Model AV1-N4X
Non-Hazardous NEMA 4X Alarm Station
Operator’s Installation and Instruction Manual
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
January 25, 2008 • Document #3194 • Revision 1.1
3200 Research Forest Dr.,
www.detcon.com
Page 2
Model AV1-N4X
This page left intentionally blank
AV1-N4X Instruction Manual ii
Page 3
Model AV1-N4X
Table of Contents
Description................................................................................................................................................ 1
1.0
2.0 Installation................................................................................................................................................ 2
3.0 Specifications............................................................................................................................................ 3
3.1 Strobe ................................................................................................................................................... 3
3.2 Horn...................................................................................................................................................... 4
4.0 Troubleshooting ....................................................................................................................................... 4
5.0 Spare Parts List........................................................................................................................................ 5
6.0 Warranty .................................................................................................................................................. 5
Table of Figures
Figure 1 Alarm Station Dimensions..................................................................................................................... 2
Figure 2 Wiring Diagram ..................................................................................................................................... 2
AV1-N4X Instruction Manual iii
Page 4
Model AV1-N4X
This page left intentionally blank
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
AV1-N4X Instruction Manual iv
www.detcon.comsales@detcon.com
Page 5
Model AV1-N4X
1.0 Description
Detcon Model AV1-N4X audiovisual alarm stations are designed for installation and use in light industrial environments. The alarm station consists of a strobe and siren. The strobe can consist of any dome color such as amber, blue, clear, green, magenta, or red. The siren is capable of producing coded blasts or sustained tones. Model AV1-N4X alarm assemblies are specifically designed for non-hazardous general-purpose locations or environments where a very bright visual and high decibel alarm signal is required. The high­intensity strobe light provides 60-80 flashes per minute. The siren produces a noise level of 99dbA @ 10 feet. The light is UL listed and CSA Certified and meets Type 4X watertight, dust-tight requirements. The siren is UL listed and CSA Certified. Alarm components are pre-assembled and packaged in a NEMA 4X rain tight enclosure. The alarm station can be wired to control circuit alarm devices for the purpose of warning personnel of hazardous conditions. When used in conjunction with Detcon controllers, the alarm station is typically used to provide an alarm 1 (strobe) and an alarm 2 (siren) for predetermined hazardous environmental gas levels (toxic or flammable) as indicated by remote mount gas sensors. A terminal strip mounted on the base plate of the enclosure is provided for power input and discrete switched power to both the strobe and the siren.
AV1-N4X Instruction Manual Rev. 1.1 Page 1 of 6
Page 6
Model AV1-N4X
2.0 Installation
Securely mount the alarm station enclosure in accordance with the drawing in figure #1. Connect wiring in accordance with the drawing in figure #2. To determine the proper voltage of the strobe and siren, refer to the specifications label inside the enclosure
12.25"
7.75"
7.375"
5"
7.75"
Figure 1 Alarm Station Dimensions
120 OR 240 VAC WIRING
STROBE HORN
NL1 NL1
12 OR 24 VDC WIRING
STROBE HORN
NL1 NL1
L2 Neutral
Earth Ground
Switched L1 to Strobe
Switched L1 to Horn
Earth Ground
VDC-
Switched VDC+ to Strobe
Switched VDC+ to Horn
Figure 2 Wiring Diagram
AV1-N4X Instruction Manual Rev. 1.1 Page 2 of 6
Page 7
Model AV1-N4X
3.0 Specifications
3.1 Strobe
Specifications:
Voltage: 12VDC, 24VDC, 50/60HZ 120VAC 50/60HZ, 240VAC 50/60HZ (See specifications label for voltage rating) Mount: 1/2" Pipe Operating Current: 0.44 Amps at 12VDC,
0.22 Amps at 24VDC,
0.10 Amps at 120VAC,
0.07 Amps at 240VAC Dome Colors: Amber, Blue, Clear, Green, Red, and Magenta Operating Temperature: -31°F to 150°F Light Source/Lamp Style: Strobe Tube Lamp Life: 7,000 Hours Candle Power Peak: 175,000 Flash Rate/Minute: 60-80 Joules per Flash: 1.75 Intensity Candela: 40 Amber, 20 Blue, 50 Clear, 20 Green, and 10 Red Enclosure Rating: Type 4 Approvals: UL Listed, CSA Certified, and CE Pending Dimensions: 5"H x 3"Diameter Warranty: 1 Year
AV1-N4X Instruction Manual Rev. 1.1 Page 3 of 6
Page 8
Model AV1-N4X
3.2 Horn
Specifications:
Voltage: 12VDC, 24VDC, 50/60HZ, 120VAC 50/60HZ, 240VAC 50/60HZ, (See specifications label for voltage rating) Mount: Surface / Panel Operating Current: 0.50 Amps at 12VDC,
0.25 Amps at 24VDC,
0.18 Amps at 120VAC,
0.09 Amps at 240VAC Temperature Rating: -65°F to +150°F Sound Output: 99db @ 10 feet, 109dB @ 1 meter Enclosure Rating: Type 4 Approvals: UL Listed, CSA certified, FM Approved Height: 4 in. Width: 4 in. Depth: 2.5 in Warranty: 1 Year
4.0 Troubleshooting
Tools Required Digital volt-ohm meter Refer to . Figure 2 Wiring Diagram Verify proper voltage is being applied to the strobe and siren by measuring with the digital voltmeter probes (see specifications label located inside the enclosure to determine correct voltage).
Strobe: measure voltage from the second terminal on the terminal strip to the third terminal.
Siren: measure voltage from the second terminal on the terminal strip to the fourth terminal.
If power is being provided and the corresponding strobe or siren does not activate, return the alarm station for repair or replacement as discussed in section 6.0 ( ) of this manual or replace damaged components as referred to in section 5.0 (Spare Parts List).
AV1-N4X Instruction Manual Rev. 1.1 Page 4 of 6
Warranty
Page 9
Model AV1-N4X
5.0 Spare Parts List
Part #
Description 3016 4 pin Terminal Block 027-002627-000 Strobe Gasket 027-24412-0 Horn Gasket
Strobe Light
354-49506-
└──┬──┘ Color of strobe Voltage 2 – Red 124 – 12 to 80 VDC 4 – Amber 120 – 120 VAC 5 – Green 240 – 240 VAC 6 – Blue 7 – Magenta 9 – Clear
Horn
356-000-
└──┬──┘ └──┬──┘ Voltage Type Voltage 350 – VAC 012 – 12 VDC 450 – VDC 024 – 24 VDC 120 120VAC 240 240VAC
6.0 Warranty
Detcon Inc., as manufacturer, warrants under intended normal use each new Model AV1-N4X NEMA 4X alarm station to be free from defects in material and workmanship for a period of one year. The warranty period begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas.
AV1-N4X Instruction Manual Rev. 1.1 Page 5 of 6
Page 10
Model AV1-N4X
This page left intentionally blank
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
AV1-N4X Instruction Manual Rev. 1.1 Page 6 of 6
www.detcon.comsales@detcon.com
Loading...