Operating Guide
AMV 23 SL
MAINTENANCE
T ambient 0-55 °C
T media 0-150 °C
FREE
5-95 % RH
no condensing
T surface 0 -150 °C
AMV 23 SL +
VS 2 (DN20-25), VM 2 (DN 15-50)
=
=
AMV 23 SL +
VB 2 (DN 15-50)
AUTO
5-7 mm × 1 mm
T20
AMV 23 SL, AMV 33 SL +
AVQM (see Data sheet)
32 mm 5 mm
❶
© Danfoss | 2018.12
②
①
Max 25 Nm
1× 32 mm
③
⑥
IP 54
②
④
4×
⑤
⑦
②
min. 4 Nm
max. 5 Nm
IP 54
①
min. 4 Nm
max. 5 Nm
VI.AE.I7.00 | 1

AMV 23 SL
❷
❹
❸
1×
❺
②
4×
=
SD
①
AMV 23 SL
230V
Additional switch S2
N 0 V Neutral
L 24 / 230 Vac (Only for AMV 23 SL) Power supply
1
24/230 Vac Input
15
4, 13
1
15
4
13
Output
Stroke limitation and additional switch adjustment
Technical data for contact max. 250 Vac, 2 A
2 | © Danfoss | 2018.12 VI.AE.I7.00

AMV 23 SL
❻
Stroke adjustment VS2, VM2, VB2
k
DN
15
20
25
32
40
50
VS
(m/h)
0.25
0.40
0.63
1.0
1.6
2.5
4.0
2.5 5 -
4.0
6.3 7 5
4.0 5 - -
6.3
8.0
10.0 - 7
10
16 - 10
16
25 - 10
25
40 - 10
VS2 VM2 VB2
4
-
-
-
-
-
-
❼
Stroke adjustment AVQM PN 16
Valve stroke (mm)
5 5
5
5 -
7 -
10 -
10 -
-
S1 = 10 mm (max)
S1 = 0 mm
Example:
AVQM PN 25
DN 20
max. flow: 2 m3/h
Stroke S1 ≈ 3.5 mm
DN 15
kvs 1.0
kvs 4.0
kvs 2.5
kvs 0.4
kvs 1.6
DN 20, kvs 6.3 DN 25, kvs 8.0 DN 32, kvs 10
© Danfoss | 2018.12 | 3VI.AE.I7.00

AMV 23 SL
❽
Stroke adjustment AVQM PN 25
DN 15
DN 20, kvs 6.3
DN 25, kvs 8.0
kvs 1.0
kvs 0.4
DN 32, kvs 12. 5 DN 40, kvs 16
DN 32, kvs 12. 5 DN 40, kvs 20
kvs 4.0
kvs 2.5
kvs 1.6
DN 50, kvs 20
DN 50, kvs 25
❾
7369xxx0 / VI.AE.I7.004 | © Danfoss | DHS-SRMT/SI | 2018.12