Danfoss AMV 120 NL-1 Data sheet

Data sheet
Actuator for 3-point Triac Control AMV 120 NL-1
Description
Ordering Actuators
AMV 120 NL-1 24 VAC 10 s/mm @ 60Hz (12 s/mm @ 50Hz) 082H5005
The AB-QM assembly is suitable for installation within fan coil units, VAV, induction units or additional units that require combined balancing and valve control, which could be located within enclosures or plenum rated spaces. Designed within the actuator is an overload and gap function to prevent unnecessary travel from the actuator.
Main data:
• 3-point triac control
• End position feedback indication
• Force switch-off at stem down position prevents overload of actuator and valve
• Gap function detection on stem up travel
• No tools required for mounting
• Maintenance free during lifetime
• Low noise operation
• 1/2” Conduit hole, removable plate
• Wiring terminal block
• In accordance with UL 2043 for plenum installation
• cULus listed
Typ e Supply voltage Speed Code No.
Technical data
Typ e AMV 110 NL AMV 120 NL
Power supply V 24AC; +10%... -15%
Electrical Connection 1/2” electrical conduit, wiring terminal block
Power consumption VA 1
Frequency Hz 50/60
Control Input 3-point triac control
Output Signal End travel position feedback
Actuator Force lbf (N) 29.3 (130)
Max. Stem Travel mm 5
Travel Speed 12s/mm @ 50Hz, 10s/mm @ 60Hz
Max. Medium Temperature °F (°C) 248 (120)
Stroke mm 5
Ambient temperature °F (°C) 32 to 131 (0 to 55)
Humidity 5 to 95% RH, noncondensing
Weight
C US
USA
Canada
Europe
lbs (kg)
UL Listed , CCN XABE, File E480529 ; to ANSI/UL 60730-1 and ANS I/ UL 60730-2-14
Investig ated and approved f or plenum use in accor dance with UL 2043
UL listed , CCN XABE7, File E480529; to CAN/CS A-E60730-1:13 and CAN/CSA-E60730 -2-14:13
CE Mark - Danf oss declares that t his product comp lies with all relev ant CE-marking
0.66 (0.3)
directives
© Danfoss | 2019.12 AI313848539589en-000201 | 1
Data sheet Actuator for 3-point Triac Control AMV 120 NL-1
50/60Hz
Installation
Disposal
Wiring
Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.
The actuator is fixed to the valve body by means of a mounting ring, which requires no tools for mounting. The ring should be tightened by hand.
Electrical
Important: Prior to energizing the actuator should be assembled to the AB-QM.
The actuator must be dismantled and the elements sorted into various material groups before disposal.
AMV 120 NL-1
SN 4 1 3 5
½”
(Oponal)(Oponal)
~ AC 24V
A field supplied 1/2” trade size electrician’s fitting and lock nut can be mounted to the actuator enclosure. Insert wiring material through the removable plug or conduit fitting, and wire connection to the terminal block.
2 | AI313848539589en-000201 © Danfoss | 2019.12