1.0Description
The Detcon A1V1-CI Div2 Alarm Stations are specifically designed for use with the Detcon Sentinel series of
controllers. These alarm stations utilize a 5 Joule Strobe and a 110Db @ 1mtr Horn that can provide one of 16
possible alarm tones.The unit is designed for installation and use in Hazardous duty, corrosive work
environments rated at Class 1, Division 2, Groups E, F, and G.
19.9"
3.5"
6.4"
14.5"
Figure 1
10.7"
The alarm station is designed to be pole mounted, and can be positioned almost anywhere. The alarm station is
powered by external 10-18VDC (typically 12VDC) and utilizes an internal DC/DC Converter to create
24VDC to drive the strobe and horn. The Horn and strobe are driven by independent voltage inputs with a
common return. Input voltage to ALM1 provides power to the strobe, and ALM2 provides power to the horn.
Wiring to/from
Controller
Alarm 2
wiring
Figure 2 12V to 24V Alarm Station Board
Sebtinel A1V1 Instruction ManualRev. 0.0Page 1 of 5
Alarm 1
wiring
A1V1-DV2
1.1Strobe
The alarm station warning light is configured with choice of dome colors such as amber, blue, clear, green,
magenta, or red. Dome guard is included. The rugged warning light is specifically designed for hazardous
locations or corrosive environments where a very bright visual signal is required.
Figure 3 Strobe
1.2Horn
The alarm station vibrating horn produces a noise level of a 100dB of sound by the electromechanical
vibration of a stainless steel diaphragm. The horn mechanism has an effective broadcast range of 200 feet.
The horn is enclosed in heavy-duty copper-free cast aluminum housing tapped for 3/4 - inch conduit.
The horn is capable of producing coded blasts or sustained tones, and is excellent for general alarm,
start/dismissal, coded paging, and process control signaling in areas where their sound output exceeds ambient
noise levels. The horn in the Strobe/Horn alarm stations has 16 possible combinations of sounds that are
selectable by switch settings inside the alarm.
Figure 4 Horn
Horn only units provide one unique tone for each alarm level. The tone settings for these units are set at the
Detcon factory and cannot be changed by the user. These alarm tones can be initiated individually, but if both
alarms are active, the tone for alarm two has priority.
Sebtinel A1V1 Instruction ManualRev.0.0Page 2 of 5
A1V1-DV2
2.0Installation
The A1V1-DV2 Alarm Station is made to be mounted on a 2” or 3” diameter pipe. Two 3” U-bolts with
hardware are provided for mounting. The location for mounting the wireless alarm station should be carefully
selected. Occasional access to the unit will be necessary for maintenance.
19.9"
3.5"
2~3" Pipe
2~3" Pipe
Mounting
10.7"
Hardware
6.4"
14.5"
Figure 5 Basic C1D2 Wireless Alarm Stations
Wiring to the unit will normally be provided by use of the Alarm Cable provided with the Sentinel Controller
that the unit will be connected to. Feed the cable through the Cable Gland at the bottom of the alarm assembly
and connect the White wire to ‘ALM1’, the Gray wire to ‘ALM2’ and the Black wire to ‘GND’ on the
connector provided.
Wiring to
Strobe
Green/Yellow
Black
Red
Wiring from
Controller
White
Gray
Black
12-24V Alarm
Term Bd.
C1D1 Cable to Horn
Green/Yellow
Red
Black
Horn PCA
Figure 6 Unit Wiring
Sebtinel A1V1 Instruction ManualRev. 0.0Page 3 of 5
A1V1-DV2
3.0Operation
The A1V1-DV2 Alarm Stations provide one strobe and a horn. The alarm station is set to respond to alarms
from the controlling unit. The controller has independent control over the strobe and the Horn, and they will
be activated when the appropriate alarm is activated.
All strobes have a flash rate of 1 Hz (one flash per second). This is preset by the manufacture and cannot be
modified.
The horn has up to 32 possible settings for use in different configurations. The default setting of the horn is
factory set. To change the setting of the horn, remove the rear end of the horn, and set dip switch according to
the Sound Signals Table.
Table 1 Sound Signals
TONE FREQ/DESCRIPTION
1Alt Tones 800/970 Hz at 1/4 sec11111
2Sweeping 800/970 Hz at 7Hz11110Fast Sweep(LF)
3
Sweeping 800/1000 Hz at 1 Hz
4Continuous at 2850 Hz11100
5
Sweeping 2400-2850 Hz at 7 Hz
6
Sweeping 2400-2850 Hz at 1 Hz
7
8
9Alt. Tones 2400/2850 Hz at 2 Hz10111
10Int. Tone of 970 Hz at 1 Hz10110
11Alt. Tones 800/970 Hz at 7/8 Hz10101
12Int. Tone at 2850 Hz at 1Hz10100
13970Hz at 1/4 sec on 1 sec off10011
14Continuous at 970 Hz10010
15 554Hz for 100ms / 440 Hz for 400ms10001French Fire Sound
16Int. 660 Hz 150 ms on 150 ms off10000Swedish Fire Alarm
17Int. 660 Hz 1.8 sec on 1.8 sec off01111Swedish Fire Alarm
18Int. 660 Hz 6.5 sec on 13 sec off01110Swedish Fire Alarm
19Continuous 660 Hz01101Swedish Fire Alarm
20Alt 554/440 Hz at 1 Hz01100Swedish Fire Alarm
21Int. 660 Hz at 7/8 Hz01011Swedish Fire Alarm
22Int. 2850 Hz 150 ms on 100 ms off01010
23
24
25
26
27Int. 3100 Hz 0.32s on / 0.68s off00101
28
29
30
31
32
Sweep 1200-500 Hz at 1 Hz
Sweep 800-970 Hz at 50 Hz
Sweep 2400-2850 Hz at 50 Hz
3 970Hz pulses 0.5on/0.5off, 1.5 off
3 2850Hz pulses 0.5on/0.5off, 1.5 off
Slow Whoop
Spare/Customer Tone
Spare/Customer Tone
Spare/Customer Tone
Spare/Customer Tone
Spare/Customer Tone
SWITCHTONE
11101
11011
11010
11001
11000Din Tone
01001
01000
00111
00110
00100
00011
00010
00001
00000
Med Sweep(LF)
Fast Sweep
Slow Whoop
Back-Up Alarm(LF)
Back Up Alarm(HF)
Pelican Crossing
Low Freq. Buzz
High Freq. Buzz
Sebtinel A1V1 Instruction ManualRev.0.0Page 4 of 5
A1V1-DV2
4.0Parts List
Detcon Part #Description
354-1916x6-02424VDC Strobe, Ext Ground (x represents color of lamp)
Strobe colors: Red (2), Amber (4), Green (5), Blue (6), Magenta (7), and Clear (9)
356-DB3007-024Model DB3 Horn
500-005206-00012V to 24V Alarm Station Board
5.0Specifications
Strobe
Dome ColorsAmber / Blue / Clear / Green / Magenta / Red
Flash Rate/Minute60
Lamp SourceLED
Horn
Db Output115db @ 1meter (tone dependent)
Duty CycleNot rated for continuous duty (5 minute duty cycle)
Alarm Unit
Operating Current1.5A Max (@ 12VDC input, both Horn and Strobe operational)
Operating Temperature-20ºC to 60ºC
Voltage12VDC Input voltage
Dimensions14.5”H X 19.9”W X 10.7”D
6.0Warranty
Detcon Inc., as manufacturer, warrants under intended normal use each new A1V1-DV2 Alarm Station to be
free from defects in material and workmanship for a period of one year. The warranty period begins from the
date of shipment to the original purchaser and ends one year thereafter. All warranties and service policies are
FOB the Detcon Inc. facility located in The Woodlands, Texas.