Detcon AV1-C1D2C User Manual

DETCON MODEL AV1-C1D2C
Hazardous Duty Class I. Div 2, Continuous Tone Alarm Station
Operator Instruction Manual
March 7, 2006, Document #3088, Rev 1.2
3200 Research Forest Dr, The Woodla nds, TX 77381
Phone 281.367.4100 • Fax 281.292.2860
2
TA BLE O F C O NT EN T S
1.0 Description
3
1.1 Installation
6
1.2 Spare Parts List
8
1.3 Warranty
8
3
1 .0 DE SC RI PT IO N
STROBE
Detcon Model AV1-C1D2C audio visiual alarm stations are designed for installation and use
in hazardous duty, corrosive work environments. The alarm station consists of a warning light and siren.
The alarm station can be wired to control circuit alarm devices for the purpose of warning personnel of hazardous conditions. When used in conjunction with Detcon controllers, the alarm station is typically used to provide an alarm 1 (strobe) and alarm 2 (horn) for pre-determined hazardous environmental gas levels (toxic or flammable) as indicated by remote mount sensors.
The alarm station warning light is configured with any combination of dome colors such as amber, blue, clear, green, magenta, or red. Dome guards are included. The rugged warning light is specifically designed for hazardous locations or corrosive environments where a very bright visual signal is required.
Hazardous location warning lights are available in voltage ratings of 120VAC or 240VAC.
The strobe light provides 80 high-intensity flashes per minute. UL listed and CSA certified for Class I, Division 2, Groups A, B, C and D; Class II, Division I, Groups E, F, and G; and Class III.
The light meets Type 4X watertight, dust-tight, and corrosion resistant requirements; constructed to IP66. It has an aluminum base coated for corrosion-resistance. The dome guard fits over the glass dome to protect it against accidental collision with moving equipment.