Actuators for three point control
AMV 01, AMV 02, AMV-H 01, AMV-H 02
Description AMV 01/02 and AMV-H 01/02 actuators are used
with VZ, VZL, VRBZ or with AB-QM valves (AMV
version only). The actuator can be used with
fan coil units, induction units, small reheaters,
recoolers, and zone applications in which hot/
cold water is the controlled medium.
Main data:
• 3-point versions
• The advanced design incorporates no-force
switch-off at stem up position, which enables
AMV 01, AMV 02
use of the actuator on valves with different
nominal strokes and improves the controller
response
• Force switch-off at stem down position
prevents overload of actuator and valve
• No tools required for mounting
• Maintenance free during the lifetime
• Low noise operation
• Supplied with 1.5 m cable.
Ordering
Technical data
AMV-H 01, AMV-H 02
Type
AMV 01
AMV 0212 s/mm082H8004
AMV-H 0124 s/mm082H8021
AMV-H 0212 s/mm082H8024
AMV 01
AMV 0212 s/mm082H8005
AMV-H 0124 s/mm082H8022
AMV-H 0212 s/mm082H8025
TypeAMV 01, AMV-H 01AMV 02, AMV-H 02
Power supply24 Vac, 230 Vac; +10 to –15%
Power consumption1 VA - 24 Vac; 7 VA-230 Vac
Frequency50 Hz/60 Hz
Close of force200 N
Max. stroke5.5 mm
Speed24 s/mm12 s/mm
Max. medium temperature inside the pipe120 °C
Ambient temperature0 to 55 °C
Storage and transport temperature–40 to +70 °C
Protection codeIP 42
Weight0.34 kg
Supply
voltage
24 V~
230 V~
- marking in accordance with standards
SpeedCode No.
24 s/mm082H8001
24 s/mm082H8002
Spare parts
TypeCode No.
1.5 m cable for AMV, AMV-H - 24 V082H8007
1.5 m cable for AMV, AMV-H - 230 V082H8008
EMC- Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN 50081-1 and EN 50082-1
Low voltage Directive 73/23/EEC and 93/68/EEC,
EN 60730/2/14
Data sheet Actuators for three point control AMV 01, AMV 02, AMV-H 01, AMV-H 02
Manual override
AMV-H 01, AMV-H 02
The position indicator is factory calibrated, but if
you need to make incication more precise or have
moved the knob while the actuator is removed
from the valve, then the following advice applies:
1 Energize the actuator with a signal to drive the
stem up (with the actuator fitted to the valve).
2 When it stops, rotate the position indicator
ring while pressing the setting lever , to
the position where the orienting groove
points to the minus sign (-). The knob
should not be turned in this case.
3 Energize the actuator with a signal to drive the
stem down.
Knob
Position indicator ring
Minus sign
Orienting groove
Setting lever
Disconnecting the cable
from the actuator
To disconnect the cable, first ensure that
the actuator is electrically isolated. Insert a
screwdriver into the cable release slot, push the
handle away from the mounting ring, and pull
the connector out of the actuator by hand.