Please read this instruction manual carefully before starting the appliance and keep it in a safe place for future reference. If you pass on the
appliance to another person, hand over this operating manual along
with it.
CAUTION!
Safety instruction: Failure to observe this instruction can lead to
!
A
injury.
NOTICE!
Failure to observe this instruction can cause material damage and
impair the function of the product.
NOTE
Supplementary information for operating the product.
I
➤ Action: This symbol indicates that action is required on your part. The
required action is described step-by-step.
✓ This symbol describes the result of an action.
fig. 1 5, page 3: This refers to an element in an illustration. In this case,
item 5 in figure 1 on page 3.
2Safety instructions
The manufacturer accepts no liability for damage in the following cases:
Faulty assembly or connection
Damage to the product resulting from mechanical influences and excess
voltage
Alterations to the product without express permission from the manu-
facturer
Use for purposes other than those described in the operating manual
2.1General safety
CAUTION!
!
4
Electronic devices are not toys!
Keep electrical appliances out of reach from children or infirm
persons.
Do not let them use the appliances without supervision.
EN
MCS5, MCS15Target group for this manual
Persons (including children) whose physical, sensory or mental
capabilities or lack of experience and knowledge prevents them
from using the appliance safely should not use this appliance
without initial supervision or instruction by a responsible person.
Use the device only as intended.
Do not make any alterations or conversions to the device.
Installation and repairing of the air conditioner may only be car-
ried out by qualified personnel who are familiar with the risks involved and the relevant regulations. Inadequate repairs can
lead to considerable hazards. For repair service, please contact
the service centre in your country (addresses on the back).
3Target group for this manual
This operating manual is for air conditioner users.
4Proper use
The Marine Climate System is an air conditioning system designed for use
on boats or yachts. It can cool down or warm up the interior of the boat or
yacht.
5Technical description
The Marine Climate Systems MCS5 and MCS15 are marine air conditioners
which can be used for variable air conditioning inside a boat or a yacht. They
can cool and warm the room.
The Marine Climate System consists mainly of the air conditioning unit and a
control panel. A refrigerant gas is circulating through the system which is seawater cooled.
5
EN
Operating elementsMCS5, MCS15
6Operating elements
6.1Control Panel
Key to fig. 1, page 2:
Item NameDescription
1Power ButtonPress and release to toggle between the On
and Off Modes.
2
Fan ButtonPress to advance through the available fan
settings. “1”(lowest) through “6” (highest) indicates Manual Fan Speeds.
The letter “a” indicates automatic fan operation
selected.
3Down ButtonPress and release to display the set point.
Press and hold the Down Button to decrease
the set point. Set point is decreased one
degree each time the button is depressed.
4Faceplate sensorThe faceplate sensor will read the room
temperature unless a remote air sensor is
installed.
5Up ButtonPress and release to display the set point.
Press and hold the Up Button to increase the
set point. Set point is increased one degree
each time the button is depressed.
6DisplayThe inside air temperature is displayed when
the control is on. The set point is displayed
when either Up or Down Button is pressed.
The display also indicates program information
and fault codes.
When the control resumes operation after a
power interruption all the display LEDs will turn
on for one second. This is normal operating
condition and is referred to as Power On
Reset.
7LED “Heat Mode”This LED is lit when
– the Heat Only Mode is selected
– or the unit is in a heating cycle.
6
EN
MCS5, MCS15Operating
Item NameDescription
8LED “Fan Indicator”This LED is lit when a Manual Fan Speed is
selected.
9LED “Cool Mode”This LED is lit when
– the Cool Only Mode is selected
– or when the unit is in a cooling cycle.
6.2Dual Button Functions
Up and Down Buttons
While in the On Mode: Simultaneously press the Up and Down Buttons
to display outside air temperature providing the optional outside air temperature sensor is installed.
While in the Program Mode: Simultaneously press the Up and Down
Buttons to set new program defaults.
Power and Down Buttons
While viewing the service fault history log: Simultaneously press the
Power and Down Buttons to clear the fault history log (see “Service History Log” on page 13).
While in the On Mode: Simultaneously press the Power and Down
Buttons to enter the Moisture Mode (see “Moisture Mode” on page 10).
7Operating
7.1Initial startup
NOTICE!
Do not turn the unit off and immediately turn it back on. Allow at
A
➤ Ensure seawater intake ball valve (seacock) is open.
➤ Make sure the control is powered OFF.
➤ Turn on air conditioner circuit breaker.
➤ If the seawater pump has its own circuit breaker, turn that on too.
least 30 s for refrigerant pressure equalization.
7
EN
OperatingMCS5, MCS15
➤ Press the Fan Button (fig. 1 2, page 2).
✓ This energizes the fan.
➤ Verify that the fan is running and that there is steady airflow out of the sup-
ply-air grille.
➤ Select a temperature set point lower than the current cabin temperature.
✓ This starts the compressor and seawater pump.
➤ Check for a steady solid stream of seawater from the overboard
discharge.
➤ If the unit does not appear to be operating properly, refer to trouble-
shooting guidelines (“Troubleshooting” on page 23).
7.2Overview
Power On
➤ Press the Power button (fig. 1 1, page 2) once to engage the system.
✓ The display indicates room temperature when the system is on and is
blank when the system is off.
Set Temperature
➤ Press the Up or Down button (fig. 1 3 and 4, page 2) to set the desired
room temperature.
The set point can be viewed by momentarily pressing and releasing the
Up or Down button.
Fan Speed
Fan-speed operation is automatic, allowing fan speed to decrease as the set
point temperature is approached in the Cool Mode. The fan operates at low
speed when set point is satisfied.
➤ Use the Fan button (fig. 1 2, page 2) to select manual fan speeds.
You can program the fan to run only when cooling or heating is required. Normally the automatic fan-speed operation is reversed in the Heating Mode,
however, the fan can be programmed to operate the same as in the Cooling
Mode.
8
EN
MCS5, MCS15Operating
Memory
The control’s nonvolatile memory requires no batteries or backup power.
When power is lost, the operating parameters are retained indefinitely. When
power is restored, the control resumes operating as last programmed.
7.3Modes of Operation
Off Mode
When the Marine Climate System is in the Off Mode, all control outputs are
turned off. Program parameters and user settings are saved in nonvolatile
memory.
On Mode
When the Marine Climate System is in the On Mode, power is supplied to the
appropriate outputs and the display indicates the current state of operation.
The operating and program parameters resume based on those stored the
last time the unit was operating.
Cool Mode
When Cool Mode is selected, the Cool Mode LED is lit and the cooling
systems are operated as required. When the temperature drops below the
set point, the system will not automatically switch to the Heat Mode.
Heat Mode
When the Heat Mode LED is lit, only the heating systems are selected and
operated as required. Should the temperature rise above the set point, the
system will not automatically switch to the Cool Mode.
Automatic Mode
Automatic Mode provides both heating and cooling as required. The Heat or
Cool LED will be lit according to the mode required.
Temperature in a given mode is maintained within 2 °F (1.1 °C) of set point,
however a 4 °F (2.2 °C) difference is required to allow the Marine Climate
System to change modes.
Once the mode changes temperature will be maintained within 2 °F (1.1 °C)
of set point.
9
EN
OperatingMCS5, MCS15
Manual Fan Mode
Manual Fan Mode allows to select the desired fan speed manually. When a
manual fan speed has been selected, the Fan LED will be lit. Manual Fan
Mode is sometimes preferred when room temperature is constantly changing
due to varying heat loads.
The fastest fan speed is represented by “6”, the slowest represented by “1”.
➤ Press and hold the Fan Button during normal operation to select one of
the six manual fan speeds available.
Circulation Mode
When the system is off at the control panel the fan can be used to only
circulate the air.
➤ Press and hold the Fan Button when the display is off until the desired
speed number appears in the window.
➤ Release the Fan Button
✓ The fan will run at the selected speed circulating the air without heating or
cooling.
➤ Press the Power Button once to cancel the Circulation Mode and enter the
On Mode.
Moisture Mode
➤ While in the On Mode simultaneously press the Power and Down Buttons.
✓ The first cycle will start in one minute.
➤ Press the Power Button to end the Moisture Mode.
✓ The “HU1” mnemonic code is displayed while in the Moisture Mode.
Program Mode
NOTE
The program mode can only be entered from the Off Mode.
I
The Program Mode is used to adjust the systems operating parameters to
suit the particular needs of individual users. The Program Mode is also used
to tailor the air conditioning system for the most efficient operation within an
installation.
10
EN
MCS5, MCS15Operating
Variables such as ducting, sensor location and system layout affect the
system operation. The Marine Climate System is shipped with factory default
settings which are stored in permanent memory and can be recalled at any
time.
7.4Operating the Marine Climate System
NOTICE!
Do not turn the unit off and immediately turn it back on. Allow at
A
I
➤ Press the Power Button (fig. 1 1, page 2) shortly to engage the system.
✓ The display indicates room temperature when the system is on and is
least 30 s for refrigerant pressure equalization.
NOTE
When powering on the Marine Climate System, press and immediately release the Power Button in order to not unintentionally en-
tering Program Mode.
If the Program Mode is entered unintentionally, any subsequent
presses of the Up or Down Button will change the P-1 parameter
setting, which can result in improper system operation.
blank when the system is off.
➤ Press the Down Button (fig. 1 3, page 2) or Up Button (fig. 1 5, page 2)
to choose the desired set point.
✓ The display indicates room temperature when the system is on and is
blank when the system is off.
✓ The thermostat is now set to maintain a constant temperature.
➤ Set the desired room temperature by pressing the Up or Down Button.
The set point can be viewed by momentarily pressing and releasing the
Up or Down Button.
The Marine Climate System has nonvolatile memory requiring no batteries or
backup power. When power is lost the operating parameters are retained indefinitely. When power is restored, the Marine Climate System resumes operating as last programmed.
Automatic fan speed operation allows fan speed to decrease as room temperature is approached in the Cool Mode. The fan will operate at low speed
when set point is satisfied.
Manual fan speeds can be selected with the Fan Button.
11
EN
OperatingMCS5, MCS15
The fan can be programmed to run only when cooling or heating is required.
Normally the automatic fan speed operation is reversed in the Heating Mode,
however, the fan can be programmed to operate the same as in the Cooling
Mode.
7.5Automated Factory Self Test Program
The Marine Climate System software provides a self test program to facilitate
factory testing of the entire air conditioning system. Once the self test program is activated, the test cycle will continue until the AC power is interrupted
or the Power Button is pressed once which returns the system to the Off
Mode.
➤ Activate the self test program by pressing the Power Button while turning
on the AC power.
➤ Release the Power Button while the display indicates “888” and all LEDs
are lit.
✓ The Marine Climate System is now in the self test program.
✓ “tSt” appears in the display while in the self test program.
Once activated the self test software will continuously execute the following
procedure:
Turn on in the Heat Mode and supply heating for 10 min.
Stop heating and run the fan only for 5 min.
Switch to Cool Mode and continue cooling for 10 min.
Stop cooling and run the fan only for 5 min.
Return to step one and continue until interrupted.
The self test program will continue until the power is interrupted or the test is
halted by pressing the Power Button once.
12
EN
MCS5, MCS15Operating
7.6Service Tools
Hour Meter
Total compressor cycle time is saved in EEPROM every six minutes of continuous compressor running time. Cycles less than six minutes are discarded
to conserve memory and allow the most flexible hour-meter possible.
To view the hour meter proceed as follows:
➤ Turn off the AC power.
➤ Press the Down Button and hold it.
➤ Restore AC power.
✓ After Power-On Reset is complete, the following appears in the display:
– “Hr” is displayed for one second.
– The display blanks out for one second then displays the thousands of
hours for three seconds.
– The display blanks out for one second then displays the hundreds
units for three seconds.
✓ The unit returns to the last operating state before power was removed.
Maximum recorded time is 65,536 hours, the meter stops and can only be
reset by a service technician.
Service History Log
The Marine Climate System records and remembers the eight most recent
faults. Each time a fault is detected, a one hour timer is started.
Three consecutive faults within that hour cause system shut down, lock out
and display the fault code. During that hour, to conserve memory, the same
recurring fault is not recorded in the service history log. Continuous operation
for one hour without the same recurring fault clears that fault counter but the
event remains in the service history log until overwritten. Should a different
fault be detected during the hour, it will be entered into the service history log.
The following events are entered into the service history log:
High Freon Pressure
Low Freon Pressure
Air Sensor Fault
13
EN
ProgrammingMCS5, MCS15
To view the service history log proceed as follows:
➤ Turn off the AC power.
➤ Press the Fan Button and hold it.
➤ Turn on the AC power.
➤ Once Power On Reset is completed (display indicates “888” and all LEDs
are lit) release the Fan Button.
✓ The display will flash the most recent fault detected, followed by the event
chronology number.
➤ To view other events detected press either the Up or Down Button.
➤ To clear the service history log simultaneously press the Power and Down
Buttons.
➤ To exit the service history log
– press either the Power, the Up or the Down Buttons or
– wait thirty seconds without pressing any button.
8Programming
8.1Entering Program Mode
➤ Press and hold the Power Button while in the Off Mode until the letter “P”
appears in the display.
✓ The characters “P1” followed by the parameter setting, appear in the
display.
✓ The Marine Climate System is now in the Program Mode.
NOTE
The Marine Climate System will exit the Program Mode and return
I
to the Off Mode if no programming is attempted for one minute.
8.2Changing Program Parameters
➤ Increment from one program parameter to the next by pressing the Fan
Button.
➤ Press the Up and Down Buttons to select the data or set the desired limits
for the parameter being programmed.
14
EN
MCS5, MCS15Programming
8.3Saving New Program Parameters
NOTE
Factory defaults shown in the “Programmable Parameters Table”
I
➤ Simultaneously press the Up and Down Buttons to save the new program
✓ This will set the new program defaults.
on page 16 may be reset manually (see “Restore Memorized Default Settings” on page 16).
parameters.
8.4Exiting the Program Mode
There are two methods to exit the Program Mode.
➤ Press the Power Button
✓ The Marine Climate Systemwill return to the Off Mode.
… or
➤ Do not press any buttons and do not attempt any program changes for
one minute.
✓ The Marine Climate Systemwill exit the Program Mode.
8.5Software Identification
The software version of the Marine Climate System is identified for one second prior to the exit from the Program Mode. The software identification number, e.g. (“A12”) will appear in the display for one second, then the Marine
Climate System will return to the Off Mode.
NOTE
Should there be any reason to contact Dometic about the system
I
or programming the Marine Climate System be sure to have the
software identification number and air conditioning unit serial number available. The serial number may be found on the typeplate.
15
EN
ProgrammingMCS5, MCS15
8.6Restore Memorized Default Settings
The memorized default settings can be restored as follows.
➤ Enter the Program Mode.
➤ Set P-17 to “rSt”.
➤ Exit the Program Mode.
✓ The software version number (e.g. “A12”) appears in the display.
✓ The memorized default settings are restored and the Marine Climate Sys-
tem returns to the Off Mode.
8.7Programmable Parameters
Programmable Parameters Table
Program
number
P-1Operating Mode00 = Automatic mode
P-2High Fan Speed Limit
P-3Low Fan Speed Limit
P-4Compressor Staging
P-5Temperature Sensor
P-6Failsafe30 = Minimum protection
P-7Low AC Voltage Shut-
P-8De-Icing Cycle1OFF
P-9High Water Tempera-
DescriptionDefault Range
1 = Cool only mode
2 = Heat only mode
9565 – 95
(arbitrary units)
5530 – 64
(arbitrary units)
Time Delay
Calibration
down (Volts)
ture Limit (°F)
155 – 135 s
Ambient
Temperature
115 V – OFF
220/230 V – OFF
OFF100 – 150
Ambient 10 °F
1 = Continuous, no display
2 = Continuous, with display
3 = Four failures, reset required
75 – 105
175 – 205
1 = On with 5 °F faceplate sensor
differential
2 = On with 7 °F faceplate sensor
differential
16
EN
MCS5, MCS15Programming
Program
number
P-10Display Brightness
P-11Display ºF or ºC FF = Fahrenheit displayed
P-12Cycle Pump With
P-13Reverse Fan Speeds
P-14Continuous Fan or
P-15Reverse Cycle Heating
P-16Fan Motor type selec-
P-17Reset Memorized
P-18Reserved for Future
P-19Reserved for Future
P-20Filter Threshold
P-21Current Filter Time
P-22Voltage Calibration
DescriptionDefault Range
94 = Low
Control
Compressor or
Continuous Pump
During Heating Mode
Cycle Fan with
Compressor
or Electric Heat Only
Option Installed (cooling only units)
tion Shaded Pole or
Split Capacitor.
Programming Defaults
Option
Option
(x10 hours)
(x10 hours)
(Volts)
OFFOFF = Cycle with compressor
rEFnor = Normal fan operation
conCYC = Cycle fan with compressor
nornor = Reverse cycle heating
SCSP = Shaded pole fan motor
norrSt = Reset defaults
––
––
0000 – 250
x10 Hours Using
Current Filter
AC Voltage–
13 = Maximum
C = Celsius displayed
On = Continuous pump
rEF = Reversed fan in heating
con = Continuous fan operation
ELE = Electric heater installed
SC = Split capacitor fan motor
nor = Normal
–
I
NOTE
Should any programming problems or confusion occur, reset the
Memorized Default Settings by entering the program mode and
setting P-17 to “rSt”.
If recent programming changes were made but not saved, the reset
will return to the last saved defaults, which could differ from the
factory defaults.
17
EN
ProgrammingMCS5, MCS15
P-1: Operating Mode
The following operating modes can be selected:
Automatic Mode by selecting “0”
Cool Only Mode by selecting “1”
Heat Only Mode by selecting “2”.
P-2: High Fan Limit
The upper fan speed limit can be adjusted for various motors. The high fan
limit is adjusted with the system installed and operating. The values range
from 65 through 95, arbitrary units.
➤ Use the Up and Down Buttons to select the desired speed.
– Increase the number for a higher fan speed.
– Decrease the number to lower the fan speed.
P-3: Low Fan Limit
The low fan limit determines the lowest output allowed for the low fan speed.
The values range from 30 through 64, arbitrary units.
➤ Use the Up and Down Buttons to select the low fan limit.
– Increase the number for a higher fan speed.
– Decrease the number to lower the fan speed.
NOTE
Once the high and low fan speed limits are set, the unit will auto-
I
P-4: Compressor Staging Time Delay
The compressor staging delay is provided for installations where more than
one system operates from the same power source. Setting different staging
delays allows compressors to start at different times when power is interrupted.
Units should be staged 5 s apart. The minimum delay is 5 s and the maximum is 135 s.
matically readjust the remaining speeds to produce three equally
spaced fan speeds in both Automatic and Manual Fan Modes.
18
EN
MCS5, MCS15Programming
P-5: Temperature Calibration
Use this feature to calibrate the ambient sensor.
➤ Select P-5.
✓ The ambient temperature appears in the display.
➤ Use the Up and Down Buttons to set the correct reading.
✓ The temperature in the display will increase or decrease as required.
P-6: Failsafe Level
There are four failsafe levels (see “Failsafe and Fault Handling Codes” on
page 26).
P-7: Low AC Voltage Shutdown
Use this feature to shut down the unit if the voltage drops to a dangerously
low level.
By default it is off, but it can be set from 175 – 205. This feature works immediately at start up, but while running will require a 5 min delay before displaying a fault to prevent nuisances.
The fault code is “LAC”.
P-8: De-Icing Cycle
The Marine Climate System is equipped with a de-icing cycle to prevent ice
build up on the evaporator coil during extended periods of cooling operation.
Installation variables such as grille sizes, length of ducting, insulation R factors and ambient temperatures determine the cooling run time required to
achieve set point. Customer usage may substantially increase run times by
operating the system with the hatches and doors open.
Programming an unrealistic set point (e.g. 65 °F/18.3 °C) and leaving the
salon door open will usually cause the evaporator to ice up on warm humid
days.
De-icing is accomplished by using an algorithm that closely monitors the
room air temperature in repeating 10 min intervals during a cooling cycle.
19
EN
ProgrammingMCS5, MCS15
The de-icing feature has two different, selectable behavior modes when it is
used in conjunction with the control panel’s built-in room air temperature sensor. It attempts to compensate for any temperature discrepancy that the faceplate sensor may experience. Although this discrepancy is not typical,
installation variables such as where the control panel is placed inside the
room (e.g. near an open door or in direct sunlight) can affect how accurately
it can read the actual room temperature.
By default with P-8 set to “1” (ON), the algorithm is applied assuming the
faceplate sensor may be reading the room temperature as much as 5 °F
(2.8 °C) greater than the actual evaporator temperature.
With programmable parameter P-8 set to “2”, the temperature differential that
is applied to the faceplate sensor reading is increased to 7 °F (3.9 °C) for
even more extreme installations. Setting P-8 to “2” should only be used if a
setting of “1” does not prevent evaporator ice from forming.
Alternately, the installation of an optional alternate air temperature sensor
(located in the return air path) will greatly increase the effectiveness of the
de-icing feature, and this option should be considered whenever the faceplate sensor cannot read the room temperature accurately.
P-9: High Water Temperature Limit
Use this feature to shut down the unit if the water in condenser coil rises to a
dangerously high level.
By default it is off, but it can be set between 100 and 150 °F.
The fault code is “PLF”.
P-10: Display Brightness Control
The display brightness can be adjusted from 4 (dimmest) to 13 (brightest).
P-11: Fahrenheit or Celsius Selection
The default setting is “°F”. Select “°C” for Celsius. Celsius readings are displayed in tenths, e.g. 22.2°.
P-12: Cycle Pump With Compressor
The pump can also be programmed to operate continuously or cycle on demand.
➤ To program continuous operation select “On”.
20
EN
MCS5, MCS15Programming
P-13: Reverse Automatic Fan Speeds During Heating
The automatic fan speeds can be reversed during Heating Mode. The fan will
speed up as the set point is approached. Lowering the fan speed when the
cabin is cold increases head pressure and helps raise supply temperature.
The fan switches to low speed when the set point is satisfied and the compressor cycles off.
Normal fan operation is represented by “nor”.
➤ To reverse fan speeds in heating, select “rEF”.
P-14: Cycle Fan with Compressor
The fan can be programmed to run continuously when the system is on or
can be allowed to cycle with the compressor.
The default is “con”, continuous fan.
➤ To cycle the fan with the compressor select “CYC”.
NOTE
When used with optional electric heat the fan will remain on 4 min
I
P-15: Reverse Cycle or Electric Heat
after the heater cycles off.
➤ Do not change the default parameter.
P-16: Fan Motor Selection
NOTE
The unit’s High Velocity (HV) blower has a Split Capacitor (SC) fan
I
➤ Select “SC”.
➤ Save this change as a new default by simultaneously pressing and releas-
➤ Make note of new default in the Programmable Parameters table for
motor. For this motor this parameter must be changed from “SP” to
“SC” in order for the blower to work at peak efficiency.
ing the Up and Down Buttons prior to exiting the program mode.
future reference and servicing.
21
EN
ProgrammingMCS5, MCS15
P-17: Reset Memorized Defaults
The default programming parameters can be reset as follows:
➤ Select “rSt”.
✓ This restores the programmable parameters to the default values.
The default parameters listed in the “Programmable Parameters Table” on
page 16 may be altered by the installing dealer or end user. Once new defaults are entered and memorized the factory defaults will be overwritten. The
original factory program parameters as listed in the table may be restored
manually.
P-18, P-19: Reserved for Future Option
P-20: Filter Threshold
This feature is to remind you to change the air filter on a unit. The units are
x10 hours.
By default it is off, which is designated with a “00”, but it can be set between
100 and 2500 hours. After the unit has reached its threshold time, it will display a “FIL” remind 1 s every 10 s.
P-21: Current Filter Time
This feature is used to display the amount of time the current filter has been
on the unit. The units are x10 hours.
➤ In order to reset this parameter, simply press the Up or Down Button.
P-22: Voltage Calibration
This feature displays the voltage reading as seen by the display. Calibrating
this parameter will provide a more accurate voltage when calculating low
voltage for P-7. It will display a live reading of the voltage.
➤ Manipulate the reading by pressing the Up or Down Button.
22
EN
MCS5, MCS15Troubleshooting
9Troubleshooting
9.1General Troubleshooting
ProblemPossible ReasonSolution
System will not start.Air conditioning unit circuit
breaker is off.
Control is not turned on.Turn control on.
Wrong wiring at terminal strip.Check wiring diagram and correct
Push-on butt connectors became
disconnected during installation.
Input line voltage is insufficient.Check power source (shore/gen-
Fan is not running.–See corresponding section in
No cooling or heating. Temperature set point is satisfied. Lower or raise set point.
Obstructed seawater flow.Clean seawater strainer.
Seawater pump may be airlocked.
Loss refrigerant gas.Check air conditioning unit for
Seawater temperature too high
for cooling or too low for heating.
Turn circuit breaker on at ship’s
panel.
if necessary.
Disconnect power supply and
open electric box.
Check wiring diagram, correct if
necessary.
erator) for proper voltage.
Check wiring and terminals for
proper sizes and connections.
Verify with a volt-meter that the
power at the unit is the same as
the power source.
“Control Panel Troubleshooting”
on page 27.
Check for obstructions at speed
scoop thru-hull inlet.
Check for a good steady flow
from the overboard discharge.
Remove hose from pump discharge to purge air from line.
refrigerant oil leakage.
Call service technician.
Seawater temperature will
directly affect air conditioning
unit’s efficiency.
This air conditioning unit can
effectively cool your boat in water
temperature up to 90 °F (32.2 °C)
and heat in water temperatures
as low as 40 °F (4.4 °C).
23
EN
TroubleshootingMCS 5, MCS15
ProblemPossible ReasonSolution
No cooling or heating
(contn’d).
No coolingControl panel may not be in “cool”
No heating.Unit is “cool only”, or if reverse
Fan coil is iced (in cooling).See below.
Fan is not running.See corresponding section in
“Control Panel Troubleshooting”
on page 27.
Seawater plumbing is air-locked. Ensure that seawater plumbing is
installed per the guidelines in the
Installation Manual.
The Marine Climate System is
programmed for Cool or Heat
only, or mechanical control thermostat is rotated too far towards
either Cooler or Warmer setting.
High pressure switch open (in
cooling) due to improper seawater flow.
Strainer or intake may be
plugged, seacock may be closed.
High pressure switch open (in
heating) due to improper airflow.
High-pressure switch is open in
heating mode.
Compressor’s thermal overload is
open due to either of the above
reasons.
position.
Coil iced. See below.
cycle, reversing valve may be
stuck.
Set P1 to the desired value or
rotate the mechanical control
thermostat.
Check seawater hose for kinks or
collapses.
Verify pump operation.
Check pump circuit breaker if
applicable.
Remove any obstructions in
return air stream.
Clean return air filter and grille.
Check for crushed or restricted
ducting (ducting must be as
straight, smooth and taut as
possible).
System may cycle on high-pressure if seawater temperature is
above 55 °F (12.8 °C).
Compressor needs to cool down.
Turn system off for a while (it may
take up to three hours to reset
thermal overload).
Reset control panel.
Tap reversing valve lightly with
rubber mallet while unit is in heat
mode.
Call for service if that does not
correct the problem.
24
EN
MCS5, MCS15Troubleshooting
ProblemPossible ReasonSolution
Low airflow.Airflow is blocked.Remove any obstructions in
Fan Coil is iced.See below.
Fan coil is iced.Thermostat set point is too low.Check setting on control panel.
Improper airflow.Remove any obstructions in
Supply air is short-cycling.Redirect supply air so that is not
Humidity level too high.Close hatches and doors.
When all else fails.Switch air conditioning unit to
Water coil is iced in
the Heating Mode.
System runs
continuously.
Seawater temperature is below
40 °F (4.4 °C).
Set point temperature is improperly set: too low for cooling or too
high for heating.
Porthole or hatches open.Close all port holes and hatches.
return air stream.
Clean return air filter and grille.
Check for crushed or restricted
ducting, ducting must be as
straight, smooth and taut as possible.
If setting is extreme for conditions, raise set point until unit
cycles off to give coil time to
thaw.
return air stream.
Clean return air filter and grille.
Check for crushed or restricted
ducting.
Ducting run must be as straight
as possible; remove any excess
ducting.
See the “Control Panel Troubleshooting” on page 27 for reprogramming options.
blowing into the return air stream.
Seal any air leaks on duct.
heat until ice melts or use hair
dryer to melt.
Shut down system to prevent
damage to condenser.
Allow coil to defrost.
Raise or lower set point.
25
EN
TroubleshootingMCS 5, MCS15
ProblemPossible ReasonSolution
System runs
continuously
(contn’d).
Short cycling
compressor
Seawater temperature too high
for cooling or to low for heating.
Improper air sensor location.See corresponding section in
Cold supply air returning directly
to return air grille.
Seawater temperature will
directly affect the air conditioning
unit’s efficiency.
This air conditioning unit can
effectively cool your boat in water
temperatures as low as 40 °F
(4.4 °C) and heat (if reverse cycle
option is installed) in water up to
90 °F (32.2 °C).
“Control Panel Troubleshooting”
on page 27.
Redirect supply air so that it is not
directed into the return air
stream.
9.2Failsafe and Fault Handling Codes
When a fault is detected the Marine Climate System will display one of the
following Mnemonic fault codes:
“ASF”: Indicates Air Sensor Fault.
“FIL”: Indicates filter needs replacing (if this option is enabled).
“HPF”: Indicates High Freon Pressure.
“LAC”: Indicates Low AC voltage (if this option is enabled).
“LPF”: Indicates Low Freon Pressure (Not applicable to MCS models).
“PLF”: Indicates high water temperature in condensing coil (if this option
is enabled).
NOTE
“HPF” is not indicated and does not cause lockout in Heat Mode.
I
“LPF” has a 10 min shut down delay.
Failsafe Level 0
Only “ASF” detected and displayed.
The Marine Climate System will shut down and will not restart until the fault
is repaired.
Once the fault is repaired the Marine Climate System will restart.
26
EN
MCS5, MCS15Troubleshooting
Failsafe Level 1
All actions in level 0 plus all other faults detected but not indicated.
The system shuts down for 2 min or until the fault is cleared, whatever is
longer.
The system will restart if the fault is cleared.
Failsafe Level 2
All actions same as level 0 and 1. Faults are indicated.
The system shuts down for 2 min or until the fault is cleared, whatever is
longer.
Failsafe Level 3
All actions the same as level 0, 1 and 2.
The system shuts down for 2 min or until the fault is cleared, whatever is
longer.
The system will lockout after four consecutive “HPF” or “LPF” faults.
To clear the lockout:
➤ Pressing the Power Button once to Off Mode.
➤ Pressing the Power Button again to On Mode.
9.3Control Panel Troubleshooting
ProblemPossible ReasonSolution
Control panel is not lit. 8-pin display cable plugs are not
making contact (unplugged, dirty,
bent, or broken pins).
Fan is not running or
runs continuously.
Fan is not running but
the compressor is.
The Marine Climate System is
programmed for either fan cycling
with compressor or continuous
fan operation.
Failed triac on control panel
circuit board.
Power off at the circuit breaker.
Remove connector and inspect.
If damaged, replace connector or
entire display cable.
Reprogram parameter P-14.
Note: After the compressor
cycles off, the fan will continue to
run for 2 min in Cool Only Mode
and 4 min in Heat Only Mode
regardless of parameter setting.
Send for repair or call local
service technician.
27
EN
TroubleshootingMCS 5, MCS15
ProblemPossible ReasonSolution
Fan runs continuously although it is set
to cycle with compressor.
No cooling or heating. The Marine Climate System is
No heat.The Marine Climate System may
Unit switches to heat
while in Cool Mode.
Fan coil is iced.Improper airflow.See corresponding section in
System runs
continuously.
“ASF” (Air Sensor
Failure) is displayed.
“FIL” (Filter Replacement) is flashing.
Failed triac on control panel
circuit board.
programmed for heat or cool only.
“HPF” or “LPF” is displayed.See below.
be set to Electric Heat, not
Reverse Cycle.
De-icing feature enabled due to
coil icing up.
Improper air sensor location.Verify display head location.
Unrealistic set point.Adjust set point until unit cycles
Indicates failed face plate air
sensor, alternate air sensor or
display cable.
Damaged jack/socket in display
head or on circuit board.
Filter needs replacement.Replace filter.
Send for repair or call local
service technician.
Reprogram parameter P-1.
Reprogram parameter P-15.
Reprogram parameter P-8
“General Troubleshooting” on
page 23, before reprogramming
the Marine Climate System.
Reprogram parameter P-8 to
enable de-icing.
If de-icing cycle does not melt ice,
switch air conditioning unit to
heat until ice melts or use hair
dryer to melt ice.
If problem persists, reprogram
Low Fan Speed Limit for maximum value: Set P-3 to 64.
Install alternate air sensor if
necessary.
off.
Unplug alternate air sensor if
installed or plug in alternate air
sensor if not installed.
Try another display cable.
Visually check to see that pins
inside socket are not bent or
corroded.
Repair or replace display or
circuit board if needed.
Reset P-21 to “00”.
28
EN
MCS5, MCS15Troubleshooting
ProblemPossible ReasonSolution
“HPF” (High Freon
Pressure) is
displayed.
“LAC” (Low AC
Voltage) is displayed.
“LPF” (Low Freon
Pressure) is
displayed.
“PLF” (Low Pump
Flow) is displayed.
High-pressure switch is open (in
cooling) due to improper seawater flow.
Strainer or intake may be
plugged, seacock may be closed.
High-pressure switch open (in
heating) due to improper airflow.
Supply voltage is too low.Verify power to unit with multi-
Voltage is improperly calibrated.Verify that P-22 matches voltage
Low-pressure switch is open due
to low seawater and/or low return
air temperatures.
Low pressure switch is open due
to loss of refrigerant.
Condenser coil is too hot.Verify that unit is getting water
Thermistor is damaged.Unplug water sensor if installed.
Damaged jack/socket on circuit
board.
Check seawater hose for kinks or
collapses.
Verify pump operation.
Check pump circuit breaker if
applicable.
Remove obstructions in return air
stream.
Clean air filter and grille.
Check for crushed or restricted
ducting (ducting must be as
straight, smooth and taut as
possible).
If problem persists,
– reprogram Low Fan Speed
Limit for maximum value: Set
P-3 to “64”
– set the reverse fan speeds dur-
ing Heating Mode parameter
P-13 to “rEF”, or manually set
fan speed to high
meter.
reading to unit with a multimeter.
Try restarting the air conditioning
unit, the optional low pressure
switch has a ten minute shutdown time delay that may be in
affect.
Check air conditioning unit for
refrigerant oil leakage.
Call service technician.
flow, and that condenser is not
fouled.
Try another if it is available.
Visually check to see that pins
inside socket are not bent or corroded.
Repair or replace circuit board if
needed.
29
EN
MaintenanceMCS5, MCS15
10Maintenance
10.1Reversing Valve
The reversing valve must be energized periodically to keep the internal parts
moving freely.
➤ Switch the air conditioner unit into heat for a few seconds once a month.
10.2Seawater Strainer
➤ Ensure that your pump receives adequate seawater flow by regularly
cleaning the strainer basket.
➤ Periodically check the overboard discharge for a steady stream of water.
➤ Check seawater intake speed scoop for obstructions.
➤ Make sure hoses are not looped, kinked or crushed.
10.3Condenser Coil Cleaning
NOTE
For the purpose of protecting the environment, dispose of any con-
I
taminated acid solutions in accordance with federal, state and/or
local regulations.
Coils can become fouled over a period of time due to marine growth or scale
build-up. This both obstructs water flow and prohibits proper heat transfer.
➤ Turn off the system at the circuit breaker on the ship’s panel.
➤ Disconnect the inlet and outlet connections of the condenser coil.
➤ Place a strainer or piece of screen over the inlet of the pump.
➤ Submerse the pump into a container filled with a 5 % solution of muriatic
or hydrochloric acid and fresh water or use a premixed over-the-counter
solution.
CAUTION!
Avoid spilling or splashing the solution.
!
Follow all warnings and recommendations given by the manufacturer of any acids or premixed solutions.
30
Loading...
+ 382 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.