Daikin LRYEN10A7Y1, LRNUN5A7Y1 Installer reference guide

Installer and user reference guide
CO₂ Conveni-Pack outdoor unit
LRYEN10A7Y1 LRNUN5A7Y1

Table of contents

Table of contents
1 About the documentation 5
1.1 About this document ...................................................................................................................................................... 5
2 General safety precautions 6
2.1 About the documentation .............................................................................................................................................. 6
2.1.1 Meaning of warnings and symbols ................................................................................................................ 6
2.2 For the installer............................................................................................................................................................... 7
2.2.1 General ........................................................................................................................................................... 7
2.2.2 Installation site ............................................................................................................................................... 8
2.2.3 Refrigerant — in case of R744........................................................................................................................ 10
2.2.4 Electrical ......................................................................................................................................................... 11
3 Specific installer safety instructions 13
For the user 17
4 User safety instructions 18
4.1 General............................................................................................................................................................................ 18
4.2 Instructions for safe operation....................................................................................................................................... 19
5 About the system 23
5.1 System layout.................................................................................................................................................................. 23
6 Before operation 25
7 Operation 27
7.1 Operation range.............................................................................................................................................................. 27
7.2 Design pressure............................................................................................................................................................... 27
8 Energy saving and optimum operation 28
9 Maintenance and service 29
9.1 Maintenance before a long stop period......................................................................................................................... 29
9.2 Maintenance after a long stop period............................................................................................................................ 30
9.3 About the refrigerant...................................................................................................................................................... 30
9.4 Recommended maintenance and inspection ................................................................................................................ 30
10 Troubleshooting 32
10.1 Error codes: Overview .................................................................................................................................................... 34
11 Relocation 35
12 Disposal 36
For the installer 37
13 About the box 38
13.1 Overview: About the box ................................................................................................................................................ 38
13.2 Outdoor unit ................................................................................................................................................................... 38
13.2.1 To unpack the outdoor unit ........................................................................................................................... 38
13.2.2 To handle the outdoor unit............................................................................................................................ 39
13.2.3 To remove the accessories from the outdoor unit........................................................................................ 40
Installer and user reference guide
2
14 About the units and options 41
14.1 Identification ................................................................................................................................................................... 41
14.1.1 Identification label: Outdoor unit .................................................................................................................. 41
14.2 About the outdoor unit................................................................................................................................................... 42
14.2.1 Labels on outdoor unit ................................................................................................................................... 43
14.3 System layout .................................................................................................................................................................. 46
14.4 Combining units and options .......................................................................................................................................... 47
14.4.1 Possible combinations of indoor units........................................................................................................... 47
14.4.2 Possible options for the outdoor unit............................................................................................................ 48
14.5 Indoor unit constraints ................................................................................................................................................... 48
14.5.1 Constraints for air conditioning ..................................................................................................................... 48
14.5.2 Constraints for refrigeration .......................................................................................................................... 49
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
Table of contents
15 Unit installation 50
15.1 Preparing the installation site......................................................................................................................................... 50
15.1.1 Installation site requirements of the outdoor unit........................................................................................ 50
15.1.2 Additional installation site requirements of the outdoor unit in cold climates............................................ 53
15.1.3 Additional installation site requirements for CO₂ refrigerant....................................................................... 53
15.2 Opening and closing the unit.......................................................................................................................................... 58
15.2.1 About opening the units................................................................................................................................. 58
15.2.2 To open the outdoor unit............................................................................................................................... 58
15.2.3 To open the electrical component box of the outdoor unit ......................................................................... 59
15.2.4 To close the outdoor unit............................................................................................................................... 60
15.3 Mounting the outdoor unit............................................................................................................................................. 61
15.3.1 About mounting the outdoor unit ................................................................................................................. 61
15.3.2 Precautions when mounting the outdoor unit.............................................................................................. 61
15.3.3 To provide the installation structure ............................................................................................................. 61
15.3.4 To install the outdoor unit on the installation structure............................................................................... 63
15.3.5 To provide drainage........................................................................................................................................ 63
16 Piping installation 64
16.1 Preparing refrigerant piping ........................................................................................................................................... 64
16.1.1 Refrigerant piping requirements.................................................................................................................... 64
16.1.2 Refrigerant piping material ............................................................................................................................ 65
16.1.3 Refrigerant piping length and height difference ........................................................................................... 65
16.1.4 To select the piping size ................................................................................................................................. 67
16.1.5 To select refrigerant branch kits .................................................................................................................... 69
16.1.6 To select expansion valves for refrigeration.................................................................................................. 70
16.2 Using stop valves and service ports................................................................................................................................ 71
16.2.1 Overview stop valves for refrigeration and air-conditioner.......................................................................... 71
16.2.2 Overview stop valves for maintenance.......................................................................................................... 71
16.2.3 To handle the stop valve ................................................................................................................................ 72
16.2.4 To handle the service port ............................................................................................................................. 74
16.2.5 Tightening torques ......................................................................................................................................... 75
16.3 Connecting the refrigerant piping .................................................................................................................................. 75
16.3.1 About connecting the refrigerant piping ....................................................................................................... 75
16.3.2 Precautions when connecting the refrigerant piping.................................................................................... 76
16.3.3 To remove the spun pipes.............................................................................................................................. 77
16.3.4 To connect the refrigerant piping to the outdoor unit ................................................................................. 78
16.3.5 To braze the pipe end..................................................................................................................................... 80
16.3.6 Guidelines to connect T-joints ....................................................................................................................... 81
16.3.7 Guidelines to install a dryer............................................................................................................................ 82
16.3.8 Guidelines to install safety valves .................................................................................................................. 83
16.3.9 Guidelines to install blow off piping............................................................................................................... 83
16.4 Checking the refrigerant piping ...................................................................................................................................... 83
16.4.1 About checking the refrigerant piping........................................................................................................... 84
16.4.2 Checking refrigerant piping: General guidelines ........................................................................................... 84
16.4.3 Checking refrigerant piping: Setup ................................................................................................................ 85
16.4.4 To perform a leak test .................................................................................................................................... 85
16.4.5 To perform vacuum drying............................................................................................................................. 86
16.5 Insulating the refrigerant piping ..................................................................................................................................... 87
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
17 Electrical installation 88
17.1 About electrical compliance ........................................................................................................................................... 88
17.2 Field wiring: Overview .................................................................................................................................................... 89
17.3 Guidelines when knocking out knockout holes.............................................................................................................. 90
17.4 Guidelines when connecting the electrical wiring ......................................................................................................... 90
17.5 Specifications of standard wiring components .............................................................................................................. 92
17.6 Connections to the outdoor unit .................................................................................................................................... 93
17.6.1 Low voltage wiring – Outdoor unit ................................................................................................................ 93
17.6.2 High voltage wiring – Outdoor unit................................................................................................................ 95
17.7 Connections to the capacity up unit............................................................................................................................... 96
17.7.1 Low voltage wiring – Capacity up unit ........................................................................................................... 97
17.7.2 High voltage wiring – Capacity up unit .......................................................................................................... 99
18 Charging refrigerant 101
18.1 About charging refrigerant ............................................................................................................................................. 101
18.2 About the refrigerant...................................................................................................................................................... 101
18.3 Precautions when charging refrigerant.......................................................................................................................... 102
18.4 To determine additional refrigerant amount ................................................................................................................. 104
18.5 To charge refrigerant ...................................................................................................................................................... 106
19 Finishing the outdoor unit installation 107
Installer and user reference guide
3
Table of contents
19.1 To check the insulation resistance of the compressor .................................................................................................. 107
20 Configuration 108
20.1 Overview: Configuration ................................................................................................................................................. 108
20.2 Making field settings ....................................................................................................................................................... 108
20.2.1 About making field settings............................................................................................................................ 108
20.2.2 To access the field setting components......................................................................................................... 108
20.2.3 Field setting components............................................................................................................................... 109
20.2.4 To access mode 1 or 2.................................................................................................................................... 110
21 Commissioning 112
21.1 Overview: Commissioning .............................................................................................................................................. 112
21.2 Precautions when commissioning .................................................................................................................................. 112
21.3 Checklist before commissioning ..................................................................................................................................... 113
21.4 About the test run........................................................................................................................................................... 114
21.5 To perform a test run (7-segment display) .................................................................................................................... 114
21.5.1 Test run checks............................................................................................................................................... 115
21.5.2 Correcting after abnormal completion of the test run.................................................................................. 118
21.6 Operating the unit........................................................................................................................................................... 118
21.7 Logbook ........................................................................................................................................................................... 118
22 Hand-over to the user 120
23 Maintenance and service 121
23.1 Overview: Maintenance and service .............................................................................................................................. 121
23.2 Maintenance safety precautions .................................................................................................................................... 121
23.2.1 To prevent electrical hazards......................................................................................................................... 121
23.3 To release refrigerant ..................................................................................................................................................... 122
24 Troubleshooting 123
24.1 Overview: Troubleshooting ............................................................................................................................................ 123
24.2 Precautions when troubleshooting ................................................................................................................................ 123
24.3 Solving problems based on error codes ......................................................................................................................... 123
24.3.1 Error codes: Overview.................................................................................................................................... 124
25 Disposal 128
26 Technical data 129
26.1 Service space: Outdoor unit ........................................................................................................................................... 129
26.2 Piping diagram: Outdoor unit ......................................................................................................................................... 132
26.3 Piping diagram: Capacity up unit .................................................................................................................................... 133
26.4 Wiring diagram: Outdoor unit ........................................................................................................................................ 134
27 Glossary 139
Installer and user reference guide
4
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

1 About the documentation

1.1 About this document

Target audience
Authorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the outdoor unit)
1 | About the documentation
Installation and operation manual of the outdoor unit:
- Installation and operation instructions
- Format: Paper (in the box of the outdoor unit)
Installer and user reference guide of the outdoor unit:
- Preparation of the installation, reference data,…
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
5
2 | General safety precautions

2 General safety precautions

2.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

2.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
Installer and user reference guide
6
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbols used in the documentation:
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
2 | General safety precautions

2.2 For the installer

2.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
Installer and user reference guide
7
2 | General safety precautions
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.

2.2.2 Installation site

Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
Instructions for equipment using R744 refrigerant
Installer and user reference guide
8
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
WARNING
Do NOT pierce or burn refrigerant cycle parts.Be aware that the refrigerant inside the system is odourless.
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
2 | General safety precautions
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well­ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater) and have a room size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
NOTICE
Precautions shall be taken to avoid excessive vibration or pulsation to
refrigeration piping.
Protection devices, piping and fittings shall be protected as far as possible against
adverse environmental effects.
Provision shall be made for expansion and contraction of long runs of piping.Piping in refrigerating systems shall be designed and installed such as to minimise
the likelihood of hydraulic shock damaging the system.
The indoor equipment and pipes shall be securely mounted and guarded such
that accidental rupture of equipment or pipes cannot occur from events such as moving furniture or reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant leaks.
NOTICE
Do NOT re-use joints and copper gaskets which have been used already.Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
Installation space requirements
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
NOTICE
Pipework shall be protected from physical damage.Installation of pipework shall be kept to a minimum.
Installer and user reference guide
9
2 | General safety precautions

2.2.3 Refrigerant — in case of R744

See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Carbon dioxide poisoningAsphyxiation
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
CAUTION
A vacuumed system will be under triple point. To avoid solid ice, ALWAYS start charging with R744 in vapour state. When the triple point is reached (5.2 bar absolute pressure or 4.2bar gauge pressure), you may continue charging with R744 in liquid state.
Installer and user reference guide
10
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use R744 (CO2) as refrigerant. Other substances may cause explosions and
accidents.
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

2.2.4 Electrical

2 | General safety precautions
Do NOT charge liquid refrigerant directly from a gas line. Liquid compression
could cause compressor operation failure.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
Open refrigerant cylinders slowly.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
11
2 | General safety precautions
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
Installer and user reference guide
12
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
3 | Specific installer safety instructions

3 Specific installer safety instructions

Always observe the following safety instructions and regulations.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at high speed, it will cause injury.
General installation requirements
WARNING
Make sure to install all necessary countermeasures in case of refrigerant leakage
according to standard EN378 (see "15.1.3 Additional installation site
requirements for CO₂ refrigerant"[453]).
Make sure to install a CO
refrigerant piping, air conditioning units, showcases or blower coils, and enable the function for refrigerant leak detection (see the installation manual of the indoor units).
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
leak detector (field supply) in every room with
2
Installation site (see
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
WARNING
All installed safety valves MUST ventilate to the outdoor space and NOT into a closed area.
CAUTION
If the safety valve operates, CO2 gas may concentrate inside the casing of the outdoor unit. Therefore, you should ALWAYS take a distance for your own safety. You can close the outdoor unit if your portable CO2 detector confirmed that the concentration of CO2 is at an acceptable level. For example, if 7kg CO2 is released inside the casing, it takes around 5 minutes until the concentration of CO2 is low enough.
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the main unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
"15.1Preparing the installation site"[450]
)
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
WARNING
Install the unit only in locations where the doors of the occupied space are not tight fitting.
Installer and user reference guide
13
3 | Specific installer safety instructions
NOTICE
Serious injury and/or damage can result from blow off of the liquid receiver safety valve (see "26.2Piping diagram: Outdoor unit"[4132]):
NEVER service the unit when the pressure at the liquid receiver is higher than the
set pressure of the liquid receiver safety valve (86 barg±3%). If this safety valve releases refrigerant, it can cause serious injury and/or damage.
If the pressure > set pressure, ALWAYS discharge from pressure relief devices
before servicing.
It is recommended to install and secure blow off piping to the safety valve.Remove the refrigerant before altering the safety valve position.
NOTICE
Adverse effects shall be considered. For example, danger of water collecting and freezing in discharge pipes for pressure relief devices, accumulation of dirt and debris, or blockage of the discharge pipes by solid CO2 (R744).
INFORMATION
Instructions on how to fix the unit in a correct way can be found in "15 Unit
installation"[450].
Refrigerant piping installation (see
NOTICE
During brazing or welding, refrigerant shall be removed from parts of the system affected by the heat from brazing or welding. It is recommended that such components are shipped without refrigerant charge.
WARNING
ONLY use R744 (CO
accidents.
) as refrigerant. Other substances may cause explosions and
2
When installing, charging refrigerant, maintaining or performing service, ALWAYS
use personal protective equipment, such as safety shoes, safety gloves and safety glasses.
If the unit is installed indoors (for example, in a machine room), ALWAYS use a
portable CO2 detector.
If the front panel is open, ALWAYS beware of the rotating fan. The fan will
continue rotating for a while, even after the power switch has been turned off.
CAUTION
Do NOT reuse piping from previous installations.
"16Piping installation"[464]
)
Installer and user reference guide
14
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrigerant, unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion.
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
3 | Specific installer safety instructions
WARNING
Use K65 piping for high-pressure applications with a working pressure of 120bar
or 90bar, depending on its location in the system.
Use K65 unions and fittings approved for a working pressure of 120bar or 90bar,
depending on its location in the system.
Only brazing is allowed for connection of pipes. No other types of connections are
allowed.
Expanding of pipes is not allowed.
NOTICE
Piping outside a machinery room or enclosure shall be protected against possible accidental damage.
NOTICE
Refrigerant piping shall be protected or enclosed to avoid damage.
NOTICE
Refrigerant piping passing through fire resistant walls and ceilings shall be sealed in such a way as to be consistent with the fire rating of the partition.
NOTICE
Piping shall be suitably supported according to its size and service weight. For more information, see European Standard EN378.
INFORMATION
To complete the refrigerating system, additional charging of refrigerant is required. See "18Charging refrigerant"[4101].
Electrical installation (see
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
"17Electrical installation"[488]
)
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
15
3 | Specific installer safety instructions
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
INFORMATION
A wiring diagram can be found on the applicance and its description of the connections and wiring to external control devices and supply cord can be found in
"26.4Wiring diagram: Outdoor unit"[4134].
INFORMATION
The method of connection of the appliance to the electrical supply and interconnection of separate components is described in "17.2 Field wiring:
Overview"[489].
INFORMATION
Details of type and rating of fuses, or rating of circuit breakers are described in
"17Electrical installation"[488].
Installer and user reference guide
16
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

For the user

For the user
For the user
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
17
4 | User safety instructions

4 User safety instructions

Always observe the following safety instructions and regulations.

4.1 General

WARNING
If you are NOT sure how to operate the unit, contact your installer.
WARNING
Children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge can only use this appliance if they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
Children MUST NOT play with the appliance. Cleaning and user maintenance MUST NOT be carried out
by children without supervision.
WARNING
To prevent electrical shocks or fire:
Do NOT rinse the unit.Do NOT operate the unit with wet hands.Do NOT place any objects containing water on the unit.
CAUTION
Do NOT place any objects or equipment on top of the
unit.
Do NOT sit, climb or stand on the unit.
Installer and user reference guide
18
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4 | User safety instructions
Units are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration. Possible chemical symbols are: Pb: lead (>0.004%). Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.

4.2 Instructions for safe operation

WARNING
Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
CAUTION
If this unit is installed indoors, it must ALWAYS be equipped with an electrically powered safety measure such as a CO2 refrigerant leak detector (field supply). In order to be effective, the unit must ALWAYS be electrically powered after installation.
If for any reason the CO2 refrigerant leak detector is powered OFF, ALWAYS use a portable CO2 detector.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at high speed, it will cause injury.
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
19
4 | User safety instructions
CAUTION
NEVER touch the internal parts of the controller.Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
CAUTION
NEVER expose little children, plants or animals directly to the airflow.
WARNING
Installer and user reference guide
20
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the main unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4 | User safety instructions
WARNING
Do NOT place a flammable spray bottle near the air conditioner and do NOT use sprays near the unit. Doing so may result in a fire.
Maintenance and service (see
WARNING: System contains refrigerant under very high pressure.
The system MUST be serviced by qualified persons only.
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running. Be sure to turn off the main switch before executing any
maintenance task.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
CAUTION
"9Maintenance and service"[429]
)
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
CAUTION
Before accessing terminal devices, make sure to interrupt all power supply.
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop operation and turn all power supplies off. Otherwise, an electric shock and injury may result.
WARNING
Be careful with ladders when working in high places.
WARNING
Do NOT let the indoor unit get wet. Possible consequence: Electric shock or fire.
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
21
4 | User safety instructions
About the refrigerant (see
WARNING
Do NOT pierce or burn refrigerant cycle parts.Be aware that the refrigerant inside the system is
odourless.
WARNING
The R744 refrigerant (CO2) inside the unit is odourless, non-flammable and normally does NOT leak.
If the unit is installed indoors, ALWAYS install a CO detector according to the specifications of standard EN378.
If the refrigerant leaks in high concentrations in the room, it may have negative effects on its occupants such as asphyxiation and carbon dioxide poisoning. Ventilate the room and contact the dealer where you purchased the unit.
"9.3About the refrigerant"[430]
)
2
Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.
Troubleshooting (see
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
"10Troubleshooting"[432]
)
Installer and user reference guide
22
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

5 About the system

The indoor units can be used for heating/cooling and refrigerating applications. The type of indoor units which can be used depends on the outdoor units series.
WARNING
Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
NOTICE
Do NOT use the system for other purposes. In order to avoid any quality deterioration, do NOT use the unit for cooling precision instruments or works of art.
NOTICE
Do NOT use the system for cooling water. It may freeze.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available in technical engineering data and should be consulted. Contact your installer to receive more information and professional advice.
5 | About the system

5.1 System layout

INFORMATION
The following illustration is an example and might NOT match your system layout.
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
23
5 | About the system
ab
e e
d c
f
h
i
j
k
h
l
i
j
k
l
g
a Main outdoor unit (LRYEN10*) b Capacity up unit (LRNUN5*) c Communication box (BRR9B1V1) d Indoor unit for air conditioning e Indoor unit for refrigeration (showcase)
f Indoor unit for refrigeration (blower coil) g Safety valve h CO2 control panel
i CO2 detector
j CO2 alarm k CO2 ventilator
l Shut off valve
Installer and user reference guide
24
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

6 Before operation

WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
NOTICE
NEVER inspect or service the unit by yourself. Ask a qualified service person to perform this work.
WARNING
NEVER use a flammable spray such as hair spray, lacquer or paint near the unit. It may cause a fire.
6 | Before operation
WARNING
Do NOT keep flammable materials inside the unit. They may cause an explosion or a fire.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
NOTICE
Be sure to turn ON the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor.
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Operation modes:
Refrigeration only
Cooling only
Cooling and refrigeration
Heating and refrigeration:
- With fully heat recovery
- With outdoor heat exchanger as gas cooler
- With outdoor heat exchanger as evaporator
Heating only
Installer and user reference guide
25
6 | Before operation
Dedicated functions exist depending on the type of indoor unit, refer to dedicated installation/operation manual for more information.
Installer and user reference guide
26
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

7 Operation

7.1 Operation range

Use the system in the following temperature ranges for safe and effective operation.
Outdoor temperature
7 | Operation
Refrigeration A/C cooling A/C heating
–20~43°CDB
(a)
–5~43°CDB –20~16°CWB
Indoor temperature
(a)

7.2 Design pressure

Always keep the following design pressures in mind:
Side Design pressure
Refrigeration 90bar
Air conditioning 120bar
14~24°CWB 15~27°CDB
For low load restrictions, see "14.5.2Constraints for refrigeration"[449].
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Installer and user reference guide
27
8 | Energy saving and optimum operation

8 Energy saving and optimum operation

Observe the following precautions to ensure the system operates properly.
Adjust the air outlet properly and avoid direct air flow to room inhabitants.
Adjust the room temperature properly for a comfortable environment. Avoid
excessive heating or cooling.
Adjust the room temperature properly for a comfortable environment. Avoid
excessive heating or cooling. Notice that it may take some time for the room temperature to reach the set temperature. Consider using the timer setting options.
Adjust the evaporating temperature for refrigeration properly in the settings of
the outdoor unit.
Prevent direct sunlight from entering a room during cooling operation by using
curtains or blinds.
Ventilate often. Extended use requires special attention to ventilation.
Keep doors and windows closed. If the doors and windows remain open, air will
flow out of your room causing a decrease in the cooling or heating effect.
Be careful NOT to cool or heat too much. To save energy, keep the temperature
setting at a moderate level.
NEVER place objects near the air inlet or the air outlet of the unit. Doing so may
cause a reduced heating/cooling effect or stop operation.
Turn off the main power supply switch to the unit when the unit is not used for
longer periods of time. If the switch is on, it consumes electricity. Before restarting the unit, turn on the main power supply switch 6 hours before operation to ensure smooth running. (Refer to "Maintenance" in the indoor unit manual.)
When the display shows (time to clean the air filter), ask a qualified service
person to clean the filters. (Refer to "Maintenance" in the indoor unit manual.)
Installer and user reference guide
28
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit

9 Maintenance and service

NOTICE
NEVER inspect or service the unit by yourself. Ask a qualified service person to perform this work.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any maintenance task.
9 | Maintenance and service
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Wipe it with another dry cloth.

9.1 Maintenance before a long stop period

E.g., at the end of the season.
Let the indoor units run in fan only operation for about half a day in order to dry
the interior of the units. See the operation manual of the indoor unit.
Turn off the power. The user interface display disappears.
WARNING
When turning the power OFF for a long stop period, ALWAYS remove the refrigerant from the units. If you cannot remove the refrigerant for any reason, ALWAYS keep the power turned ON.
LRYEN10A7Y1+LRNUN5A7Y1 CO₂ Conveni-Pack outdoor unit 4P605460-1 – 2020.08
Clean air filters and casings of indoor units. Contact your installer or maintenance
person to clean air filters and casings of the indoor unit. Maintenance tips and procedures for cleaning are provided in the installation/operation manuals of dedicated indoor units. Make sure to install cleaned air filters back in the same position.
Installer and user reference guide
29
9 | Maintenance and service

9.2 Maintenance after a long stop period

E.g., at the beginning of the season.
Check and remove everything that might be blocking inlet and outlet vents of
indoor units and outdoor units.
Clean air filters and casings of indoor units. Contact your installer or maintenance
person to clean air filters and casings of the indoor unit. Maintenance tips and procedures for cleaning are provided in the installation/operation manuals of dedicated indoor units. Make sure to install cleaned air filters back in the same position.
Clean showcase and unit cooler. Maintenance tips and procedures for cleaning
are provided in the installation/operation manuals of dedicated indoor units.
Turn on the power at least 6 hours before operating the unit in order to ensure
smoother operation. As soon as the power is turned on, the user interface display appears.

9.3 About the refrigerant

This product contains refrigerant gases.
Refrigerant type: R744 (CO2)
WARNING
Do NOT pierce or burn refrigerant cycle parts.Be aware that the refrigerant inside the system is odourless.
WARNING
The R744 refrigerant (CO2) inside the unit is odourless, non-flammable and normally does NOT leak.
If the unit is installed indoors, ALWAYS install a CO2 detector according to the specifications of standard EN378.
If the refrigerant leaks in high concentrations in the room, it may have negative effects on its occupants such as asphyxiation and carbon dioxide poisoning. Ventilate the room and contact the dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.

9.4 Recommended maintenance and inspection

Installer and user reference guide
30
Since dust collects when using the unit for several years, performance of the unit will deteriorate to some extent. As taking apart and cleaning interiors of units requires technical expertise and in order to ensure the best possible maintenance of your units, we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities. Our network of dealers has access to a permanent stock of essential components in order to keep your unit in operation as long as possible. Contact your dealer for more information.
When asking your dealer for an intervention, always state:
The complete model name of the unit.
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
Loading...
+ 110 hidden pages