks, lights, etc.) from this
transformer. Do not run 16 VAC access control system power lines over 200 feet. It is advisable to keep these wires as short as possible. Use 18 AWG wire for wire runs up to 100 feet, and 16
AWG wire for wire runs up to 200 feet. Install a low voltage surge suppresser (DoorKing p/n 1878-
010 or equivalent) to help protect the entry system from power surges.
Wiegand wire runs are 500-feet maximum. Use 6-conductor stranded wire with overall shield. 18,
20, 22 or 24 gauge is sufficient for these connections.
A 12 volt .8 amp hour gel-cell battery (DoorKing p/n 1801-008) can be installed in the system to
provide stand-by power in the event of a power outage. Two batteries are required, one for the
system power and one for the auxiliary terminal power.
Proper grounding of this system is a requirement. The use of surge suppressers can significantly
reduce the chance of component failure because of static charges or surges. To be effective, ground
connections should be made with a minimum 12 AWG, 600 volt insulated wire to a ground point
within 10 feet of the access control system. The ground point must be at an electrical panel, a
metallic cold water pipe that runs in the earth, or a stainless steel grounding rod driven at least ten
(10) feet into the soil.
Be sure that you use proper wire that has an insulation rated for an underground environment. All
wires should be placed in conduits. Proper pre-planning can greatly ease the installation and wiring
of this system. Always check with the local building code to determine the type of wire required in
your municipality.
The 1838 is shipped with two (2) Ferrite Filters. One is installed on the 16 VAC power wires to the
main circuit board (terminals 19-20). The second is installed and around the wires connected to the
Auxiliary Terminal strip.
To install the ferrite filter, simply snap the filter open, place the wires in the circular core, then
snap the filter closed.
16 VAC POWERAUX TERMINAL WIRES
Page 14 1838-065-U-4-13
2.2 TERMINAL DESCRIPTIONS
MAIN DESCRIPTION
1 Phone Line Connection – 800 ft. maximum with 24 AWG wire; 1600 ft. maximum with 22 AWG wire.
2 Phone Line Connection – 800 ft. maximum with 24 AWG wire; 1600 ft. maximum with 22 AWG wire.
3 Earth Ground Only.
4 Switch Input. A closure between terminals 4 and 6 will cause the designated relay(s) to activate for the
5 Microphone Input.
6 Common for switch input, A and Z input, speaker, microphone and battery negative.
7 Speaker Output.
8 Not Used.
9 Not Used.
10 Not Used.
11 Z Input. A closure between terminals 11 and 6 will dial the phone number stored under directory code 1,
12 A Input. A closure between terminals 12 and 6 will dial the phone number stored under directory code 0,
13 Relay 2 Common – 30 Volt, 3 Amp maximum.
14 Relay 2 Contact – 30 Volt, 3 Amp maximum.
15 Relay 1 Common – 30 Volt, 3 Amp maximum.
16 Relay 1 Normally Closed – 30 Volt, 3 Amp maximum.
17 Relay 1 Normally Open – 30 Volt, 3 Amp maximum.
18 Microphone Power and Back-up Battery POSITIVE (connect negative to terminal 6).
19 16 VAC Input Power – 20 VA minimum.
20 16 VAC Input Power – 20 VA minimum.
AUXILIARY DESCRIPTION
1 16 VAC Input Power – 20 VA.
2 16 VAC Input Power – 20 VA.
3 Back-up Battery POSITIVE.
4 Back-up Battery NEGATIVE.
5 16 VAC for Card Reader lights only.
6 16 VAC for Card Reader lights only.
7 DATA 0 – Card Reader 2.
8 DATA 1 – Card Reader 2.
9 COMMON – Card Reader 2.
10 +12 VDC Power – Card Reader 2.
11 DATA 0 – Card Reader 1.
12 DATA 1 – Card Reader 1.
13 COMMON – Card Reader 1.
14 +12 VDC Power – Card Reader 1.
ELEVATOR DESCRIPTION
1 DATA 1 – connect to Elevator Control Board (2348-010) Terminal 20.
2 DATA 0 – connect to Elevator Control Board (2348-010) Terminal 21.
3 COMMON – connect to Elevator Control Board (2348-010) Terminal 22.
programmed strike time. The Postal Switch is connected here.
01, 001 or 0001.
00, 000 or 0000.
100 ft. maximum with 18 AWG wire; 200 ft. maximum with 16 AWG wire.
100 ft. maximum with 18 AWG wire; 200 ft. maximum with 16 AWG wire.
1838-065
-U-4-13 Page
15
2.3 WIRING DETAIL
2.3.1 Controller Only
30 Series Controller Detail Wiring
DATA 1
1
2
3
4
5
6
RS 232
Connection
1833, 1834, 1835, 1837, 1838 CONTROLLER
NOTES: Relay 0 is not available on the 1834 controller.
3
7
Relay 0
11
12
NEG 12 VDC INPUT
POS 12 VDC INPUT
Elevator
Control
16
+ 12 VDC
COMMON
DATA 1
DATA 0
+ 12 VDC
COMMON
DATA 1
DATA 0
3
1
DATA 0
2
COMMON
3
RED
14
BLK
13
WHT
12
GRN
11
Auxiliary Terminals
16
RED
10
BLK
9
WHT
8
GRN
7
6
5
BLK
4
RED
3
2
1
17
16 VAC
OUTPUT
16 VAC
PWR
INPUT
6
WHT
GRN
BLK
10
94
20
21
22
6
6
12 VDC
BATT
ELEVATOR
CONTROL
2348-010
8
CARD
RDR-1
CARD
RDR-2
Central Office phone line - touch tone, loop start.
1
A switch closure across terminals 4 & 6 will activate relay 1
2
for its programmed strike time.
Battery Backup - separate batteries required for phone
3
system and weigand terminals.
16 Volt, 20 VA UL Listed Transformer.
4
For 1837, use 16 Volt, 40 VA UL Listed Transformer.
5
6 conductor, stranded with overall shield, 18, 20, 22 or 24
6
gauge is sufficient for these connections.
See Dwg No. M1835-065-5 for detail.
7
See Elevator Control Board Manual 2348-065 for detail.
8
Aux power transformer must be connected. Otherwise, RS232,
9
elevator control and weigand inputs will not function.
16 VAC output can be used to power lights on card readers that
10
have additional lighting for outdoor use.
Card reader connected to these terminals will operate Relay 1
11
for its programmed strike time.
Card reader connected to these terminals will operate Relay 2
12
for its programmed strike time.
Relay 2 contact is set N.O or N.C. with a jumper on the circuit
13
board.
Electric strikes are wired to Normally Open (N.O.) contacts;
14
magnetic locks are wired to the Normally Closed (N.C.) contacts.
Power for electric strikes or magnetic locks is not provided by the
15
system. Use a separate UL listed power supply.
Auxiliary and Elevator Control terminals are not available on the
16
1834 controller.
Use 18 AWG wire for runs up to 100 Ft. Use 16 AWG wire for
17
runs up to 200 Ft.
NONCCOM
- 12 VDC BATT INPUT
+12 VDC BATT INPUT
RELAY 0 COMMON
RELAY 0 NORMALLY CLOSED
RELAY 0 NORMALLY OPEN
BASIC DOOR CONTROL
LOCK
PWR
15
Main Terminal
12317161514132019
4618
C.O.
PHN
2
1
16 VAC
PWR
INPUT
4 5
17
RELAY 1 NORMALLY OPEN
RELAY 1 NORMALLY CLOSED
RELAY 1 COMMON
RELAY 2 CONTACT
RELAY 2 COMMON
To Control
Relay
14
To Card
Reader Input
13
DOORKING, INC., INGLEWOOD, CA 90301
Detail Wiring - 30 Series Controller
Title:
Date:Dwg. No.Rev.
7/12
DOOR
LOCK
M1835-065-2
CARD
READER
E
Page 16 1838-065-U-4-13
2.3.2 Controller & Expansion Boards 1-8
30 Series Controller to 2351-010 Expansion Boards 1- 8
Detail Wiring
1
2
3
4
5
6
RS 232
Connection
12
Elevator
Control
1
2
3
14
13
12
11
Auxiliary Terminals
+ 12 VDC
COMMON
DATA 1
DATA 0
10
9
8
7
8
Controller main terminals 13-14 = SYSTEM RELAY 2.
16 VAC
6
OUTPUT
5
NOTES: Controller main terminals 15-16-17 = SYSTEM RELAY 1.
1833, 1835, 1837, 1838 CONTROLLER
3
- 12 VDC INPUT
+12 VDC INPUT
NEG 12 VDC INPUT
POS 12 VDC INPUT
Relay 0
NONCCOM
3
+
4
3
16 VAC
PWR
2
INPUT
1
114
MAIN
DR/GATE
Main Terminal
12317161514132019
4618
C.O.
PHN
2
1
Central Office phone line - touch tone, loop start.
1
A switch closure across terminals 4 & 6 will activate relay 1
2
for its programmed strike time.
Battery Backup - separate batteries required for phone
3
system and weigand terminals.
16 Volt, 20 VA UL Listed Transformer.
4
16 VAC
PWR
INPUT
4 5
77
Board 1
System Relay 3
P2P1
GRN
6
5
7
6
8
9
10
7
8
9
17
12
13
14
2351-010
For 1837, use 16 Volt, 40 VA UL Listed Transformer.
5
6 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
6
sufficient for these connections.
4 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
7
sufficient for these connections.
No connection at controller.
8
Communication cable to additional boards is connected in parallel.
9
Allows “teeing” of communication cable for optimal cable routing.
Power for door strikes or magnetic locks is not provided by the
10
system. It must be provided by an external power supply.
Aux power transformer must be connected. Otherwise, RS232,
11
elevator control and weigand inputs will not function.
See Dwg No. M1835-065-5
12
for detail.
RED
BLK
WHT
GRN
BRN
BLU
WHT
BLK
RED
6
RED
BLK
WHT
GRN
BRN
BLU
LOCK
PWR
DOOR
LOCK
66
16 VAC
PWR
INPUT
Title:
Date:Dwg. No.
1010
LOCK
PWR
Board 2
System Relay 4
P2P1
GRN
6
7
8
9
10
17
2351-010
5
6
7
8
9
12
13
14
M1835-065-3
RED
BLK
WHT
GRN
BRN
BLU
16 VAC
44
PWR
INPUT
Rev.
WHT
BLK
RED
RED
BLK
WHT
GRN
BRN
BLU
DOORKING, INC., INGLEWOOD, CA 90301
Detail Wiring - 30 Series Controller to 2351-010
Expansion Boards 1-8
10/11
DOOR
LOCK
To
Boards
3-8
9
D
1838-065
-U-4-13 Page
17
2.3.3 Controller & Expansion Boards 1-16
30 Series Controller to 2351-010 Expansion Boards 1-1 6
Detail Wiring
1
2
3
4
5
6
RS 232
Connection
1833, 1835, 1837, 1838 CONTROLLER
13
12
NOTES: Controller main terminals 15-16-17 = SYSTEM RELAY 1.
Relay 0
Controller main terminals 13-14 = SYSTEM RELAY 2.
NONCCOM
Elevator
Control
+ 12 VDC
COMMON
DATA 1
DATA 0
+ 12 VDC
COMMON
DATA 1
DATA 0
LOCK
1
2
3
7
P2P1
6
5
7
6
8
9
11
14
13
12
11
RED
BLK
WHT
GRN
BRN
BLU
10
7
8
9
17
12
13
14
2351-010
6
1010
PWR
DOOR
LOCK
7
P2P1
6
5
7
6
8
9
RED
BLK
WHT
GRN
BRN
BLU
13
16 VAC
PWR
INPUT
6
4
RED
WHT
GRN
BRN
10
BLK
BLU
17
2351-010
7
8
9
12
13
14
RED
BLK
WHT
GRN
BRN
BLU
13
16 VAC
PWR
INPUT
LOCK
PWR
6
DOOR
LOCK
Boards
To
9-16
4
Auxiliary Terminals
RED
BLK
WHT
GRN
BRN
BLU
10
16 VAC
INPUT
PWR
LOCK
PWR
DOOR
LOCK
6
To
Boards
3-8
13
4
LOCK
RED
BLK
WHT
GRN
BRN
BLU
10
13
16 VAC
PWR
INPUT
PWR
DOOR
LOCK
7
P2P1
6
5
7
6
8
9
10
6
4
RED
WHT
GRN
BRN
BLK
BLU
17
2351-010
7
8
9
12
13
14
7
11
10
9
8
7
P2P1
16 VAC
6
OUTPUT
5
+
4
3
2
1
16 VAC
PWR
INPUT
8
To Main
Door / Gate
3
4
RED
BLK
WHT
GRN
BRN
BLU
6
5
7
6
8
9
10
7
8
9
17
12
13
14
2351-010
6
Rev.
9
D
Main Terminal
12317161514132019
4618
BLU
BRN
BLU
BRN
+
16 VAC
PWR
INPUT
5
C.O.
PHN
2
1
Central Office phone line - touch tone, loop start.
1
A switch closure across terminals 4 & 6 will activate relay 1
2
for its programmed strike time.
Battery Backup - separ ate batteries required for phone
3
system and weigand terminals.
16 Volt, 20 VA UL Listed Transformer.
4
For 1837, use 16 Volt, 40 VA UL Listed Transformer.
3
4
5
6 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
6
sufficient for these connections.
4 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
7
sufficient for these connections.
Aux power transformer must be connected. Otherwise, RS232, elevator control and
8
weigand inputs will not f u nc t i o n.
Communication cable to additional boards is connected in parallel. Allows “teeing” of
9
communication cable for optimal cable routing.
Power for door strikes or magnetic locks is not provided by the system. It must be
10
provided by an external power supply.
No connection at controller.
11
See Dwg No. M1835-065-5 for
12
detail.
EARTH Ground.
13
DOORKING, INC., INGLEWOOD, CA 90301
Detail Wiring - 30 Series Controller to 2351-010
Title:
Expansion Boards 1-16
Date:Dwg. No.
10/11
M1835-065-4
Page 18 1838-065-U-4-13
2.3.4 Controller and 1838-120 or 1838-121 Remote Call Station
1
2
3
4
5
6
RS 232
Connection
3
Elevator
Control
+ 12 VDC
COMMON
8
DATA 1
DATA 0
16 VAC OUTPUT
7
16 VAC OUTPUT
NEG 12 VDC INPUT
POS 12 VDC INPUT
1838 CONTROLLER
3
Relay 0
NONCCOM
- 12 VDC BATT IN PUT
+12 VDC BATT INPUT
Main Terminal
12317161514132019
57 1211
4618
C.O.
PHN
1
1
2
3
RED
14
BLK
13
WHT
12
GRN
11
10
9
8
7
Auxiliary Terminals
6
5
4
3
2
1
RELAY 0 NORMALLY CLOSED
RELAY 0 NORMALLY OPEN
RELAY 1 NORMALLY OPEN
RELAY 1 NORMALLY CLOSED
16 VAC
PWR
4
INPUT
RELAY 0 COMMON
16 VAC
PWR
INPUT
RELAY 1 COMMON
5
RED
14
BLK
13
WHT
12
GRN
11
10
9
8
7
6
5
4
3
2
1
6
Central Office phone line - touch tone, loop start.
13
9 10
4
11
9
10
1
A switch closure across terminals 4 & 6 will activate relay 1 for its
2
programmed strike time.
Battery Backup - separate batteries required for phone system and
3
weigand terminals.
16 Volt, 20 VA UL Listed Transformer.
4
4 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
5
sufficient for these connections.
Aux power transformer must be connected. Otherwise, RS232, elevator
6
control and weigand inputs will not function.
16 VAC output can be used to power lights on card readers that have
7
additional lighting for outdoor use.
Weigand card reader or keypad connected to these terminals will operate
8
Relay 1 for its programmed strike time.
Electric strikes are wired to Normally Open (N.O.) contacts; magnetic
9
locks are wired to the Normally Closed (N.C.) contacts.
Power for electric strikes or magnetic locks is not provided by the system.
10
Use a separate UL listed power supply.
Use 18 AWG wire for runs up to 100 Ft. Use 16 AWG wire for runs up to
11
200 Ft.
1838-120 uses a keypad. 1838-121 uses a card reader. The wiring is the
12
same regardless which device is used.
100 Feet maximum between remote call station and controller.
13
GRN
PUR
WHT
WHT
RED
WHT
GRN
ORG
GRY
LED Lights
Card Reader
12
Push To Call
Speaker
Microphone
1838-120/121
1838-065
2
-U-4-13 Page
DOORKING, INC., INGLEWOOD, CA 90301
1838 Remote Call Station - Telephone Interface
Title:
Wire Diagram
Date:Dwg. No.Rev.
7/12
M1838-065-5
E
19
2.3.5 Controller and Two (2) 1838-120 or 1838-121 Remote Call Stations
1
2
3
4
5
6
RS 232
Connection
3
Elevator
Control
+ 12 VDC
COMMON
8
DATA 1
DATA 0
+ 12 VDC
COMMON
DATA 1
DATA 0
16 VAC OUTPUT
7
16 VAC OUTPUT
NEG 12 VDC INPUT
POS 12 VDC INPUT
1838 CONTROLLER
3
Relay 0
NONCCOM
RELAY 0 COMMON
RELAY 0 NORMALLY CLOSED
- 12 VDC BATT IN PUT
+12 VDC BATT INPUT
Main Terminal
12317161514132019
57 1211
4618
C.O.
PHN
1
2
RELAY 0 NORMALLY OPEN
RELAY 1 NORMALLY OPEN
RELAY 1 NORMALLY CLOSED
1
2
3
RED
14
BLK
13
WHT
12
GRN
11
RED
10
BLK
9
WHT
8
GRN
7
Auxiliary Terminals
6
5
4
3
2
1
RELAY 1 COMMON
9 10
16 VAC
PWR
INPUT
4
16 VAC
PWR
INPUT
RED
14
BLK
13
WHT
12
GRN
11
10
9
8
7
6
5
5
4
3
2
1
GRN
PUR
WHT
WHT
RED
WHT
GRN
ORG
GRY
LED Lights
Card Reader
12
Push To Call
Speaker
Microphone
1838-120/121
5
RED
14
BLK
13
WHT
12
GRN
11
10
9
8
7
6
WHT
5
4
3
2
1
1
GRN
2
3
4
6
13
RED
RED
GRN
WHT
1494-010
14
COM
MIC
BAT
WHT
RED
GRN
5
6
7
4
11
8
9
10
9
10
11
12
13
14
GRN
PUR
WHT
WHT
RED
WHT
GRN
ORG
GRY
LED Lights
Central Office phone line - touch tone, loop start.
A switch closure across terminals 4 & 6 will activate relay 1 for its
programmed strike time.
Battery Backup - separate batteries required for phone system and
weigand terminals.
16 Volt, 20 VA UL Listed Transformer.
4 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
sufficient for these connections.
Aux power transformer must be connected. Otherwise, RS232, elevator
control and weigand inputs will not function.
16 VAC output can be used to power lights on card readers that have
additional lighting for outdoor use.
Weigand card reader or keypad connected to these terminals will operate
Relay 1 for its programmed strike time.
Electric strikes are wired to Normally Open (N.O.) contacts; magnetic
locks are wired to the Normally Closed (N.C.) contacts.
Power for electric strikes or magnetic locks is not provided by the system.
Use a separate UL listed power supply.
Use 18 AWG wire for runs up to 100 Ft. Use 16 AWG wire for runs up to
200 Ft.
1838-120 uses a keypad. 1838-121 uses a card reader. The wiring is the
same regardless which device is used.
100 Feet maximum between remote call station and controller.
1494-010 Microphone combiner required when using two call stations.
Card Reader
12
Push To Call
Speaker
Microphone
1838-120/121
DOORKING, INC., INGLEWOOD, CA 90301
1838 Remote Call Stations - Telephone Interface
Title:
Wire Diagram
Date:Dwg. No.Rev.
7/12
M1838-065-7
A
Page 20 1838-065-U-4-13
2.3.6 Controller and 1504-120 & 121 Intercom Stations
Aiphone
LEM-1
Master
E
13
1
1
2
3
4
5
6
RS 232
Connection
Elevator
Control
1
2
3
Aiphone
LEF
Master
E
1
-
13
+ 12 VDC
COMMON
8
DATA 1
DATA 0
16 VAC OUTPUT
7
16 VAC OUTPUT
NEG 12 VDC INPUT
3
POS 12 VDC INPUT
1838 CONTROLLER
3
Relay 0
NONCCOM
- 12 VDC BATT IN PUT
+12 VDC BATT INPUT
Main Terminal
12317161514132019
4618
57 1211
C.O.
PHN
2
1
RED
14
BLK
13
WHT
12
GRN
11
10
9
8
7
Auxiliary Terminals
6
5
4
3
2
1
RELAY 0 NORMALLY CLOSED
RELAY 0 NORMALLY OPEN
RELAY 1 NORMALLY OPEN
RELAY 1 NORMALLY CLOSED
16 VAC
PWR
4
INPUT
RELAY 0 COMMON
16 VAC
PWR
4
INPUT
RELAY 1 COMMON
5
RED
14
BLK
13
WHT
12
GRN
11
+
GRN
WHT
47 uF Cap
PUR
WHT
ORG
GRY
LED Lights
10
9
8
14
7
6
5
4
3
2
1
6
Central Office phone line - touch tone, loop start.
1
A switch closure across terminals 4 & 6 will activate relay 1 for its
2
programmed strike time.
Battery Backup - separate batteries required for phone system and
3
weigand terminals.
16 Volt, 20 VA UL Listed Transformer.
4
4 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is
5
sufficient for these connections.
Aux power transformer must be connected. Otherwise, RS232, elevator
6
control and weigand inputs will not function.
16 VAC output can be used to power lights on card readers that have
7
9 10
11
9
10
additional lighting for outdoor use.
Weigand card reader or keypad connected to these terminals will operate
8
Relay 1 for its programmed strike time.
Electric strikes are wired to Normally Open (N.O.) contacts; magnetic
9
locks are wired to the Normally Closed (N.C.) contacts.
Power for electric strikes or magnetic locks is not provided by the system.
10
Use a separate UL listed power supply.
Use 18 AWG wire for runs up to 100 Ft. Use 16 AWG wire for runs up to
11
200 Ft.
1504-120 uses a keypad. 1504-121 uses a card reader. The wiring is the
12
same regardless which device is used.
Aiphone Master Intercom Station supplied by others.
13
Place a jumper wire from terminal 6 to terminal 10 if an Aiphone LEM-1
14
master station is used.
Card Reader
12
Push To Call
Speaker
1504-120/121
1838-065
DOORKING, INC., INGLEWOOD, CA 90301
1838 Remote Call Station - Intercom Interface
Title:
Wire Diagram
Date:Dwg. No.Rev.
7/12
-U-4-13 Page
M1838-065-6
E
21
2.3.7 RS-232 Cable Connection
P/N 1818-040
Female End
RED
BLACK
WHITE
BROWN
GREEN
SHIELD
15
69
1
2
3
4
5
6
BOARD
TERMINALS
132
223
374
485
557
6
Connector on 30 Series
Circuit Boards
DB - 9
DB - 25
PINS
PINS
Title:
Date:Dwg. No.
FUNCTION
Transmit Data
Receive Data
Request to Send
Clear to Send
Signal Ground - Shell
Not Used
DOORKING, INC., INGLEWOOD, CA 90301
Detail Wiring - 30 Series RS-232 Connector
6/11
M1835-065-5
Rev.
B
Page 22 1838-065-U-4-13
2.3.8 Postal Lock Box Installation & Wiring – Optional
At some locations, such as gated communities, it may be necessary to provide access to the mail
carrier so that they can deliver the mail. Mail carrier access can be provided by the installation of an
Arrow Postal Lock into a DoorKing Postal Lock Box (p/n 1402-080). This is the same lock that the
Post Office uses for gang mail boxes. These locks are not available to the public. The installer or the
building owner/manager will have to call the Post Office and arrange for the installation of this lock
into the Postal Lock Box.
1402 Postal Lock Box
Installation and Wire Connections
COMMON
N.C.
POSTAL
LOCK BOX
MADE BY DOORKING INGLEWOOD, CALIF.
5
6.5
2.375
.875 DIA.
1.875
2.5
3.0
2.5
2.5
INSTRUCTIONS
1. Remove the hole plug from the faceplate of the 1402 lock box.
2. Cut the wire tie wrapped around the micro-switch.
3. Mount the postal lock on the studs. The pawl of the lock should
depress the micro-switch.
4. Connect COMMON and t he NO RM ALLY CLOSED switch
contacts to main terminals 4 and 6 in the controller.
NOTE: The Arrow Postal Lock IS NOT included with the 1402 lock
box. This lock is not available to the general public and must be
ordered from the local Post Office.
1838-065
Arrow Postal Lock
DOORKING, INC., INGLEWOOD, CA 90301
1402 Postal Lock Box
Title:
Installation and Wire Connections
Date:Rev.Dwg. No.
4/03M1838-065-3
-U-4-13 Page
A
23
Page 24 1838-065-U-4-13
SECTION 3 – PROGRAMMING
IMPORTANT! Many of the advanced features available with this access control system cannot be
programmed from the system keypad. These features include relay hold open time zones, security
levels, anti-pass back tables, elevator control options and programming via the internet using the
Internet Modem (IM) Server. If any of these features are used, the system must be programmed with
the DoorKing Remote Account Manager for Windows software, VERSION 6.3.b or higher. Refer to
the software help screen for more information on these features.
We strongly suggest that you read these programming instructions in their entirety before beginning
any programming of this access control system.
3.1 GENERAL PROGRAMMING INFORMATION
T
he DoorKing PC Programmable Access Control System is primarily programmed by using the
DoorKing Remote Account Manager for Windows software. However, the system can also be
programmed from the keypad in the control cabinet. When programming from an off site location with
a PC, the RING pin must be installed on the circuit board.
The PC programmable access control system has three (3) relays on the circuit board, all of which
are programmable for any function required. These relays are designated as Relay 0 (R-0), Relay 1
(R-1), and Relay 2 (R-2). If Tracker expansion boards are used with this system, it is very important
that you understand the function of these relays. The wiegand input auxiliary terminals (also the
Tracker board input terminals) will cause R-1 or R-2 to activate. Therefore, if Tracker expansion
boards are used with this system, R-1 and R-2 are designated as Tracker board command (CMD)
relays with R-2 controlling tracker boards 1 through 8 (system relays 3-10), and R-1 controlling
tracker boards 9 through 16 (system relays 11-18). Relay 0 is phone controlled when the 1838 has a
C.O. phone line connected to it.
3.1.1 Programming with a PC
Prior to p
Software, there is certain information that you must know and must program into the system before
the computer can communicate with the system. See page 23 to set-up the access control system
for PC programming. Programming can be with a PC by modem, RS-232, RS-422 (requires 1508055 adapters), a LAN connection (requires 1830-175 TCP/IP kit) or via the internet using the Internet
Modem Server (use of the IM Server is fee based. Visit http://www.doorking.com/IMServer
information).
rogramming the system with a PC and the DoorKing Remote Account Manager for Windows
for more
1838-065
-U-4-13 Page
25
3.1.2 Programming from the Keypad
Follow the programming instructions as described in each section of this manual. The system will
prompt you with short tones (beep) when programming steps have been followed correctly, and with
a long tone (beeeeeep) when the programming step is ended. It is highly recommended that you
complete the user listing in the appendix prior to starting any programming from the keypad. This
listing will provide you with the information needed to complete the manual programming sequence.
This symbol _ in the programming steps indicates numbers that you will need to enter, one number
per symbol. When programming from the keypad, after each programming step is performed
correctly, a short tone (beep) will be heard. When the programming session is ended, a long tone
(beeeeeep) will be heard.
NOTE: Relay hold open time zones, security levels, anti-pass back IN / OUT tables, anti-pass
back re-sync schedules, holiday schedules and elevator control functions cannot be
programmed from the system keypad. These functions can only be programmed from a PC
using the Remote Account Manager Software.
3.1.3 System Memory
Beginni
ng in January, 2010, the 1838 access control system is available with a 500 or 3000 memory
(APB) chips installed in the system. The information below is to assist you with programming older
systems or when there is a need to change the memory chips to match a chip set on another system
already installed. Prior to starting the programming of the PC programmable access control system,
you must know the memory capacity and type of the EEPROM chips that are installed in the unit.
This can be determined by inspecting the small chip that has a tag listing the memory size on it and
will be labeled APB if anti-pass back is enabled. The memory size determines the number of
residents, vendors, four-digit entry codes and device codes that can be stored in the system. APB
indicates that the chip set has anti-pass back capability. The table shows the valid numbers available
with each memory level.
Prior to prog
Account Manager for Windows software and the user supplied PC, the system must have the
MASTER CODE programmed into it. The master code cannot be set with the PC and must be
programmed from the system keypad.
NOTE: The programming steps in this section (3.2.1 through 3.2.6) can only be programmed
from the system keypad. There is no programming sequence in the Remote Account Manager
Software for these functions.
3.2.1 Master Code
programming step sets the system MASTER CODE. The master code is the four-digit number
This
required to gain access to the system memory. You need to know the master code prior to
programming the system with the PC, or to perform any of the programming functions on the
following pages.
Factory setting = 9999
1. Open the cabinet of the telephone entry system and turn the master code switch (the
2. Enter a four-digit master code _ _ _ _ then press *
3. Turn the master code switch off and close the cabinet.
3.2.2 Single or Multiple Systems
This prog
or to share the phone line with other units. If multiple systems are sharing the same phone line, then
each one must be set as a "multiple system" and each must have a unique master code.
Factory setting =Single System.
1. Press *
2. Enter 0
3. Press 0
3.2.3 Programming Resident Elevator Button Relay Time
n elevator control is in use, an access device such as a card reader must be installed in the
Whe
elevator car to allow residents access to the floors in the building. The time interval that the button(s)
is “live” after the resident activates the access device is dependant on the revision level of the 1838
access controller circuit board, not the 2348 elevator control board. The relay time interval for 1838
circuit boards with revision level A-C is set at 7 seconds. The time interval can be
programmed from 1 – 254 seconds on boards with revision level D and higher.
Factory setting = 007
1. Press *
2. Enter the relay time in seconds _ _ _ (001-254) then press *
3. Press 0
ramming the PC Programmable Access Control System with the DoorKing Remote
small slide switch) to the on position.
(beep).
ram sequence sets the access control system to operate as a single unit on the phone line,
0 4 and then enter the four-digit MASTER CODE _ _ _ _ (beep).
* (beep) for a single system or 1* (beep) for multiple systems.
# TOGETHER to end this programming step (beeeeeep).
3 6 and then enter the four digit master code _ _ _ _ (beep).
(beep).
# together to end this programming sequence (beeeeeep).
1838-065
-U-4-13 Page
27
3.2.4 Open Tone On or Off
The following programming sequence turns the open tone (when the relays activate) either On or Off.
This feature is available on Rev J boards or higher.
Factory setting = 1 (tone on)
1. Press * 1 5 and then enter the four digit master code _ _ _ _ (beep).
2. Enter 1 for yes (tone will sound) or 0 for no (tone will not sound) then press * (beep).
3. Press 0 # together to end this programming sequence (beeeeeep).
3.2.5 Elevator Control Function
The elevator control feature authorizes floor access to the Floor Level identified in the Resident
Screen in the software program AND to the floor(s) level identified in the Security Level screen. If this
feature is turned off, access will be granted only the floor identified in the user’s security level. This
feature is available on Rev J boards or higher.
1. Press * 7 5 and then enter the four digit master code _ _ _ _ (beep).
2. Enter 1 for yes (access is authorized to both the floor identified in the resident screen and
to the floor(s) identified in the user’s security level) or 0 for no (access is authorized only
to the floor(s) identified in the security level screen) then press * (beep).
3. Press 0 # together to end this programming sequence (beeeeeep).
3.2.6 RS-232 Speed Setting
The following programming sequence sets an optional faster RS-232 speed. This feature is available
on Rev L boards or higher and the Remote Account Manager Software, Version 6.2, must be used.
Factory setting = 0 (9600 baud rate)
1. Press * 8 5 and then enter the four digit master code _ _ _ _ (beep).
2. Enter 0 for 9600 baud rate or 1 for 19200 baud rate then press * (beep).
3. Press 0 # together to end this programming sequence (beeeeeep).
STOP!!
If the access control system is to be programmed from a PC, no other programming is required at the
system itself. Refer to the Remote Account Manager for Windows Software help screens for
additional programming information. Continue with the remaining sections in this chapter if the
access control system will be programmed by any other method. If the factory setting matches your
need, there is no reason to reprogram that section.
Remember that relay hold open time zones, security levels, and elevator control functions can only be
programmed from the Remote Account Manager Software. If any of these features are being used,
do not proceed with any other programming steps in this manual.
Page 28 1838-065-U-4-13
3.3 GENERAL PROGRAMMING
Proceed
3.3.1 Relay Strike Time
These steps
00 in step 4) up to 99 seconds by entering the desired time in seconds. If Tracker expansion boards
are going to be used with this system, set Relay 2 strike time to 00 for Tracker boards 1-8. If more
than 8 Tracker boards are being used, set Relay 1 strike time to 00 (for Tracker boards 9-16).
Factory setting for relay strike times are: Relay 0 = 01, Relay 1 = 01, Relay 2 = 01.
3.3.2 Talk Time
with the programming steps on the following pages only if PC programming will not be used.
will program relay strike times. Strike times can be programmed from 1/4 second (enter
1. Press *
2. Press 0
3. Enter the two-digit strike time _ _ (00-99) then press *
0 3 and enter the four-digit MASTER CODE _ _ _ _ (beep).
* to set relay 0 or, 1 * to set relay 1, or 2 * to set relay 2 strike time.
(beep).
4. Repeat steps 2 and 3 to set other relay strike times.
5. Press 0
# TOGETHER to end this programming step (beeeeeep).
The talk time set here does not affect the telephone numbers that are programmed under directory
codes 0, 00, 000, 0000 (input A) and 1, 01, 001, 0001 (input Z). The talk time for these two directory
codes are factory set to the maximum. Phone numbers programmed under these directory codes
should be reserved for management or emergency phone numbers that generally require longer
conversations. This programming sequence can be used to set the maximum time allowed for
conversation when the entry system places a call to a phone number programmed under directory
code 2, 02, 002 or 0002 (inputs A-Z together). The talk time can be set from 1 second up to 255
seconds (4 minutes, 15 seconds) and is entered as a three-digit number. For example, to set a talk
time of 20 seconds, enter 020 in step 3.
Factory setting for talk time = 60 seconds.
NOTE: This programming step is only used when a DKS Remote Call Station is connected to
the 1838 system.
1. Press *
0 8 and enter the four digit MASTER CODE _ _ _ _ (beep).
2. Enter three digits for talk time (seconds) _ _ _ (001-255) then press * (beep).
3. Press 0
# TOGETHER to end this programming step (beeeeeep).
1838-065
-U-4-13 Page
29
3.3.3 Tone Open Numbers
These steps will program the tone open numbers for the relays. You will need to enter a four-digit
number (see chart below) to set the relay functions. If a function is not desired, enter # in place of a
number. For example, if you want the relay to have a momentary activation function only, and you
want the relay to activate when the number 9 is pressed on a touch-tone phone after calling the
system, enter 9 # # # in step 4. Do not duplicate tone open numbers, i.e., don’t set relay 0, relay 1
and 2 tone-open numbers all to 9. If Tracker expansion boards are connected to the system, there is
no need to set a momentary open tone open number for the tracker control relay(s). However, you
may want to set HOLD and DEACTIVATE tone numbers, which will allow management to have a
function to automatically unlock all doors/gates controlled by a Tracker board (refer to 4.2.2).
Factory setting is: Relay 1 = 9876, Relay 2 =5432.
1. Press *
2. Press 0
3. Enter the four-digit tone open number code _ _ _ _ then press *
0 5 and enter the four-digit MASTER CODE _ _ _ _ (beep).
* to set relay 0 or 1 * to set relay 1 or 2 * to set relay 2 tone numbers.
(beep).
4. Repeat steps 2 and 3 to set the other relay tone open numbers.
5. Press 0
# TOGETHER to end this programming step (beeeeeep).
NUMBER FUNCTION
1st Digit Momentary activation. Relay will activate for the programmed strike time (3.3.1).
2nd Digit Relay hold. Relay will activate and remain activated until commanded to release.
3rd Digit Relay release. Deactivates the relay hold command.
4th Digit Relay hold 1-hour. Relay will activate for 1-hour and then will automatically deactivate itself.
3.3.4 Input Switch
This p
rogramming sequence sets what relay(s) will activate when the input (postal) switch input is
activated on the access control system. The system can be programmed so that only one relay will
activate, or any combination of relays will activate. To cause a relay to activate, enter a 1 in it's
respective character slot, or enter a zero to not activate the relay. Any combination of 1's or 0's is
permissible. For example, entering 010 in step 3 will cause only relay 1 to activate. Entering 011 will
cause relay 1 and relay 2 to activate. Entering 111 will cause all three relays to activate.
Factory setting = 010 (Only relay 1 will activate)
1. Press *
2. Enter the three-digit (1's or 0's only) postal relay code _ _ _ then press *
3. Press 0
50 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
Page 30 1838-065-U-4-13
3.3.5 Touch-tone / Rotary-dial
This programming sequence will set the remote call station to dial out in either a touch-tone or rotary
format. Generally, this will be set for touch-tone.
Factory setting = touch-tone.
NOTE: This programming step is only used when a DKS Remote Call Station is connected to
the 1838 system.
1. Press *
2. Enter 0
3. Press 0
0 7 and enter the four digit MASTER CODE _ _ _ _ (beep).
* (beep) for touch-tone or enter 1 * (beep) for rotary.
# TOGETHER to end this programming step (beeeeeep).
1838-065
-U-4-13 Page
31
3.4 PROGRAMMING PHONE NUMBER
: These programming steps are only used w hen a DKS 1838-120 or 1838-121 Remote
NOTE
Call Station is connected to the 1838 system.
3.4.1 Programming the Directory Code Length
rogramming sequence sets the directory code length to 1 - 2 - 3 or 4 digits.
This p
Factory setting is three (3) digits.
CAUTION: This programming sequence will delete all directory codes that have been
previously programmed into the system.
1. Press *
2. Enter the desired directory code length _ (1, 2, 3 or 4) then press *
3. Enter 0
tone (beeeeeep) will sound when the programming is complete.
3.4.2 Programming 7-digit Phone Number
In this programming sequence, the directory code and 7-digit phone number will be programmed into
the system. Be sure you have programmed the directory code length that you desire as described in
3.4.1. Changing the directory code length after programming the telephone number will erase all the numbers and directory codes that have been programmed. To program a phone number
that will be referenced to an area code (long distance calls and 10 digit calling), follow the instructions
under 3.4.3 and 3.4.4.
NOTE: If this system is being used in an area that requires 10 digit dialing, proceed to 3.4.3
and 3.4.4 to program the area code and phone number.
1. Press *
2. Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in 3.4.1)
then press *
3. Enter the seven-digit phone number _ _ _ _ _ _ _ then press * (beep). If the number that
you are entering in this step is less than seven-digits, enter # in the empty spaces. For
example, if the system is connected to a PBX that requires four-digit extension numbers
and you want to enter extension 2217, you would enter this number as 2217#### then
press *
4. Press 0
NOTE: Only the following Directory Codes may be used: 0, 00, 000, 0000, OR 1, 01, 001, 0001.
2 0 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
then * to cancel this command or enter 1 then * to confirm this command. A long
0 1 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep),
(beep).
# TOGETHER to end this programming step (beeeeeep).
Page 32 1838-065-U-4-13
3.4.3 Programming Area Code
Program an area code when 10-digit or long distance calling is required. You can program up to 10
area codes, but since the 1838 can only dial three phone numbers, only three will be used. The area
code will be entered as a four-digit number (1 + the three digit area code) for long distance dialing. If
an area code is being programmed to facilitate 10-digit calling requirements, precede the three-digit
area code with #. To program different area codes, you will use a different area code reference
number, 0 through 9, entered in step 2 below. We suggest using 1 for the first area code reference
number, 2 for the second, 3 for the third and so on. Use 0 for the tenth reference number.
1. Press *
2. Enter the area code reference number (0 – 9) _ then press *
3. Enter the four digit area code _ _ _ _ then press *
2 4 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
(beep). NOTE-1: for long distance
calling requirements, enter 1 and the three-digit area code. NOTE-2: for 10-digit
calling requirements, enter # and the three-digit area code.
4. Press 0
# TOGETHER to end this programming step (beeeeeep).
3.4.4 Programming Phone Numbers with Area Code
In this section, phone number is referenced to the area code that was programmed in 3.4.3.
NOTE: If long distance or 10-digit dialing is not required, program the seven digit telephone
numbers as described in 3.4.2.
1. Press *
4 1 and enter the four-digit MASTER CODE _ _ _ _ (beep).
2. Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in
3.5.1) then press *
3. Enter the area code reference number (0 – 9) _ then press *
4. Enter the seven-digit phone number _ _ _ _ _ _ _ then press *
(beep).
(beep).
(beep). If the number
that you are entering in this step is less than seven-digits, enter # in the empty
spaces. See 3.4.2, step 3.
5. Press 0
# TOGETHER to end this programming step (beeeeeep).
1838-065
-U-4-13 Page
33
3.4.5 Delete Phone Number
This programming sequence is used to delete the phone number under a known dire ctory code.
1. Press *
01 and enter the four-digit MASTER CODE _ _ _ _ (beep).
2. Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in
3.5.1) then press *
3. Press #
4. Press 0
# # # # # # then press * (beep).
# TOGETHER to end this programming step (beeeeeep).
(beep).
3.4.6 Delete Area Code
This program sequence deletes the area code programmed into the system.
1. Press *
2. Enter 1
3. Enter #
4. Press 0
24 and enter the four-digit MASTER CODE _ _ _ _ (beep).
then press * (beep).
# # # then press * (beep).
# TOGETHER to end this programming step (beeeeeep).
3.4.7 PBX Line Access Code Programming
If the 1838 / Remote Call Station system is connected to a PBX telephone system rather than a
dedicated C.O. line, you may need to set the unit to dial a line access code prior to dialing the a
phone number. Typically, the line access code is “9”, but check with the PBX system administrator to
be sure.
1. Press *
2. Enter the line access code number _ then press *
3. Press 0
09 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
NOTE: To change a line access number, enter the correct number in step 2. To
delete a line access number, enter # in step 2.
3.4.8 Touch Tone Dialing Pause
During touch-tone dialing, the system (by default) places a 2 second pause after dialing a line access
code (9 in a PBX system for example) and after the area code. For example:
9 (2 second pause) 1310 (2 second pause) 6450023
The 2 second pause can be removed by programming 0 into the steps below. In this example, the
system would simply dial out the line access code (9), area code (1310) and phone number
(6450023) without any pauses.
913106450023
Factory setting is 1 (pause ON).
1. Press *27 and enter the four-digit MASTER CODE _ _ _ _ (beep).
2. Enter 0 * (beep) to turn the pause OFF, or enter 1 * to turn the pause ON..
3. Press 0# TOGETHER to end this programming step (beeeeeep).
Page 34 1838-065-U-4-13
3.5 PROGRAMMING DEVICE CODES
Device code
device code that you enter is assigned to the directory code that you select. Up to 25 device
numbers can be entered under a single directory code, up to a maximum of 8,000 for the system.
You cannot duplicate device codes.
3.5.1 Programming Device Codes
This p
1. Press *
2. Enter the directory code that the device code is to be assigned to (1, 2, 3 or 4 digits
3. Enter the five-digit device code _ _ _ _ _ then press *
4. Repeat steps 2 and 3 to enter additional device codes.
5. Press 0
3.5.2 Deleting Device Codes
This p
1. Press *
2. Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in
3. Enter the five-digit device code _ _ _ _ _ then press *
4. Repeat steps 2 and 3 to delete additional device codes.
5. Press 0
3.5.3 Enabling Facility Codes
This program
1. Press *
2. Enter 0
3. Press 0
3.5.4 Programming Facility Codes
This program
(reference numbers 0 through 9) may be programmed. Valid facility codes are 000 – 255.
1. Press *
2. Enter the first facility code reference number _ (0 – 9) then press *
3. Enter the three-digit facility code _ _ _ then press *
4. Repeat steps 2 and 3 to enter additional facility codes.
5. Press 0
s must be five (5) digits in length and are typically card and transmitter codes. Each
rogram sequence enters device (card, transmitter, digital) codes into the system memory.
7 0 and enter the four-digit MASTER CODE _ _ _ _ (beep).
depending on what was programmed in 3.4.1) then press *
(beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
rogram sequence deletes individual device codes.
71 and enter the four-digit MASTER CODE _ _ _ _ (beep).
3.4.1) then press *
(beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
sequence allows you to use (enable) or not use (disable) facility codes.
7 2 and enter the four-digit MASTER CODE _ _ _ _ (beep).
to disable facility codes or enter 1 to enable facility codes then press * (beep).
# TOGETHER to end this programming step (beeeeeep).
sequence enters device facility codes into the system memory. Up to 10 facility codes
7 3 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
1838-065
-U-4-13 Page
35
3.6 FOUR-DIGIT ENTRY CODE
orKing remote keypad (P/N 1814-075) is required if four-digit entry codes are going to be used to
A Do
access a door or gate. It is important to understand that four-digit entry codes are not the same as a
five-digit PIN (Personal Identification Number) code inputted to the system from a wiegand keypad.
Four-digit entry codes can only activate relays 0, 1 or 2 on the 1838 circuit board, regardless if
Tracker expansion boards are used or not. If Tracker expansion boards are controlled by relay 2, the
four-digit entry codes must be set to activate relay 0 or 1. If relays 1 and 2 are used to control
Tracker expansion boards, then four-digit entry codes must be set to activate rel ay 0.
3.6.1 Programming Four-digit Entry Codes
1. Press *
2. Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in
3.4.1) then press *
3. Enter the four-digit entry code _ _ _ _ then press *
4. Repeat steps 2 and 3 to enter additional entry codes.
5. Press 0
3.6.2 Delete Four-digit Entry Codes
1. Press *
2. Enter the directory code (1, 2, 3 or 4 digits depending on what was programmed in
3.4.1) then press *
3. Press #
4. Repeat steps 2 and 3 to delete more entry codes.
5. Press 0
3.6.3 Entry Code Ranges
Four-di
by programming HI and LOW ranges for each relay. Ranges may overlap, which will cause more
than one relay to activate if this is desired. For example, if the low boundary for relay 1 and 2 is 2000,
and the hi boundary is 3000 for relay 1 and 4000 for relay 2, then entry codes between 2000 and
3000 will activate both relays, and entry codes between 3001 and 4000 will only activate relay 2.
git entry codes can be made to activate relay 0, relay 1, relay 2 or any combination of relays
1. Press *
2. Press 0
3. Enter the four-digit low boundary _ _ _ _ then press *
4. Enter the four-digit high boundary _ _ _ _ then press *
5. Repeat steps 2, 3, and 4 to set the other relay boundaries (or proceed to step 7).
6. Press 0
02 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
02 and enter the four-digit MASTER CODE _ _ _ _ (beep).
(beep).
###* (beep).
# TOGETHER to end this programming step (beeeeeep).
12 and enter the four-digit MASTER CODE _ _ _ _ (beep).
* to set relay 0, 1* to set relay 1, or 2* to set relay 2 boundaries.
(beep).
(beep).
# TOGETHER to end this programming step (beeeeeep).
Page 36 1838-065-U-4-13
3.7 ANTI-PASS BACK
The pro
pass back feature. However, you must set up the IN and OUT relay programming table in the
Remote Account Manager software. Refer to manual 1835-066.
3.7.1 Programming the Anti-Pass Back Mode
Anti-Pass
an APB Violation and will allow entry or exit. ACTIVE APB records an APB Violation and will not
allow entry or exit. TRAP APB records an APB Violation and will allow entry but not exit.
3.7.2 Re-Sync All Devices
This
Violation to be recorded.
3.7.3 Re-Sync Individual Devices
This p
gramming steps below will allow you to set up and program some basic functions for the anti-
Back (APB) can be set to operate in one of three different modes. PASSIVE APB records
1. Press *
2. Enter 0
3. Press 0
programming step is used to allow all cards one ‘move’ either in or out without causing an APB
1. Press *
2. Press 1
3. The programming sequence will end itself after all cards are re-synced.
rogramming step is used to re-sync a single card only.
1. Press *
2. Enter the five digit device number _ _ _ _ _ then press *
3. Press 0
43 and enter the four-digit MASTER CODE _ _ _ _ (beep).
for OFF, 1 for PASSIVE, 2 for ACTIVE or 3 for TRAP, then press * (beep).
# TOGETHER to end this programming step.
45 and enter the four digit MASTER CODE _ _ _ _ (beep).
to Re-Sync ALL devices or press 0 to not Re-Sync, then press * (beeeeeep).
46 and enter the four digit MASTER CODE _ _ _ _ (beep).
(beep).
# TOGETHER to end this programming step.
3.7.4 Reset Facility Counter
This programming step is used to reset the facility counter. The facility counter keeps track of the
number of “IN’s” and “OUT’s” when using APB mode.
1. Press *
2. Enter a five digit number that you want the count to start at _ _ _ _ _ then press *
(Example: to start at 25, enter 00025)
3. Press 0
1838-065
-U-4-13 Page
48 and enter the four digit MASTER CODE _ _ _ _ (beep).
(beep).
# TOGETHER to end this programming step.
37
3.8 CONTROL BOARD ADJUSTMENTS
1838 Series Control Board Adjustments
RS 232
D
654321
MIC
VOL
2
SPK
FEED
BACK
VOL
3
4
1816
1
B
C
ELEVATOR
1
2
3
1413121110987654321
HF
HS
5
6
RING
A
123456789101112131514161718 1920
Microphone Volume (Gain) Adjustment
1
Speaker Volume Adjustment
2
Feedback Adjustment
3
1816 Interface Jumper
4
Hands Free (HF) – Hand Set (HS) Jumper
5
Ring Pin
6
Master Code Switch
7
Relay 2 Contact Jumper NO / NC
8
KEYPAD
ON
MASTER
CODE
OFF
7
E
NO NC C
Main Terminal
A
Weigand Input Terminals
B
Elevator Control Terminals
C
RS-232 Terminals
D
Relay 0 Terminals
E
NCNO
8
DOORKING, INC. INGLEWOOD, CA 90301
Title:1838 Series Board Adjustments
Date:7/12 Dwg. No. M1838-065-4
D
Page 38 1838-065-U-4-13
3.8.1 Master Code Switch
1. The master code switch is left in the off position for normal operation. Turn the master
code switch on when setting the system master code. See programming instructions to
set the system master code. If the master code switch is turned on and a new master
code is not entered, the system will sound a long tone after approximately 30 seconds.
This tone will continue every 30 seconds until a new master code is entered, or until the
switch is turned off.
3.8.2 Ring Pin
The ring pin is labeled RING on the control board. This shorting pin must be installed to
1.
allow the system to answer any calls placed to it. If remote programming or remote relay
operation is to be used, the shorting pin must be installed. Removing the shorting pin will
cause the system to never answer any call placed to it.
3.8.3 Relay 2 Contact Pin
This shorting pin sets the contacts on relay number two to be set to either Normally Open
1.
(NO) or Normally Closed (NC). The pin is set to NO from the factory.
1838-065
-U-4-13 Page
39
Note: 3.8.4 is applicable only if a Remote Call Station is connected to the 1838 controller.
3.8.4 Speaker Volume, Microphone and Feedback
Spea
ker volume, microphone volume and feedback all interact with each other to affect the audio
performance of the system. Use the following steps to set these adjustments.
1. Open the 1838 controller and locate the speaker volume, microphone volume and
feedback adjustments (see page 34).
2. Set the speaker volume about 1/3 from full counter-clockwise.
3. Set the microphone volume to 1/2.
4. Place a phone call from Remote Call Station. If feedback occurs, turn the speaker
volume counter-clockwise until it ceases.
5. While still on the line, ask the other party to remain silent while rubbing your finger over
the microphone hole on the face plate. Rotate the feedback adjustment throughout its
range while listening to the sound coming from the speaker. When the sound is
minimum, this is the correct setting.
6. Speaker volume and microphone volume may now be adjusted to desired levels. If both
are set too loud, feedback may result. For louder speaker volume, the microphone
volume may need to be decreased. For louder microphone volume, the speaker volume
may need to be decreased.
7. Normal setting for both speaker volume and microphone volume is about 1/2.
8. After setting these adjustments, place some test calls. If feedback occurs, microphone
and/or speaker volume will need to be reduced.
Page 40 1838-065-U-4-13
SECTION 4 – OPERATING INSTRUCTIONS
4.1 USER INSTRUCTIONS
4.1.1 Card Access
Card access is provided by card readers or automatic vehicle Identification devices (AVID) that can
be connected to the 1838 controller.
1. If the system uses proximity type readers, present the card or PROXmtr™ to the reader
by holding it close the reader head.
2. If the system uses an AVID system, operation is automatic.
4.1.2 RF Transmitters
RF tra
nsmitters are typically used to control vehicular access through automated gates. Some RF
transmitters, called PROXmtr’s™, have a proximity card built-in that enables them to also be used as
cards to access areas controlle d by a card reader.
1. Press the transmitter button when in view of, and within 75 feet of the access gate.
2. PROXmtr’s™ only: hold the transmitter near the proximity card reader head.
4.1.3 Five-Digit PIN Codes
Five-digit PIN (Perso
codes. Although both type codes are entered on a keypad, the access system processes them and
treats the codes in different ways.
1. Enter the five-digit code directly on the wiegand keypad. A valid code will open the door
or gate.
If management decides to utilize PIN codes, system users should be instructed to keep their unique
code secret. Telling other persons their code or allowing other persons to use their code
compromises security and defeats the purpose of the system.
4.1.4 Four-Digit Entry Codes
Four-di
on a remote keypad connected to the controller. The four-digit code will activate either relay 0, relay
1, relay 2 a combination of relays depending on the boundaries that have been programmed in 3.6.3.
If management decides to utilize entry codes, system users should be instructed to keep their unique
code secret. Telling other persons their code or allowing other persons to use their code
compromises security and defeats the purpose of the system.
git entry codes provide a means for a person to gain access by using a four-digit code entered
1. Press #
nal Identification Number) codes should not be confused with four-digit entry
and then enter the four-digit code on the slave keypad.
1838-065
-U-4-13 Page
41
4.2 SYSTEM ADMINISTRATOR INSTRUCTIONS
The syste
tone telephone if the optional telephone line has been connected to the 1838 controller. You
must know the phone number of the line that the system is installed on and the system master code.
4.2.1 Opening the Door / Gate From A Remote Location
Note: Step-3, refer to 3.3.3 to determine which tone-open numbers have been programmed
(momentary open, hold open, release, hold open 1-hour).
4.2.2 Tracker Board Override Command
The T
system. This command will cause ALL Tracker boards connected to the system to open or
unlock the door or gate that they are controlling, and will remain in this state until commanded
to return to normal operation. This feature is useful when management wants to open all gates or
unlock all doors – perhaps during an emergency situation for example. Hold-open tone numbers
must be programmed for the override command to be functional. See 3.3.3.
To release the override command, repeat the steps above but enter the RELEASE tone number in
step 3.
4.3.3 Relay Check
The
system are in a "hold open" mode. This check can be useful if your gate (or door) is held open and
you suspect that one of the system relays may be the cause.
m administrator can perform the following operations from a remote location using a touch-
Call the telephone number that the system is installed on. The 1838 will answer with a
1.
short beep.
2. Press *
3. Press the desired tone-open number _ (short beep).
4. Hang-up.
racker board override command is used when Tracker expansion boards are connected to the
1. Call the telephone number that the system is installed on. The 1838 will answer with a
short beep.
2. Press *
3. Enter the HOLD tone number _ (short beep).
4. Hang-up.
access system can be called and a check can be made to determine if any of the relays in the
1. Call the telephone number that the system is installed on. The system will answer with a
short beep.
2. Press *
3. The system will emit a series of short tones if the relay is in a continuous activation mode.
4. Press the programmed tone number _ to deactivate the relay (short beep). The system
will automatically hang up.
16 and enter the four-digit master code _ _ _ _ (short beep).
16 and enter the four-digit master code _ _ _ _ (short beep).
16 and enter the four-digit master code _ _ _ _ (short beep).
The DoorKing 1838 access controller is essentially a maintenance free device. When the unit is
properly installed, it should provide years of trouble free service. Maintenance is limited to updating
the directory and phone number and/or card/transmitter codes as users are added and deleted from
the system.
5.1 TROUBLE SHOOTING
If proble
following pages to try and correct any problems. Our experience has shown that a majority of
reported problems are actually programming related and can be corrected on site. If problems persist
and they cannot be corrected, contact your authorized DoorKing dealer for assistance. Before
performing any trouble-shooting, check the following:
ms should develop with your access control system, refer to the trouble-shooting guide on the
1. Have a good VOM meter handy to check voltages and continuity.
2. Have a telephone test set (DoorKing p/n 1800-050 or equivalent) to check the
telephone line. Noise on the phone line will cause problems with the entry system.
3. Be sure that the entry system case is properly grounded.
4. Be sure that the telephone wires are twisted.
5. A hum on the system indicates that the phone line or 16 VAC power lines may be
grounded. Check to be sure that the phone lines or power lines are not shorted to
ground.
6. Check the 16 VAC system power. Be sure that the transformer is properly rated (20
VA). Keep the wire run from the transformer to the entry system as short as possible.
Use 16 or 18 AWG, 600 volt insulated wire only. The importance of proper power wiring cannot be over stressed!
7. Isolate the access controller. Disconnect any external devices, such as Tracker
expansion boards, elevator control boards, RS232 connection, card readers, RF
receivers, keypads, etc. which may affect the operation of the controller.
1838-065
-U-4-13 Page
43
SYMPTON POSSIBLE SOLUTION(S)
Cannot get into
programming mode.
System emits a long
tone and cancels
programming.
Keypad is dead. No power. Check for 16 VAC input power.
Buzz or noise on the
phone line.
Ringing or howling
from the speaker.
Door strike locks on. Excessive voltage-drop on 16 VAC line.
Door strike or gate
operator holds open.
System will not
answer when called.
Touch-tone 9 will not
activate relay.
Relay activates but
gate operator will not
open.
Postal switch will not
activate relay.
Wrong master code entered. Start over.
Waiting too long between pushing buttons. Enter information quicker.
Keypad is not plugged into board correctly. Cable points to the left.
Memory chips are installed backwards.
Waiting too long between pushing buttons.
Forgetting to press #
Check that the keypad is properly connected to the circuit board. The cable on the
plug points to the left when connected to the circuit board.
Disconnect the phone line from the system and check it with a handset. If line is
noisy, problem is with the phone line and not the entry system.
Check for any shorts to ground behind the circuit board.
Check for pinched wires near the door hinge.
Check for 16-volt power shorted to ground.
Check for phone line shorted to ground.
Check that phone wires are twisted.
Check that the proper type of phone wire was used for an outdoor and / or
underground application.
Check that all wires, speaker, keypad, etc. are isolated from ground.
Check that the cabinet is properly grounded. Be sure that case ground (terminal 3)
is not used as a low voltage common.
Check for excessive voltage drop on 16 VAC power.
Volume is set too high (3.8.4).
Using a transformer with too low VA rating.
Relay strike time programmed too long (3.3.1).
System was given a hold open command. Call the system and press the tone
deactivate number (3.3.3).
Ring pin is not installed (3.8.2).
Bad phone line or insufficient ring voltage.
Re-program tone-open number to 9 (3.3.3).
If phone emits a short pulse rather than a long tone, press 9 twice in rapid
succession 9
Try another phone that is known to work.
Lower speaker volume (3.8.4).
Re-program relay strike time for a longer period (3.3.1).
Check wiring to gate operator.
Check gate operator.
Be sure that the wire-tie has been clipped off the postal switch.
Be sure that the relay has been programmed for postal switch input (3.3.4).
Be sure postal switch is connected properly.
first when programming.
9.
Page 44 1838-065-U-4-13
SYMPTON POSSIBLE
Four-digit entry codes
will not work.
Entry codes will not
activate relay 1.
Entry codes will not
activate relay 2.
System emits a beep
every 30 seconds.
System emits 2 short
beeps when powered
up.
System emits 3 short
beeps when powered
up.
Forgetting to press # first.
Re-program the entry code ranges (3.6.3).
Re-program relay 1 low and high ranges (3.6.3).
Re-program relay 2 low and high ranges (3.6.3).
Master code switch is in the ON position (3.8.1).
The memory chip size (small chip) and the main memory storage ship (large chip)
do not match in memory size. By pressing 1, the main memory storage chip will be
matched to the memory size chip. All data in the main memory will be erased when this function is performed.
The small chip in the PC board socket is for a telephone entry system and cannot be
used in the access control system.
SOLUTION(S)
5.1.1 RS-232 Test
This test p
rocedure will check the RS-232 hardware to determine a pass or fail mode. You will need
two short pieces of wire to perform this test.
1. Open the cabinet of the access control system and locate the RS-232 terminals in the
upper right hand corner of the control board.
2. Short terminal 1 to terminal 2 using the first piece of wire.
3. Short terminal 3 to terminal 4 using the second piece of wire.
4. Press *
5. Press *
17 and enter the four-digit master code _ _ _ _ (beep).
.
PASS - A long tone will be heard (Beeeeeep).
FAIL - Two short tones and then a long tone will be heard (Beep - Beep - Beeeeeep).
6. Remove the jumper wires from the terminal after performing this test.
1838-065
-U-4-13 Page
45
5.1.2 Floor, Elevator, Security Level Test Programming
This programming sequence is included for troubleshooting the elevator control board(s) only. It
allows you to enter basic information for troubleshooting purposes. You will need the Elevator
Control Installation Manual for additional information regarding troubleshooting the elevator control
board(s).
1. Press *
42 and enter the four-digit master code _ _ _ _ (beep).
2. Enter a know directory code that has been programmed into the system (1, 2, 3 or 4
digits depending on the number programmed in 3.4.1) then press *
(beep).
3. Enter a five-digit number that represents a two-digit floor number (01-64); a singledigit elevator reference number (1-8); and a two-digit security level number (00-30)
_ _ _ _ _ then press *
(beep).
4. Repeat steps 2 and 3 to program additional floor numbers, elevator reference and
security level codes.
5. Press 0
# TOGETHER to cancel the wiegand test mode.
5.1.3 Elevator Board(s) Hardware Test
This p
rogramming sequence is designed for trouble shooting the elevator control board(s) that may
be connected to the access control system. This sequence will take approximately four (4) minutes to
complete and will check the operation of the CALL relay, and then all the odd numbered relays, then
all the even numbered relays on the elevator control board(s). This test confirms communication
between the 1818 circuit board and the elevator control board(s).
1. Press *
2. Enter the elevator shaft number _ (1, 2, 3 or 4) then press *
76 and enter the four-digit master code _ _ _ _ (beep).
(beep).
Once the test starts, the CALL relay (LED ON) will activate, and then ALL odd
numbered relays will activate, and then ALL even numbered relays will activate on
the 1st elevator control board. After this sequence, if more than one elevator control
board is connected, ALL odd numbered relays, and then ALL even numbered relays
will activate on the 2nd elevator control board. After this sequence, ALL odd
numbered relays, and then ALL even numbered relays will activate on the 3rd
elevator control board. After this sequence, ALL odd numbered relays, and then ALL
even numbered relays will activate on the 4th elevator control board. This sequence
will repeat itself ten (10) times.
3. Once the test is complete (approximately 4 minutes), this programming sequence will
automatically end itself.
Page 46 1838-065-U-4-13
5.1.4 Elevator Board / Floor Hardware Test
This testing sequence will allow you to check activation of individual relays on the elevator control
board(s) and will confirm communication between the 1838 circuit board and the elevator control
board(s).
1. Press *
2. Enter the elevator shaft number _ (1, 2, 3 or 4) then press *
3. Enter the two-digit floor number _ _ , then press *
77 and enter the four-digit master code _ _ _ _ (beep).
(beep).
(beep).
4. The relay LED on the elevator control board that represents the floor number entered will
turn ON for approximately 1 second.
5. To check other floor relays, repeat steps 2 and 3.
6. When complete with the testing, press 0
# TOGETHER to end this testing sequence.
NOTE: This program test sequence will automatically end itself if no keypad inputs are
detected after approximately 30 seconds.
Refer to the Elevator Control board installation manual for more information on trouble
shooting the elevator control boards.
5.1.5 Modem Output Level
This program
ming sequence sets the output level of the modem tones. This programming step
should only be used if you are experiencing modem trouble. A higher setting increases the tone
volume while a lower setting decreases the tone volume.
Factory setting is: 4
1. Press *
2. Enter a modem level _ (1 through 8) then press *
3. Press 0
90 and enter the four-digit master code _ _ _ _ (beep).
(beep).
# TOGETHER to exit this programming step.
1838-065
-U-4-13 Page
47
5.2 ACCESSORIES
rd Readers A variety of DKS, AWID and HID proximity readers are available for use
Ca
with the 1838 controller. Most 26-bit card readers will interface with the
1838 controller.
RF Devices RF devices provide remote access control for vehicular gates. Use
DoorKing MicroPLUS™ wiegand receiver (P/N 8056-080) or DoorKing
MicroCLIK wiegand receiver (P/N 8059-080) and corresponding
transmitters.
PROXmtr™ DoorKing PROXmtr’s provide both RF access control and proximity card
access control in a single, compact package. Requires a MicroPLUS
wiegand receiver and DKS, AWID or HID proximity card readers.
Digital Keypad Provides a wiegand output when users enter their 5-digit PIN code.
P/N 1815-050 and 1815-051.
Slave Keypad Provides for use of 4-digit entry codes (P/N 1814-075).
Surge Suppressers High voltage (115 V) suppresser. P/N 1878-076. Phone line
suppresser. P/N 1878-077. Low voltage (28 V) suppresser. P/N 1878-
078.
Telephone Test Set Includes clips, cord and carrying case. P/N 1800-050.
Battery 12 volt .8 amp hour gel cell provides stand by power during power
interruptions. P/N 1801-008.
Tracker Boards Tracker expansion boards (P/N 2351-010) allow the system to operate
up to sixteen individual doors or gates, provides door ajar and forced
entry alarms, and can activate local and building alarm systems. Also
allows DoorKing gate operators to report gate operator data and activity
to the entry system.
RS-232 Cable RS-232 cable with DB-9 connector on one end and wires on the other
end. Use this cable to program the entry system from a PC using RS232 communications instead of the modem. P/N 1818-040.
TCP/IP Kit P/N 1830-175 – enables the 1838 system to send and receive da ta via
the DKS Internet Server or a LAN.
Elevator Board Elevator control boards (P/N 2348-010) provide control of up to four
elevators, with each elevator having a maximum of 64 floors.
Small Enclosure Provides a weather resistant lockable enclosure for a single T racker™
expansion board.
Large Enclosure Provides a weather resistant lockable enclosure for up to four (4)
Tracker™ expansion boards and includes convenience outlets for four
(4) accessory transformers.
Remote Call Station Provides voice communication to a remote location via the telephone
network. Available with a keypad (1838-120) or card reader (1838-121).
Page 48 1838-065-U-4-13
5.3 LOG TABLES
plete the information in the tables on the following pages to maintain a record of the information
Com
that has been programmed into the access control system if the system IS NOT being programmed
from a PC. If PC programming is being utilized, there is no reason to maintain these log sheets since
the PC will maintain a complete record of the information that has been programmed.
Make copies of the user log sheet so that you have enough to complete a listing of all users and data.
Enter the information as shown in the example below. DIR is the user’s unique directory code and
can be 1 to 4 digits (3.4.1). Enter the user ’s four-digit entry code (3.6.1) in the ENT field if they are
used. Enter the user’s unique device code (3.5.1) in the DEVICE field if access control devices
(Transmitters, cards, etc.) are used. Enter the SEC LEVEL (Security Level), FL (Floor), and ER
(Elevator Reference) numbers as required.