Thank you for purchasing this Daikin air conditioner.
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
INTRODUCTION
The Daikin EWWP-KA packaged water-cooled water chillers are
designed for indoor installation and used for cooling and/or heating
applications. The units are available in 14 standard sizes with
nominal cooling capacities ranging from 43 to 195 kW.
The EWWP units can be combined with Daikin fan coil units or air
handling units for air conditioning purposes. They can also be used
for supplying chilled water for process cooling.
The present installation manual describes the procedures for
unpacking, installing and connecting the EWWP units.
■Glycol application for leaving evaporator water down to –10°C or
–5°C
■BMS-Connection (MODBUS/J-BUS, BACNET)
■Low noise operation kit (field installation)
Features
■Voltage free contacts
• general operation/pumpcontact
• alarm
■Remote inputs
• remote start/stop
• remote change-over cooling/heating
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30040-1C
(1) Refer to the operation manual or engineering data book for the complete
list of specifications, options and features.
Installation manual
1
OPERATIONRANGE
ZL
ZH
a b
LWC
60
55
50
45
40
30
20
10
0
LWC
LWE
a
b
a b
a b
ZH
ZH
ZL
ZL
–5532
-2-2–2
01020–10
Leaving water temperature condenser
Leaving water temperature evaporator
Glycol
Water
Continuous operation range
MAINCOMPONENTS(refer to the outlook diagram supplied
with the unit)
1Compressor
2Evaporator
3Condenser
4Switchbox
5Chilled water in
6Chilled water out
7Condenser water out
8Condenser water in
9Evaporator entering water temperature sensor
10 Freeze-up sensor
11 Condenser entering water temperature sensor
12 Digital display controller
13 Power supply intake
UNPACKINGANDPLACINGTHEUNIT
1Cut the straps and remove the cardboard box from the unit.
2Remove the four screws fixing the unit to the pallet.
3Level the unit in both directions with the lifting lugs which are
delivered with the control box (ECB*MUW).
4Use four anchor bolts with M8 thread to fix the unit in concrete
(directly or using the floor standing supports).
IMPORTANTINFORMATIONREGARDINGTHE
REFRIGERANTUSED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type:R407C
(1)
GWP
value:1652.5
(1)
GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate.
CHECKINGTHEWATERCIRCUIT
The units are equipped with water inlets and water outlets for
connection to a chilled water circuit and to a hot water circuit. These
circuits must be provided by a licensed technician and must comply
with all relevant European and national regulations.
Before continuing the installation of the unit, check the following
points:
1A circulation pump must be provided in such a way that it dis-
charges the water directly into the heat exchanger.
2A flow switch must be installed in the water outlet pipe to prevent
the unit from operating at a water flow which is too low. A
terminal is provided in the switch box for the electrical
connection of the flow switch.
SELECTIONOFLOCATION
The units are designed for indoor installation and should be installed
in a location that meets the following requirements:
1The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
2The space around the unit is adequate for servicing.
3There is no danger of fire due to leakage of inflammable gas.
4Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone.
5Ensure that water cannot cause any damage to the location in
case it drips out of the unit.
The equipment is not intended for use in a potentially explosive
atmosphere.
INSPECTINGANDHANDLINGTHEUNIT
At delivery, the unit should be checked and any damage should be
reported immediately to the carrier claims agent.
3A wire mesh strainer (<1 mm) must be installed at the pump
suction as to protect the pump and the heat exchanger from
foreign matter.
4Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.
5Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing.
6Shut-off valves should be provided at the unit so that normal
servicing can be accomplished without draining the system.
7Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.
Installation manual
2
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30040-1C
WATERQUALITYSPECIFICATIONS
evaporator watercondenser water
Items to be controlled
pHat 25°C
Electrical
conductivity
Chloride ion
Sulfate ion
M-alkalinity
(pH 4.8)
Total hardness
Calcium
hardness
Silica ion
Items to be referred to
Iron[mg Fe/l]
Copper[mg Cu/l]
Sulfide ion
Ammonium ion
Remaining
chloride
Free carbide
Stability index
[mS/m]
at 25°C
[mg Cl–/l]
2–
[mg SO
4
[mg CaCO3/l]
[mg CaCO3/l]
[mg CaCO3/l]
[mg SiO2/l]
[mg S2–/l]
+
[mg NH
4
[mg Cl/l]
[mg CO2/l]
/l]
/l]
circulating
water
[<20°C]
6.8~8.0 6.8~8.0 7.0~8.0 7.0~8.0A + B
<40<30<30<30A + B
<50<50<50<50A
<50<50<50<50A
<50<50<50<50B
<70<70<70<70B
<50<50<50<50B
<30<30<30<30B
<1.0<0.3<1.0<0.3A + B
<1.0<0.1<1.0<0.1A
<1.0<0.1<0.3<0.1A
<0.3<0.3<0.25<0.3A
<4.0<4.0<0.4<4.0A
————A + B
circulating
supply
water
not detectableA
water
[20°C~60°C]
supply
water
tendency
if out of
criteria
The water pressure should not exceed the maximum
working pressure of 10 bar.
NOTE
Provide adequate safeguards in the water circuit to
make sure that the water pressure will never exceed
the maximum allowable working pressure.
PIPINGINSULATION
The complete water circuit, inclusive all piping, must be insulated to
prevent condensation and reduction of the cooling capacity.
Protect the water piping against water freezing during winter period
(e.g. by using a glycol solution or heatertape).
FIELDWIRING
All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.
The field wiring must be carried out in accordance with the
wiring diagram supplied with the unit and the instructions
given below.
Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.
A = corrosion B = scale
CONNECTINGTHEWATERCIRCUIT
The evaporator and condenser are foreseen of GAS male pipe
thread for the water inlet and outlet (refer to the outlook diagram).
Evaporator and condenser water connections are to be made in
accordance with the outlook diagram, respecting the water in- and
outlet.
If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:
1.Use clean pipes only.
2.Hold the pipe end downwards when removing burrs.
3.Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.
WATERCHARGE, FLOWANDQUALITY
To assure proper operation of the unit a minimum water volume is
required in the system and the water flow through the evaporator
must be within the operation range as specified in the table below.
S11L.......................Contact that closes if the pump is working
S12S ......................Main isolator switch
- - - .........................Field wiring
Power circuit and cable requirements
1The electrical power supply to the unit should be arranged so
that it can be switched on or off independently of the electrical
supply to other items of the plant and equipment in general.
2A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector. Recommended fuses are mentioned on the wiring
diagram supplied with the unit.
Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30040-1C
Installation manual
3
Connection of the water-cooled water chiller power
supply
1Using the appropriate cable, connect the power circuit to the N,
L1, L2 and L3 terminals of the unit.
2Connect the earth conductor (yellow/green) to the earthing
terminal PE.
Point for attention regarding quality of the public
electric power supply
■This equipment complies with EN/IEC 61000-3-11
that the system impedance Z
is less than or equal to Z
sys
the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected
only to a supply with a system impedance Z
equal to Z
EWWP0450.22
EWWP0550.21
EWWP0650.20
max
.
Z
(Ω)
max
■Only for 16~40 Hp: Equipment complying with
EN/IEC 61000-3-12
(2)
(1)
provided
less than or
sys
max
at
Interconnection cables
■In addition to the power supply cable, a cable must be provided
for the connection of the flow switch.
Be sure to interlock so, that the compressor will not come into
operation unless the waterpump is operated. For this purpose 2
spare terminals are provided in the switch box. Refer to the
wiring diagram supplied with the unit.
■Voltage free contacts
The controller is provided with some voltage free contacts to
indicate the status of the unit. These voltage free contacts can
be wired as described on the wiring diagram.
■Remote inputs
Besides the voltage free contacts, there are also possibilities to
install remote inputs.
They can be installed as shown on the wiring diagram.
BEFORESTARTING
The unit should not be started, not even for a very short
period of time, before the following pre-commissioning
checklist is filled out completely.
tick ✓
when
checked
1
■
2Install main fuses, earth leak detector and main switch.
■
3Supply the main voltage and check if it is within the allowable
■
4Supply water to the evaporator and verify if waterflow is within
■
5The piping should be completely purged. See also chapter
■
6Connect the flowswitch and pumpcontact in series, so that
■
7
■
8
■
NOTE
I do confirm having executed and checked all the above
mentioned items.
standard steps to go through before starting the unit
Check for external damage.
Recommended fuses: aM according to IEC standard 269-2.
Refer to the wiring diagram for size.
±10% limits of the nameplate rating.
The electrical main power supply should be arranged so, that
it can be switched on or off independently of the electrical
supply to other items of the plant and equipment in general.
Refer to the wiring diagram, terminals N, L1, L2 and L3.
the limits as given in the table under "Water charge, flow and
quality" on page 3
"Checking the water circuit" on page 2
the unit can only come in operation when the waterpumps are
running and the waterflow is sufficient.
Connect the optional field wiring for pumps start-stop.
Connect the optional field wiring for remote control.
■Tr y to reduce the drilling in the unit to a minimum.
If drilling is impreventable, remove the iron filling
thoroughly in order to prevent surface rust!
■It is necessary to read the operation manual delivered with the unit before operating the unit. It will
contribute to understand the operation of the unit
and its electronic controller.
■Ver ify on the wiring diagram all electrical actions
mentioned above, in order to understand the
operation of the unit more deeply.
■Close all switch box doors after installation of the
unit.
(1) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current ≤75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and ≤75 A per phase.
Installation manual
4
DateSignature
Keep for future reference.
HOWTOCONTINUE
After installation and connection of the packaged water-cooled water
chiller, the complete system should be checked and tested as
described in "Checks before initial start-up" in the operation manual
supplied with the unit.
Fill out the brief operation instructions form and fix it visibly near the
operating site of the refrigeration system.
EWWP045~065KAW1M + ECB1~3MUW
Packaged water-cooled water chillers
4PW30040-1C
BRIEF OPERATION INSTRUCTIONS
EWWP-KA Packaged water-cooled water chiller