Detcon Aluminum Junction Box User Manual

Page 1
INSTALLATION, OPERATION &
INSTRUCTION MANUAL
Aluminum Junction Box
July 29, 2009• Document #3491• Revision 0.0
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
DETCON, Inc.
3200 Research Forest Dr.,
www.detcon.com
Page 2
Aluminum Junction Box
Page intentionally blank
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
www.detcon.comsales@detcon.com
Aluminum Junction Box Detcon JBox Instruction Manual_R0.doc ii
Page 3
Aluminum Junction Box
Aluminum Junction Box
PN 897-850901-010 (Glass Lens version) PN 897-850000-010 (Solid cover version)
This product is for use as a stand-alone certified junction box or for use in product applications where a certified XP component junction box is part of a more advanced product package.
The Ratings are as follows:
Class 1, Division 1, Groups BCD II 2 G Ex d IIB+H2 Ta -40ºC to 75ºC
Figure 1 Aluminum Condulet Approvals label
The ratings comply with EN 60079-0-2006 and EN 60079-1-2007 standards.
NOTE: Properly rated ¾” NPT blanking plugs must be installed on any conduit entry that is not used. The blanking plugs shall be approved components and shall have hazardous location ratings that are rated equal or greater than the junction box.
CSA
NOTE: All component types that may be attached to this ATEX and
c
certified junction
us
box shall be approved components and shall have hazardous location ratings that are rated equal to or greater than the junction box.
Special Conditions for Safe Use:
1. The equipment is only to be used in Zone 1 and Zone 2 hazardous locations.
2. Where necessary for safety, the contents of the enclosure shall comply with the appropriate requirements of relevant standards for electrical apparatus for use in potentially explosive atmospheres.
3. The assembled equipment shall comply with the appropriate requirements of relevant standards for electrical apparatus for use in potentially explosive atmospheres.
4. The enclosed apparatus may be placed in any arrangement provided that an area of at least 20% of each cross sectional area remains free to permit unimpeded gas flow and therefore unrestricted development of an explosion.
5. Rotating or other devices creating turbulence shall not be incorporated.
Detcon J-Box Instruction Manual Rev. 0.0 Page 1 of 3
Page 4
Aluminum Junction Box
6. Liquids shall not be used when there is risk of producing and explosive mixture by the decomposition of or release of oxygen by these liquids.
7. Oil-filled contactors shall not be used.
8. The use of energy storage devices may present difficulties, due to the possibility of sparking, after isolation from the supply, when the enclosure cover is removed. In addition, secondary cells, and in some cases primary cells may emit flammable gas not considered under the normal certification conditions. The following requirements shall apply:
8.1 All such devices shall be provided with adequate means to prevent incendive sparking when flameproof covers are removed.
8.2 Enclosures which can be opened more quickly than the time necessary for the discharge of incorporated capacitors to a residual energy of:
0.2 mJ for electrical apparatus of Group I or Group IIA, or
06 mJ for electrical apparatus of Group IIB
0.02 mJ for electrical apparatus of Group IIC
shall be provided with label stating delay needed before attempting to open the enclosure. If enclosed components have a temperature above that of the temperature classification of the electrical apparatus a label shall be provided stating the delay necessary before attempting to open the enclosure to allow the component to cool below the temperature classification
9. No holes whether for mechanical or electrical purposes and whether blind or clear shall be drilled in the enclosure other than those shown on the Component Certificate drawings.
10. All entry devices shall be of a type specified in the certification documents having an appropriate component certificate and suitable for the conditions of use, or be specifically certified with the apparatus.
11. Any unused entry shall be closed by a device of a type specified in the certification documents having an appropriate component certificate and suitable for the conditions of use, or be specifically certified with the apparatus.
12. The holder of the final Certificate will be required to provide information to enable the test authority to verify compliance with the above and the relevant parts of the certification standard not explicitly covered by the Component Certificate. (e.g., Temperature classification)
13. The window temperature must not exceed 75ºC.
Installation
Use the 0.25” mounting holes on the ears and suitable hardware for mounting to a wall or pipe.
Use internal and external grounding points as required or recommended by electrical installation guidelines.
When installed with conduit runs, install a properly rated conduit seal within 18” of each conduit entry point.
Properly rated ¾” NPT blanking plugs must be installed on any conduit entry that is not used.
Make sure the ambient temperature at place of installation is within the rated temperature limits of this device.
Operation
Always remove power to devices within junction box prior to removing cover
Detcon J-Box Instruction Manual Rev. 0.0 Page 2 of 3
Page 5
Aluminum Junction Box
A 7/64” (2.77 mm) Allen screwdriver tool is required for lock/unlocking of threaded cover prior to removal.
If the cover cannot be unthreaded by hand force, use a wide span wrench (grabbing knobs on cover) or use a strap wrench (grabbing circumference of cover) to unthread cover.
When returning junction box to service, always tighten the cover down snugly until the O-ring seal is compressed.
Maintenance
If threading of cover becomes difficult, apply small amount of non-volatile non-corrosive thread grease to keep aluminium threads from locking up.
Replace this junction box if there are visible signs of significant corrosion on the metallic enclosure. Replace the cover if there is any evidence of damage to glass lens. Replace the O-ring if it is damaged.
Avoid scratching of the exterior paint to maximize corrosion resistance. Do not submerge in liquids. Minimize direct exposure to highly corrosive vapors and liquids.
Service & Warranty Information
Detcon Inc. warrants, under normal intended use, each aluminum condulet for a one year period under the conditions described as follows: The warranty period begins on the date of shipment to the original purchaser. The Detcon Aluminum Condulet is warranted to be free of defects in material and workmanship. Should any Condulet fail to perform in accordance with published specifications within the warranty period, return the defective part to Detcon, Inc., 3200 A-1 Research Forest Dr., The Woodlands, Texas 77381, for necessary repairs or replacement.
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
Detcon J-Box Instruction Manual Rev. 0.0 Page 3 of 3
www.detcon.comsales@detcon.com