Detcon DM-600IS User Manual

Detcon Model Series
DE
TCON, Inc.
DM-600IS
Explosion Proof and Intrinsically Safe Toxic Gas Sensors
Operator’s Installation and Instruction Manual
The Woodlands, Texas 77381
Ph.281.367.4100 / Fax 281.298.2868
www.detcon.com
January10, 2013 • Document #2448 • Revision 1.5.9
This page left intentionally blank
DM-600IS
DM-600IS Instruction Manual ii
DM-600IS
Table of Contents
1.0 DESCRIPTION ..................................................................................................................................2
1.1 Sensor Technology..........................................................................................................................2
1.2 Universal Microprocessor Control Transmitter Circuit.....................................................................3
1.3 Base Connector Board .....................................................................................................................4
1.4 Explosion Proof Enclosure...............................................................................................................4
2.0 PRINCIPLE OF OPERATION..........................................................................................................5
3.0 APPLICATION..................................................................................................................................5
3.1 Sensor Placement/Mounting ............................................................................................................5
3.2 Interference Data.............................................................................................................................5
3.3 Interference Gas List........................................................................................................................6
3.4 Interference Gas Table (page 1 of 5) ................................................................................................7
4.0 SPECIFICATIONS ..........................................................................................................................12
5.0 INSTALLATION..............................................................................................................................13
5.1 Field Wiring Table (4-20 mA output).............................................................................................13
5.2 Sensor Location............................................................................................................................. 14
5.3 Local Electrical Codes................................................................................................................... 15
5.4 Installation Procedure....................................................................................................................16
5.5 Remote Mounting Applications ..................................................................................................... 19
6.0 STARTUP.........................................................................................................................................20
6.1 Initial Operational Tests.................................................................................................................21
7.0 OPERATING SOFTWARE & MAGNETIC INTERFACE...........................................................21
7.1 Normal Operation..........................................................................................................................22
7.2 Calibration Mode........................................................................................................................... 22
7.2.1 Zero Adjustment.....................................................................................................................22
7.2.2 Span Adjustment .................................................................................................................... 22
7.3 Program Mode............................................................................................................................... 22
7.3.1 Program Status......................................................................................................................22
7.3.2 Alarm 1 Level Adjustment ......................................................................................................23
7.3.3 Alarm 2 Level Adjustment ......................................................................................................23
7.3.4 Calibration Level Adjustment.................................................................................................23
7.4 Programming Magnet Operating Instructions.................................................................................23
8.0 Software Flow Chart.........................................................................................................................24
9.0 Calibration........................................................................................................................................25
9.1 Calibration Procedure - Zero.......................................................................................................... 25
9.2 Calibration Procedure - Span .........................................................................................................25
9.3 Additional Notes............................................................................................................................26
9.4 Calibration Frequency.................................................................................................................... 27
10.0 STATUS OF PROGRAMMING: SOFTWARE VERSION, ALARMS, CALIBRATION LEVEL,
RS-485 ID, AND SENSOR LIFE................................................................................................................27
11.0 PROGRAMMING ALARMS ..........................................................................................................28
11.1 Alarm Levels.................................................................................................................................28
11.2 Alarm Reset................................................................................................................................... 28
11.3 Other Alarm Functions .................................................................................................................. 28
12.0 PROGRAM FEATURES .................................................................................................................29
DM-600IS Instruction Manual iii
DM-600IS
13.0 UNIVERSAL TRANSMITTER FEATURE (RE-INITIALIZATION)...........................................29
14.0 RS-485 PROTOCOL.........................................................................................................................30
15.0 DISPLAY CONTRAST ADJUST.....................................................................................................33
16.0 TROUBLE SHOOTING...................................................................................................................33
17.0 SPARE PARTS LIST........................................................................................................................35
18.0 WARRANTY.....................................................................................................................................37
19.0 SERVICE POLICY...........................................................................................................................37
20.0 Revision History................................................................................................................................37
Table of Figures
Figure 1 Construction of Electrochemical Sensor......................................................................................... 3
Figure 2 Universal Microprocessor Control Transmitter Circuit................................................................... 3
Figure 3 Base connector board..................................................................................................................... 4
Figure 4 Explosion-Proof Enclosure ............................................................................................................ 4
Figure 5 Functional Block Diagram............................................................................................................. 5
Figure 6 Typical Installation........................................................................................................................ 15
Figure 7 Typical Outline and Mounting Dimensions.................................................................................... 16
Figure 8 Jumper Tab Positions on Term Board ............................................................................................ 17
Figure 9 Alarm Programming Jumpers ........................................................................................................ 17
Figure 10 RS-485 ID set Dip Switches......................................................................................................... 18
Figure 11 Remote Mount wiring.................................................................................................................. 20
Figure 12 Programming Magnet .................................................................................................................. 23
Figure 13 Universal Microprocessor Control Transmitter Circuit................................................................. 23
Figure 14 Software Flow Chart.................................................................................................................... 24
Figure 15 Spare parts diagram ..................................................................................................................... 35
List of Tables
Table 1 Model #, Gas Name, and Symbol.................................................................................................... 1
Table 2 Sensor cell specifications................................................................................................................ 12
Table 3 Field wiring Table........................................................................................................................... 13
Table 4 Over-current Protection per AWG................................................................................................... 13
Table 5 RS-485 Rotary Dip Switch Settings................................................................................................. 19
Table 6 Replacement IS Sensor Head / Plug-in Replacement Sensor Cell..................................................... 36
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas 77381
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas 77381
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
DM-600IS Instruction Manual iv
This manual covers the following Models...
Model #
Gas Name
Symbol
DM-600-C2H3
O
Acetaldehyde
C2H3O
DM-600-C2H2
Acetylene
C2H2
DM-600-C3H3N
Acrylonitrile
C3H3N
DM-600-NH3 (
-
20°C)
Ammonia
NH3
DM-501-NH3 (
-
40°C)
Ammonia
NH3
DM-502-NH3
Ammonia (continuous exposure)
NH3
DM-600-AsH3
Arsine
AsH3
DM-600-Br2
Bromine
Br2DM-
600-C4H6
Butadiene
C4H6
DM-600-CS2
Carbon Disulfide
CS2DM-
600-CO
Carbon Monoxide
CODM-
600-COS
Carbonyl Sulfide
COS
DM-600-CL2
Chlorine
CL2DM-
600-CLO2
Chlorine Dioxide (>50 ppm range)
CLO2
DM-501-CLO2
Chlorine Dioxide (
≤50 ppm range)
CLO2
DM-600-B2H6
Di
borane
B2H6
DM-600-C2H6S
Dimethyl Sulfide
C2H6S
DM-600-C3H5OCL
Epichlorohydrin
C3H5OCL
DM-600-C2H5OH
Ethanol
C2H5OH
DM-600-C2H5SH
Ethyl Mercaptan
C2H5SH
DM-600-C2H4
Ethylene
C2H4
DM-600-C2H4O
Ethylene Oxide
C2H4O
DM-600-F2
Fluorine
F2DM-
600-CH2O
F
ormaldehyde
CH2O
DM-600-GeH4
Germane
GeH4
DM-600-N2H4
Hydrazine
N2H4
DM-600-H2
Hydrogen (ppm range)
H2DM-
501-H2
Hydrogen (% LEL range)
H2DM-
600-HBr
Hydrogen Bromide
HBrDM-
600-HCL
Hydrogen Chloride
HCL
DM-600-HCN
Hydrogen Cyanide
HCN
DM-600-HF
Hydrogen Fluoride
HFDM-
600-H2S
Hydrogen Sulfide
H2SDM-
600-CH3OH
Methanol
CH3OH
DM-600-CH3SH
Methyl Mercaptan
CH3SH
DM-600-NO
Nitric Oxide
NODM-
600-NO2
Nitrogen Dioxide
NO2
DM-600-O3
Ozone
O3DM-
600-COCL2
Phosgene
COCL2
DM-600-PH3
Phosphine
PH3DM-
600-SiH4
Silane
SiH4
DM-600-SO2
Sulfur Dioxide
SO2DM-
600-C4H8S
Tetrahydrothiophene
C4H8S
DM-600-C4H4S
Thiophane
C4H4S
DM-600-C6H5CH3
Toluene
C6H5CH3
DM-600-C4H6O2
Vinyl Acetate
C4H6O2
DM-600-C2H3CL
Vinyl Chloride
C2H3CL
Table 1 Model #, Gas Name, and Symbol
DM-600IS
DM-600IS Instruction Manual Rev 1.5.9 Page 1 of 37
DM-600IS
Intrinsically Safe
1.0 DESCRIPTION
Detcon MicroSafeModel DM600IS, toxic sensors are nonintrusive “Smart” sensors designed to detect and monitor for toxic gas in the ppm range. One of the primary features of the sensor is its method of automatic calibration which guides the user through each step via instructions displayed on the backlit LCD. The sensor features LED indicators for 2 ALARMS, FAULT and CAL status, field adjustable, fully programmable alarms and provides relays for two alarms plus fault as standard. The sensor comes with two different outputs: analog 4-20 mA, and serial RS-485. These outputs allow for greater flexibility in system integration and installation. The microprocessor supervised electronics are packaged as a universal plugin transmitter module that mates to a standard connector board. Both are housed in an explosion proof condulet that includes a glass lens. A 16 character alpha/numeric indicator is used to display sensor readings as well as the sensor’s menu driven features via a handheld programming magnet.
Typical ranges of detection are 0-10ppm, 0-25ppm, 0-50ppm, and 0-100ppm. Other ranges are available and all ranges are covered by this manual. To determine sensor model number, reference the label located on the enclosure cover.
Sensor Head
To determine gas type and range, reference labeling on the intrinsically-safe sensor head.
1.1 Sensor Technology
The sensors are electrolytic chemical cells. Each cell consists of three electrodes embedded in an electrolyte solution all housed beneath a diffusion membrane. Sensitivity to specific target gases is achieved by varying composition of any combination of the sensor components. Good specificity is achieved in each sensor type. The cells are diffusion limited via small capillary barriers resulting in long service life of up to 3 or more years. The fuel cell is packaged as field replaceable plug-in sensor via gold plated pins. Pre-amplifier and intrinsically safe barrier circuits are epoxy potted in the stainless steel housing and include the mating sockets for the sensor.
DM-600IS Instruction Manual Rev 1.5.9 Page 2 of 37
DM-600IS
Figure 1 Constructionof Electrochemical Sensor
1.2 Universal Microprocessor Control Transmitter Circuit
The control circuit is microprocessor based and is packaged as a universal plug-in field replaceable module, facilitating easy replacement and minimum down time. The universality includes the ability to set it for any range concentration and for any gas type. These gas and range settings must be consistent with the IS Sensor Head it is mated with. Circuit functions include a basic sensor pre-amplifier, on-board power supplies, microprocessor, back lit alpha numeric display, fault, alarm, and calibration status LED indicators, magnetic programming switches, an RS-485 communication port, and a linear 4-20 mA DC output.
Figure 2 Universal Microprocessor Control Transmitter Circuit
DM-600IS Instruction Manual Rev 1.5.9 Page 3 of 37
DM-600IS
1.3 Base Connector Board
The base connector board is mounted in the explosion proof enclosure and includes: the mating connector for the control circuit, reverse input and secondary transient suppression, input filter, alarm relays, lugless terminals for all field wiring, and a terminal strip for storing unused programming jumper tabs. The alarm relays are contact rated 5 amps @ 125 VAC, 5 amps @ 30 VDC and coil rated at 24 VDC. Gold plated program jumpers are used to select either the normally open or normally closed relay contacts.
NOTE: The yellow wire should not be connected and should be cut off!
Figure 3 Base connector board
1.4 Explosion Proof Enclosure
The transmitter electronics are packaged in a cast metal explosion proof enclosure. The enclosure is fitted with a threaded cover that has a glass lens window. Magnetic program switches located behind the transmitter module face plate are activated through the lens window via a hand-held magnetic programming tool allowing non-intrusive operator interface with the sensor. Calibration can be accomplished without removing the cover or declassifying the area. Electrical classification is Class 1; Groups B, C, D; Division 1 (explosion proof). The sensor housing section employs an Intrinsically Safe Barrier circuit which allows for the safe usage of plastic housing materials in the lower section. This design benefit avoids the requirement for stainless steel flame arrestors which reduce the sensitivity and response time to “active” gas species such as NH3, CL2, CLO2, and HCL...etc.
Transmitter Electronics in Explosion-Proof Housing
Intrinsically Safe Sensor Head
Figure 4 Explosion-Proof Enclosure
DM-600IS Instruction Manual Rev 1.5.9 Page 4 of 37
DM-600IS
NOTE
: Interference factors may differ from sensor to sensor and with life time. I
t is not
2.0 PRINCIPLE OF OPERATION
Method of detection is by an electrochemical reaction at the surface of an electrode called the sensing electrode. Air and gas diffuse through the capillary diffusion barrier. The controlling circuit maintains a small external operating voltage between the sensing and counter electrodes of the proper bias and magnitude so that no current flows to or from the reference electrode while its potential is maintained at the correct fixed voltage — usually ground. The electrochemical reaction creates a change in current flow from the counter electrode to the sensing electrode. This change in current is proportional to the gas concentration and is reversible. The quick response of the sensor results in continuous monitoring of ambient air conditions. The Intrinsically Safe Sensor Housing design allows direct contact of the target gas to the electrochemical sensor, thus maximizing response time, detectability and repeatability.
Figure 5 FunctionalBlock Diagram
3.0 APPLICATION
3.1 Sensor Placement/Mounting
Sensor location should be reviewed by facility engineering and safety personnel. Area leak sources and perimeter mounting are typically used to determine number and location of sensors. The sensors are generally located 2 - 4 feet above grade.
3.2 Interference Data
Detcon Model DM-600IS series electrochemical sensors are subject to interference from other gases. This interaction is shown in the table in section 3.4 as the relation between the amount of the interfering gas applied to the sensor, and the corresponding reading that will occur. All measurements are in ppm unless otherwise noted.
The table is laid out with the Model Number of each sensor in a column on the left side of the page. The interfering gases are listed in a row across the top of the page. Each page lists all Model Numbers but 5 pages are necessary to list all interfering gases, thus each page is a repeat of the full line of Detcon sensors. Be sure to reference each page to ascertain the full listing of interfering gases for a particular sensor.
As an example, the first listing shows that the Model DM-600IS-C2H30 acetaldehyde sensor will have an interference reading of 340 ppm if 40 ppm of C2H2 (Acetylene) is applied.
advisable to calibrate with interference gases. They should be used as a guide only
DM-600IS Instruction Manual Rev 1.5.9 Page 5 of 37
3.3 Interference Gas List
Gas Name
Symbol
Gas Name
Symbol
Acetaldehyde
C2H3O
Hydrocarbons
C-H’s
Acetylene
C2H2
Hydrocarbons (unsaturated)
C-H’s (u)
Acrylonitrile
C3H3N
Hydrogen
H2
Alcohols
Alcohols
Hydrogen Bromide
HBr
Amines
Amines
Hydrogen Chloride
HCL
Ammonia
NH3
Hydrogen Cyanide
HCN
Arsenic Trifluoride
AsF3
Hydrogen Fluoride
HF
Arsenic Pentafluoride
AsF5
Hydrogen Selenide
HSe
Arsine
AsH3
Hydrogen Sulfide
H2S
Boron Trifluoride
BF3
Iodine
I2
Bromine
Br2
Isopropanol
C3H8O
Butadiene
C4H6
Methane
CH4
Buten
-1Buten
-1Methanol
CH3OH
Carbon Dioxide
CO2
Methyl
-Ethyl-K
etone
C4H8O
Carbon Disulfide
CS2
Methyl Mercaptan
CH3SH
Carbon Oxide Sulfide
COS
Nitric Oxi
deNOCarbon Monoxide
CO
Nitrogen
N2
Carbonyl Sulfide
COS
Nitrogen Dioxide
NO2
Chlorine
CL2
Ozone
O3
Chlorine Dioxide
CLO2
Phosgene
COCL2
Chlorine Trifluoride
CLF3
Phosphine
PH3
Diborane
B2H6
Phosphorous Trifluoride
PF3
Dimethyl Sulfide
C2H6S
Silane
SiH4
Disilane
Si2H6
Silicon
Si
Epichlorohydrin
C3H5OCL
Silicon Tetra Fluoride
SiF4
Ethanol
C2H5OH
Sulfur Dioxide
SO2
Ethyl Mercaptan
C2H5SH
Tetrahydrothiophene
C4H8S
Ethylene
C2H4
Thiophane
C4H4S
Ethylene Oxide
C2H4O
Toluene
C6H5CH3
Fluorine
F2
Tun
gsten Hexafluoride
WF6
Formaldehyde
CH2O
Vinyl Acetate
C4H6O2
Germane
GeH4
Vinyl Chloride
C2H3CL
Hydrazine
N2H4
DM-600IS
DM-600IS Instruction Manual Rev 1.5.9 Page 6 of 37
DM-600IS
DM-600IS-C3H3N
DM-600IS-NH3(-
20°C)
DM-501IS-NH3(-
40°C)
DM-502IS-NH3 (CE)
DM-600IS-AsH3
DM-600IS-Br2
DM-600IS-C4H6
DM-600IS-CS2
DM-600IS-CO
DM-600IS-COS
DM-600IS-CL2
DM-600IS-CLO2 (>10ppm)
DM-501IS-CL
O2 (≤10ppm)
DM-600IS-B2H6
DM-600IS-C2H6S
DM-600IS-C3H5OCL
DM-600IS-C2H5OH
DM-600IS-C2H5SH
DM-600IS-C2H4
DM-600IS-C2H4O
DM-600IS-F2
DM-600IS-CH2O
DM-600IS-GeH4
DM-600IS-N2H4
200=0.04
n/d
DM-600IS-H2 (ppm
)
n/d
n/d
DM-501IS-H2 (LEL)
100=0
n/d
DM-600IS-HBr
n/d
n/d
DM-600IS-HCL
n/d
n/d
DM-600IS-HCN
n/d
n/d
DM-600IS-H
F
n/d
yes
n/d
DM-600IS-H2S
n/d
n/d
DM-600IS-CH3OH
n/d
n/d
DM-600IS-C
H3SH
n/d
n/d
DM-600IS-NO
n/d
n/d
DM-600IS-NO2
n/d
n/d
DM-600IS-O3
n/d
n/d
DM-600IS-COCL2
50=0.5
n/d
DM-600IS-PH3
100=0.01
n/d
DM-600IS-SiH4
100=<1
n/d
DM-600IS-SO2
n/d
n/d
DM-600IS-C4H8S
n/d
n/d
DM-600IS-C4H4S
n/d
n/d
DM-600IS-C6H5CH3
n/d
n/d
DM-600IS-C4H6O2
n/d
n/d
DM-600IS-C2H3CL
n/d
n/d
3.4 Interference Gas Table (page 1 of 5)
NOTE: Reference the listing in Section 3.3 to match model number with gas name. Reference the listing in
section 3.3 to match the interfering gas symbol with the gas name.
Model Number C2H30 C2H2 C3H3N Alcohols Amines NH3 AsF3 AsF5 AsH3 BF3 Br2 C4H6 Buten-1
DM-600IS-C2H3O n/a 40=340 40=75 n/d n/d n/d n/d n/d n/d n/d n/d 40=170 n/d DM-600IS-C2H2 340=40 n/a 340=75 n/d n/d n/d n/d n/d n/d n/d n/d 340=170 n/d
75=40 75=340 n/d n/d n/d n/d n/d n/d n/d n/d n/d 75=170 n/d
n/d n/d n/d 1000=0 yes n/d n/a n/d n/d 1=0 n/d n/d n/d n/d n/d n/d n/d n/d yes n/d n/d n/d n/d 1=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 100=0.01 n/d n/a n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/a n/d n/d 170=40 170=340 170=75 n/d n/d n/d n/d n/d n/d n/d n/d n/a n/d 140=40 140=340 140=75 n/d n/d n/d n/d n/d n/d n/d n/d 140=170 n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 135=40 135=340 135=75 n/d n/d n/d n/d n/d n/d n/d n/d 135=170 n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1=0.55 n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1=0.18 n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d 100=0.013 n/d n/d 0.15=0.2 n/d n/d n/d n/d 150=40 150=340 150=75 n/d n/d n/d n/d n/d n/d n/d n/d 150=170 n/d
50=40 50=340 50=75 n/d n/d n/d n/d n/d n/d n/d n/d 50=170 n/d
180=40 180=340 180=75 n/d n/d n/d n/d n/d n/d n/d n/d 180=170 n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 220=40 220=340 220=75 n/d n/d n/d n/d n/d n/d n/d n/d 220=170 n/d 275=40 275=340 275=75 n/d n/d n/d n/d n/d n/d n/d n/d 275=170 n/d
n/d n/d n/d 1000=0 n/d n/d n/d n/d 0.1=0 n/d yes n/d n/d n/d 330=40 330=340 330=75 n/d n/d n/d n/d n/d n/d n/d n/d 330=170 n/d
n/d n/d n/d n/d n/d 100=<1 n/d n/d 0.2=0.14 n/d n/d n/d n/d
n/d n/d n/d 1000=0 n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d 1000=0 No
n/d n/d n/d 1000=0 No
n/d n/d n/d 1000=0 n/d
n/d n/d n/d 1000=0 n/d
n/d n/d n/d n/d n/d 415=40 415=340 415=75 n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d 1000=0 n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d
45=40 45=340 45=75 n/d n/d
55=40 55=340 55=75 n/d n/d 200=40 200=340 200=75 n/d n/d 200=40 200=340 200=75 n/d n/d
n/a = not applicable n/d = no data
n/d 0.1=0.1 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 0.1=0.3 n/d n/d n/d n/d n/d 0.1=0.3 n/d n/d n/d n/d n/d 0.1=0 n/d yes n/d n/d n/d
yes n/d 0.1=0 yes n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 415=170 n/d n/d n/d n/d n/d 275=170 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 0.1=0.05 n/d yes n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1=1 n/d n/d n/d n/d n/d 0.2=0.14 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 45=170 1%=1.8 n/d n/d n/d n/d 55=170 n/d n/d n/d n/d n/d 200=170 n/d n/d n/d n/d n/d 200=170 n/d
DM-600IS Instruction Manual Rev 1.5.9 Page 7 of 37
DM-600IS
DM-600IS-C3H3N
DM-600IS-NH3
DM-501IS-NH3
DM-502IS-NH3 (CE)
DM-600IS-AsH3
DM-600IS-Br2
DM-600IS-C4H6
DM-600IS-CS2
DM-600IS-CO
DM-600IS-COS
DM-600IS-CL2
DM-600IS-CLO2 (>10ppm)
DM-501IS-CLO2 (
10ppm)
DM-600IS-B2H6
DM-600IS-C2H6S
DM-600IS-C3H5OCL
DM-600IS-C2H5OH
DM-600IS-C2H5SH
DM-600IS-C2H4
DM-600IS-C2H4O
DM-600IS-F2
DM-600IS-CH2O
DM-600IS-GeH4
DM-600IS-N2H4
n/d
n/d
DM-600IS-H2 (ppm
)
n/d
n/d
DM-6
01IS-H2 (LEL)
n/d
n/d
DM-600IS-HBr
n/d
yes n
/d
DM-600IS-HCL
n/d
1=yes n/d
DM-600IS-HCN
n/d
n/d
DM-600IS-H
F
n/d
yes
n/d
DM-600IS-H2S
n/d
n/d
DM-600IS-CH3OH
n/d
n/d
DM-600IS-CH3SH
n/d
n/d
DM-600IS-NO
n/d
n/d
DM-600IS-NO2
n/d
n/d
DM-600IS-O3
0.1=0.12
1=1(theor.)
DM-600IS-COCL2
n/d
n/d
DM-600IS-PH3
n/d
n/d
DM-600IS-SiH4
300=0
n/d
n/d
DM-600IS-SO2
300=
<5
n/d
n/d
DM-600IS-C4H8S
n/d
n/d
DM-600IS-C4H4S
n/d
n/d
DM-600IS-C6H5CH3
n/d
n/d
DM-600IS-C4H6O2
n/d
n/d
DM-600IS-C2H3CL
n/d
n/d
Interference Gas Table (page 2 of 5)
Model Number CO2 CS2 CO COS CL2 CL02 CLF3 B2H6 C2H6S Si2H6 C3H5OCL C2H5OH
DM-600IS-C2H3O n/d 40=140 40=100 40=135 n/d n/d n/d n/d 40=150 n/d 40=50 40=180 DM-600IS-C2H2 n/d 340=140 340=100 340=135 n/d n/d n/d n/d 340=150 n/d 340=50 340=180
n/d 75=140 75=100 75=135 n/d n/d n/d n/d 75=150 n/d 75=50 75=180
(-20°C)
(-40°C)
n/a = not applicable n/d = no data
5000=0 n/d 1000=0 n/d 1=0 n/d n/d 0.1=0 n/d n/d n/d n/d
5000=0 n/d 300=100 n/d 5=0 n/d n/d 0.1=0 n/d n/d n/d n/d
n/d n/d 300=8 n/d 1=1 10%=15 n/d n/d n/d n/d n/d n/d
5000=0 n/d 300=0 n/d 0.5 = -0.04 n/d n/d 0.2=0.15 n/d 5=yes n/d n/d n/d
n/d n/d 300=0 n/d 1=2 1=6 n/d n/d n/d n/d n/a n/d n/d 170=140 170=100 170=135 n/d n/d n/d n/d 170=150 n/d 170=50 170=180 n/d n/a 140=100 140=135 n/d n/d n/d n/d 140=150 n/d 140=50 140=180 n/d n/d n/a n/d 1=0 n/d n/d n/d n/d n/d n/d 200=0 n/d 135=140 135=100 n/a n/d n/d n/d n/d 135=150 n/d 135=50 135=180 n/d n/d 300=0 n/d n/a n/d n/d n/d n/d n/d n/d n/d
n/d n/d 300=0 n/d 3=1 n/a n/d n/d n/d n/d n/d n/d 5000=0 n/d 1000=0 n/d 1=0.9 n/a yes n/d 0.1=0 n/d n/d n/d n/d 5000=0 n/d 300=0 n/d 0.5 = -0.05 n/d n/d n/a n/d 5=yes n/d n/d n/d
n/d 150=140 150=100 150=135 n/d n/d n/d n/d n/a n/d 150=50 150=180
n/d 50=140 50=100 50=135 n/d n/d n/d n/d 50=150 n/d n/a 50=180
n/d 180=140 180=100 180=135 n/d n/d n/d n/d 180=150 n/d 180=50 n/a
n/d n/d 300≤5 n/d 1 = -0.6 n/d n/d n/d n/d n/d n/d n/d
n/d 220=140 220=100 220=135 n/d n/d n/d n/d 220=150 n/d 220=50 220=180
n/d 275=140 275=100 275=135 n/d n/d n/d n/d 275=150 n/d 275=50 275=180 5000=0 n/d 1000=0 n/d 1=1.3 n/d n/d n/d n/d n/d n/d n/d
n/d 330=140 330=100 330=135 n/d n/d n/d n/d 330=150 n/d 330=50 330=180 5000=0 n/d 300=0 n/d 0.5 = -0.04 n/d n/d 0.2=0.11 n/d 5=yes n/d n/d n/d 5000=0 n/d 1000=0 n/d 1=0
n/d n/d 300=<30 n/d 1=0
1000-0 n/d 50=6 n/d 5=0 5000=0 n/d 1000=0 n/d 5=1 5000=0 n/d 1000=0 n/d 5=1 5000=0 n/d 1000=0 n/d 5 = -1 5000=0 n/d 1000=0 n/d 1=0.4
n/d n/d 300=≤1.5 n/d 1 = ≈ -0.2 n/d 415=140 415=100 415=135 n/d n/d n/d 300 ≤ 3 n/d 1 = -0.4 n/d n/d 300=0 n/d 1=0
n/d n/d 300=0 n/d 1= ≈1
5000=0 n/d 300=0 n/d 1=1.4 5000=0 n/d 1000=0 n/d 1=0 5000=0 n/d 300=0 n/d 0.5 = -0.04 5000=0 n/d
n/d n/d
5000=0 n/d 0.1%=1.2 1%=10 n/d
n/d 45=140 45=100 45=135 n/d n/d 55=140 55=100 55=135 n/d n/d 200=140 200=100 200=135 n/d n/d 200=140 200=100 200=135 n/d
n/d 0.5 = -0.04 n/d 1=<0.5
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
0.1=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 415=150 n/d 415=50 415=180 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
0.2=0.15 n/d 5=yes n/d n/d n/d
0.2=0.11 n/d 5=yes n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 45=150 n/d 45=50 45=180 n/d 55=150 n/d 55=50 55=180 n/d 200=150 n/d 200=50 200=180 n/d 200=150 n/d 200=50 200=180
DM-600IS Instruction Manual Rev 1.5.9 Page 8 of 37
Interference Gas Table (page 3 of 5)
DM-600IS-C3H3N
DM-
600IS-NH3(-
20°C)
n/d
DM-501IS-NH3(-
40°C)
yes
n/d
DM-502IS-NH3 (CE)
DM-600IS-AsH3
5=0
DM-600IS-Br2
5=0
DM-600IS-C4H6
DM-600IS-CS2
DM-600IS-CO
DM-600IS-COS
DM-600IS-CL2
5=0
10=0
DM-600IS-CLO2 (>10ppm)
5=0
10=0
DM-501IS-CLO2 (
10ppm)
n/d
DM-600IS-B2H6
n/d
DM-600IS-C2H6S
DM-600IS-C3H5OCL
DM-600IS-C2H5OH
DM-600IS-C2H5SH
DM-600IS-C2H4
DM-600IS-C2H4O
DM-600IS-F2
n/d
DM-600IS-CH2O
n/d
DM-600IS-GeH4
n/d
5=0
DM-600IS-N2H4
n/d
%range=0
n/d
5=0
.1
DM-600IS-H2 (ppm
)
n/d
n/d
n/d
5=0
DM-501IS-H2 (LEL)
n/d
n/d
n/d
DM-600IS-HBr
n/d
%range=0
n/d
1%=0
15=
1
DM-600IS-HCL
n/d
%range=0
n/d
1%=0
15=
1
DM-600IS-HCN
n/d
%range=0
n/d1000=0
5=0
DM-600IS-H
F
n/d
%range=0
n/d
5=
3.3
DM-600IS-H2S
n/d
n/d
n/d
5=0
DM-600IS-CH3OH
n/d
n/d
n/d
DM-600IS-
CH3SH
n/d
n/d
n/d
5=0
10=0
DM-600IS-NO
n/d
n/d
n/d
5=<110=0
DM-600IS-NO2
n/d
n/d
n/d
5=0
10=0
DM-600IS-O3
n/d
n/dn/d
10
=0
DM-600IS-COCL2
n/d
%range=0
n/d
5=0
DM-600IS-PH3
n/d
%range=0
n/d
5=0
10=0
.1
DM-600IS-SiH4
n/d
%range=0
n/d
5=010=
1
DM-600IS-SO2
n/d
n/d
n/d
5=0
10=
<5
DM-600IS-C4H8S
n/d
%range=0
yes
n/d
DM-600IS-C4H4S
n/d
n/d
n/d
DM-600IS-C6H5CH3
n/d
n/d
n/d
DM-600IS-C4H6O2
n/d
n/d
n/d
DM-600IS-C2H3CL
n/d
n/d
n/d
Model Number C2H4 C2H4O F2 CH2O GeH4 N2H4 C-H’s C-H’s (U) H2 HBr HCL HCN HF
DM-600IS-C2H3O 40=220 40=275 n/d 40=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d DM-600IS-C2H2 340=220 340=275 n/d 340=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
75=220 75=275 n/d 75=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d 1=0 n/d %range=0 n/d n/d n/d n/d 1=0 n/d %range=0
100=0 n/d n/d n/d n/d n/d n/d n/d 200=4 n/d 5 = -3 10=0 n/d
n/d n/d n/d n/d 1=0.4 n/d %range=0 n/d 3000=0 n/d
100=0 n/d n/d n/d n/d n/d n/d n/d 100=0 n/d 170=220 170=275 n/d 170=330 n/d n/d n/d n/d n/d n/d n/d n/d n/a 140=220 140=275 n/d 140=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
100=<100 n/d n/d n/d n/d n/d n/d n/d 100 = <60 n/d 5=0 10 = -2 n/d
135=220 135=275 n/d 135=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
100=0 n/d n/d n/d n/d n/d n/d n/d 100=0 n/d
100=0 n/d n/d n/d n/d n/d n/d n/d 100=0 n/d
n/d n/d yes n/d n/d 1=0 n/d %range=0 n/d n/d n/d n/d 1=0.53 n/d %range=0
150=220 150=275 n/d 150=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
50=220 50=275 n/d 50=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
180=220 180=275 n/d 180=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
100=0 n/d n/d n/d n/d n/d n/d n/d 1%=<15 n/d 5=0 10=0 n/d
n/d 220=275 n/d 220=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
275=200 n/a n/d 275=330 n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/a n/d n/d n/d %range=0
330=220 330=275 n/d n/a n/d n/d n/d
n/d n/d n/d n/d n/a n/d %range=0 n/d n/d n/d n/d n/d
100= ≈80 n/d n/d n/d n/d
yes n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d 1=n/d n/d n/d n/d n/d n/d n/d n/d yes n/d n/d 1=0
100=0 n/d n/d n/d n/d 415=220 415=275 n/d 415=330 n/d
100=0 n/d n/d n/d n/d
100=0 n/d n/d n/d n/d
100=0 n/d n/d n/d n/d
n/d n/d 0.1=0.07 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1=0.4 n/d n/d n/d n/d 1=1.0
100=0 n/d n/d n/d n/d
1%=2.4 n/d n/d n/d n/d 45=220 45=275 n/d 45=330 n/d
55=220 55=275 n/d 55=330 n/d 200=220 200=275 n/d 200=330 n/d 200=220 200=275 n/d 200=330 n/d
n/a = not applicable n/d = no data
1%=0 n/d 5=0 10=0 4=0
1000=35 n/d yes n/d 10 = -18 n/d
1%=0 n/d n/d n/d n/d
3000=0 n/d 5=0 10=0.13 4=0
1%=0 n/d 5=0 1 = -3 3=0
n/d n/d n/d n/d n/d 3000=0 n/d 1000=0 n/d
n/d n/d
n/d n/d n/d 10=0 n/d
n/a 1=1
1=1 n/a
n/d
1%=0 n/d
1%=<5 n/d
n/d n/d n/d n/d n/d
1%=<10 n/d
100=0 n/d 100=0 n/d
1%=0.003 n/d
1%=0 n/d 3000=0 n/d 3000=0 n/d
100=0 n/d
0.1%=0.3 n/d yes n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
DM-600IS
10=0.1 4=0
10=0 n/d
n/d n/d
10=1 4=0
n/d 3=0
10 = ≈3 n/d
3=0
3=0 n/a 3=0 n/d n/a
10=0 n/d
n/d n/d n/d
10=0.33 5=0
5=0 3=0
4=0
4=0
n/d
DM-600IS Instruction Manual Rev 1.5.9 Page 9 of 37
DM-600IS
DM-600IS-C3H3N
DM-600IS-NH3(-
20°C)
DM-501IS-NH3(-
40°C)
DM-502IS-NH3 (CE)
DM-600IS-AsH3
DM-600IS-Br2
DM-600IS-C4H6
170
=275
DM-600IS-CS2
140
=275
DM-600IS-CO
DM-600IS-COS
DM-600IS-CL2
15
=-0.75
35=
0
DM-600IS-CLO2 (>10ppm)
15=
0.25
DM-501IS-CLO2 (
10ppm)
DM-600IS-B2H6
DM-600IS-C2H6S
150
=415
DM-600IS-C3H5OCL
50
=415
50
=275
DM-600IS-C2
H5OH
180
=415
180
=275
DM-600IS-C2H5SH
n/d
DM-600IS-C2H4
220
=415
220
=275
DM-600IS-C2H4O
275
=415
275
=275
DM-600IS-F2
n/d
DM-600IS-CH2O
330
=415
DM-600IS-GeH4
1=0
100%=0
DM-600IS-N2H4
1=0
.1
n/d
100%=0
DM-600IS-H2 (ppm
)
15=
<3
n/d
DM-501IS-H2 (LEL)
n/d
n/d
DM-600IS-HBr
10=
2.75
n/d
100%=0
DM-600IS-HCL
10=
2.75
n/d
100%=0
DM-600IS-HCN
10=0
n/d
100%=0
DM-600IS-H
F
10=0
n/d
100%=0
DM-600IS-H2S
n/d
DM-600IS-CH3OH
n/d
DM-600IS-CH3SH
n/d
5 =-1.0
DM-600IS-NO
15=
≈5
n/d
5 =
<1.5
DM-600IS-NO2
15=-0.75
n/d
DM-600IS-O3
1
=-015
n/d
100%=0
DM-600IS-COCL2
1=0
n/d
100%=0
DM-600IS-PH3
1=0
n/d
100%=0
DM-600IS-SiH4
1=0
n/d
n/d
100%=0
DM-600IS-SO2
15=0
n/d
35=
0
DM-600IS-
C4H8S
20=0.3
1300=64
n/d
10=7.5
DM-600IS-C4H4S
45
=415
n/d45=275
DM-600IS-C6H5CH3
55
=415
n/d55=275
DM-600IS-C4H6O2
200
=415
n/d
200=27
5
DM-600IS-C2H3CL
200
=415
n/d
200=27
5
Interference Gas Table (page 4 of 5)
Model Number HSe H2S I2 C3H8O CH4 CH3OH C4H8O CH3SH NO N2 NO2 03 COCL2
DM-600IS-C2H3O n/d n/d n/d n/d n/d 40=415 n/d 40=275 n/d n/d n/d n/d n/d DM-600IS-C2H2 n/d n/d n/d n/d n/d 340=415 n/d 340=275 n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d 75=415 n/d 75=275 n/d n/d n/d n/d n/d
0.1=0 10=0 n/d n/d n/d n/d n/d n/d n/d 100%=0 n/d n/d n/d
n/d 14=18 n/d n/d n/d yes n/d n/d n/d n/d 100%=0 10 = -5 n/d n/d n/d 15=30 n/d n/d n/d n/d n/d n/d 35=6 n/d 5 = -1 n/d n/d
0.05=0.005 1=0 n/d n/d n/d n/d n/d n/d n/d 100%=0 n/d n/d n/d
n/d 15 = -1.5 n/d n/d n/d n/d n/d n/d 35=0 n/d 5 = ≈10 n/d n/d
n/a = not applicable n/d = no data
n/d n/d n/d n/d n/d 170=415 n/d n/d n/d n/d n/d n/d 140=415 n/d
n/d 15=<0.3 n/d n/d n/d n/d n/d n/d 35=≤7 n/d 5=0.5 n/d n/d
n/d n/d n/d n/d n/d 135=415 n/d 135=275 n/d n/d n/d n/d n/d n/d n/d n/d 10= -0.015 n/d n/d n/d n/d n/d n/d n/d n/d yes n/d yes n/d n/d
0.05=0.006 1=0 n/d n/d n/d n/d n/d n/d n/d 100%=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1:3 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1 = -1.5 n/d n/d n/d n/d n/d n/d n/d n/d
0.05=0.005 n/d n/d n/d
0.1=0
0.1=0 n/d n/d n/d n/a n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 1:2 n/d n/d n/d n/d n/d n/d n/d n/d
0.05=0.005
0.05=0.005 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 35=0 n/d 5=1.66 n/d n/d
n/d 1:15 n/d n/d n/d n/d n/d n/d n/d n/d 5=8 35=<6 n/d 5 = -1.5 n/d n/d n/d n/d n/d n/d n/d 100%=0 1=0.05 0.1=0.2 n/d
n/d 330=275 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d yes n/d 1%=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d
yes n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 100%=0
n/d n/d n/d 35= ≈10 n/d 5=0 n/d n/d n/d yes n/d n/d 10=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 2:1 35=<2 n/d 5 = -0.5 n/d n/d
415=275 n/d n/d n/d n/d n/d
n/a 35=<4 n/d n/d 100=0 n/d n/d 35=0 n/d n/d n/d n/d n/d 10=0 n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d 5 = ≈5 n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d
1 = -0.25 0.1 = -0.1 n/d
n/d n/d 0.1=0 n/d n/d 0.1=0
10 = -12 0.1=0 n/d
10=0.1 n/d n/d
n/d n/d n/d n/d
1=0.7 n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d 5 = ≈ -5 n/d n/d
100%=0 10=0.9 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
DM-600IS Instruction Manual Rev 1.5.9 Page 10 of 37
DM-600IS
DM-600IS-C3H3N
DM-60
0IS-NH3
DM-501IS-NH3
DM-502IS-NH3 (CE)
DM-600IS-AsH3
DM-600IS-Br2
DM-600IS-C4H6
17
0=45
170=55DM-
600IS-CS2
1
40=45
1
40=55DM-600IS-CO
DM-600IS-COS
DM-600IS-CL2
DM-600IS-CLO2
DM-501IS-CLO2
DM-600IS-B2H6
DM-600IS-C2H6S
150=45
150=55DM-
600IS-C3H5OCL
50=45
50=55DM-
600IS-C2H5OH
180=45
180=55DM-
600IS-C2H5SH
DM-600IS-C2H4
22
0=45
220=55DM-
600IS-C2H4O
275
=45
275=55DM-
600IS-F2
DM-600IS-CH2O
DM-600IS-GeH4
DM-600IS-N2H4
2=0
n/d
n/dDM-
600IS-H2 (ppm
)
5
=0
n/d
n/dDM-
501IS-H2 (LEL)
2=0
n/d
n/dDM-
600IS-HBr
5=2.5
n/d
n/dDM-
600IS-HCL
5=2.5
n/d
n/dDM-
600IS-HCN
2=0
n/d
n/dDM-
600IS-H
F
yes
n/d
n/d
n/dDM-
600IS-H2S
5=<1
n/d
n/dDM-
600IS-CH3OH
n/d
415=45
415=55
DM-600IS-CH3SH
5=<2
n/d
n/dDM-
600IS-NO
5
=0
n/d
n/dDM-
600IS-NO2
5
=-0.025
n/d
n/dDM-
600IS-O3
2=0
n/d
n/dDM-
600IS-COCL2
2=0
n/d
n/dDM-
600IS-PH3
2=0
n/d
n/dDM-
600IS-SiH4
2=0
n/d
n/dDM-
600IS-SO2
n/
a
n/d
n/dDM-
600IS-C4H8S
2=0.6
n/
a
n/dDM-600IS-C4H4S
n/d
n/d
45=55
DM-600IS-C6H5CH3
n/d
55
=45
n/a
DM-600IS-C4H6O2
n/d
20
0=45
200=55DM-
600IS-C2H3CL
n/d
20
0=45
200=55
Interference Gas Table (page 5 of 5)
Model Number PH3 PF3 SiH4 Si SiF4 SO2 C4H8S C4H4S C6H5CH3 WF6 C4H6O2 C2H3CL C2H5SH C6H5CH3
DM-600IS-C2H3O n/d n/d n/d n/d n/d n/d n/d 40=45 n/d n/d 40=200 40=200 n/d 40=55 DM-600IS-C2H2 n/d n/d n/d n/d n/d n/d n/d 340=45 n/d n/d 340=200 340=200 n/d 340=55
n/d n/d n/d n/d n/d n/d n/d 75=45 n/d n/d 75=200 75=200 n/d 75=55
(-20°C)
(-40°C)
(>10ppm)
(≤10ppm)
n/a = not applicable n/d = no data
300=0 n/d n/d n/d n/d 2=0 n/d n/d n/d n/d n/d n/d n/d n/d
0.3=0 n/d n/d n/d n/d yes n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d 5= -0.5 n/d n/d n/d n/d n/d n/d n/d n/d
0.1=0.11 n/d 1=0.56 n/d n/d 2=0 n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d 5= -0.1 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 5=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 135=45 n/d n/d 135=200 135=200 n/d 135=55 n/d n/d n/d n/d n/d 5=-0.05 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 5=-0.016 n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
0.1=0.14 n/d 1=0.72 n/d n/d 2=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 5=<3 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 2=0 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 330=45 n/d n/d 330=200 330=200 n/d 330=55
0.1=0.13 n/d 1=1 n/d n/d 2=0 n/d n/d n/d n/d n/d n/d n/d n/d
0.3=0.1 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
0.1=0.3 n/d n/d n/d n/d
0.1=0.3 n/d n/d n/d n/d
0.3=0 n/d n/d n/d n/d
0.1=0 yes n/d n/d n/d 3=4 (theor.)
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
0.3=0.03 n/d 1=0.015 n/d n/d
0.3=0 n/d n/d n/d n/d
n/a n/d 1=0.56 n/d n/d
0.1=0.13 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d
n/d n/d 170=200 170=200 n/d n/d n/d 140=200 140=200 n/d
n/d n/d 150=200 150=200 n/d n/d n/d 50=200 50=200 n/d n/d n/d 180=200 180=200 n/d
n/d n/d 220=200 220=200 n/d n/d n/d 275=200 275=200 n/d
n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d yes n/d n/d n/d n/d
n/d n/d n/d n/d 3=1 n/d n/d 415=200 415=200 n/d n/d n/d n/d n/d 2=1 n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d 45=200 45=200 n/d n/d n/d 55=200 n/d n/d n/d n/d n/a 200=200 n/d n/d n/d 200=200 n/a n/d
DM-600IS Instruction Manual Rev 1.5.9 Page 11 of 37
4.0 SPECIFICATIONS
3 relays (alarm 1, alarm 2, and fault) contact rated 5 amps @ 125 VAC,
± 2% FS
Model Number
Gas Name
Response
Span Drift
Temperature
Temperature
Humidity
SensorCell
DM-500IS-C2H3O
Acetaldehyde
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C2H2
Acetylene
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C3H3N
Acrylonitrile
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-NH3(-20°C)
Ammonia
T90 <60
<1% signal loss/month
-
20 to +40
-
4 to +104
10 to 95
2 years
DM-501IS-NH3(-40°C)Ammonia
T90 <90
<2% signal loss/month
-
40 to +40
-
40 to +104
5 to 95
11/2
yearsDM-
502IS-NH3 (CE)
Ammonia
T90 <90
<2% signal loss/month
-
40 to +50
-
40 to +122
15 to 90
2 years
DM-500IS-AsH3
Arsine
T90 <60
<5% signal loss/month
-
20 to +40
-
4 to +104
20 to 95
11/2years
DM-500IS-Br2
Bromine
T90 <60
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C4H6
Butadiene
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-CS2
Carbon Disulfide
T90 <140
<5% signal
loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-CO
Carbon Monoxide
T90≤30
<5% signal loss/year
-
40 to +50
-
40 to +122
15 to 90
3 years
DM-500IS-COS
Carbonyl Sulfide
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-
CL2
Chlorine
T90 <60
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-CLO2(>10ppm)
Chlorine Dioxide
T90 <60
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-501IS-CLO2(≤10ppm)
Chlorine Dioxide
T90 <120
<1% signal l
oss/month
-
20 to +40
-
4 to +104
10 to 95
2 years
DM-500IS-B2H6
Diborane
T90 <60
<5% signal loss/month
-
20 to +40
-
4 to +104
20 to 95
11/2years
DM-500IS-C2H6S
Dimethyl Sulfide
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-
C3H5OCL
Epichlorohydrin
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C2H5OH
Ethanol
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C2H5SH
Ethyl Mercaptan
T90 <45
<2% signal loss/month
-40to +50-40 to +122
15 to 90
2 years
DM-500IS-C2H4
Ethylene
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C2H4O
Ethylene Oxide
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-F2
Fluorine
T90 <80<5% signal loss/year
-
10 to +40
+14 to +104
10 to 95
11/2years
DM-500IS-CH2O
Formaldehyde
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-GeH4
Germane
T90 <60
<1% signal loss/month
-
20 to +40
-
4 to +104
20 to 95
11/2y
earsDM-
500IS-N2H4
Hydrazine
T90 <120
<5% signal loss/month
-
10 to +40
+14 to +104
10 to 95
1 yearDM-
500IS-H2 (ppm)
Hydrogen
T90≤30
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-501IS-H2 (LEL)*
Hydrogen
T90 <60
<2% signal loss/month
-
40 to +40
-
40 to +104
5 to 95
2 years
DM-500IS-HBr
Hydrogen Bromide
T90 <70
<3% signal loss/month
-
20 to +40
-
4 to +104
10 to 95
11/2years
DM-500IS-HCL
Hydrogen Chloride
T90 <70
<2% signal loss/month
-
20 to +40
-
4 to +104
10 to 95
11/2years
DM-500IS-
HCN
Hydrogen Cyanide
T90 <40
<5% signal loss/month
-
40 to +40
-
40 to +104
5 to 95
2 years
DM-500IS-HF
Hydrogen Fluoride
T90 <90
<10% signal loss/month
-
20 to +35
-
4 to +95
10 to 80
11/2years
DM-500IS-H2S
Hydrogen Sulfide
T90≤30
<2% signal loss/month
-
40 to +50
-
40 to +122
15 to 90
2 years
DM-500IS-CH3OH
Methanol
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-CH3SH
Methyl Mercaptan
T90 <45
<2% signal loss/month
-
40 to +50
-
40 to +122
15 to 90
2
yearsDM-
500IS-NO
Nitric Oxide
T90≤10
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
3 years
DM-500IS-NO2
Nitrogen Dioxide
T90 <40
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-O3
Ozone
T90 <120
<1% signal loss/month
-10to +40
+14 to +104
10 to 95
2 years
DM-500IS-COCL2
Phosgene
T90 <120
<1% signal loss/month
-
20 to +40
-
4 to +104
10 to 95
11/2years
DM-500IS-PH3
Phosphine
T90 <30
<1% signal loss/month
-
20 to +40
-
4 to +104
20 to 95
11/2years
DM-500IS-SiH4
SilaneT90 <60
<1% signal loss/month
-
20 to +40
-
4 to +104
20 to 95
11/2years
DM-500IS-SO2
Sulfur Dioxide
T90≤20
<2% signal loss/month
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C4H8S
Tetrahydrothiophene
T90 <30
<2% signal loss/month
-
10 to +40
+14 to +104
10 to 95
2 years
Method of Detection
Electrochemical Cell
Electrical Classification
CSA-NRTL (US OSHA) approved* Class 1; Groups B, C, D; Div. 1.
Input Voltage
22.5-28 VDC
Power Consumption
Normal operation = 44 mA (1.1 watts @ 24VDC); Maximum @ 24VDC = 120 mA (2.9 watts) Maximum @ 22.5VDC = 102 mA (2.3 watts)
Output
5 amps @ 30 VDC Linear 4-20 mA DC; RS-485 Modbus
Repeatability
Table 2 Sensor cell specifications
DM-600IS
Time(seconds)
Range °C
Range °F
Range %
Warranty
DM-600IS Instruction Manual Rev 1.5.9 Page 12 of 37
DM-600IS
DM-500IS-C4H4S
Thiophane
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 9
0
2 years
DM-500IS-C6H5CH3
Toluene
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C4H6O2
Vinyl Acetate
T90 <140
<5% signal loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
DM-500IS-C2H3CL
Vinyl Chloride
T90 <140
<5% signal
loss/year
-
20 to +50
-
4 to +122
15 to 90
2 years
AWG
Meters
Feet20240
80018360
1200
16
600
2000
14
900
3000
Note
1
: This wiring ta
ble is based on stranded tinned copper wire and is designed to serve as a
Note
2: Shielded cable may be required in installations where cable trays or conduit runs
Note
3
: The supply of power must be from an isolating source with over
-
current protection as
AWG
Over
-
current Protection
AWG
Over
-
current Protection
223A16
10A205A1420A187A1225A
*LELrangeH2isnot CSAapproved.
5.0 INSTALLATION
Optimum performance of ambient air/gas sensor devices is directly relative to proper location and installation practice.
5.1 Field Wiring Table (4-20 mA output)
Detcon Model DM-600IS toxic gas sensor assemblies require three conductor connection between power supplies and host electronic controllers. Wiring designators are + (DC), – (DC), and mA (sensor signal).
Maximum single conductor resistance between sensor and controller is 10 ohms. Maximum wire size for termination in the sensor assembly terminal board is 14 gauge.
Table 3 Field wiring Table
reference only.
include high voltage lines or other sources of induced interference.
follows:
Table 4 Over-current Protection per AWG
The RS-485 (if applicable) requires 24 gauge, two conductor, shielded, twisted pair cable between sensor and host PC. Use Belden part number 9841. Two sets of terminals are located on the connector board to facilitate
serial loop wiring from sensor to sensor. Wiring designators are A & B (IN) and A & B (OUT).
DM-600IS Instruction Manual Rev 1.5.9 Page 13 of 37
DM-600IS
Note:
In all installat
ions, the sensor element in SS housing points down relative to grade
5.2 Sensor Location
Selection of sensor location is critical to the overall safe performance of the product. Five factors play an important role in selection of sensor locations:
1) Density of the gas to be detected
2) Most probable leak sources within the industrial process
3) Ventilation or prevailing wind conditions
4) Personnel exposure
5) Maintenance access
Density - Placement of sensors relative to the density of the target gas is such that sensors for the detection of heavier than air gases should be located within 2-4 feet of grade as these heavy gases will tend to settle in low lying areas. For gases lighter than air, sensor placement should be 4-8 feet above grade in open areas or in pitched areas of enclosed spaces.
Leak Sources - Most probable leak sources within an industrial process include flanges, valves, and tubing connections of the sealed type where seals may either fail or wear. Other leak sources are best determined by facility engineers with experience in similar processes.
Ventilation - Normal ventilation or prevailing wind conditions can dictate efficient location of gas sensors in a manner where the migration of gas clouds is quickly detected.
Personnel Exposure - The undetected migration of gas clouds should not be allowed to approach concentrated personnel areas such as control rooms, maintenance or warehouse buildings. A more general and applicable thought toward selecting sensor location is combining leak source and perimeter protection in the best possible configuration.
Maintenance Access
Consideration should be given to easy access by maintenance personnel as well as the consequences of close proximity to contaminants that may foul the sensor prematurely.
(Figure 6). Improper sensor orientation may result in false reading and permanent sensor damage
DM-600IS Instruction Manual Rev 1.5.9 Page 14 of 37
Conduit
DM-600IS
"T"
Drain
EYS Seal Fitting
PGM 1
HOUSTON,TEXAS
MODEL DM-6xx
TM
MicroSafe Gas Sensor
ALM ALM
1 2
FLT CAL
PGM 2
Figure 6 Typical Installation
5.3 Local Electrical Codes
Sensor and transmitter assemblies should be installed in accordance with all local electrical codes. Use appropriate conduit seals. Drains & breathers are recommended. The sensor assemblies are CSA-NRTL approved for Class I; Groups B, C, D; Div. 1 environments.
DM-600IS Instruction Manual Rev 1.5.9 Page 15 of 37
5.4 Installation Procedure
Note: Per U.L. approval, these relays may only be used in connecting to devices that are
6.1"
5.5"
8.985"
1/4" Mounting holes
3/4" NPT Ports
5.825"
Intrinsically Safe Sensor Head
4.65"
8-32 tapped ground point
Wall (or other
mounting surface
DM-600IS
Splash Guard
2"
0.5"
Cal Port
Figure 7 Typical Outline and Mounting Dimensions
a) Securely mount the sensor junction box in accordance with recommended practice. See dimensional
drawing (Figure 7).
b) Remove the junction box cover and un-plug the control circuit by grasping the two thumb screws and
pulling outward.
c) Observing correct polarity, terminate 3 conductor field wiring, RS-485 wiring, and applicable alarm
wiring to the sensor base connector board in accordance with the detail shown in Figure 8. Normally open and normally closed Form C dry contacts (rated 5 amp @ 125VAC; 5 amp @ 30VDC) are provided for Fault, Alarm 1, and Alarm2.
powered by the same voltages.
d) Position gold plated jumper tabs located on the connector board in accordance with desired Form C
dry contact outputs: NO = Normally Open; NC = Normally closed (see Figure 8).
DM-600IS Instruction Manual Rev 1.5.9 Page 16 of 37
DM-600IS
corresponds to 0
-
100% of scale (see
Figure
8
).
Figure 8 Jumper Tab Positions on Term Board
Note: If a voltage signal output is desired in place of the 4-20mA output, a 1/4 watt resistor must be installed in position R1 of the terminal board. A 250resistor will provide a 1-5V output (– to mA). A 100resistor will provide a .4-2V output, etc. This linear signal
e) Program the alarms via the gold plated jumper tab positions located on the CPU board (see Figure 9).
Alarm 1 and Alarm 2 have three jumper programmable functions: latching/non-latching relays, normally energized/normally de-energized relays, and ascending/descending alarm set points. The fault alarm has two jumper programmable functions: latching/non-latching relay, and normally energized/normally de-energized relay. The default settings of the alarms (jumpers removed) are normally de-energized relays, non-latching relays, and alarm points that activate during descending gas conditions.
Figure 9 Alarm Programming Jumpers
DM-600IS Instruction Manual Rev 1.5.9 Page 17 of 37
DM-600IS
If a jumper tab is installed in the latch position that alarm relay will be in the latching mode. The latching mode will latch the alarm after alarm conditions have cleared until the alarm reset function is activated. The non-latching mode (jumper removed) will allow alarms to de-activate automatically once alarm conditions have cleared.
If a jumper tab is installed in the energize position, that alarm relay will be in the energized mode. The energized mode will energize or activate the alarm relay when there is no alarm condition and de­energize or de-activate the alarm relay when there is an alarm condition. The de-energized mode (jumper removed) will energize or activate the alarm relay during an alarm condition and de-energize or de-activate the alarm relay when there is no alarm condition.
If a jumper tab is installed in the ascending position that alarm relay will be in the ascending mode. The ascending mode will cause an alarm to fire when the gas concentration detected is greater than or equal to the alarm set point. The descending mode (jumper removed) will cause an alarm to fire when the gas concentration detected is lesser than or equal to the alarm set point. Except in special applications, toxic gas monitoring will require alarms to fire in “ASCENDING” gas conditions.
Any unused jumper tabs should be stored on the connector board on the terminal strip labeled “Unused Jumpers” (see Figure 8).
f) If applicable, set the RS-485 ID number via the two rotary dip switches located on the preamp board
(see Figure 10). There are 256 different ID numbers available which are based on the hexadecimal numbering system. If RS-485 communications are used, each sensor must have its own unique ID number. Use a jeweler’s screwdriver to set the rotary dip switches according to the table listed on the following page. If RS-485 communications are not used, leave the dip switches in the default position which is zero/zero (0)-(0).
Figure 10 RS-485 ID set Dip Switches
g) Replace the plug-in control circuit and replace the junction box cover.
DM-600IS Instruction Manual Rev 1.5.9 Page 18 of 37
DM-600IS
Table 5 RS-485 Rotary Dip Switch Settings
ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2
0 0 0 43 2 B 86 5 4 129 8 1 172 A C 215 D 7 1 0 1 44 2 C 86 5 6 130 8 2 173 A D 216 D 8 2 0 2 45 2 D 87 5 7 131 8 3 174 A E 217 D 9 3 0 3 46 2 E 88 5 8 132 8 4 175 A F 218 D A 4 0 4 47 2 F 89 5 9 133 8 5 176 B 0 219 D B 5 0 5 48 3 0 90 5 A 134 8 6 177 B 1 220 D C 6 0 6 49 3 1 91 5 B 135 8 7 178 B 2 221 D D 7 0 7 50 3 2 92 5 C 136 8 8 179 B 3 222 D E 8 0 8 51 3 3 93 5 D 137 8 9 180 B 4 223 E F
9 0 9 52 3 4 94 5 E 138 8 A 181 B 5 224 E 0 10 0 A 53 3 5 95 5 F 139 8 B 182 B 6 225 E 1 11 0 B 54 3 6 96 6 0 140 8 C 183 B 7 226 E 2 12 0 C 55 3 7 97 6 1 141 8 D 184 B 8 227 E 3 13 0 D 56 3 8 98 6 2 142 8 E 185 B 9 228 E 4 14 0 E 57 3 9 99 6 3 143 8 F 186 B A 229 E 5 15 0 F 56 3 8 100 6 4 144 9 0 187 B B 230 E 6 16 1 0 57 3 9 101 6 5 145 9 1 188 B C 231 E 7 17 1 1 58 3 A 102 6 6 146 9 2 189 B D 232 E 8 18 1 2 59 3 B 103 6 7 147 9 3 190 B E 233 E 9 19 1 3 60 3 C 104 6 8 148 9 4 191 B F 234 E A 20 1 4 61 3 D 105 6 9 149 9 5 192 C 0 235 E B 21 1 5 62 3 E 106 6 A 150 9 6 193 C 1 236 E C 22 1 6 63 3 F 107 6 B 151 9 7 194 C 2 237 E D 23 1 7 64 4 0 108 6 C 152 9 8 195 C 3 238 E E 24 1 8 65 4 1 109 6 D 153 9 9 196 C 4 239 F F 25 1 9 66 4 2 110 6 E 154 9 A 197 C 5 240 F 0 26 1 A 67 4 3 111 6 F 155 9 B 198 C 6 241 F 1 27 1 B 68 4 4 112 7 0 156 9 C 199 C 7 242 F 2 28 1 C 69 4 5 113 7 1 157 9 D 200 C 8 243 F 3 29 1 D 70 4 6 114 7 2 158 9 E 201 C 9 244 F 4 30 1 E 71 4 7 115 7 3 159 9 F 202 C A 245 F 5 31 1 F 72 4 8 116 7 4 160 A 0 203 C B 246 F 6 32 2 0 73 4 9 117 7 5 161 A 1 204 C C 247 F 7 33 2 1 74 4 A 118 7 6 162 A 2 205 C D 248 F 8 34 2 2 75 4 B 119 7 7 163 A 3 206 C E 249 F 9 35 2 3 76 4 C 120 7 8 164 A 4 207 C F 250 F A 36 2 4 77 4 D 121 7 9 165 A 5 208 D 0 251 F B 37 2 5 78 4 E 122 7 A 166 A 6 209 D 1 252 F C 38 2 6 79 4 F 123 7 B 167 A 7 210 D 2 253 F D 39 2 7 80 5 0 124 7 C 168 A 8 211 D 3 254 F E 40 2 8 81 5 1 125 7 D 169 A 9 212 D 4 255 F F 41 2 9 82 5 2 126 7 E 170 A A 213 D 5 42 2 A 83 5 3 127 7 F 171 A B 214 D 6
5.5 Remote Mounting Applications
Some sensor mounting applications require that the gas sensor head be remotely mounted away from the sensor transmitter. This is usually true in instances where the gas sensor head must be mounted in a location that is difficult to access. Such a location creates problems for maintenance and calibration activities. Detcon provides the DM-600IS sensor in a remote-mount configuration in which the sensor (Model DM-600IS-RS) and the transmitter (Model DM-600IS-RT) are provided in their own condulet housing and are interfaced together with a four conductor cable. Sensor can be separate from transmitter up to 50 feet using shielded twisted pair cable. See Figure 11 for wiring diagram.
DM-600IS Instruction Manual Rev 1.5.9 Page 19 of 37
DM-600IS
NOTE 1
: If the display contrast needs adjustment, refe
r to section
15.0
.
NOTE 2: Zero Clearing with Biased Cells
Figure 11 Remote Mount wiring
6.0 STARTUP
Upon completion of all mechanical mounting and termination of all field wiring, apply system power and observe the following normal conditions:
a. DM-6xxIS “Fault” LED is off.
b. A temporary upscale reading will occur as the sensor powers up. This upscale reading will clear to “0”
ppm within approximately 30 minutes of turn-on, assuming there is no gas in the area of the sensor.
Some electrochemical sensors are biased with an excitation voltage. When power to the sensor is lost, this bias voltage slowly decays. When power is restored after long periods (multiple hours) of being unpowered, a surge in sensor output takes place and a long and slow re­establishing of the sensor’s zero baseline takes place. This re-stabilization time may range from 1 hour to 24 hours depending on the type of sensor and range of operation. The sensor types that this applies to are the following: HCl, NO, plus all the VOC sensors, C2H30, C2H2, C3H3N, C4H6, CS2, COS, C2H6S, C3H5OCL, C2H5OH, C2H4, C2H4O, CH2O, CH3OH, C4H4S, C4H6O2, C6H5CH3 and C2H3CL.
DM-600IS Instruction Manual Rev 1.5.9 Page 20 of 37
DM-600IS
All alarms will be disabled for 1 minute after power up. In the event of power failure,
If this characteristic is problematic for your specific application, a battery backup or uninterruptible power supply is recommended.
NOTE 3:
the alarm disable periods will begin again once power has been restored. If using a biased cell (see note 2 above), this 1 minute delay may likely be inadequate for the signal to clear below alarm levels so manually disabling alarms is advised.
6.1 Initial Operational Tests
After a warm up period has been allowed for, the sensor should be checked to verify sensitivity to its target gas.
Material Requirements
Detcon PN 943-000006-132 Calibration Adapter Span gas containing the target gas in air or nitrogen. It is recommended that the target gas
concentration be 50% of scale at a controlled flow rate of 500 ml/min. For example, a Model DM­600IS-H2S sensor in the range 0-100ppm would require a test gas of 50ppm H2S. For a sensor with a range of 0-10ppm a test gas of 5ppm is recommended, etc.
a) Attach the calibration adapter to the sensor housing. Apply the test gas at a controlled flow rate of 500
ml/m. Observe that the LCD display increases to a level of 20% of range or higher. b) Remove the test gas and observe that the LCD display decreases to “0 PPM”. c) If alarms are activated during the test, and have been programmed for latching operation, reset them
according to the instructions in section 11.2.
Initial operational tests are complete. Detcon toxic gas sensors are pre-calibrated prior to shipment and will, in most cases, not require significant adjustment on start up. However, it is recommended that a complete calibration test and adjustment be performed within 24 hours of installation. Refer to calibration instructions in section 9.0.
7.0 OPERATING SOFTWARE & MAGNETIC INTERFACE
Operating software is menu listed with operator interface via the two magnetic program switches located under the face plate. The two switches are referred to as “PGM 1” and “PGM 2”. The menu list consists of 3 items which include sub-menus as indicated below. (Note: see section 8.0 for a complete software flow chart.)
1) Normal Operation
a) Current Status
1) Calibration Mode
a) Zero b) Span
1) Program Menu
a) View Program Status b) Alarm 1 Level c) Alarm 2 Level d) Set Calibration Level
DM-600IS Instruction Manual Rev 1.5.9 Page 21 of 37
DM-600IS
7.1 Normal Operation
In normal operation, the display tracks the current status of the sensor and gas concentration and appears as: “0 PPM xxx” (the “xxx” is the abbreviated gas type, i.e. “0 PPM H2S”. The mA current output corresponds to the monitoring level of 0-100% of range = 4-20 mA.
7.2 Calibration Mode
Calibration mode allows for sensor zero and span adjustments. “1-ZERO 2-SPAN
7.2.1 Zero Adjustment
Zero is set in ambient air with no target gas present or with zero gas applied to the sensor. “AUTO ZERO
7.2.2 Span Adjustment
Span adjustment is performed with a target gas concentration of 50% of range in air or nitrogen. Span gas concentrations other than 50% of range may be used. Refer to section 7.3.4 for details. “AUTO SPAN
7.3 Program Mode
The program mode provides a program status menu and allows for the adjustment of alarm set point levels and the programming of the calibration gas level setting.
7.3.1 Program Status
The program status scrolls through a menu that displays: The software version number. Range is ### The alarm set point level of alarm 1. The menu item appears as: “ALM1 SET @ ##PPM The alarm firing direction of alarm 1. The menu item appears as: “ALM1 ASCENDING” or
descending.
The alarm relay latch mode of alarm 1. The menu item appears as: “ALM1 NONLATCHING” or
latching.
The alarm relay energize state of alarm 1. The menu item appears as: “ALM1 DE-ENERGIZED” or
energized.
The alarm set point level of alarm 2. The menu item appears as: “ALM2 SET @ ##PPM The alarm firing direction of alarm 2. The menu item appears as: “ALM2 ASCENDING” or
descending.
The alarm relay latch mode of alarm 2. The menu item appears as: “ALM2 LATCHING” or non-
latching.
The alarm relay energize state of alarm 2. The menu item appears as: “ALM2 DE-ENERGIZED” or
energized.
The alarm relay latch mode of the fault alarm. The menu item appears as: “FLT NONLATCHING
or latching.
The alarm relay energize state of the fault alarm. The menu item appears as: “FLT ENERGIZED” or
de-energized.
The calibration gas level setting. The menu item appears as: “CalLevel @ xxPPM Identification of the RS-485 ID number setting. The menu item appears as: “485 ID SET @ ## The estimated remaining sensor life. The menu item appears as: “SENSOR LIFE 100%”
DM-600IS Instruction Manual Rev 1.5.9 Page 22 of 37
DM-600IS
NOTE:
If, after entering the calibration or program menus, there is no interaction with the
7.3.2 Alarm 1 Level Adjustment
The alarm 1 level is adjustable from 10% to 90% of range. The menu item appears as: “SET ALM1 @ ##PPM
7.3.3 Alarm 2 Level Adjustment
The alarm 2 level is adjustable from 10% to 90% of range. The menu item appears as: “SET ALM2 @ ##PPM
7.3.4 Calibration Level Adjustment
The Calibration level is adjustable from 10% to 90% of range. The menu item appears as: “CalLevel @ ##PPM
7.4 Programming Magnet Operating Instructions
Operator interface to MicroSafegas detection products is via magnetic switches located behind the transmitter face plate. DO NOT remove the glass lens cover to calibrate or change programming parameters. Two switches labeled “PGM 1” and “PGM 2” allow for complete calibration and programming without removing the enclosure cover, thereby eliminating the need for area de-classification or the use of hot permits.
Figure 12 Programming Magnet
A magnetic programming tool (see Figure 12) is used to operate the switches. Switch action is defined as momentary contact, 3 second hold, and 30-second hold. In momentary contact use, the programming magnet is waved over a switch location. In 3 second hold, the programming magnet is held in place over a switch location for 3 or more seconds. In 30 second hold, the programming magnet is held in place over a switch location for 30 or more seconds. Three and thirty second hold is used to enter or exit calibration and program menus while momentary contact is used to make adjustments. The location of “PGM 1” and “PGM 2” are shown in Figure 13.
menu items for more than 30 seconds, the sensor will return to its normal operating condition
Figure 13 UniversalMicroprocessor Control Transmitter Circuit
DM-600IS Instruction Manual Rev 1.5.9 Page 23 of 37
8.0 Software Flow Chart
DM-600IS
Figure 14 Software Flow Chart
DM-600IS Instruction Manual Rev 1.5.9 Page 24 of 37
9.0 Calibration
NOTE:
Before performing a zero calibration, be sure there is no background gas present or
CAUTION:
Verification of the correct calibration gas level setting and calibration span gas
Material Requirements
Detcon PN 327-000000-000 MicroSafeTM Programming Magnet Detcon PN 943-000006-132 Calibration Adapter Span gas containing the target gas in air or nitrogen. The target gas concentration is recommended at
50% of range (which is the factory default) at a controlled flow rate of 500 ml/min. Example: for a Model DM-600IS-H2S sensor with a range of 0-100ppm, a test gas of 50 ppm is recommended. For a sensor with a range of 0-10 ppm a test gas of 5 ppm is recommended, etc. Other concentrations can be used as long as they fall within 10% to 90% of range. See section 9.2 for details. Reference section 10-
2) -b) if you do not know the sensor target gas or range of detection.
9.1 Calibration Procedure - Zero
apply a zero gas standard prior to performing zero calibration.
a) Enter the calibration menu by holding the programming magnet stationary over “PGM 1” (see figure
6) for 3 seconds until the display reads “1-ZERO 2-SPAN” then withdraw the magnet. Note that the “CAL” LED is on.
DM-600IS
b) Next, enter the zero menu by holding the magnet stationary over “PGM 1” for 3 seconds until the
display reads: “SETTING ZERO”, then withdraw the magnet. The sensor has now entered the auto zero mode. When it is complete the display will read “ZERO COMPLETE” for 5 seconds and then return to the normal operations menu reading “(0 PPM)”.
Zero calibration is complete.
9.2 Calibration Procedure - Span
concentration is required before “span” calibration. These two numbers must be equal.
Calibration consists of entering the calibration function and following the menu-displayed instructions. The display will ask for the application of span gas in a specific concentration. This concentration must be equal to the calibration gas level setting. The factory default setting for span gas concentration is 50% of range. In this instance, a span gas containing a concentration equal to 50% of range is required. If a span gas containing 50% of range is not available, other concentrations may be used as long as they fall within 10% to 90% of range. However, any alternate span gas concentration value must be programmed via the calibration gas level menu before proceeding with span calibration. Follow the instructions below for span calibration.
a) Verify the current calibration gas level setting as indicated by the programming status menu. To do
this, follow the instructions in section 10 and make note of the setting found in listing number 12. The item appears as “CalGas @ xxPPM”.
b) If the calibration gas level setting is equal to your calibration span gas concentration, proceed to item
“f”. If not, adjust the calibration gas level setting so that it is equal to your calibration span gas concentration, as instructed in items “c” through “e”.
DM-600IS Instruction Manual Rev 1.5.9 Page 25 of 37
DM-600IS
NOTE 1
: If there is not a minimal response to the cal gas
in the first minute, the
sensor will
NOTE 2
: If during the auto
-
span function the sensor fails to meet a minimum signal stability
c) Enter the programming menu by holding the programming magnet stationary over “PGM 2” for 30
seconds until the display reads “VIEW PROG STATUS” then withdraw the magnet. At this point you can scroll through the programming menu by momentarily waving the programming magnet over “PGM 1” or “PGM 2”. The menu options are: View Program Status, Set Alarm 1 Level, Set Alarm 2 Level, and Set Cal Level.
d) From the programming menu scroll to the calibration level listing. The menu item appears as: “SET
CAL LEVEL”. Enter the menu by holding the programming magnet stationary over “PGM 1” for 3 seconds until the display reads “CalGas @ ##PPM”, then withdraw the magnet. Use the programming magnet to make an adjustment to “PGM 1” to increase or “PGM 2” to decrease the display reading until the reading is equal to the desired calibration span gas concentration. Exit to the programming menu by holding the programming magnet over “PGM1” for 3 seconds.
e) Exit back to normal operation by holding the programming magnet over “PGM 2” for 3 seconds, or
automatically return to normal operation in 30 seconds.
f) From the calibration menu “1-ZERO 2-SPAN” (section 9.1-a) proceed into the span adjust function
by holding the programming magnet stationary over “PGM 2” for 3 seconds then withdraw the programming magnet. At this point the display will ask for the application of the target gas and concentration. The display reads “APPLY xxx PPM” The x’s here will indicate the actual concentration requested.
g) Apply the calibration test gas at a flow rate of 500 milliliters per minute. As the sensor signal changes,
the display will change to “AutoSpan xxPPM”. The “xx” part of the reading indicates the actual gas reading which will increase until the sensor stabilizes. When the sensor signal is stable it will auto span to the correct ppm reading and the display will change to “SPAN COMPLETE” for 3 seconds, then to “SENSOR LIFE: xxx%” and then “REMOVE GAS”. Remove the gas. When the signal level has fallen below 10% of full scale, the display will return to the normal operating mode.
enter into the calibration fault mode which will cause the display to alternate between the sensor’s current status reading and the calibration fault screen which appears as: “SPAN FAULT #1” (see section 9.3).
criteria, the sensor will enter the calibration fault mode which will cause the display to alternate between the sensor’s current status reading and the calibration fault screen which appears as: “SPAN FAULT #2” (see section 9.3).
9.3 Additional Notes
1. Upon entering the calibration menu, the 4-20 mA signal drops to 2 mA and is held at this level until you return to normal operation.
2. If during calibration the sensor circuitry is unable to attain the proper adjustment for zero or span, the sensor will enter into the calibration fault mode which may activate fault alarm functions (see section
12.0) and will cause the display to alternate between the sensor’s current status reading and the reported calibration fault description. In these cases, the previous calibration points will remain in memory. If this occurs you may attempt to recalibrate by entering the calibration menu as described in section 9.1-a. If the sensor fails again, defer to technical trouble shooting (see section 16.0).
DM-600IS Instruction Manual Rev 1.5.9 Page 26 of 37
DM-600IS
9.4 Calibration Frequency
In most applications, monthly to quarterly calibration intervals will assure reliable detection. However, industrial environments differ. Upon initial installation and commissioning, close frequency tests should be performed, weekly to monthly. Test results should be recorded and reviewed to determine a suitable calibration interval.
10.0 STATUS OF PROGRAMMING: SOFTWARE
VERSION, ALARMS, CALIBRATION LEVEL, RS-485 ID, AND SENSOR LIFE
The programming menu has a programming status listing that allows the operator to view the gas, range, and software version number of the program, as well as the current alarm settings, calibration gas level setting, RS­485 ID number, and estimated remaining sensor life. The programming menu also allows the changing of alarm levels (see section 11.0) and the programming of the calibration gas level setting (see section 9.2).
The following procedure is used to view the programming status of the sensor:
1) First, enter the programming menu by holding the programming magnet stationary over “PGM 2” for 30
seconds until the display reads “VIEW PROG STATUS”, then withdraw the magnet. At this point you can scroll through the programming menu by momentarily waving the programming magnet over “PGM 1” or “PGM 2”. The menu options are: View Program Status, Set Alarm 1 Level, Set Alarm 2 Level, and Set Cal Level.
2) Next, scroll to the “VIEW PROG STATUS” listing and then hold the programming magnet over “PGM
1” for 3 seconds. The menu will then automatically scroll, at five second intervals, through the following information before returning back to the “VIEW PROG STATUS” listing. a) The software version number. b) Range is ### c) The alarm set point level of alarm 1. The menu item appears as: “ALM1 SET @ xxPPM” d) The alarm firing direction of alarm 1. The menu item appears as: “ALM1 ASCENDING” e) The alarm relay latch mode of alarm 1. The menu item appears as: “ALM1 NONLATCHING” f) The alarm relay energize state of alarm 1. The menu item appears as: “ALM1 DE-ENERGIZED” g) The alarm set point level of alarm 2. The menu item appears as: “ALM2 SET @ xxPPM” h) The alarm firing direction of alarm 2. The menu item appears as: “ALM2 ASCENDING” i) The alarm relay latch mode of alarm 2. The menu item appears as: “ALM2 LATCHING” j) The alarm relay energize state of alarm 2. The menu item appears as: “ALM2 DE-ENERGIZED” k) The alarm relay latch mode of the fault alarm. The menu itemappears as: “FLT NONLATCHING” l) The alarm relay energize state of the fault alarm. The menu item appears as: “FLT ENERGIZED” m) Calibration gas level setting. The menu item appears as: “CalLevel @ xxPPM” n) Identification of the RS-485 ID number setting. The menu item appears as: “485 ID SET @ 1” o) The estimated remaining sensor life. The menu item appears as: “SENSOR LIFE 100%
3) Exit back to normal operations by holding the programming magnet over “PGM 2” for 3 seconds, or
automatically return to normal operation in 30 seconds.
DM-600IS Instruction Manual Rev 1.5.9 Page 27 of 37
DM-600IS
11.0 PROGRAMMING ALARMS
11.1 Alarm Levels
Both alarm 1 and alarm 2 levels are factory set prior to shipment. Alarm 1 is set at 20% of range and alarm 2 at 40% of range. Both alarms can be set in 1% increments from 10% to 90% of range. The following procedure is used to change alarm set points:
a) First, enter the programming menu by holding the programming magnet stationary over “PGM 2” for
30 seconds until the display reads “VIEW PROG STATUS”, then withdraw the magnet. At this point you can scroll through the programming menu by momentarily waving the programming magnet over “PGM 1” or “PGM 2”. The menu options are: View Program Status, Set Alarm 1 Level, Set Alarm 2 Level, and Set Cal Level.
b) ALARM 1 LEVEL From the programming menu scroll to the alarm 1 level listing. The menu item
appears as: “SET ALARM 1 LEVEL”. Enter the menu by holding the programming magnet stationary over “PGM 1” for 3 seconds until the display reads “SET ALM1 @ ##PPM”, then withdraw the magnet. Use the programming magnet to make an adjustment to “PGM 1” to increase or “PGM 2” to decrease the display reading until the reading is equal to the desired alarm set point. Exit to the programming menu by holding the programming magnet over “PGM1” for 3 seconds, or automatically return to the programming menu in 30 seconds.
c) ALARM 2 LEVEL From the programming menu scroll to the alarm 2 level listing. The menu item
appears as: “SET ALARM 2 LEVEL”. Enter the menu by holding the programming magnet stationary over “PGM 1” for 3 seconds until the display reads “SET ALM2 @ ##PPM”, then withdraw the magnet. Use the programming magnet to make an adjustment to “PGM 1” to increase or “PGM 2” to decrease the display reading until the reading is equal to the desired alarm set point. Exit to the programming menu by holding the programming magnet over “PGM1” for 3 seconds, or automatically return to the programming menu in 30 seconds.
d) Exit back to normal operations by holding the programming magnet over “PGM 2” for 3 seconds, or
automatically return to normal operation in 30 seconds.
11.2 Alarm Reset
An alarm condition will cause the applicable alarm to activate its corresponding relay and LED. If alarm 1, alarm 2, or fault alarms have been programmed for latching relays, an alarm reset function must be activated to reset the alarms after an alarm condition has cleared. To reset the alarms, simply wave the programming magnet over either “PGM 1” or “PGM 2”, momentarily, while in normal operations mode and note that the corresponding alarm LED(s) turn off.
11.3 Other Alarm Functions
Alarms are factory programmed to be non-latching, de-energized; and to fire under ascending gas conditions. The fault alarm relay is programmed as normally energized which is useful for detecting a 24VDC power source failure. All alarm functions are programmable via jumper tabs. Changing alarm functions requires the sensor housing to be opened, thus declassification of the area is required. See section 5.4 for details.
DM-600IS Instruction Manual Rev 1.5.9 Page 28 of 37
DM-600IS
12.0 PROGRAM FEATURES
Detcon MicroSafeTM toxic gas sensors incorporate a comprehensive program to accommodate easy operator interface and fail-safe operation. Program features are detailed in this section. Each sensor is factory tested, programmed, and calibrated prior to shipment.
Over Range
When the sensor detects gas greater than 100% of range, it will cause the display to flash the highest reading of its range on and off.
Under Range Fault(s) If the sensor should drift below a zero baseline of -10% of range, the display will indicate a fault: “ZERO FAULT”. This is typically fixed by performing another zero cal. When the total negative zero drift exceeds
the acceptable threshold the display will indicate “SENSOR FAULT” and you will longer be able to zero calibrate.
Span Fault #1
If during span calibration the sensor circuitry is unable to attain a minimum defined response to span gas, the sensor will enter into the calibration fault mode and cause the display to alternate between the sensor’s current status reading and the calibration fault screen which appears as: “SPAN FAULT #1”. The previous calibration settings will remain saved in memory. Previous span calibration is retained.
Span Fault #2
If during the span routine, the sensor circuitry is unable to attain a minimum defined stabilization point, the sensor will enter into the calibration fault mode and cause the display to alternate between the sensor’s current status reading and the calibration fault screen which appears as “SPAN FAULT #2”. Previous span calibration is retained.
Memory Fault
If new data points cannot successfully be stored to memory the display will indicate: “MEMORY FAULT”.
Fail-Safe/Fault Supervision
Detcon MicroSafeTM sensors are programmed for fail-safe operation. All fault conditions illuminate the fault LED, and cause the display to read its corresponding fault condition: “ZERO FAULT”, “SENSOR FAULT”, “SPAN FAULT #1”, or “SPAN FAULT #2”. A “SENSOR FAULT” and “ZERO FAULT” will activate the fault relay and cause the mA output to drop to zero (0) mA.
Sensor Life
The “Sensor Life” feature gauges the remaining sensor life based on signal output from the sensor cell. When sensor life of 25% or less remains the sensor cell should be replaced within a reasonable maintenance schedule.
13.0 UNIVERSAL TRANSMITTER FEATURE (RE-
INITIALIZATION)
The Model DM600IS uses a universal transmitter design that allows the transmitter to be set up for any target gas and any toxic concentration range. The original transmitter set-up is done at Detcon Inc. as part of the sensor test and calibration procedure, but it may also be changed in the field if necessary. The Universal Transmitter feature is a significant convenience to the user because it allows hardware flexibility and minimizes the spare parts requirements to handle unexpected transmitter failures of different gas/ranges. It is
DM-600IS Instruction Manual Rev 1.5.9 Page 29 of 37
DM-600IS
NOTE:
If the Universal Transmitter is changed for gas type and range, it must be consistent
NOTE 1:
If the gas symbol has more than 6 characters, th
e symbol can be replaced by an
NOTE 2
: When the Universal Tra
nsmitter is re
-
initialized and a new gas and range is entered,
however, absolutely critical that changes to gas/range set-up of the Universal Transmitter be consistent with the gas type and range of the Intrinsically Safe Sensor Head that it is connected to.
with the Intrinsically Safe sensor head it is mated with.
If the Universal Transmitter needs to be changed for gas type and range follow this procedure. First, unplug the transmitter temporarily and then plug it back in. While the message “Universal Transmitter” appears, take the program magnet and swipe it over magnet PGM1. This will reveal the set-up options for gas range and gas type.
Swipe over PGM1to advance through the options for gas range which include: 1, 2, 3....10 ppm
10, 15, 20...100 ppm 100, 200, 300...1000 ppm 1000, 2000, 3000 10,000 ppm When the correct range is displayed, hold magnet over PGM1 for 3 seconds to accept the selection.
Next is your selection for the gas type. In this set-up you will enter the alpha-numeric characters of the gas type. Reference the list on page 3 for correct symbols. There is space for the chemical formula up to six characters. Use GM1 and PGM2 swipes to advance through the alphabet and numbers 0-9 selection (there is a blank space after 9). When the correct alphanumeric character is highlighted, hold the magnet over PGM1 for 3 seconds to lock it in. This moves you to the next blank and the procedure is repeated until the chemical formula is completed. After the 6th character is locked in the transmitter will proceed to normal operation.
abbreviated version of the target gas name such as TOL or TOLUEN for Toluene which has the symbol C6H5CH3. For Epichlorohydrin (symbol C3H5OCL) you can substitute the name EPI or EPICHL etc.
all of the previous customer settings for alarm levels and span gas value are reset to their default levels. These must be re-programmed back to the customer specific settings
14.0 RS-485 PROTOCOL
Detcon MicroSafetoxic gas sensors feature Modbuscompatible communications protocol and are addressable via rotary dip switches for multi-point communications. Other protocols are available. Contact the Detcon factory for specific protocol requirements. Communication is two wire, half duplex 485, 9600 baud, 8 data bits, 1 stop bit, no parity, with the sensor set up as a slave device. A master controller up to 4000 feet away can theoretically poll up to 256 different sensors. This number may not be realistic in harsh environments where noise and/or wiring conditions would make it impractical to place so many devices on the same pair of wires. If a multi-point system is being utilized, each sensor should be set for a different address. Typical address settings are: 01, 02, 03, 04, 05, 06, 07, 08, 09, 0A, 0B, 0C, 0D, 0E, 0F, 10, 11, etc.
In most instances, RS-485 ID numbers are factory set or set during installation before commissioning. If required, the RS-485 ID number can be set via rotary dip switches located on the preamp circuit board. However, any change to the RS-485 ID number would require the sensor housing to be opened, thus
DM-600IS Instruction Manual Rev 1.5.9 Page 30 of 37
DM-600IS
declassification of the area would be required. See section 5.4-f) for details on changing the RS-485 ID number.
The following section explains the details of the Modbusprotocol that the MicroSafeTM sensor supports.
Code 03 - Read Holding Registers is the only code supported by the transmitter. Each transmitter contains 6 holding registers which reflect its current status.
Register # High Byte Low Byte 0000 Gas type Sensor Life
Gas type is one of the following: 01=CO, 02=H2S, 03=SO2, 04=H2, 05=HCN, 06=CL2, 07=NO2, 08=NO, 09=HCL, 10=NH3, 11=LEL, 12=O2
Sensor life is an estimated remaining use of the sensor head, between 0% and 100% Example: 85=85% sensor life
Register # High Byte Low Byte 40001 Detectable Range
i.e. 100 for 0-100 ppm, 50 for 0-50 ppm, etc.
Register # High Byte Low Byte 40002 Current Gas Reading
The current gas reading as a whole number. If the reading is displayed as 23.5 on the display, this register would contain the number 235.
Register # High Byte Low Byte 40003 Alarm 1 Set point
This is the trip point for the first alarm.
Register # High Byte Low Byte 40004 Alarm 2 Set point
This is the trip point for the second alarm.
Register # High Byte Low Byte 40005 Status Bits Status Bits
High Byte Bit 7 Not used, always 0 Bit 6 Not used, always 0 Bit 5 Not used, always 0 Bit 4 Not used, always 0 Bit 3 1-Unit is in calibration 0-Normal operation Bit 2 1-Alarm 2 is ascending 0-Alarm 2 is descending Bit 1 1-Alarm 2 is normally energized 0-Alarm 2 is normally de-energized Bit 0 1-Alarm 2 is latching 0-Alarm 2 is non-latching
DM-600IS Instruction Manual Rev 1.5.9 Page 31 of 37
Low Byte
Field Name
HEX
DEC
RTU
Slave Address
0880000 1000
Function
0330000 0011
Start Address Hi
0000000 0000
Start Address Lo
0000000 0000
No. of Registers Hi
0000000 0000
No. of Registers Lo
0660000 0110
CRC
##
#### ####
CRC
##
#### ####
Function
0330000 0011
Byte Count
0C120000 1100
Reg40000 Data Hi
0220000 0010
Reg400
00 Data Lo
64
100
0110 0100
Reg40001 Data Hi
0000000 0000
Reg40001 Data Lo
64
100
0110 0100
Reg40002 Data Hi
0000000 0000
Reg40002 Data Lo
0770000 0111
Reg40003 Data Hi
0000000 0000
Reg40003 Data Lo
0A100000 1010
Reg40004 Data Hi
0000000
0000
Reg40004 Data Lo
14200001 0100
Reg40005 Data Hi
0550000 0101
Reg40005 Data Lo
50800101 0000
CRC
##
#### ####
Bit 7 1-Alarm 2 Relay is energized 0-Alarm 2 Relay is not energized Bit 6 1-Alarm 1 is ascending 0-Alarm 1 is descending Bit 5 1-Alarm 1 is normally energized 0-Alarm 1 is normally de-energized Bit 4 1-Alarm 1 is latching 0-Alarm 1 is non-latching Bit 3 1-Alarm 1 Relay is energized 0-Alarm 1 Relay is not energized Bit 2 1-Fault is normally energized 0-Fault is normally de-energized Bit 1 1-Fault is latching 0-Fault is non-latching Bit 0 1-Fault Relay is energized 0-Fault Relay is not energized
The following is a typical Master Query for device # 8:
The following is a typical Slave Response from device # 8:
Field Name HEX DEC RTU Slave Address 08 8 0000 1000
DM-600IS
CRC ## #### ####
Additional Notes: The calibration LED will light when the transmitter is sending a response to a Master Query. Communications are 9600 baud, 8 data bits, 1 stop bit, No parity, and half-duplex 485.
On ranges set from 1 ppm to 10 ppm the reading and alarm set points are displayed as ##.##ppm.
On ranges set from 15 ppm to 50 ppm the reading and alarm set points are displayed as ##.#ppm.
To accommodate these fractional readings using the Modbusinterface, the reading and alarm set points are multiplied by 100 before they are stored for retrieval by a Modbuscommand.
DM-600IS Instruction Manual Rev 1.5.9 Page 32 of 37
DM-600IS
Examples: The transmitter is set for a range of 5 ppm. The display on the transmitter reads 2.74 ppm. The transmitter is polled for its reading using a Modbuscommand. The value returned in the response is decimal 274. Obtain the correct reading by dividing. 274/100 = 2.74 ppm.
The transmitter is set for a range of 25 ppm. The display on the transmitter reads 22.9 ppm. The transmitter is polled for its reading using a Modbuscommand. The value returned in the response is decimal 2290. Obtain the correct reading by dividing. 2290/100 = 22.9 ppm.
On ranges above 50 ppm there is no math involved. The readings are stored the same as they are seen on the transmitters display.
15.0 DISPLAY CONTRAST ADJUST
Detcon MicroSafeTM sensors feature a 16 character backlit liquid crystal display. Like most LCDs, character contrast can be affected by viewing angle and temperature. Temperature compensation circuitry included in the MicroSafeTM design will compensate for this characteristic; however temperature extremes may still cause a shift in the contrast. Display contrast can be adjusted by the user if necessary. However, changing the contrast requires that the sensor housing be opened, thus declassification of the area is required.
To adjust the display contrast, remove the enclosure cover and use a jeweler’s screwdriver to turn the contrast adjust screw located beneath the metallic face plate. The adjustment location is marked “CONTRAST”. See Figure 13 for location.
16.0 TROUBLE SHOOTING
Sensor reads Over-range after Power-up
Probable Cause: Biased sensor requiring additional stabilization time.
1. Verify if this is a Biased sensor (see section 6.0).
2. Wait up to 8 hours for unit to come on-scale if using a low range biased sensor.
3. Verify that there is not large amounts of target gas or interfering gases in background.
Reading Higher than Anticipated
Probable Causes: Target or Interfering gases in background, Incorrect calibration for Zero or Span, Biased sensor still stabilizing.
1. Verify no target or interfering gases are present.
2. Redo Zero and Span calibrations with validated Zero Gas and Span Gas standards.
3. If recovering after a start-up, give more time to stabilize.
Reading Lower than Anticipated
Probable Causes: Target gas or Interfering gases in background during Zero Calibration, Zero Calibration done before unit finished stabilizing, Incorrect Span Calibration.
1. Redo Zero and Span calibrations with validated Zero Gas and Span Gas standards.
DM-600IS Instruction Manual Rev 1.5.9 Page 33 of 37
DM-600IS
Sensor Fault
Probable Causes: Yellow wire is connected. Sensor has drifted since last zero cal.
1. Remove yellow wire if connected.
2. Redo Zero calibration
Zero Calibration Fault Probable Causes: Target gas or Interfering gases in background during Zero Calibration, Failed electrochemical sensor.
1. Verify no target or interfering gases are present.
2. Redo Zero and Span calibrations with validated Zero Gas and Span Gas standards.
3. If recovering after a start-up, give more time to stabilize.
Span Calibration Fault
Probable Causes: Failed electrochemical sensor, ice/mud/dust blocking sensor membrane, invalid span calibration gas do to age and contamination or insufficient flow rate.
1. Verify there is no ice/mud/dust blocking sensor membrane.
2. Redo Span Calibration with validated Span Gas standard (check with Pull Tube).
3. Reinitialize unit by plugging in transmitter while holding the magnet on PGM1. Scroll through and select the correct gas type. Make sure all customer settings are re-entered after “re-initialization”.
4. Replace with new electrochemical sensor.
Noisy Sensor (continuous drift) or suddenly Spiking
Probable Cause: Unstable power source, Inadequate grounding, Inadequate RFI protection.
1. Verify power Source output and stability.
2. Contact Detcon for assistance in optimizing shielding and grounding.
3. Add RFI Protection accessory available from Detcon.
LCD Difficult to Read
Probable Cause: Needs adjustment.
1. Adjust contrast pot as necessary.
Reporting “ERROR @ XXXXXXX”
Probable Cause: Span calibration calculation error.
1. Reinitialize unit by plugging in transmitter and then swiping the magnet over PGM1 while “Universal Transmitter” is displayed. Scroll through and select the correct gas type and range (see section 13.0 Universal Transmitter Features). Make sure all customer specific settings are re-entered after “re­initialization”.
DM-600IS Instruction Manual Rev 1.5.9 Page 34 of 37
17.0 SPARE PARTS LIST
943-000006-132 Calibration Adapter 500-001794-004 Connector board 327-000000-000 Programming Magnet 897-850901-010 Detcon Aluminum Enclosure with glass lens cover 960-202200-000 Condensation prevention packet (replace annually). 926-995580-000 DM-6xx Series Universal Plug-in Control Circuit 926-845580-04P* DM-6xx-H2 LEL range Series Universal Plug-in Control Circuit
* The H2 LEL range transmitter is not universal but is discrete to Hydrogen in the 0-4% by volume range.
N7 Aluminum Lid with window, part
Customer Supplied
Wiring
+24VDC Power IN
Common DC Power IN
4-20 mA Output
of Assembly # 897-850901-010
DM-600IS
Standard Connector Board P/N 500-01794-001
DM Plug-In Sensor Replacement Cell P/N 370-XXXX00-000
Where XXXX represents GAS code and Cell code
Toxic Is Hsg Gasket
P/N 027-02364-1
O'ring 1 1/4"ID X 1 7/16OD 0.103W
O'ring 1 9/16" ID X 1 3/4"OD 0.103W
P/N 171
Splashguard with Calibration Adapter
P/N:613-120000-700
P/N 173
Sensor Head Wiring Connection
Sensor Head Wiring Connection
Sensor Head Wiring Connection
STANDARD CONNECTOR BOARD
Condensation Prevention Packet
P/N:960-202200-000
IS Sensor Head P/N 394-XXXX00-Range Where XXXX represents GAS code and Cell code
Figure 15 Spare parts diagram
Transmitter Module DM-600IS P/N 926-995580-000
P/N:500-001794-001
N7 Aluminum condulet, part of
Assembly # 897-850901-010
6/32 X 3/8 Screw (2ea.)
#6 internal Star Washer (2ea.)
DM-600IS Instruction Manual Rev 1.5.9 Page 35 of 37
Table 6 Replacement IS Sensor Head / Plug-in Replacement Sensor Cell
Model Number
GasName
IS Sensor Head
Plug
-
in Replacement
DM-
500IS
-
C2H3O
Acetaldehyde
394-12EA00
-
Range
370-12EA00
-
000DM-
500IS
-
C2H2
Acetylene
394-12EG00
-
Range
370-12EG00
-
000DM-
500IS
-
C3H3N
Acrylonitrile
394-12EM00
-
Range
370-12EM00
-
000DM-
500IS
-
NH3 (
-
20°C)
Ammonia
394-171700
-
Range
370-171700
-
000DM-
501IS
-
NH3 (
-
40°C)
Ammonia
394-151500
-
Range
370-151500
-
000DM-
502IS
-
NH3 (CE)
Ammonia
394-505000
-
Range
370-505000
-
000DM-
500IS
-
AsH3
Arsine
394-191900
-
Range
370-191900
-
000DM-
500IS
-
Br2
Bromine
394-747500
-
Range
370-747500
-
000DM-
500IS
-
C4H6
Butadiene
394-12EB00
-
Range
370-
12EB00
-
000DM-
500IS
-
CS2
Carbon Disulfide
394-12EH00
-
Range
370-12EH00
-
000DM-
500IS
-COCarbon Monoxide
394-444400
-
Range
370-444400
-
000DM-
500IS
-
COS
Carbonyl Sulfide
394-12EN00
-
Range
370-12EN00
-
000DM-
500IS
-
CL2
Chlorine
394-747400
-
Range
370-747400
-
000
DM-500IS
-
CLO2 (>10ppm)
Chlorine Dioxide
394-747600
-
Range
370-747600
-
000
DM-501IS
-
CLO2 (
≤10ppm)
Chlorine Dioxide
394-777700
-
Range
370-777700
-
000DM-
500IS
-
B2H6
Diborane
394-192100
-
Range
370-192100
-
000DM-
500IS
-
C2H6S
Dimethyl Sulfide
394-12EC00
-
Range
370-12EC00
-
000DM-
500IS
-
C3H5OCL
Epichlorohydrin
394-12EI00
-
Range
370-12EI00
-
000DM-
500IS
-
C2H5OH
Ethanol
394-12EO00
-
Range
370-12EO00
-
000DM-
500IS
-
C2H5SH
Ethyl Mercaptan
394-24EZ00
-
Range
370-24EZ00
-
000DM-
500IS
-
C2H4
Ethylene
394-12ED00
-
Range
370-12ED00
-
000DM-
500IS
-
C2H4O
Ethylene Oxide
394-12EJ00
-
Range
370-12EJ00
-
000DM-
500IS
-F2Fluorine
394-272700
-
Range
370-272700
-
000DM-
500IS
-
CH2O
Formaldehyde
394-12EP00
-
Range
370-12EP00
-
000DM-
500IS
-
GeH4
Germane
394-232500
-
Range
370-232500
-
000DM-
500IS
-
N2H4
Hydrazine
394-262600
-
Range
370-262600
-
000DM-
500IS
-
H2 (ppm)
Hydrogen
394-848400
-
Range
370-848400
-
000DM-
501IS
-
H2 (LEL)
Hydrogen
394-050500
-
Range
370-050500
-
000DM-
500IS
-
HBr
Hydrogen Bromide
394-090800
-
Range
370-090800
-
000DM-
500IS
-
HCL
Hydrogen Chloride
394-09090
0-Range
370-090900
-
000DM-
500IS
-
HCN
Hydrogen Cyanide
394-131300
-
Range
370-131300
-
000DM-
500IS
-HFHydrogen Fluoride
394-333300
-
Range
370-333300
-
000DM-
500IS
-
H2S
Hydrogen Sulfide
394-242400
-
Range
370-242400
-
000DM-
500IS
-
CH3OH
Methanol
394-12EE00
-
Range
370-
12EE00
-
000
DM-500IS
-
CH3SH
Methyl Mercaptan
394-24EK00
-
Range
370-24EK00
-
000
DM-500IS
-NONitric Oxide
394-949400
-
Range
370-949400
-
000DM-
500IS
-
NO2
Nitrogen Dioxide
394-646400
-
Range
370-646400
-
000DM-
500IS
-O3Ozone
394-393900
-
Range
370-393900
-
000DM-500IS-COCL2
Phosgene
394-414100
-
Range
370-414100
-
000DM-
500IS
-
PH3
Phosphine
394-192000
-
Range
370-192000
-
000DM-
500IS
-
SiH4
Silane
394-232300
-
Range
370-232300
-
000DM-
500IS
-
SO2
Sulfur Dioxide
394-555500
-
Range
370-555500
-
000DM-
500IS
-
C4H8S
Tetrahydrothiophen
e
394-434300
-
Range
370-434300
-
000DM-
500IS
-
C4H4S
Thiophane
394-12EQ00
-
Range
370-12EQ00
-
000DM-
500IS
-
C6H5CH3
Toluene
394-12ER00
-
Range
370-12ER00
-
000DM-
500IS
-
C4H6O2
Vinyl Acetate
394-12EF00
-
Range
370-12EF00
-
000DM-
500IS
-
C2H3CL
Vinyl Chloride
394-12EL00
-
Range
370-12EL00
-
000
Sensor Cell
DM-600IS
DM-600IS Instruction Manual Rev 1.5.9 Page 36 of 37
DM-600IS
Revision
Date
Changes made
Approval
1.5.6
09/12/2006
Previously issued
BM
1.5.7
08/19/2010
Calibration Adapter
changed from 943
-
000217
-
5A1 to 943
-
BM
1.5.8
11/08/2010
Correction of wrong value in Cross Interference table. Value for
BM
1.5.9
01/10/2013
Converted manual from Quark to MS Word. A
dded statement
BM
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
www.detcon.com
sales@detcon.com
18.0 WARRANTY
Detcon, Inc., as manufacturer, warrants each new electrochemical toxic gas plug-in sensor cell, for a specified period under the conditions described as follows: The warranty period begins on the date of shipment to the original purchaser and ends after the specified period as listed in the table in Section 4.0. The sensor cell is warranted to be free from defects in material and workmanship. Should any sensor cell fail to perform in accordance with published specifications within the warranty period, return the defective part to Detcon, Inc., 4055 Technology Forest Blvd. Suite 100, The Woodlands, Texas 77381, for necessary repairs or replacement.
19.0 SERVICE POLICY
Detcon, Inc., as manufacturer, warrants under intended normal use each new DM-500IS series plug-in signal transmitter Control Circuit and intrinsically safe Sensor Head circuit to be free from defects in material and workmanship for a period of two years from the date of shipment to the original purchaser. Detcon, Inc., further provides for a five year fixed fee service policy wherein any failed signal Transmitter shall be repaired or replaced as is deemed necessary by Detcon, Inc., for a fixed fee of $65.00. Any failed intrinsically safe Sensor Head circuit shall be repaired or replaced as is deemed necessary by Detcon, Inc., for a fixed fee of $55.00. The fixed fee service policy shall affect any factory repair for the period following the two year warranty and shall end five years after expiration of the warranty. All warranties and service policies are FOB the Detcon facility located in The Woodlands, Texas.
20.0 Revision History
000006-132
CO interfering with C2H3CL was 12150=100, changed to 200=100
about maximum distance of sensor separation (Section 5.5)
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas 77381
DM-600IS Instruction Manual Rev 1.5.9 Page 37 of 37
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Loading...