Det-Tronics R7495D User Manual

Instructions 95-8331-02
UVIR Flame Detection System R7495 Dual Channel Controller C7052J Detector
Detector Electronics Corporation 6901 West 110th Street •Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.3473 •Fax: 952.829.8750
4/03 95-8331-02
APPLICATION ................................................................1
FEATURES .....................................................................2
SYSTEM DESCRIPTION................................................2
Detector....................................................................2
Controller..................................................................3
SPECIFICATIONS ..........................................................5
OPTIONS ........................................................................6
RESPONSE CHARACTERISTICS .................................6
APPLICATION GUIDELINES..........................................7
INSTALLATION...............................................................9
Detector Positioning .................................................9
Wiring Requirements..............................................10
Detector Mounting and Wiring Procedure ..............10
CONTROLLER INSTALLATION AND WIRING ............15
Electrical Connections............................................15
PROGRAMMING THE CONTROLLER ........................16
TYPICAL SYSTEM APPLICATION...............................19
STARTUP PROCEDURE .............................................20
INITIAL AND PERIODIC CHECKOUT PROCEDURE..21
STAR Programming Checkout Procedure .............21
MAINTENANCE ............................................................21
Sensor Module Replacement Procedure ...............22
TROUBLESHOOTING ..................................................22
DEVICE REPAIR AND RETURN..................................23
ENGINEERING SPECIFICATIONS ..............................23
ORDERING INFORMATION.........................................24
Accessories ............................................................24
Recommended Spare Parts ...................................24
APPLICATION ASSISTANCE.......................................24
List of Illustrations
Figure 1 Detector Sensitivity Range .........................2
Figure 2 o
i
Function within the Detector ..................3
Figure 3 Controller Front Panel ................................3
Figure 4 Cone of Vision ............................................5
Figure 5 Detector Dimensions in Inches
(Millimeters) ................................................6
Figure 6 Controller Dimensions in Inches
(Millimeters) ................................................7
Figure 7 Q9001G Swivel Mounting Bracket
Dimensions.................................................7
Figure 8 Mounting Base Dimensions........................7
Figure 9 Blackbody Spectral Emittance....................8
Figure 10 Front View of the C7052 Detector ............11
Figure 11 Vertical Detector Mounting .......................11
Figure 12 C7052J Detector Part Identification..........12
Figure 13 Detector Terminal Block ...........................12
Figure 14 Detector Connection.................................13
Figure 15 Cover Locking Assembly ..........................13
Figure 16 Jumper Plug .............................................14
Figure 17 IR Module with Four-Wire Connector .......14
Figure 18 Q4004 Mounting Cage Dimensions
in Inches (Millimeters)...............................15
Figure 19 Controller Terminal Configuration.............16
Figure 20 Rocker Switch Setting ..............................17
Figure 21 Graphic Representation of STAR Logic
(Typical Settings Shown)..........................18
Figure 22 Multiplication Factors................................19
Figure 23 System Layout Chart ................................20
Figure 24 Normally Energized Load Circuit
Connected to Alarm Relay........................21
Figure 25 Normally Unenergized Load Circuit
Connected to Fire Relay...........................21
List of Tables
Table 1 C7052J Typical Response Distances.........8
Table 2 Radiation Absorbing Gases and Vapors ....9
Table 3 Troubleshooting Guide .............................23
Table of Contents
2
NOTE
Not compliant to FM 3260 (2000).
APPLICATION
The R7495D/C7052J UV/IR Flame Detection System is designed to provide continuous and automated fire pro­tection in applications where the use of ultraviolet (UV) or infrared (IR) detectors alone can result in unwanted (false) alarms. The R7495D/C7052J system features a flame detector that uses both a UV and a single fre­quency IR sensing device mounted side-by-side on a junction box assembly.
When used alone, a UV detector can respond to sources of radiation besides fire, such as lightning, x­rays or arc welding. A UV detector does not respond to the radiation emitted by flickering hot objects. Likewise, an IR detector can respond to infrared radiation sources besides hydrocarbon fires, such as flickering hot objects. An IR detector does not respond to radiation from lightning, x-rays or arc welding. Since both UV and IR sensors respond to hydrocarbon fires but have virtually no false alarm sources in common, the R7495D/C7052J UV/IR system provides reliable flame detection while being virtually immune to false alarms.
The junction box contains a power supply and signal processing circuitry for the sensors. A fire signal is gen­erated in the detector junction box and sent to the con­troller only when a fire is simultaneously detected by both the UV and IR sensors. Since the two detecting elements independently monitor different portions of the radiation spectrum and have virtually no sources of out­put actuation in common besides fire, a high degree of false alarm immunity is achieved. The controller contin­uously monitors up to two UV/IR detectors and ener­gizes the appropriate output relays in response to a fire
signal from the detectors. Five relays are provided in the controller: two instant (alarm) relays, two delayed (fire) relays, and a system fault relay.
Typical applications include:
— Transport loading terminals — Offshore drilling and production platforms — Tank farms — Refineries — Butane and propane loading and storage — Pipeline compressor stations — Turbine enclosures — Aircraft Hangars — Paint Spray Booths — Chemical and petrochemical production
INSTRUCTIONS
UV/IR Flame Detection System
R7495D Dual Channel Controller
C7052J Detector
©Detector Electronics Corporation 2003 4/03 95-8331-02
®
*o
i
is Detector Electronics' Trademark for its patented Optical Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent 1,534,969, Canada Patent 1,059,598.
DET-TRONICS
FEATURES
• Controller continuously monitors up to two UV/IR detectors.
• Ignores false alarm sources such as arc welding, x­rays, gamma radiation and radiation from flickering hot objects.
• Fast response - typically 1 to 5 seconds for an intense hydrocarbon fire.
• Each detector can independently register an alarm.
• Front panel LEDs indicate fire response and system fault conditions.
• Microprocessor control.
• All automatic test functions performed with the system on line.
• Automatic Optical Integrity (oi) for both UV and IR sensors.
• Field adjustable sensitivity and time delay.
• Explosion-proof (flame-proof) detector housing.
• FM approved, CSA and BASEEFA/CENELEC certified.
• Relay outputs can be set for latching or non-latching response.
SYSTEM DESCRIPTION
DETECTOR
The C7052J UV/IR Flame Detector is an explosion-proof device that consists of a UV sensor and an IR sensor mounted side-by-side on a junction box. This mounting arrangement allows both sensors to monitor the same hazardous location with an 80 degree cone of vision. Either one or two C7052J Detectors can be connected to one R7495D Controller.
The UV sensor responds to high energy radiation with wavelengths from 0.185 to 0.245 microns (1850 to 2450 angstroms). See Figure 1. It detects radiation from sources such as fire, arc welding, lightning, x-rays and gamma rays. However, it is not sensitive to radiation from the sun or radiation from flickering hot objects (blackbodies).
The IR sensor is sensitive to IR radiation over the range of 4.2 to 4.7 microns. See Figure 1. It is not sensitive to radiation from the sun, lightning, x-rays, gamma rays, or arc welding. However, it will respond to fire and flicker­ing blackbody (heat) radiation sources. IR radiation is generated by a hydrocarbon flame, which reaches the detector in pulsations or “flicker.” These pulsations are present in all flames and are created by turbulent mix­ing of fuel with air. For this reason, electronic circuitry in the detector monitors the output of the IR sensing ele­ment for the appropriate amplitude and a flicker fre­quency between 1 and 16 cycles per second. If both the radiation and flicker requirements are met, a fire sig­nal is generated. This dual criteria for the IR detector results in increased reliability. However, since the IR detector responds only to hydrocarbon fires, the UV/IR detector cannot respond to non-hydrocarbon fires such as burning hydrogen, ammonia or metal.
The detector junction box contains a +290 vdc power supply for the UV sensor as well as circuitry to process signals from both sensors. When both sensors detect a fire, the IR sensor activates the circuitry in the junction box to allow the signal from the UV sensor to be sent to the controller. By using both a UV and an IR sensor, the C7052J is able to discriminate virtually all false alarm sources from a true hydrocarbon fire.
oi Feature
Both sensors are equipped with the automatic Optical Integrity (oi) test feature. This patented system assures proper operation of the detector by checking the clean­liness of the optical surfaces, sensitivity of the sensors, and proper functioning of the electronic components of the detector once every minute. If a problem should occur, it is quickly detected. The oi test is accom­plished without the use of an external UV or IR source. To minimize the possibility of nuisance fault signals, the detector must fail the automatic oi test three consecu­tive times for an oi fault signal to be generated.
The oi test is initiated by a signal from the controller, which causes actuation of the oi test lamps. A calibrat­ed low level test beam is generated by the oi test lamps, as shown in Figure 2. Although the test lamps are mounted in the same enclosure with the sensor, an
4
Figure 1—Detector Sensitivity Range
5.04.03.02.01.51.00.90.80.70.60.50.40.30.20.1
ATMOSPHERIC
TRANSMISSION
WAVELENGTH (MICRONS)
SOLAR RADIATION REACHING THE EARTH
INFRARED
SENSOR
RESPONSE
VISIBLE INFRARED
ULTRAVIOLET
SENSOR
RESPONSE
ULTRAVIOLET
100
75 50
25
0
A1070
optical shield prevents the test beam from reaching the sensor directly. The test beam travels out through the viewing window, where it encounters the reflective o
i
ring and is directed back through the window to the sensor. Electronic circuitry in the detector then evalu­ates the return signal from the sensor and generates the appropriate output response. Since the test beam must pass through the same portion of the viewing window as radiation produced by a fire, this test of the ability of the detector to “see” a flame has a high degree of reliability.
Enclosure
The C7052J features an explosion-proof, dust-tight, and water-tight (NEMA 4/IP66) housing that is designed for installation in hazardous locations in both indoor and outdoor environments. The enclosure is FM approved, CSA certified, and BASEEFA/ CENELEC approved.
CONTROLLER
The R7495D is designed for use with 24 volt dc power supplies, but will operate from any direct current supply
between 18 and 32 volts. The unit will tolerate tran­sients such as those that can occur when fully dis­charged batteries are placed on charge. When power is present at the R7495D Controller, it is indicated by a continuously energized green LED. All other lights and displays on the R7495D front panel are normally off, but may be periodically checked for operation by pressing the RESET/LAMP TEST button located directly below the POWER light as illustrated in Figure 3.
With power applied and the TEST/NORM toggle switch in the normal mode, the R7495D Controller continuously cycles through the Automatic Optical Integrity test (see the “oi Feature” section), checking each detector and its wiring. At the same time, it monitors the system for any status changes, such as a fault or a “fire” signal from one of the detectors, or a change in the setting of the TEST/NORM toggle switch. If a status change occurs, the controller will respond accordingly by indi­cating the change on the front panel and generating the appropriate output.
Front Panel
The front panel of the R7495D provides a switch for selecting mode of operation and initiating test functions. It also provides LEDs for indicating system status. Figure 3 illustrates the front panel of the controller.
1. A DETECTOR LED for each channel provides an immediate visual indication that a fire has been detected. The LED blinks slowly (once per second) if the fire intensity does not exceed the fire thresh­old and blinks rapidly if a fire output is generated. Steady illumination indicates that the fire intensity has returned below the alarm threshold (i.e., fire has been extinguished).
UV DETECTOR
IR DETECTOR
UV TEST LAMP
OPTICAL SHIELD
VIEWING WINDOW
SNAP-IN
o
i
RING
IR TEST LAMP (2)
IR SENSING ELEMENT
SNAP-IN
o
i
RING
OPTICAL FILTER
VIEWING WINDOW
UV SENSOR
B1048
5 95-8331
Figure 2—oiFunction within the Detector
Figure 3—Controller Front Panel
A1700
2. The FIRE ZONE LEDs signal actuation of the corre­sponding fire (timed) relay outputs.
3. Illumination of the ALARM LED indicates actuation of an alarm (instant) relay output.
4. Illumination of the FAULT LED indicates a system malfunction when in the the Normal mode, or that the controller is in the Reset or Test mode.
5. The POWER LED is illuminated when power is applied to the controller.
6. Pressing the RESET/LAMP TEST button illuminates all LEDs for testing and resets the system. While the button is depressed, the outputs are disabled. This will cause a fault condition until the controller restarts (approximately two seconds).
7. The TEST/NORM toggle switch selects Test or Normal mode.
Normal Mode
Under normal operating conditions, the POWER LED is on and all others are off. The alarm and fire relays are nor­mally de-energized and the fault relay is normally ener­gized. The LEDs can be tested periodically by pressing the LAMP TEST pushbutton. It is not necessary for the controller to be in the TEST mode when this test is being performed, however, depressing the LAMP TEST push­button will disable the outputs and reset the operating program. After the pushbutton is released, a fault condi­tion remains until reset is complete and the controller restarts (i.e., the fault relay drops out for 2 seconds).
Resetting The Controller
Any existing system status indications and the controller outputs are returned to normal operating condition with all LEDs except the POWER LED off, and all relays except the Fault relay de-energized (after the radiation source is removed or the fault is corrected) in one of the following ways:
1. Depress the RESET/LAMP TEST button.
2. Place the mode switch in the TEST position, then return it to NORMAL.
3. Close the optional remote reset switch connected between terminals 31 and 32.
Fire Response
Four output relays are provided for controlling fire response devices. Two relays are designated as
“Alarm” and two as “Fire.” Alarm relays 1 and 2 are directly controlled by detectors 1 and 2, respectively. When either detector generates a fire signal that lasts for two consecutive gates (regardless of the number of gates that the controller has been programmed for):
— The ALARM LED flashes (approximately four times
per second).
— The corresponding alarm (instant) relay is ener-
gized.
— The corresponding DETECTOR LED flashes to iden-
tify the detector responding to flame.
When the signal from the detector meets all the pro­grammed STAR logic requirements for a fire output, the appropriate fire relay(s) will also be actuated.
The grouping of the detectors into Individual or Combined fire zones determines whether the fire relays are actuated individually or together. When the con­troller is programmed for Individual fire zone operation, each detector controls its corresponding fire relay. When the controller is programmed for Combined fire zone operation, a fire at either detector will cause both fire relays to be energized simultaneously.
The FIRE ZONE LEDs flash to signal actuation of their corresponding fire relay.
If the controller is programmed for latching outputs: — The DETECTOR LEDs flash while the signal thresh-
old requirements are met (fire being detected) and are on steady after the fire is no longer detected.
— The relays remain energized until the fire is extin-
guished and the controller is reset.
If the controller is programmed for non-latching opera­tion:
— The LEDs flash and the output relays are actuated
only while the fire signal exceeds the minimum threshold requirements (2 consecutive gates for alarm, the programmed number of gates for fire out­put). When the threshold requirements are no longer met, the LEDs are on steady until the con­troller is reset.
Fault Detection
The Automatic oi feature continuously checks the cleanliness of the detector viewing windows and the sensitivity of the sensors. In addition, automatic diag­nostic circuitry in the controller monitors the system for
6
various faults that could prevent the system from responding in the event of a fire. If a fault is detected:
1. The normally energized fault relay is de-energized. This relay can be used to activate an external fault annunciation device or to remove power from a haz­ardous process.
2. The FAULT LED on the front panel of the controller is illuminated to provide a visual indication that a problem has occurred.
Programming Switches
Rocker switches that are located on the side of the con­troller are used for selecting various options available with the R7495D. These programming options are listed below and must be set prior to system operation. Refer to the “Programming the Controller” section of this man­ual for detailed instructions.
1. Number of detectors connected to the controller (one or two).
2. Gate Length, Consecutive Gate Selection, Count Selection (system sensitivity and time delay).
3. Fire zone grouping.
4. Latching/non-latching outputs.
Field Wiring Connector
The R7495D Controller is furnished with a field wiring connector that incorporates pressure type screw termi­nals for connecting the external wiring. The use of a Q4004 Mounting Cage is recommended for mounting the controller. The controller is designed for installation in a non-hazardous area.
SPECIFICATIONS
SPECTRAL SENSITIVITY RANGE—
UV: The UV sensor responds to radiation over the range
of 0.185 to 0.245 microns (1850 to 2450 angstroms).
IR: The single frequency infrared sensor responds to
radiation between 4.2 and 4.7 microns.
Figure1 illustrates the spectral response range of the UV and IR sensors.
CONE OF VISION—
The C7052J has a 80 degree cone of vision with the highest sensitivity lying along its central axis. See Figure 4.
FLAME SENSITIVITY—
The C7052J5 with a part number DE5500 IR Sensor Module (the sensor part number is printed on its side) detects a 1 foot by 1 foot gasoline fire at 50 feet, a 2 foot by 2 foot JP4 fire at 100 feet, and a 10 foot by 10 foot JP4 fire at 150 feet.
The C7052J with a part number DE3895 IR Sensor Module (the sensor part number is printed on its side) detects a 1 foot by 1 foot gasoline fire at 35 to 45 feet, a 2 foot by 2 foot JP4 fire at 100 feet, and a 10 foot by 10 foot JP4 fire at 150 feet.
RESPONSE TIME—
The response time of the detector is a function of fuel, fire size, distance, orientation of the fire source and the field programmable controller settings. With typical controller settings of 0.25 second gate length, 4 counts per gate, and 4 consecutive gates, the system will respond to an intense fire signal in less than 2 seconds.
Response times of less than 1 second to an intense fire signal can be achieved by setting the controller for a
0.125 second gate length, 2 counts per gate, and 3 consecutive gates.
INPUT VOLTAGE—
Controller and Detector 24 vdc nominal (18 vdc minimum, 32 vdc maximum) with less than 1 volt of ripple.
POWER CONSUMPTION—
Controller: 1.0 watt typical, 3.5 watts maximum. Detector: 1.0 watt typical, 3.5 watts maximum.
RELAY CONTACT RATING—
Five form C (NO/NC) relay outputs, rated 3 amperes at up to 30 vdc or up to 250 vac. Dry nitrogen gas is
15°
30°
45°
15°
30°
45°
A1461
100
90
80
70
60
50
40
30
20
10
DETECTION
DISTANCE
(PERCENT)
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A 
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF 
INCIDENCE DECREASES.
7 95-8331
Figure 4—Cone of Vision
sealed inside the relays to eliminate arcing and corro­sion, thereby increasing reliability.
CONTROLLER TEMPERATURE RANGE—
Operating: +32°F to +140°F (0°C to +60°C). Storage: –40°F to +140°F (–40°C to +60°C).
DETECTOR TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C). Storage: –67°F to +185°F (–55°C to +85°C).
DETECTOR HUMIDITY RANGE—
0 to 95% relative humidity.
DETECTOR ENCLOSURE MATERIAL—
Copper-free aluminum (red) or 316 stainless steel, with optional stainless steel mounting bracket.
DETECTOR ENCLOSURE RATINGS—
FM approved and CSA certified for Class I, Groups C and D, and Class II, Groups E, F, and G hazardous locations. NEMA 4 enclosure. BASEEFA/CENELEC certified flame-proof for EExd IIB T6; IP66 enclosure rating.
RFI/EMI HARDENED—
Detector designed to meet RFI and EMI immunity requirements of MIL STD 461, 462, and 463.
DIMENSIONS—
See Figures 5, 6, 7, and 8.
SHIPPING WEIGHT—
R7495D Controller
4.4 pounds (2.0 kilograms)
C7052J Detector
Aluminum: 6.0 pounds (2.7 kilograms). Stainless Steel: 14.0 pounds (6.4 kilograms).
OPTIONS
Power supplies are available for operating the R7495D and C7052J from line (mains) voltage.
The Q4004 Mounting Cage is designed for holding up to eight micro-module devices and is recommended for ease of installation and servicing. Mounting cages that hold fewer modules are also available. See Figure 18. Optional filler panels (part number 002188-001) can be used to cover unused sections of the mounting cage.
Locking devices must be used on detector housings to comply with applicable regulations in some areas (BASEEFA/CENELEC).
Q1113 Air Shields for areas where there is an abnormal­ly high level of airborne contaminants. Two Q1113 Air Shields are required for each detector.
Q9001G Swivel Assembly (part number 004404-001) for easy mounting and sighting of detector assemblies.
T2P/Q1201 Laser with holder for sighting and identifying the detector cone of vision.
RESPONSE CHARACTERISTICS
The response time of the detector is a function of fuel, fire size, distance, orientation of the fire source and the field programmable controller settings. As with all fire tests, results must be interpreted according to the indi-
8
Figure 5—Detector Dimensions in Inches (Millimeters)
C1047
3.38 (85.8 MM) 7.11 (181 MM)
7.81
(198 MM)
2.5 DIA. (64 MM)
5.25
(133 MM)
CONDUIT ENTRY 3/4 NPT OR 25 MM
vidual application, taking into account all possible vari­ables (see the Application Guidelines” section for a dis­cussion of of these factors).
Typical response distances of the C7052J Detector to various fuels are listed in Table 1. Each liquid fuel fire (acetone, diesel, gasoline, methanol, and toluene) con­sisted of approximately one pint of fuel burned in a 1 foot by 1 foot steel pan unless otherwise noted. The excelsior (wood shaving) fire consisted of one pound of wood shavings. The wood fire consisted of a 10-inch by 10-inch crib (wood stack). The methane fire was per­formed to FM standard, with the flame approximately 30 inches high and 6 to 8 inches in diameter. The detec­tors were sited to observe the fire at center axis ±10 degrees. The controller sensitivity and time delay set­tings were 4 counts per gate, 4 consecutive gates, and
0.25 second gate lengths.
APPLICATION GUIDELINES
Certain guidelines must be followed when using any type of sensing device as a fire detector. This involves not only recognizing the strengths and advantages of a particular device, but also understanding its limitations.
It is also important to note that in any system that uses two or more sensors to produce a fire signal, the detec­tor will be disabled should one of its sensors fail. The Automatic oi feature will warn of such failure. Routine manual testing and checking of the system is recom­mended for increased system reliability.
A1020
10.0 INCHES (254 MM)
2 INCHES
(50 MM)
7 INCHES
(177 MM)
9 95-8331
Figure 6—Controller Dimensions in Inches (Millimeters)
5-1/4 INCHES
(133 MM)
2-1/2 INCHES
(64 MM)
MOUNTING BASE
1/2 INCH NUT USED TO ADJUST ELBOW TO DESIRED ANGLE
1-3/8 INCH NUT USED TO ROTATE SWIVEL/DETECTOR ASSEMBLY TO DESIRED POSITION
3/4 INCH NUT USED TO SECURE DETECTOR BRACKET TO SWIVEL MOUNT
JUNCTION BOX MOUNTING BRACKET (ATTACHES WITH TWO ENCLOSED FLATHEAD SCREWS)
B1303
Figure 7—Q9001G Swivel Mounting Bracket Dimensions
5-1/4 INCHES
(133 MM)
2-1/2 INCHES
(64 MM)
MOUNTING BASE
2–1/2 (64 MM) DIA.
0.25 (6.4 MM) DIA. (3)
120
° ± 2° (2)
2.00 (50.8 MM) DIA.
B1303
B1303
Figure 8—Mounting Base Dimensions
Potential radiation sources in the environment must also be carefully considered. A UV sensor will respond to sources of UV besides fire, such as electric arc welding, lightning, x-rays and gamma radiation. The C7052J has been designed to ignore steady state infrared sources that do not have a flicker frequency characteristic of a fire, however, it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts of infrared radiation in the response range of the IR sensor and if this radiation becomes interrupted from the view of the detector in a pattern characteristic of a flickering flame, the IR sensor can respond. Any object having a temperature greater than 0° Kelvin (–273°C) emits infrared radiation. The hotter the object, the greater the intensity of the emitted radiation. See Figure 9. The closer the infrared source is to the detec­tor, the greater the potential for the IR sensor to produce an alarm. The IR sensor can respond to IR radiation sources that can meet the amplitude and flicker require­ments of the detector such as vibrating hot objects. Although the C7052J Detector is designed to reduce false actuations, certain combinations of ambient radia-
tion must be avoided. For example, if IR radiation with an intensity that exceeds the fire threshold of the IR sen­sor should reach the detector as a flickering signal, and if at the same time an electric arc welding signal also reaches the sensors, an alarm output will be generated. The C7052J ignores arc welding beyond 15 feet from the detector. However, the UV sensor will respond to the intense UV radiation generated by the arc welding, and at distances closer than 15 feet the heated metal from the welding can become a false alarm source for the IR sensor.
Another important fact regarding a radiation detector of any type is that radiation must reach the detector in order for it to respond. Care must be taken to keep physical obstructions out of the line of view of the detec­tor. In addition, UV or IR absorbing gases or vapors must not be allowed to accumulate between the detec­tor and the protected hazard. See Table 2 for a listing of these substances. Smoke will also absorb radiation, therefore, the detector should not be mounted close to the ceiling or other areas where smoke can accumulate.
It is important to keep the detector viewing windows as free of contaminants as possible in order to maintain maximum sensitivity and to assure proper operation of the flame detection system. Commonly encountered substances that can significantly attenuate UV and/or IR radiation include, but are certainly not limited to, the fol­lowing:
Silicones Oils and greases Ice buildup Dust and dirt buildup Paint overspray
The oi test feature is designed to register an oi fault when the detector sensitivity is reduced to approximate­ly 50% of its maximum detection range. For maximum system reliability, it is recommended that the detector viewing windows be cleaned on a regularly scheduled basis. (Refer to the “Maintenance” section of this manu­al for additional information regarding detector mainte­nance.) The use of model Q1113 Air Shields can help extend the time period between required maintenance.
The C7052J is designed to be resistant to interference from EMI and RFI. It will not respond to a 5 watt walkie­talkie at a distance of greater than 1 foot.
The C7052J uses a single frequency IR sensing device with detection limited to the hot CO2emission peak, therefore, it cannot be used to detect fires that do not contain carbon, such as hydrogen, sulfur, burning met­als, or other non-hydrocarbons without thorough testing.
10
Table 1—C7052J Typical Response Distances
Fuel Distance from C7052J5 Acetone 45 feet (13.7 meters)
Diesel 40 feet (12.2 meters) Gasoline 50 feet (15 meters) JP4 (surface area)
2 ft
2
100 feet (30 meters)
4 ft
2
150 feet (45 meters)
10 ft
2
150 feet (45 meters) Methane 35 feet (10.7 meters) Methanol 35 feet (10.7 meters) Wood Shavings (Excelsior) 50 feet (15 meters) Wood Stack (Crib) 50 feet (15 meters)
Figure 9—Blackbody Spectral Emittance
10
4
10
3
10
2
10
1
1
10
–1
10
–2
10
–3
10
–4
0.4
0.6 0.8 1 2 4 6 8 10 20 30
RADIANT EMITTANCE
WATTS
(CM ) (MICRON)
2
6000°K
2000°K
250°K
500°K
300°K
4000°K
1000°K
INSTALLATION
DETECTOR POSITIONING
When determining the proper number and positioning of detectors needed for adequately protecting any given installation, it is essential to consider the cone of vision of the detector. The C7052J Detector has a nominal 80 degree cone of vision with the highest sensitivity along
its central axis. Refer to Figure 4. Careful observation of this graph reveals that at 50 percent of the maximum detection distance, the cone of vision is still 80 degrees. As the detection distance increases beyond 50 percent, the cone of vision gradually decreases. For example, the C7052J will detect a 1 foot by 1 foot gasoline fire at 50 feet. Therefore, we can assume that at 25 feet (50% maximum distance) the cone of vision will be 80 degrees. If the fire increases in size, both the maximum detection distance and the cone of vision at longer dis­tances will be increased.
It is also important to note that as the distance increases between the detector and the fire source, the time need­ed for the detector to respond to a fire of a given size also increases (fastest response requires maximum fire signal). The intensity of the radiation reaching the detector decreases with distance. For fastest response time, locate the detector as close as possible to the anticipated fire source.
The following recommendations should be observed in designing or installing any fire detection system:
— Use enough detectors to adequately cover the pro-
tected area with overlapping cones of vision.
— For fastest response time, position the detectors as
close as possible to the anticipated fire source.
— Aim the detector as directly as possible at the antic-
ipated fire source.
— If possible, conduct actual flame tests to verify cor-
rect detector positioning and proper system opera­tion.
Whenever possible, the detector should be positioned in a manner that will minimize the buildup of contami­nants on the viewing window and oi ring. Substances such as snow, ice, dirt, oil, paint overspray, and numer­ous other commonly encountered materials are capable of attenuating UV or IR radiation and adversely affecting detector response.
For outdoor applications, the detector should be aimed downward to minimize the buildup of water or ice on the detector viewing window and to prevent it from scanning the horizon. This minimizes the response to distant radiation sources outside the protected area.
The detector should not be placed where smoke can obscure its view of the hazardous area. For indoor applications, if dense smoke is expected to accumulate at the onset of a fire, mounting the detector on a side wall a few feet (1 meter) down from the ceiling will nor­mally allow enough time for the unit to respond before it is affected by rising smoke. The detector should be located where it can be easily accessed for periodic maintenance, testing and cleaning.
95-8331
The following is a partial list of compounds that exhibit significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little consequence in small amounts, these gases can restrict UV detection if they are in the atmosphere in heavy concentrations. It should also be determined whether or not large amounts of these gases may be released as a result of a fire­causing occurrence.
Acetaldehyde Methyl Methacrylate Acetone Alpha-Methylstyrene Acrylonitrile Naphthalene Ethyl Acrylate Nitroethane Methyl Acrylate Nitrobenzene Ethanol Nitromethane Ammonia 1-Nitropropane Aniline 2-Nitropropane Benzene 2-Pentanone 1,3 Butadiene Phenol 2—Butanone Phenyl Clycide Ether Butylamine Pyridine Chlorobenzene Hydrogen Sulfide 1-Chloro-1-Nitropropane Styrene Chloroprene Tetrachloroethylene Cumene Toluene Cyclopentadiene Trichloroethylene O-Dichlorobenzene Vinyl Toluene P-Dichlorobenzene Xylene
If UV-absorbing gases may be a factor in a given application, precautionary measures should be taken. Detectors can be placed closer to the poten­tial hazard area, and/or the sensitivity of the detec­tion system can be increased. Contact the factory for further details.
Substances such as methane, propane, butane, hexane, camphor and octane are not UV absorbing.
Absorption of infrared radiation in the range of 4.2 to 4.7 microns is not a significant problem with most organic vapors, with the exception of those com­pounds that have triple bonds such as acetylene, nitriles, silane, or isocyanates. Carbon dioxide con­centrations higher than normally present in the atmosphere can also cause substantial loss of fire detection sensitivity.
Table 2—Radiation Absorbing Gases and Vapors
11
WIRING REQUIREMENTS
The system should be wired using four conductor shielded cable, at least 18 gauge (1.024 mm diameter). The length of cable should be considered when wiring the system to ensure that a minimum input voltage of 18 vdc is present at the detector. The cable length should not exceed 2000 feet. In applications where the wiring cable is installed in conduit, the conduit should not be used for wiring to other electrical equipment. Foil type shielded cable is recommended to protect from electro­magnetic and radio frequency interference. When using cables with shields, the shield should be insulated at the detector and grounded only at the control cabinet.
NOTE It is important to use cable that is suitable for the installation environment. In applications involving high humidity or salt water, use a cable that is made specifically for harsh, salt water environ­ments. In all cases, typical cable insulation resis­tance should be at least 100 megohms. If the resistance drops below 10 megohms, the cable could be deteriorating and should be replaced to avoid shorting. When testing the insulation resis­tance, disconnect the leads from the detector/con­troller before connecting the megohmmeter (insula­tion tester) to the cable.
Since moisture can be detrimental to electronic devices, it is important that moisture not be allowed to come in contact with the electrical connections of the system. Moisture in the air can become trapped within sections of conduit, therefore the use of conduit seals is required to prevent damage to electrical connections caused by condensation within the conduit. These seals must be water-tight and explosion-proof and are to be installed even if they are not required by local wiring codes. A seal must be located as close to the C7052J as possi­ble. In no case should this seal be located more than 18 inches (46 cm) from the unit. If a conduit swivel is used, the seal must be located between the swivel and the detector. When an explosion-proof installation is required, an additional seal must also be installed at any point where the conduit enters a non-hazardous area. When pouring a seal, the use of a fiberdam is required to assure proper formation of the seal. The seals should never be poured in temperatures that are below freezing, since the water in the sealing com­pound will freeze and the compound will not dry proper­ly. Contamination problems can then result when tem­peratures rise above the freezing point and the com­pound thaws. The shielding of the cable should be stripped back to permit the seal to form around the indi­vidual leads, rather than around the outside of the shield. This will prevent any siphoning action that might occur through the inside of the shield. The electrical continuity of the shield must be maintained through the seal by means of the shield drain wire.
Moisture in the air can be trapped within sections of conduit and can condense and accumulate at the base of vertical conduit runs. To eliminate this condition, explosion-proof drains and breathers should be installed to automatically bleed off accumulated water.
It is recommended that the detector be oriented with the conduit opening at the bottom or at either side of the device. This will reduce the possibility of moisture entering the junction box through the conduit entry and also ensure that the oi test lamps are not in a position that would make the detector overly susceptible to o
i
faults. Whenever possible, slope the conduit run down­ward from the detector. Do not use conduit runs that enter the device from the top. See Figure 10 for identifi­cation of the detector parts of interest when mounting, and Figure 11 for an example of vertical detector mount­ing.
DETECTOR MOUNTING AND WIRING PROCEDURE
The following procedure should be used for mounting and wiring the C7052J.
1. Detectors should be located in positions best suited for covering the area to be protected. Whenever practical, they should be placed where they will be easily accessible for cleaning and other periodic servicing. Particular attention should also be paid to potential false alarm sources within the cone of vision of the detector, such as distant arc welding, rotating fan blades, surface vibration of an IR source, and movement of people or machines between the detector and an IR source, all of which could allow a flickering IR signal to reach the detec­tor. Rain or ice can absorb radiation, which can reduce the capability of the detector. For outdoor applications, aim the detector downward to mini­mize the buildup of water or ice on the detector viewing windows and to prevent the cone of vision from scanning the horizon. This minimizes response to distant radiation sources outside the protected area. See Figure 11 for an example of vertical detector mounting.
NOTE The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaran­teed. Be certain that all wiring complies with appli­cable regulations that relate to the installation of electrical equipment in a hazardous area. If in doubt, consult a qualified electrician before wiring the system.
12
2. Remove the junction box cover assembly from the base by loosening the six screws on the cover (see Figure 12).
3. Mount the detector junction box base and mounting bracket assembly on the wall or ceiling. See Figures 7 and 8 for dimensions of the mounting bracket. The mounting surface should be free of excessive heat and vibration.
NOTE Do not wire the system, or plug in or remove the sensor modules with power applied.
4. Figure 13 shows the detector terminal block. Letter designations correspond to connections as indicat­ed below.
A = +24 vdc B = detector output signal C = circuit ground D = oi control signal
Minimum requirements for wiring the detector are for the B-lead (signal) to be shielded. It is preferred that the A­lead, C-lead, and D-lead also be shielded to provide maximum immunity to EMI/RFI. The wiring procedure below is the preferred method of detector to controller wiring. Refer to Figure 14 for an example of detector to controller wiring.
PROVIDE ENOUGH CABLE FOR ADJUSTMENT OF SWIVEL
CONDUIT SEAL
A1478
Figure 11—Vertical Detector Mounting
13 95-8331
oi RING OPENING DOWN
CONDUIT SEAL REQUIRED WITHIN 18 INCHES OF DETECTOR. DETECTOR MUST BE ORIENTED  WITH CONDUIT ENTRY AT BOTTOM OR SIDE TO ELIMINATE DRAINAGE INTO JUNCTION BOX.
*
o
i
TEST LAMPS AT TOP OR SIDE
o
i
TEST LAMP
*o
i
TEST LAMP (2)
IR SENSOR HOUSING
UV SENSOR HOUSING
A1462
Figure 10—Front View of the C7052 Detector
14
Figure 13—Detector Terminal Block
D0947
+24 VDC (A)
OUTPUT SIGNAL (B)
CIRCUIT GND (C)
oi SIGNAL (D)
EARTH GND
Figure 12—C7052J Detector Part Identification
F0946
JUNCTION BOX
JUNCTION BOX COVER
MOUNTING PIN
IR TEST LAMPS (2)
O-RING
IR SENSOR HOUSING
IR oi RING
INDEX PIN
UV SENSOR MODULE
O-RING
UV TEST LAMP OPENING
UV SENSOR HOUSING
UV oi RING
IR SENSOR MODULE
UV TERMINAL BLOCK
a. Connect the B-lead shields to the chassis
ground connection (terminal 5) of the con­troller.
b. Be certain that the shield is NOT connected
to the detector at terminal “C” (circuit ground) or any other points.
c. Connect the C-leads of the detectors to termi-
nal 2 (circuit ground) of the controller.
d. Connect a non-polarized 0.47 microfarad 250
vdc capacitor from terminal 5 to terminal 2. This places the earth ground and the circuit ground at the same ac potential, minimizing induction of noise into the system through the detector cable.
5. Check to make sure that all wiring is correct. If con­duit is used, pour the conduit seals and allow them to dry.
6. If the UV and/or IR sensor modules are already installed in the detector housing, proceed to step
12. If the sensors are not installed, remove the applicable sensor housings from the junction box cover (see Figure 12). If the detectors are equipped with a cover locking device (see Figure
15), loosen the clamp and disengage the “catch” from the blind hole. The tool required is a 5/32-inch hexagonal (Allen) wrench.
7. If the UV sensor module is already installed, pro­ceed to step 9. If the UV module is not installed, remove the UV sensor module from its shipping package.
8. Determine the proper orientation for the UV module by lining up the long index pin on the terminal block with the hole in the printed circuit board of the mod­ule. See Figure 12. Firmly press the module into place on the terminal block, taking care not to touch the glass envelope of the sensor module, since fin­gerprints can absorb UV radiation and reduce the sensitivity of the sensor.
IMPORTANT
If the UV sensor module is supplied with a jumper plug “J” as shown in Figure 16, remove the jumper plug from the detector tube module and discard it. Jumper plug “J” is supplied for installations in which the tube module is used with other detector models.
NOTE The C7052J contains semiconductor devices that are susceptible to damage by electrostatic dis­charge. An electrostatic charge can build up on the skin and discharge when an object is touched. Therefore, use caution when handling the detector, taking care not to touch the terminals or electronic components. For more information on proper han­dling, refer to Service Memo form 75-1005 at the front of this manual.
9. If the IR sensor is already installed, proceed to step
12. If the IR sensor is not installed, remove the IR module from its shipping package (avoid touching the IR sensing element at the top of the module). Two IR sensor designs exist: 1) the DE5500 is elec­trically connected via a wire harness on the junction box that must be threaded through the sensor mod­ule to a connector at the top of the module (see Figure 17), 2) the DE3895 plugs directly onto a termi­nal block in the base of the IR housing via connec­tors on the bottom of the IR sensor module (see Figure 12).
15
95-8331
1 2 3 4 5
A B C D
31 32 33 34 35 36
24 VDC POWER
SUPPLY
+
43 44
DETECTOR
NO. 1
C7052J
A B C D
DETECTOR
NO. 2
C7052J
J2
J1
REMOTE
RESET
CHASSIS (EARTH) GROUND
CHASSIS GROUND
D1 D2
B1 B2
CKT GND
0.47µf
B1088
Figure 14—Detector Connection
BLIND HOLE
COVER
LOCKING
ASSEMBLY
CATCH
CLAMP SCREW
STRAP
BARREL
LENS CAP
A1078
Figure 15—Cover Locking Assembly (Optional)
10. If the IR sensors are the DE3895 type that electrical­ly connects directly onto the terminal block, install them by lining up the connection pins using the index pin to properly orient the module. Press the sensor firmly into place.
11. If the IR sensor is the DE5500 type that connects via a wire harness (Figure 17), thread the wire leads and keyed connector plug through the slotted opening on the side of the IR module. Plug the IR module into the two banana plugs inside the junc­tion box cover. If repositioning is necessary to properly align the oi lamps (as described in the “NOTE” below), this module can be rotated 180° and remounted on the banana plugs.
NOTE
The two
o
i
lamps on the DE5500 IR sensor should be at the top or side of the detector (when viewed from the front) and the opening on the
o
i
ring should be at the bottom. See Figure 10. This will ensure proper operation of the
o
i
system and also minimize the accumulation of moisture and con­taminants between the
o
i
ring and the viewing win-
dow. (The
o
i
lamps on the IR sensor are identified
as oblong in shape and clear in color.)
12. Connect the keyed connector plug to the 4-pin con­nector on the DE5500 IR module. Tuck the lead­wires inside the module to prevent binding or wire damage when installing or removing the sensor housing.
13. Check the O-rings on both sensor housings to be sure that they are in good condition and are fitted properly, then re-install the sensor housings on the junction box cover. (See the “Maintenance” section of this manual for information regarding care of O­rings.) The sensor housing with the large viewing window is for the UV detector and the sensor hous­ing with the small window is for the IR detector. Hand tighten the sensor housings into the base until the O-rings are fully seated to maintain the explo­sion-proof and watertight integrity of the housing. If the unit is equipped with cover locking clamps, loosen the clamps sufficiently so that the clamp catches can be seated in the blind holes on the junction box cover. Fasten the clamps securely using a 5/32 inch hexagonal (Allen) wrench. (See Figure 15.)
14. Re-install the junction box cover, making sure that the center nine-pin connector on the cover is prop­erly aligned with the connector in the junction box. The six screws must be tight to ensure a metal to metal fit to maintain explosion-proof and watertight integrity of the junction box.
15. Inspect and clean (if necessary) the detector view­ing windows and oi rings by following the instruc­tions in the “Maintenance” section of this manual.
16. The opening of the oi rings should be pointed down to minimize the accumulation of moisture or con­taminants behind the ring (see Figure 10). Verify that the oi test lamp is at the top or side of each sensor. Note that Figure 10 shows the DE5500 IR module with the test lamps located together on one side of the edge. The DE3895 IR module has test lamps located directly opposite one another. In both cases, ensure that no test lamp is positioned at the bottom when the detector is installed.
16
Figure 16—Jumper Plug
JUMPER "J"
A1702
A1331
IR MODULE
4–WIRE CONNECTOR PLUG
Figure 17—IR Module with Four-Wire Connector
17. If the detector is so equipped, install the air shields on each sensor housing, then connect the air sup­ply line to the air shields.
NOTE Be sure that the detector is correctly aimed at the potential hazard and that no obstructions interfere with its line of vision. In addition, UV and/or IR absorbing gases (see Table 2) should not exist between the detector and the potential hazard.
CONTROLLER INSTALLATION AND WIRING
The R7495D Controller must be mounted in a non-haz­ardous area. The optional Q4004 Mounting Cage is designed to hold up to eight modules in a 19 inch instrument rack. Other mounting cages are available to accommodate 1, 2, 3, or 4 units. These mounting cages can also house relay output modules, voltage converters, or other micro-module equipment that is used in conjunction with the R7495D Controller as part of the total protection system. See Figure 18 for illustra­tion and dimensions.
ELECTRICAL CONNECTIONS
All electrical connections are made to the field wiring connector that is furnished with the controller. Figure 19 shows the terminal configuration for the controller. Power to the R7495D Controller and C7052J Detectors may be furnished by external 24 volt batteries, a regu­lated dc power supply, or optional Det-Tronics voltage converters. The R7495D is designed to operate on +18 to +32 vdc.
Terminal 1 — Connect to the positive (+)
side of an external 24 vdc power source (+18 to +32 vdc).
Terminal 2 — Connect to the negative (–)
side of the dc power source (circuit ground). The C termi­nals on the detectors must also be connected to circuit ground.
Terminal 3 — Do not use.
17 95-8331
(A)
(B)
(C)
1.48 (37.59)
(D)
A1475
ALL CONTROLLER CAGES REQUIRE A MINIMUM OF 10.12 INCHES (257.1 MM) DEPTH CLEARANCE
(E)
Figure 18—Q4004 Mounting Cage Dimensions in Inches (Millimeters)
RACK PART NUMBER CONTROLLER
TYPE 005269-XXX POSITIONS FOR: HT: DIM. (A) DIM. (B) DIM. (C) DIM. (D) DIM. (E) WEIGHT
FIRE GAS INCH MM INCH MM INCH MM INCH MM INCH MM LB KG
4U –001 8 16 4U 19.00 482.6 18.30 464.8 17.36 440.9 4.00 101.6 6.97 177.1 9.3 4.2 4U –002 6 12 4U 15.06 382.6 14.36 364.7 13.42 340.9 7.6 3.5 4U –003 4 8 4U 11.13 282.6 10.43 264.9 9.49 241.1 5.9 2.7 4U –004 3 6 4U 9.16 232.7 8.46 214.9 7.52 191.0 5.1 2.3 4U –005 2 4 4U 7.19 182.7 6.49 164.9 5.55 141.0 4.2 1.9 4U –006 1 2 4U 5.22 132.6 4.52 114.8 3.58 90.9 3.1 1.4
Terminal 4 — Do not use. Terminal 5 — Chassis Ground Terminals 6 to 11 — Relay contacts - Fire Relay No.
1.
Terminals 12 to 17 — Relay contacts - Fire Relay No.
2.
Terminals 18 to 20 — Relay contacts - Alarm Relay
No. 1.
Terminals 21 to 23 — Relay contacts - Alarm Relay
No. 2. Terminals 24 to 26 — Relay Contacts - Fault Relay. Terminal 31 — External Reset. To reset the
system from a remote location,
connect switch (normally open)
between terminals 31 and 32. Terminals 32 and 33 — Circuit ground. Terminal 34 — Do not use. Terminal 35 — Connect to the D-lead (oi driv-
er) of Detector No. 1. Terminal 36 — Connect to the D-lead (oi driv-
er) of Detector No. 2. Terminal 43 — Connect to the B-lead (signal)
of Detector No. 1. Terminal 44 — Connect to the B-lead (signal)
of Detector No. 2.
PROGRAMMING THE CONTROLLER
The R7495D Controller is field programmable in order to meet the requirements of the individual installation. This is accomplished by setting rocker switches that are located on the left side of the controller (see Figure 20) to either “open” or “closed.” The programming options are listed below. A more detailed description follows.
1. Number of detectors connected to the controller (1 or 2).
2. Gate Length, Consecutive Gate Selection, and Count Selection (system sensitivity and time delay).
3. Fire zone grouping.
4. Latching/non-latching outputs.
The individual rocker switches are identified by num­bers 1-1, 1-2, 1-3, etc. in this manual. The number pre­ceding the dash indicates the number of the switch assembly. The number following the dash identifies the specific rocker on the switch assembly. See Figure 20.
The rockers are identified by the numbers one through eight on one side of the assembly. The word “open” can be seen on the opposite side. The switch is open when depressed in the direction of the word “open” and closed when depressed in the direction of the numbers.
The rocker switches must be set before power is applied to the system. Do not plug the controller in or remove it from the mounting rack while power is turned on.
CAUTION
Use care when setting the rocker switches on the controller. An incorrectly set rocker switch can result in an obvious controller malfunction, or the controller could appear to be functioning normally, but not produce the desired output in response to the input conditions. (Some of the rocker switches on the R7495D are not used. These rockers should be left open.)
Detector Selection - Rocker Switches 1-1 and 1-2
The number after the dash corresponds to the channel number. Open the rocker for each zone that has a detector connected to it. Care must be taken when set­ting these rockers. If a rocker is set open, but no detec­tor is connected in that location, the controller will indi­cate a fault. If a rocker is set closed when a detector is connected, the controller will appear to be operating correctly and will produce an alarm condition if the cor­responding detectors sense a fire. However, that detector will be eliminated from the Automatic oi test sequence, and any faults occurring in its circuitry or wiring will not be indicated.
18
J2
J1
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
31 32 33 34 35 36
43 44
+ –
NOT USED NOT USED
CHASSIS GROUND
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
EXTERNAL RESET CIRCUIT GROUND CIRCUIT GROUND NOT USED D1 D2
B1 B2
FAULT*
RELAY
ALARM
RELAY
NO. 1
ALARM
RELAY
NO. 2
FIRE
RELAY
NO. 2
FIRE
RELAY
NO. 1
+24 VDC INPUT
SIGNAL INPUTS
(B-LEADS)
oi DRIVERS
(D-LEADS)
THE FAULT RELAY, SHOWN DE-ENERGIZED, IS NORMALLY ENERGIZED IN THE NORMAL OPERATING MODE WITH NO FAULTS OCCURING
*
B1055
Figure 19—Controller Terminal Configuration
STAR Logic Programming (System Sensitivity and Time Delay) - Rocker Switches 2-1 to 2-8 (Gate Length), Rocker Switches 3-1 to 3-4 (Count Selection Per Gate), and Rocker Switches 3-5 to 3-8 (Consecutive Gates Selection).
The STAR Logic switch settings determine system sen­sitivity and time delay. The most important factor in determining the appropriate sensitivity setting for a par­ticular application is the intensity of radiation expected to reach the detector in the event of a fire. This depends on several factors, including the distance of the detector from the potential fire, the fuel type, the flame size, and whether any radiation absorbing vapors are present (these are listed in Table 2).
The most effective way to set system sensitivity is to install the system, program the STAR Logic according to the typical settings shown in Figure 21, program all other aspects of controller operation according to this section (“Programming the Controller”), then perform the “Initial and Periodic Checkout Procedure” using a UV/IR test lamp and the “STAR Programming Checkout Procedure.” If the system fails to respond appropriately during these tests and all system wiring is correct, then system sensitivity (gate length, counts per gate, and consecutive gates) needs to be adjusted. It is important that all wiring and programmed settings be checked to ensure that they are correct before adjusting these set­tings.
Rocker switch assemblies 2 and 3 control three variables: gate length, counts per gate and consecutive gates required for a fire output. Refer to Figure 21 for a visual
representation of how these variables function together with typical controller settings. Keep in mind that when the UV and IR sensors of the detector respond to a fire, the IR sensor activates the circuitry in the UV/IR detector junction box. This allows the electrical pulses (signal) from the UV sensor to be sent to the controller. The fre­quency of this signal is proportional to the intensity of the fire. The controller looks at this signal in comparison to the sensitivity settings in order to determine whether a fire exists. A brief description of each variable follows:
1. Gate Length is adjustable from 31.25 milliseconds to 8 seconds. The gate length is the increment of time that the controller looks at the detector signal to determine if the “Counts per Gate” requirement is fulfilled. In Figure 21, the gate length is 0.25 sec­onds (Rocker Switch 2-4 closed, Rocker Switches 2-1, 2-2, 2-3, 2-5, 2-6, 2-7, and 2-8 open).
2. Counts per Gate is adjustable from 2 to 15 counts. These counts make up the signal from the detector and are a direct response to a flame or other UV/IR source. In Figure 21, the counts per gate setting is 4 counts (Rocker Switch 3-3 closed, Rocker Switches 3-1, 3-2, and 3-4 open).
3. Consecutive Gates required for a fire output are adjustable from 2 to 15 gates. This is the number of consecutive gates in which the “Counts per Gate” requirement is fulfilled that the controller must see before going into a fire alarm condition. In Figure 21, the consecutive gates setting is 4 gates (Rocker Switch 3-7 closed, Rocker Switches 3-5, 3-6, and 3­8 open).
19 95-8331
Figure 20—Rocker Switch Setting
B1053
SWITCH ASSEMBLY 3
COUNT SELECTION
CLOSE ROCKERS TO ACTIVATE
ROCKER 1 – 1 COUNT ROCKER 2 – 2 COUNTS ROCKER 3 – 4 COUNTS ROCKER 4 – 8 COUNTS
VALUES OF ROCKERS CLOSED
ARE ADDED TOGETHER – 2 COUNTS MINIMUM
IF GATE IS GREATER THAN OR EQUAL
TO 0.5 SECOND, A MULTIPLICATION FACTOR
MUST BE USED.
CONSECUTIVE GATE SELECTION
CLOSE ROCKERS TO ACTIVATE
ROCKER 5 – 1 GATE ROCKER 6 – 2 GATES ROCKER 7 – 4 GATES ROCKER 8 – 8 GATES
VALUES OF ROCKERS CLOSED
ARE ADDED TOGETHER – 2 GATES MINIMUM
SWITCH ASSEMBLY 2
GATE LENGTH
CLOSE ROCKERS TO ACTIVATE
VALUES OF ROCKERS CLOSED
ARE ADDED TOGETHER
ROCKER SWITCH NUMBERS ARE DESIGNATED 1-1, 1-2, 1-3, ETC. THE NUMBER PRECEDING THE DASH INDICATES THE SWITCH ASSEMBLY. THE NUMBER FOLLOWING THE DASH INDICATES THE ROCKER NUMBER.
NOTE 1:
DEPRESS ROCKER TOWARD "OPEN" ON SWITCH ASSEMBLY TO SET IN THE OPEN POSITION.  DEPRESS ROCKER TOWARD NUMBER DESIGNATIONS TO SET IN CLOSED POSITION.
NOTE 2:
SWITCH ASSEMBLY 4
FIRE ZONES ROCKER 1 –
INDIVIDUAL RESPONSE
WHEN ROCKER IS CLOSED,
COMBINED WHEN ROCKER IS OPEN.
OUTPUTS LATCHING
ROCKER 5 –
LATCHING OUTPUTS WHEN ROCKER IS OPEN
ROCKERS 2 AND 6 NOT USED
SWITCH ASSEMBLY 1
DETECTOR SELECTION SWITCH
PLACE ROCKER IN OPEN POSITION
FOR EACH CHANNEL WITH A DETECTOR CONNECTED
ROCKER 1 – 31.25 MILLISECONDS ROCKER 2 – 62.5 MILLISECONDS ROCKER 3 – 0.125 SECOND ROCKER 4 – 0.25 SECOND ROCKER 5 – 0.5 SECOND ROCKER 6 – 1 SECOND ROCKER 7 – 2 SECONDS ROCKER 8 – 4 SECONDS
If changes in the sensitivity and/or time delay settings are required, read the detailed discussions of each of the three STAR Logic variables that follows before mak­ing changes. When changing the settings, keep in mind the following guidelines:
1. Increasing Gate Length while the other variables remain unchanged results in higher sensitivity and a longer time delay.
2. Increasing Consecutive Gates while the other vari­ables remain unchanged results in a longer time delay and greater noise rejection.
3. Increasing Counts per Gate while the other vari­ables remain unchanged results in lower sensitivity and more false alarm resistance.
Gate length - Rocker Switches 2-1 to 2-8
The gate length can be adjusted in 31.25 millisecond increments from 31.25 milliseconds to 8 seconds. Each rocker selects a particular time value. The gate length is the value of all rockers closed, added together. If no rocker is closed, the controller will select the minimum length (31.25 milliseconds). The typical gate length set­tings used in most applications are between 0.125 and
0.5 second.
Rocker 2-1 - 31.25 milliseconds Rocker 2-2 - 62.5 milliseconds Rocker 2-3 - 0.125 second Rocker 2-4 - 0.25 second Rocker 2-5 - 0.5 second Rocker 2-6 - 1 second Rocker 2-7 - 2 seconds Rocker 2-8 - 4 seconds
The value of the closed switches are added together to obtain the total time delay.
Count Selection - Rocker Switches 3-1 to 3-4
When a gate length of less than 0.5 second is used, the rockers select counts needed per gate for a fire signal. The values of all rockers closed are added together. If no counts or less than 2 counts are selected (only rock­er 1 closed), the microprocessor will select 2. Counts per gate are selectable in 1 count increments from 2 to 15 counts. The typical counts per gate setting used in most applications are between 2 and 8 counts.
Rocker 3-1 - 1 count Rocker 3-2 - 2 counts Rocker 3-3 - 4 counts Rocker 3-4 - 8 counts
SIGNAL
FLAME
C7052J
STAR LOGIC (TYPICAL SETTINGS SHOWN)
CONTROLLER
ALARM
CONDITION
COUNT (SIGNAL)
4 COUNTS PER GATE
4 CONSECUTIVE GATES
0.25 SECOND GATE LENGTH
A1708
Figure 21—Graphic Representation of STAR Logic (Typical Settings Shown)
20
R7495 STAR Logic Program
4 Counts per Gate
0.25 Second Gate Length 4 Consecutive Gates
R7495 Switch Settings
Rockers Closed Rockers Open
3-3 3-1, 3-2, 3-4 2-4 2-1, 2-2, 2-3, 2-5, 2-6, 2-7, 2-8 3-7 3-5, 3-6, 3-8
When a gate length of 0.5 second or greater is used, the programmed counts per gate value is multiplied by a fac­tor that is determined by the gate length that has been programmed using rocker switches 2-5 to 2-8. Refer to Figure 22 to determine the proper multiplication factor. Note that the multiplication factor is determined by the highest numbered rocker switch in the closed position.
The STAR logic program uses this multiplication tech­nique to prevent accidental programming of a very low count value combined with a long gate length, since this combination would result in an extremely high sensitivity level that would increase susceptibility to false alarms.
For example, suppose that a gate length of 1.5 seconds and a sensitivity of 4 counts per gate is selected. Since the gate length exceeds 0.5 second, the counts per gate value must be multiplied by the factor determined from Figure 22. In this case, 4 counts per gate is multi­plied by a factor of 4, to obtain a total programmed value of 16 counts per gate. Without this feature, it would be possible to program the system to interpret 4 counts in 1.5 seconds as a fire signal, which would make the system susceptible to frequent false alarms.
Consecutive Gate Selection - Rocker Switches 3-5 to 3-8
These rockers select the number of consecutive gates required for a fire signal. Consecutive gates are selectable in 1-gate increments from 2 to 15 gates. If fewer than 2 gates are selected (only rocker 5 closed), the microprocessor will select 2. The values of the rock-
ers closed are added together. The typical consecutive gate settings used in most applications are between 3 and 8 gates.
Rocker 3-5 - 1 Gate Rocker 3-6 - 2 Gates Rocker 3-7 - 4 Gates Rocker 3-8 - 8 Gates
Detector Grouping - Rocker Switches 4-1 to 4-2
Rocker Switch 4-1
Closed = individual Open = combined
Rocker Switch 4-2
Not used - leave open
Outputs Latching/Non-latching - Rocker Switch 4-5
Open = latching Closed = non-latching
Once energized, an output will remain on (latching) until the controller is reset if rocker 4-5 is set open.
Rocker Switch 4-6
Not used - leave open When the proper position for each of the rocker switch-
es has been determined, record this information careful­ly on the system layout chart in Figure 23. This provides a means of double checking switch positions before power is applied to the controller, and to provide a record of switch positions for future reference.
TYPICAL SYSTEM APPLICATION
The following application is an example only. For assis­tance in adapting a system to your individual require­ments, contact the Field Support Group at Detector Electronics.
Figure 14 illustrates the standard method of connecting detectors to the controller. All cable shields are tied together and connected to circuit ground, terminal 33. A switch (normally open) can be connected between terminals 31 and 32 to perform a system reset from a remote location.
The following examples show all relay contacts in the normal operating condition after the system is reset. To reset the system, switch the faceplate toggle switch from NORMAL to TEST and back to NORMAL, or press the RESET/LAMP TEST pushbutton.
21 95-8331
START
ROCKER 2–8
CLOSED?
ROCKER 2–7
CLOSED?
ROCKER 2–6
CLOSED?
ROCKER 2–5
CLOSED?
YES
YES
YES
YES
MULTIPLY BY 16
MULTIPLY BY 8
MULTIPLY BY 4
MULTIPLY BY 2
A974
NO
NO
NO
Figure 22—Multiplication Factors
Figure 24 shows power connected to a load circuit through the normally closed contacts of the Alarm relay. When a “fire” signal is received by the controller, the contacts open, removing power from the load.
Power is connected to a process or system control cir­cuit through the normally closed contacts of the Fault relay. When a system fault occurs or when the con­troller is in the Test mode, the contacts open, removing power from the process. An alarm circuit is connected to the power source through the normally open contacts of the Fault relay. When a system fault occurs, the con­tacts close, powering the alarm.
Figure 25 depicts a similar output circuit, with a normally unenergized load connected to the Fire relay.
STARTUP PROCEDURE
The startup procedure should be performed after instal­lation of the equipment is complete.
1. After making the electrical connections and setting the switches, plug the controller into the wiring con­nector.
2. Disable any extinguishing system connected to the system.
3. Turn on the input power to the system and perform the “Initial and Periodic Checkout Procedure.”
4. If the controller is operating normally and is pro­grammed correctly, remove any mechanical block­ing devices and restore power to the extinguishing loads.
22
SWITCH 1
DETECTOR SELECT
SWITCH 3
CONSECUTIVE GATE
SELECTION
SWITCH 3
COUNT SELECTION
SWITCH 2
GATE LENGTH (SECONDS)
SWITCH 4 - 5
OUTPUTS LATCHING
SWITCH 4 - 1 FIRE ZONES
ROCKER OPEN CLOSED
ROCKER OPEN CLOSED
ROCKER OPEN CLOSED
ROCKER OPEN CLOSED
ROCKER OPEN CLOSED
ROCKER OPEN CLOSED
1 2 3 4 5 6 7 8
1 2 3 4
5 – 1 GATE 6 – 2 GATES 7 – 4 GATES 8 – 8 GATES
1 (1 COUNT) 2 (2 COUNTS) 3 (4 COUNTS) 4 (8 COUNTS)
5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 – 0.031 2 – 0.062 3 – 0.125 4 – 0.25 5 – 0.5 6 – 1.0 7 – 2.0 8 – 4.0
1 2 3 4 5 6 7 8
OPEN SWITCH FOR EACH
DETECTOR CONNECTED
ADD VALUE OF CLOSED
ROCKERS – 2 GATES MINIMUM
ADD VALUE OF CLOSED ROCKERS – 2 COUNTS MINIMUM – USE MULTIPLICATION FACTOR
IF GATE IS 0.5 SECOND OR GREATER
ADD VALUE OF
CLOSED ROCKERS
OPEN = LATCHING
OPEN
B0994
1 2 3 4 5 6 7 8
OPEN
1 2 3 4 5 6 7 8
OPEN
1 2 3 4 5 6 7 8
OPEN
OPEN = COMBINED RESPONSE
CLOSED = INDIVIDUAL RESPONSE
Figure 23—System Layout Chart
INITIAL AND PERIODIC CHECKOUT PROCEDURE
The entire system should be periodically checked with a UV/IR test lamp to be sure that the detectors are not obstructed, that the area “seen” by the detector has not changed, and that there is no fault in the oi circuit.
1. Place the Mode switch in the TEST position. The FAULT LED will turn on.
CAUTION
Placing the controller in the Test mode inhibits the outputs, rendering the system incapable of actuat­ing any extinguishing or alarm circuits that are con­nected to it. However, for maximum safety, secure the output loads that would normally be actuated by the system before performing the checkout pro­cedure.
2. Shine the UV/IR test lamp into the viewing window of the detector under test. The corresponding DETECTOR LED flashes rapidly to identify the detector under test.
If the requirements are met, the appropriate ALARM LED and FIRE ZONE LED are also illuminated.
3. Turn off the UV/IR source. If turned on, the ALARM LED and FIRE ZONE LED(s) continue to flash if latching outputs are selected and are on steady if not selected. The DETECTOR LED is on steady.
4. Repeat steps 2 and 3 for the other detector in the system.
5. After all detectors have been checked, reset the system by placing the Mode switch in the NORMAL position. All LEDs except the POWER LED are off.
6. Restore power to the output loads and remove any mechanical blocking devices.
STAR PROGRAMMING CHECKOUT PROCEDURE
1. Secure output loads (remove power from valves, relays or other devices that might otherwise be actuated by the UV/IR system) before testing.
2. Apply power to the UV/IR detection system.
3. Ensure that the area being monitored is operating under normal conditions (equipment that would nor­mally be on is on).
4. Place the UV/IR controller keyswitch in the NOR­MAL position and monitor for one hour.
— If the rockers have been set correctly, transient
radiation in the area should not activate the system. The upper and lower LED displays should remain dark. If this is the case, lower (more sensitive) set­tings can be attempted.
— If the system sensitivity is set too high, one of the
two DETECTOR LEDs will turn on, and depending on the Fire Zone switch settings, one of the FIRE ZONE LEDs may turn on. If this happens, set the rocker switches for more counts per gate, for more consecutive gates required for actuation, or for a shorter gate length and repeat the test. Altering detector placement may also decrease the suscep­tibility of the system to transient radiation.
For further assistance, contact the Field Support Group at Detector Electronics.
MAINTENANCE
The C7052J Detector requires no periodic calibration. However, to maintain maximum sensitivity, the detector viewing windows must be kept clean at all times. Even a small amount of certain UV or IR absorbing materials (sometimes barely detectable to the human eye) can significantly reduce the sensitivity of the detector. The windows and oi rings should be thoroughly cleaned on a regular basis. The length of time between periodic cleanings will be determined by the nature and amount of contaminants present in the environment.
23 95-8331
17 18 19 20 21 22 23 24 25 26
ALARM
RELAY
NO. 1
FAULT RELAY
FAULT RELAY SHOWN
IN NORMAL (ENERGIZED) CONDITION
A1057
FAULT
ALARM
LOAD
PROCESS CONTROL
(+)H
(
)N
Figure 24—Normally Energized Load Circuit Connected to Alarm Relay
8
9 10 11 12
23 24 25 26 27
FIRE
RELAY
NO. 1
FAULT RELAY
FAULT RELAY SHOWN
IN NORMAL (ENERGIZED) CONDITION
A1058
FAULT
ALARM
LOAD
PROCESS CONTROL
(+)H
(
)N
Figure 25—Normally Unenergized Load Circuit Connected to Fire Relay
Remove the oi rings by squeezing the tabs together and pulling away from the detector. Clean the viewing windows thoroughly, all the way to the edge. Also clean the reflective surface of the oi rings (the surface of the ring that faces the detector viewing window). When re­installing an oi ring, hold it by its tabs to avoid leaving fingerprints on the reflective surface. Re-install the ring so that the opening is pointed down to prevent a buildup of contaminants. If corrosive contaminants in the atmosphere cause the reflective rings to deteriorate to the extent that it is no longer possible to restore them to their original condition, they must be replaced.
Det-Tronics window cleaning solution (part number 001680-001) is designed specifically for cleaning the optical surfaces of the detector. DO NOT use commer­cial cleaners. These products can leave a residue on the surface that is intended to give it a “sparkling” look, however, this residue can substantially attenuate the radiation reaching the sensor.
Use a clean cloth or tissue to clean the window. DO NOT use commercial glass cleaning tissues, since many of these contain a silicone substance that remains on the window after cleaning. Silicone readily absorbs radiation and can effectively “blind” the detector, even though the window appears to be clean.
NOTE When cleaning the detector windows, remove input power or place the system in the “Bypass” or “Reset/Inhibit” mode. Rubbing motion on the sur­face of the windows during cleaning can create an unwanted output activation.
Viton O-rings on each of the detector housings are used to ensure the watertight integrity of the detector. Periodically, the housing should be opened and the O­rings inspected for breaks, cracks, and dryness. To test them, remove the rings from the detector housing and stretch them slightly. If cracks are visible, the ring should be replaced. If they feel dry to the touch, a thin coating of lubricant should be applied. When re­installing the rings, be sure that they are properly seat­ed in the groove on the housing. It is imperative that these O-rings be properly installed and in good condi­tion. Failure to maintain these rings can allow water to enter the detector and cause premature failure. The life expectancy of Viton O-rings can vary considerably, depending on the amount and nature of contaminants that are present in the environment. The individual responsible for maintenance of the system must rely on experience and common sense to determine how fre­quently the rings should be inspected.
The recommended material for lubricating the O-rings is a silicone free polyalphaolefin grease, part number 005143-001, available from Detector Electronics. A
coating of lubricant should also be applied to the threads on the sensor housings before reassembling the detector. This will both lubricate the threads and help to prevent moisture from entering the detector housing.
Refer to “Recommended Spare Parts” in the “Ordering Information” section of this manual for a list of products available from Detector Electronics for maintenance of the detector.
SENSOR MODULE REPLACEMENT PROCEDURE
To replace a defective module:
CAUTION
Do not open the detector housing in a hazardous location without first removing power.
a. Remove power from the detector. b. Remove the sensor housing (see Figure 12). c. Remove the sensor module. d. Determine the proper orientation for the new sensor
module (with the oi test lamps positioned at the top or side of the detector), then install the module. Attach the connector plug (DE5500 models of the IR sensor only).
e. Ensure that the O-rings at the base of the sensor
housing are positioned correctly and in good condi­tion. (Refer to the “Maintenance” section of this manual for complete information regarding care of O-rings.)
f. Re-install the sensor housing. Hand tighten the
sensor housing into the base until the O-ring is fully seated to ensure explosion-proof and watertight integrity of the housing.
g. Inspect the viewing windows and oi rings and clean
if necessary. Also check the position of the o
i
rings.
h. Perform the “Startup Procedure” before returning
the system to normal operation.
TROUBLESHOOTING
Table 3 is intended to aid maintenance personnel in locating the cause of a system malfunction. The R7495D Controller and plug-in detector modules are not designed to be repaired in the field. If repairs are need­ed, the device should be returned to the factory.
24
DEVICE REPAIR AND RETURN
Prior to returning devices or components, contact the nearest local Detector Electronics office so that an RMI (Return Material Identification) number can be assigned. A written statement describing the malfunc­tion must accompany the returned device or component to expedite finding the cause of the failure, thereby reducing the time and cost of the repair.
Return all equipment transportation prepaid to the facto­ry in Minneapolis.
ENGINEERING SPECIFICATIONS
The UV/IR flame detection system shall have a micro­processor-based controller that can operate 1 or 2 detectors and provide relay outputs. The controller shall be field programmable for selecting time delay length, sensitivity, voting output configuration, and latching or non-latching operation. The system shall operate on 24 vdc. The UV/IR flame detection system shall be capable of responding to a 1 foot by 1 foot gasoline fire at a distance of 50 feet. The detector shall be capable of 1.0 second response time to an intense fire signal. It shall not respond to radiation generated by arc welding, x rays, or hot surfaces, but shall be capable of responding to a fire in their presence. The UV/IR flame detector shall be in a red, copper-free alu-
minum enclosure.1The detector shall be the Det-
Tronics model C7052J, no equal. The controller shall be the Det-Tronics model R7495D Controller that fits in the Det-Tronics model Q4004 Mounting Rack, which is designed to fit standard 19 inch racks, no equal.
The UV/IR flame detector shall have one 3/4 inch NPT
2
entry for field wiring.
The controller shall have visual annunciation of fire and fault conditions. The controller shall have two red LEDs for individual detector alarm indications, one green LED for power indication, one amber LED for fault indication, two red LEDs for fire zone output indication, and one red LED for alarm indication. The controller shall have relay outputs through a plug-in backplate connector.
The signal processing shall require the UV radiation and the flickering IR radiation to exceed field adjust thresh­old levels and time delay before signalling an alarm condition. The detector shall have an 80 degree cone of vision and be of a modular plug-in design that allows the UV and IR sensor modules to be easily field replaced without the use of special tools. All optical surfaces shall be easy to access for cleaning. No metal rods shall be allowed in front of the sensor windows.
The UV/IR flame detector shall have optical testing capabilities on both the UV and IR sensor. Films that blind the UV sensor or the IR sensor shall cause a fail­ure of the optical test.
The UV/IR flame detector shall be rated for an operating temperature range of –40°F to +167°F (–40°C to +75°C) and a storage temperature of –40°F to +185°F (–40°C to +85°C). The detector shall operate over a humidity range of 0 to 95% RH and be able to withstand 100% condensing humidity for short periods of time. All print­ed circuit boards shall be coated to provide protection from environmental conditions. The UV/IR flame detec­tor shall meet MIL-STD 810C for vibration and have a swivel mounting bracket to provide a means to easily mount and aim the detector.
The UV/IR flame detector shall be explosion-proof for
Class I, Division 1, Groups B, C and D; Class II, Division 1, Groups E, F and G. The device shall be rated NEMA 4 (dust-tight, watertight). The detector shall be FM approved.
3
An explosion-proof UV/IR test lamp shall be provided to allow field testing of the UV/IR flame detection system. The test lamp shall be FM approved for use in Class I, Division 1, Groups C and D hazardous areas. The explosion-proof UV/IR test lamp shall be the Det-Tronics model W867, no equal.
25 95-8331
Table 3—Troubleshooting Guide
Indication Status
FAULT LED on Mode switch in Test position, external reset
activated, or fault in controller circuitry.
FAULT LED oi fault - the o
i
ring and/or the window of the and a detector indicated by the DETECTOR LED DETECTOR is dirty, the detector tube module has lost LED on sensitivity or is missing, or there is an open or
shorted wire between that detector and the controller.
FAULT LED One or more detectors are responding to a off and any radiation source that is not large enough to DETECTOR LED reach the fire threshold programmed into blinking slowly the controller, or one or more detectors may
be overly sensitive.
POWER LED off No power to controller.
The following options can be substituted for the item in bold:
1
or: “in a 316 stainless steel enclosure.”
2
or: “25 mm”
3
or: “flame-proof for EEx d IIB. The device shall be rated IP66 (dust-tight/water-tight). The detector shall be BASEEFA/CENELEC certi­fied.” or: “explosion-proof for Class I, Division 1, Groups C and D; Class II, Division 1, Groups E, F and G. The device shall be rated NEMA 4 (dust-tight, watertight). The detector shall be CSA certified.
ORDERING INFORMATION
When ordering, specify:
— R7495D Controller
— C7052J Detector
— Number detectors needed
— Detector housing materials
Anodized copper-free aluminum 316 stainless steel
— Approvals required
FM CSA BASEEFA/CENELEC
ACCESSORIES
— Q4004 Mounting Cage accommodates eight mod-
ules (Controllers) and fits standard 19-inch instru­ment rack. Smaller sizes are available.
— Filler panels for empty spaces in the Q4004
Mounting Cage — 000507-XXX power supplies — Cover locking assembly — Q1113 Air Shields — W867 UV/IR Test Lamp — W8067 Long Range Test Lamp — Q9001G Swivel Assembly
RECOMMENDED SPARE PARTS
Description Part Number Quantity
UV o
i
rings 002519-001 2 per 10 detectors
IR o
i
rings 003525-001 2 per 10 detectors
UV Sensor Module DE1888 1 per 10 detectors
IR Sensor Module 003895-001 1 per 10 detectors (plug-in)
003895-002 1 per 10 detectors
IR Sensor Module 005500-001 1 per 10 detectors (wire harness)
Junction box 004432-001 1 per 10 detectors circuit board
O-rings 107427-004 4 per 10 detectors
Grease 005143-001 1 per 10 detectors (silicone-free)
Window Cleaner Kit 001680-001 (six bottles)