Installer reference guide
Daikin Altherma 3 R F
ERLA03DAV3 |
EHFZ03S18DJ3V |
Table of contents
1 General safety precautions |
6 |
||
1.1 |
About the documentation .............................................................................................................................................. |
6 |
|
|
1.1.1 |
Meaning of warnings and symbols ................................................................................................................ |
6 |
1.2 |
For the installer............................................................................................................................................................... |
7 |
|
|
1.2.1 |
General ........................................................................................................................................................... |
7 |
|
1.2.2 |
Installation site ............................................................................................................................................... |
8 |
|
1.2.3 |
Refrigerant — in case of R410A or R32.......................................................................................................... |
9 |
|
1.2.4 |
Water .............................................................................................................................................................. |
10 |
|
1.2.5 |
Electrical ......................................................................................................................................................... |
11 |
2 |
About the documentation |
13 |
||
|
2.1 |
About this document ...................................................................................................................................................... |
13 |
|
|
2.2 |
Installer reference guide at a glance .............................................................................................................................. |
14 |
|
3 |
About the box |
16 |
||
|
3.1 |
Overview: About the box ................................................................................................................................................ |
16 |
|
|
3.2 |
Outdoor unit ................................................................................................................................................................... |
16 |
|
|
|
3.2.1 |
To unpack the outdoor unit ........................................................................................................................... |
16 |
|
|
3.2.2 |
To handle the outdoor unit............................................................................................................................ |
17 |
|
|
3.2.3 |
To remove the accessories from the outdoor unit........................................................................................ |
17 |
|
3.3 |
Indoor unit ...................................................................................................................................................................... |
17 |
|
|
|
3.3.1 |
To unpack the indoor unit.............................................................................................................................. |
17 |
|
|
3.3.2 |
To remove the accessories from the indoor unit .......................................................................................... |
18 |
|
|
3.3.3 |
To handle the indoor unit............................................................................................................................... |
18 |
4 About the units and options |
19 |
|||
|
4.1 |
Overview: About the units and options.......................................................................................................................... |
19 |
|
|
4.2 |
Identification ................................................................................................................................................................... |
19 |
|
|
|
4.2.1 |
Identification label: Outdoor unit .................................................................................................................. |
19 |
|
|
4.2.2 |
Identification label: Indoor unit ..................................................................................................................... |
20 |
|
4.3 |
Combining units and options.......................................................................................................................................... |
20 |
|
|
|
4.3.1 |
Possible combinations of indoor unit and outdoor unit................................................................................ |
20 |
|
|
4.3.2 |
Possible options for the outdoor unit............................................................................................................ |
20 |
|
|
4.3.3 |
Possible options for the indoor unit............................................................................................................... |
21 |
5 |
Application guidelines |
23 |
||
|
5.1 |
Overview: Application guidelines ................................................................................................................................... |
23 |
|
|
5.2 |
Setting up the space heating system.............................................................................................................................. |
23 |
|
|
|
5.2.1 |
Multiple rooms – Two LWT zones.................................................................................................................. |
24 |
|
5.3 |
Setting up the domestic hot water tank......................................................................................................................... |
26 |
|
|
|
5.3.1 |
System layout – Integrated DHW tank........................................................................................................... |
26 |
|
|
5.3.2 |
Selecting the desired temperature for the DHW tank .................................................................................. |
26 |
|
|
5.3.3 |
Setup and configuration – DHW tank ............................................................................................................ |
27 |
|
|
5.3.4 |
DHW pump for instant hot water .................................................................................................................. |
28 |
|
|
5.3.5 |
DHW pump for disinfection ........................................................................................................................... |
28 |
|
5.4 |
Setting up the energy metering...................................................................................................................................... |
29 |
|
|
|
5.4.1 |
Produced heat ................................................................................................................................................ |
29 |
|
|
5.4.2 |
Consumed energy........................................................................................................................................... |
29 |
|
|
5.4.3 |
Normal kWh rate power supply ..................................................................................................................... |
30 |
|
|
5.4.4 |
Preferential kWh rate power supply.............................................................................................................. |
31 |
|
5.5 |
Setting up the power consumption control ................................................................................................................... |
32 |
|
|
|
5.5.1 |
Permanent power limitation .......................................................................................................................... |
32 |
|
|
5.5.2 |
Power limitation activated by digital inputs .................................................................................................. |
33 |
|
|
5.5.3 |
Power limitation process................................................................................................................................ |
34 |
|
5.6 |
Setting up an external temperature sensor ................................................................................................................... |
34 |
|
6 |
Unit installation |
36 |
||
|
6.1 |
Preparing the installation site......................................................................................................................................... |
36 |
|
|
|
6.1.1 |
Installation site requirements of the outdoor unit........................................................................................ |
37 |
|
|
6.1.2 |
Additional installation site requirements of the outdoor unit in cold climates............................................ |
39 |
|
|
6.1.3 |
Installation site requirements of the indoor unit .......................................................................................... |
40 |
|
6.2 |
Opening and closing the units ........................................................................................................................................ |
42 |
|
|
|
6.2.1 |
About opening the units................................................................................................................................. |
42 |
|
|
6.2.2 |
To open the outdoor unit............................................................................................................................... |
42 |
|
|
6.2.3 |
To close the outdoor unit............................................................................................................................... |
42 |
|
|
6.2.4 |
To open the indoor unit ................................................................................................................................. |
43 |
|
|
|
|
|
Installer reference guide |
|
|
|
ERLA03DAV3 + EHFZ03S18DJ3V |
2 |
|
|
|
Daikin Altherma 3 R F |
|
|
|
4P596821-1A – 2020.05 |
|
|
|
|
Table of contents |
|
|
6.2.5 |
To lower the switch box on the indoor unit .................................................................................................. |
45 |
|
|
6.2.6 |
To close the indoor unit ................................................................................................................................. |
45 |
|
6.3 |
Mounting the outdoor unit............................................................................................................................................. |
46 |
|
|
|
6.3.1 |
About mounting the outdoor unit ................................................................................................................. |
46 |
|
|
6.3.2 |
Precautions when mounting the outdoor unit.............................................................................................. |
46 |
|
|
6.3.3 |
To provide the installation structure ............................................................................................................. |
46 |
|
|
6.3.4 |
To install the outdoor unit ............................................................................................................................. |
47 |
|
|
6.3.5 |
To provide drainage........................................................................................................................................ |
47 |
|
|
6.3.6 |
To prevent the outdoor unit from falling over .............................................................................................. |
48 |
|
6.4 |
Mounting the indoor unit ............................................................................................................................................... |
49 |
|
|
|
6.4.1 |
About mounting the indoor unit.................................................................................................................... |
49 |
|
|
6.4.2 |
Precautions when mounting the indoor unit................................................................................................. |
49 |
|
|
6.4.3 |
To install the indoor unit ................................................................................................................................ |
49 |
|
|
6.4.4 |
To connect the drain hose to the drain ......................................................................................................... |
50 |
|
6.5 |
Finishing the outdoor unit installation ........................................................................................................................... |
51 |
|
|
|
6.5.1 |
To finish the outdoor unit installation ........................................................................................................... |
51 |
7 |
Piping installation |
52 |
||
|
7.1 |
Preparing refrigerant piping ........................................................................................................................................... |
52 |
|
|
|
7.1.1 |
Refrigerant piping requirements.................................................................................................................... |
52 |
|
|
7.1.2 |
Refrigerant piping insulation.......................................................................................................................... |
53 |
|
7.2 |
Preparing water piping ................................................................................................................................................... |
53 |
|
|
|
7.2.1 |
Water circuit requirements............................................................................................................................ |
53 |
|
|
7.2.2 |
Formula to calculate the expansion vessel pre-pressure .............................................................................. |
56 |
|
|
7.2.3 |
To check the water volume and flow rate ..................................................................................................... |
56 |
|
|
7.2.4 |
Changing the pre-pressure of the expansion vessel...................................................................................... |
58 |
|
|
7.2.5 |
To check the water volume: Examples .......................................................................................................... |
58 |
|
7.3 |
Connecting the refrigerant piping .................................................................................................................................. |
59 |
|
|
|
7.3.1 |
About connecting the refrigerant piping ....................................................................................................... |
59 |
|
|
7.3.2 |
Precautions when connecting the refrigerant piping.................................................................................... |
59 |
|
|
7.3.3 |
Guidelines when connecting the refrigerant piping...................................................................................... |
60 |
|
|
7.3.4 |
Pipe bending guidelines ................................................................................................................................. |
61 |
|
|
7.3.5 |
To flare the pipe end ...................................................................................................................................... |
61 |
|
|
7.3.6 |
To braze the pipe end..................................................................................................................................... |
62 |
|
|
7.3.7 |
Using the stop valve and service port............................................................................................................ |
62 |
|
|
7.3.8 |
To connect the refrigerant piping to the outdoor unit ................................................................................. |
64 |
|
|
7.3.9 |
To connect the refrigerant piping to the indoor unit .................................................................................... |
64 |
|
7.4 |
Checking the refrigerant piping...................................................................................................................................... |
65 |
|
|
|
7.4.1 |
About checking the refrigerant piping ........................................................................................................... |
65 |
|
|
7.4.2 |
Precautions when checking the refrigerant piping........................................................................................ |
65 |
|
|
7.4.3 |
To check for leaks ........................................................................................................................................... |
65 |
|
|
7.4.4 |
To perform vacuum drying............................................................................................................................. |
66 |
|
7.5 |
Charging refrigerant........................................................................................................................................................ |
67 |
|
|
|
7.5.1 |
About charging refrigerant............................................................................................................................. |
67 |
|
|
7.5.2 |
About the refrigerant ..................................................................................................................................... |
67 |
|
|
7.5.3 |
Precautions when charging refrigerant ......................................................................................................... |
68 |
|
|
7.5.4 |
To determine the complete recharge amount .............................................................................................. |
68 |
|
|
7.5.5 |
To fix the fluorinated greenhouse gases label............................................................................................... |
68 |
|
7.6 |
Connecting water piping................................................................................................................................................. |
69 |
|
|
|
7.6.1 |
About connecting the water piping ............................................................................................................... |
69 |
|
|
7.6.2 |
Precautions when connecting the water piping............................................................................................ |
69 |
|
|
7.6.3 |
To connect the water piping .......................................................................................................................... |
70 |
|
|
7.6.4 |
To connect the recirculation piping ............................................................................................................... |
71 |
|
|
7.6.5 |
To fill the water circuit ................................................................................................................................... |
72 |
|
|
7.6.6 |
To fill the domestic hot water tank................................................................................................................ |
72 |
|
|
7.6.7 |
To insulate the water piping .......................................................................................................................... |
72 |
8 |
Electrical installation |
73 |
||
|
8.1 |
About connecting the electrical wiring .......................................................................................................................... |
73 |
|
|
|
8.1.1 |
Precautions when connecting the electrical wiring....................................................................................... |
73 |
|
|
8.1.2 |
Guidelines when connecting the electrical wiring......................................................................................... |
74 |
|
|
8.1.3 |
Specifications of standard wiring components.............................................................................................. |
75 |
|
|
8.1.4 |
About electrical compliance........................................................................................................................... |
76 |
|
|
8.1.5 |
About preferential kWh rate power supply................................................................................................... |
76 |
|
|
8.1.6 |
Overview of electrical connections except external actuators ..................................................................... |
77 |
|
8.2 |
Connections to the outdoor unit.................................................................................................................................... |
77 |
|
|
|
8.2.1 |
To connect the electrical wiring to the outdoor unit .................................................................................... |
77 |
|
8.3 |
Connections to the indoor unit ...................................................................................................................................... |
78 |
|
|
|
8.3.1 |
To connect the main power supply................................................................................................................ |
80 |
|
|
8.3.2 |
To connect the backup heater power supply ................................................................................................ |
82 |
|
|
|
|
|
ERLA03DAV3 + EHFZ03S18DJ3V |
|
|
|
Installer reference guide |
Daikin Altherma 3 R F |
|
|
|
3 |
4P596821-1A – 2020.05 |
|
|
|
Table of contents
|
8.3.3 |
To connect the user interface ........................................................................................................................ |
84 |
|
8.3.4 |
To connect the shut-off valve ........................................................................................................................ |
85 |
|
8.3.5 |
To connect the electricity meters .................................................................................................................. |
86 |
|
8.3.6 |
To connect the domestic hot water pump .................................................................................................... |
87 |
|
8.3.7 |
To connect the alarm output ......................................................................................................................... |
88 |
|
8.3.8 |
To connect the space heating ON/OFF output.............................................................................................. |
89 |
|
8.3.9 |
To connect the changeover to external heat source..................................................................................... |
90 |
|
8.3.10 |
To connect the power consumption digital inputs........................................................................................ |
91 |
|
8.3.11 |
To connect the safety thermostat (normally closed contact) ....................................................................... |
92 |
8.4 |
After connecting the electrical wiring to the indoor unit .............................................................................................. |
94 |
9 Configuration |
96 |
||
9.1 |
Overview: Configuration................................................................................................................................................. |
96 |
|
|
9.1.1 |
To change the user permission level ............................................................................................................. |
97 |
|
9.1.2 |
To access the most used commands ............................................................................................................. |
97 |
|
9.1.3 |
To copy the system settings from the first to the second user interface ..................................................... |
99 |
|
9.1.4 |
Quick wizard: Set the system layout after first power ON ............................................................................ |
100 |
9.2 |
Basic configuration.......................................................................................................................................................... |
101 |
|
|
9.2.1 |
Quick wizard: Language / time and date ....................................................................................................... |
101 |
|
9.2.2 |
Quick wizard: Standard .................................................................................................................................. |
101 |
|
9.2.3 |
Quick wizard: Options .................................................................................................................................... |
104 |
|
9.2.4 |
Space heating/cooling control ....................................................................................................................... |
108 |
|
9.2.5 |
Domestic hot water control ........................................................................................................................... |
111 |
|
9.2.6 |
Contact/helpdesk number ............................................................................................................................. |
111 |
9.3 |
Weather-dependent curve ............................................................................................................................................. |
112 |
|
|
9.3.1 |
What is a weather-dependent curve? ........................................................................................................... |
112 |
|
9.3.2 |
2-points curve................................................................................................................................................. |
112 |
|
9.3.3 |
Using weather-dependent curves.................................................................................................................. |
113 |
9.4 |
Advanced configuration/optimisation............................................................................................................................ |
114 |
|
|
9.4.1 |
Space heating/cooling operation: advanced ................................................................................................. |
114 |
|
9.4.2 |
Domestic hot water control: advanced ......................................................................................................... |
121 |
|
9.4.3 |
Heat source settings....................................................................................................................................... |
126 |
|
9.4.4 |
System settings............................................................................................................................................... |
129 |
9.5 |
Menu structure: Overview user settings........................................................................................................................ |
137 |
|
9.6 |
Menu structure: Overview installer settings.................................................................................................................. |
138 |
10 Commissioning |
|
139 |
|
10.1 |
Overview: Commissioning .............................................................................................................................................. |
|
139 |
10.2 |
Precautions when commissioning.................................................................................................................................. |
|
139 |
10.3 |
Checklist before commissioning..................................................................................................................................... |
|
140 |
10.4 |
Checklist during commissioning ..................................................................................................................................... |
|
141 |
|
10.4.1 To check the minimum flow rate ................................................................................................................... |
|
141 |
|
10.4.2 Air purge function........................................................................................................................................... |
|
141 |
|
10.4.3 To perform a test run ..................................................................................................................................... |
|
143 |
|
10.4.4 To perform an actuator test run .................................................................................................................... |
|
143 |
|
10.4.5 Underfloor heating screed dryout ................................................................................................................. |
|
144 |
11 Hand-over to the user |
|
147 |
|
12 Maintenance and service |
|
148 |
|
12.1 |
Overview: Maintenance and service .............................................................................................................................. |
|
148 |
12.2 |
Maintenance safety precautions.................................................................................................................................... |
|
148 |
12.3 |
Checklist for yearly maintenance of the outdoor unit................................................................................................... |
|
149 |
12.4 |
Checklist for yearly maintenance of the indoor unit ..................................................................................................... |
|
149 |
|
12.4.1 To drain the domestic hot water tank ........................................................................................................... |
|
152 |
12.5 |
About cleaning the water filter in case of trouble ......................................................................................................... |
|
152 |
|
12.5.1 To remove the water filter ............................................................................................................................. |
|
152 |
|
12.5.2 To clean the water filter in case of trouble.................................................................................................... |
|
153 |
|
12.5.3 To install the water filter ................................................................................................................................ |
|
154 |
13 Troubleshooting |
|
156 |
|
13.1 |
Overview: Troubleshooting ............................................................................................................................................ |
|
156 |
13.2 |
Precautions when troubleshooting ................................................................................................................................ |
|
156 |
13.3 |
Solving problems based on symptoms........................................................................................................................... |
|
157 |
|
13.3.1 Symptom: The compressor does NOT start (space heating or domestic water heating) |
............................ 157 |
|
|
13.3.2 Symptom: The system is making gurgling noises after commissioning ........................................................ |
|
157 |
|
13.3.3 Symptom: The pump is blocked..................................................................................................................... |
|
158 |
|
13.3.4 Symptom: The pump is making noise (cavitation)......................................................................................... |
|
158 |
|
13.3.5 Symptom: The pressure relief valve opens.................................................................................................... |
|
159 |
|
13.3.6 Symptom: The water pressure relief valve leaks........................................................................................... |
|
159 |
|
13.3.7 Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... |
160 |
|
|
|
|
|
Installer reference guide |
|
ERLA03DAV3 + EHFZ03S18DJ3V |
|
4 |
|
|
Daikin Altherma 3 R F |
|
4P596821-1A – 2020.05 |
Table of contents
|
|
13.3.8 Symptom: The pressure at the tapping point is temporarily unusually high................................................ |
161 |
|
|
13.3.9 Symptom: Decoration panels are pushed away due to a swollen tank ........................................................ |
161 |
|
|
13.3.10 Symptom: Tank disinfection function is NOT completed correctly (AH-error)............................................. |
161 |
|
13.4 |
Solving problems based on error codes ......................................................................................................................... |
161 |
|
|
13.4.1 Error codes: Overview .................................................................................................................................... |
162 |
14 |
Disposal |
169 |
|
|
14.1 |
Overview: Disposal.......................................................................................................................................................... |
169 |
|
14.2 |
To pump down ................................................................................................................................................................ |
169 |
15 |
Technical data |
171 |
|
|
15.1 |
Piping diagram: Outdoor unit ......................................................................................................................................... |
171 |
|
15.2 |
Piping diagram: Indoor unit ............................................................................................................................................ |
172 |
|
15.3 |
Wiring diagram: Outdoor unit ........................................................................................................................................ |
173 |
|
15.4 |
Wiring diagram: Indoor unit ........................................................................................................................................... |
175 |
16 |
Glossary |
181 |
|
17 |
Field settings table |
183 |
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
5 |
4P596821-1A – 2020.05 |
1 | General safety precautions
1.1 |
About the documentation...................................................................................................................................................... |
6 |
|
|
1.1.1 |
Meaning of warnings and symbols ........................................................................................................................ |
6 |
1.2 |
For the installer....................................................................................................................................................................... |
7 |
|
|
1.2.1 |
General ................................................................................................................................................................... |
7 |
|
1.2.2 |
Installation site ....................................................................................................................................................... |
8 |
|
1.2.3 |
Refrigerant — in case of R410A or R32 ................................................................................................................. |
9 |
|
1.2.4 |
Water...................................................................................................................................................................... |
10 |
|
1.2.5 |
Electrical ................................................................................................................................................................. |
11 |
▪The original documentation is written in English. All other languages are translations.
▪The precautions described in this document cover very important topics, follow them carefully.
▪The installation of the system, and all activities described in the installation manual and in the installer reference guide MUST be performed by an authorised installer.
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
6 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
1 | General safety precautions
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Symbol |
Explanation |
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbols used in the documentation:
Symbol |
Explanation |
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
▪Do NOT touch the refrigerant piping, water piping or internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
7 |
4P596821-1A – 2020.05 |
1 | General safety precautions
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the product:
▪Instructions for shutting down the system in case of an emergency
▪Name and address of fire department, police and hospital
▪Name, address and day and night telephone numbers for obtaining service In Europe, EN378 provides the necessary guidance for this logbook.
▪Provide sufficient space around the unit for servicing and air circulation.
▪Make sure the installation site withstands the weight and vibration of the unit.
▪Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪Make sure the unit is level.
Do NOT install the unit in the following places:
▪In potentially explosive atmospheres.
▪In places where there is machinery that emits electromagnetic waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪In places where there is a risk of fire due to the leakage of flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
8 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
1 | General safety precautions
▪In places where corrosive gas (example: sulphurous acid gas) is produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
▪Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there is a leak in the refrigerant circuit:
▪Do NOT use the unit's automatic pump down function, with which you can collect all refrigerant from the system into the outdoor unit. Possible consequence: Selfcombustion and explosion of the compressor because of air going into the operating compressor.
▪Use a separate recovery system so that the unit's compressor does NOT have to operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.
▪When the refrigerant system is to be opened, refrigerant MUST be treated according to the applicable legislation.
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
9 |
4P596821-1A – 2020.05 |
1 | General safety precautions
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
▪In case recharge is required, see the nameplate of the unit. It states the type of refrigerant and necessary amount.
▪The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant.
▪Only use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪Charge the liquid refrigerant as follows:
If |
Then |
||
A siphon tube is present |
Charge with the cylinder upright. |
||
(i.e., the cylinder is marked with "Liquid |
|
|
|
filling siphon attached") |
|
|
|
|
|
||
A siphon tube is NOT present |
Charge with the cylinder upside down. |
||
|
|
|
|
|
|
|
|
▪Open refrigerant cylinders slowly.
▪Charge the refrigerant in liquid form. Adding it in gas form may prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83 EC.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
10 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
1 | General safety precautions
DANGER: RISK OF ELECTROCUTION
▪Turn OFF all power supply before removing the switch box cover, connecting electrical wiring or touching electrical parts.
▪Disconnect the power supply for more than 10 minutes, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪Do NOT touch electrical components with wet hands.
▪Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪Make sure the field wiring complies with the applicable legislation.
▪All field wiring MUST be performed in accordance with the wiring diagram supplied with the product.
▪NEVER squeeze bundled cables and make sure they do NOT come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪Make sure to use a dedicated power circuit. NEVER use a power supply shared by another appliance.
▪Make sure to install the required fuses or circuit breakers.
▪Make sure to install an earth leakage protector. Failure to do so may cause electrical shock or fire.
▪When installing the earth leakage protector, make sure it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
▪ When connecting the power supply: connect the earth cable first, before making the current-carrying connections.
▪When disconnecting the power supply: disconnect the current-carrying cables first, before separating the earth connection.
▪The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
11 |
4P596821-1A – 2020.05 |
1 | General safety precautions
NOTICE
Precautions when laying power wiring:
▪Do NOT connect wiring of different thicknesses to the power terminal block (slack in the power wiring may cause abnormal heat).
▪When connecting wiring which is the same thickness, do as shown in the figure above.
▪For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪Over-tightening the terminal screws may break them.
Install power cables at least 1 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 m may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
12 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
2 | About the documentation
2.1 |
About this document.............................................................................................................................................................. |
13 |
2.2 |
Installer reference guide at a glance...................................................................................................................................... |
14 |
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
▪General safety precautions:
-Safety instructions that you must read before installing
-Format: Paper (in the box of the indoor unit)
▪Operation manual:
-Quick guide for basic usage
-Format: Paper (in the box of the indoor unit)
▪User reference guide:
-Detailed step-by-step instructions and background information for basic and advanced usage
-Format: Digital files on http://www.daikineurope.com/support-and-manuals/ product-information/
▪Installation manual – Outdoor unit:
-Installation instructions
-Format: Paper (in the box of the outdoor unit)
▪Installation manual – Indoor unit:
-Installation instructions
-Format: Paper (in the box of the indoor unit)
▪Installer reference guide:
-Preparation of the installation, good practices, reference data, …
-Format: Digital files on http://www.daikineurope.com/support-and-manuals/ product-information/
▪Addendum book for optional equipment:
-Additional info about how to install optional equipment
-Format: Paper (in the box of the indoor unit) + Digital files on http:// www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
13 |
4P596821-1A – 2020.05 |
2 | About the documentation
Technical engineering data
▪A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
▪The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Online tools
In addition to the documentation set, some online tools are available for installers:
▪Heating Solutions Navigator
-Digital toolbox that offers a variety of tools to facilitate the installation and configuration of heating systems.
-To access Heating Solutions Navigator, registration to the Stand By Me platform is required. For more information, see https:// professional.standbyme.daikin.eu.
▪Daikin e-Care
-Mobile app for installers and service technicians that allows you to register, configure and troubleshoot heating systems.
-The mobile app can be downloaded for iOS and Android devices using the QR codes below. Registration to the Stand By Me platform is required to access the app.
App Store |
Google Play |
||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Chapter |
|
Description |
General safety precautions |
Safety instructions that you must read before |
|
|
installing |
|
|
|
|
About the documentation |
What documentation exists for the installer |
|
|
|
|
About the box |
How to unpack the units and remove their |
|
|
accessories |
|
|
|
|
About the units and options |
▪ |
How to identify the units |
|
▪ |
Possible combinations of units and options |
|
|
|
Application guidelines |
Various installation setups of the system |
|
|
|
|
Unit installation |
What to do and know to install the system, |
|
|
including information on how to prepare for an |
|
|
installation |
|
|
|
|
Piping installation |
What to do and know to install the piping of the |
|
|
system, including information on how to |
|
|
prepare for an installation |
|
|
|
|
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
14 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
|
|
2 | About the documentation |
|
|
|
|
Chapter |
Description |
|
Electrical installation |
What to do and know to install the electrical |
|
|
components of the system, including |
|
|
information on how to prepare for an |
|
|
installation |
|
|
|
|
Configuration |
What to do and know to configure the system |
|
|
after it is installed |
|
|
|
|
Commissioning |
What to do and know to commission the system |
|
|
after it is configured |
|
|
|
|
Hand over to the user |
What to give and explain to the user |
|
|
|
|
Maintenance and service |
How to maintain and service the units |
|
|
|
|
Troubleshooting |
What to do in case of problems |
|
|
|
|
Disposal |
How to dispose of the system |
|
|
|
|
Technical data |
Specifications of the system |
|
|
|
|
Glossary |
Definition of terms |
|
|
|
|
Field settings table |
Table to be filled in by the installer, and kept for |
|
|
future reference |
|
|
Note: There is also an installer settings table in |
|
|
the user reference guide. This table has to be |
|
|
filled in by the installer and handed over to the |
|
|
user. |
|
|
|
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
15 |
4P596821-1A – 2020.05 |
3 | About the box
3.1 |
Overview: About the box........................................................................................................................................................ |
16 |
|
3.2 |
Outdoor unit ........................................................................................................................................................................... |
16 |
|
|
3.2.1 |
To unpack the outdoor unit ................................................................................................................................... |
16 |
|
3.2.2 |
To handle the outdoor unit.................................................................................................................................... |
17 |
|
3.2.3 |
To remove the accessories from the outdoor unit ............................................................................................... |
17 |
3.3 |
Indoor unit .............................................................................................................................................................................. |
17 |
|
|
3.3.1 |
To unpack the indoor unit...................................................................................................................................... |
17 |
|
3.3.2 |
To remove the accessories from the indoor unit .................................................................................................. |
18 |
|
3.3.3 |
To handle the indoor unit ...................................................................................................................................... |
18 |
This chapter describes what you have to do after the boxes with the outdoor and indoor unit are delivered on-site.
Keep the following in mind:
▪At delivery, the unit MUST be checked for damage. Any damage MUST be reported immediately to the claims agent of the carrier.
▪Bring the packed unit as close as possible to its final installation position to prevent damage during transport.
▪When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid damage.
▪Prepare the path along which you want to bring the unit inside in advance.
2
1
3
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
16 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
3 | About the box
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
a |
b |
c |
d |
e |
aOutdoor unit installation manual
bMultilingual fluorinated greenhouse gases label
cDrain plug (located on the bottom of the packing case)
dEnergy label
eFluorinated greenhouse gases label
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
17 |
4P596821-1A – 2020.05 |
3 | About the box
1 |
|
|
|
2 |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8×
|
|
|
|
|
|
|
|||||||
a |
b |
c |
d |
e |
f |
g |
|||||||
|
1× |
|
1× |
|
1× |
|
1× |
|
6× |
|
4× |
|
1× |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
h
1×
aGeneral safety precautions
bAddendum book for optional equipment
cIndoor unit installation manual
dOperation manual
eSealing rings for field-supplied shut-off valves (space heating water circuit)
fSealing rings for field-supplied shut-off valves (domestic hot water circuit)
gSealing tape for low voltage wiring intake
hRemote user interface
Use the handles at the back and at the bottom to carry the unit.
a |
a |
b |
b |
aHandles at the back of the unit
bHandles at the bottom of the unit. Carefully tilt the unit to the back so that the handles become visible.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
18 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
4 | About the units and options
4.1 |
Overview: About the units and options ................................................................................................................................. |
19 |
|
4.2 |
Identification........................................................................................................................................................................... |
19 |
|
|
4.2.1 |
Identification label: Outdoor unit .......................................................................................................................... |
19 |
|
4.2.2 |
Identification label: Indoor unit ............................................................................................................................. |
20 |
4.3 |
Combining units and options.................................................................................................................................................. |
20 |
|
|
4.3.1 |
Possible combinations of indoor unit and outdoor unit ....................................................................................... |
20 |
|
4.3.2 |
Possible options for the outdoor unit.................................................................................................................... |
20 |
|
4.3.3 |
Possible options for the indoor unit ...................................................................................................................... |
21 |
This chapter contains information about:
▪Identifying the outdoor unit
▪Identifying the indoor unit
▪Combining the outdoor unit with options
▪Combining the indoor unit with options
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch
the service panels between different models.
Location
Model identification
Example: ER L A 03 DA V3
|
Code |
Explanation |
|
ER |
European split outdoor pair heat pump |
|
|
|
|
L |
Low water temperature – ambient zone: −10~−20°C |
|
|
|
|
A |
Refrigerant R32 |
|
|
|
|
03 |
Capacity class |
|
|
|
|
DA |
Model series |
|
|
|
|
V3 |
Power supply |
|
|
|
|
|
|
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
|
Daikin Altherma 3 R F |
19 |
|
4P596821-1A – 2020.05 |
4 | About the units and options
Location
Model identification
Example: E HF Z 03 S 18 DJ 3V
Code |
Description |
E |
European model |
|
|
HF |
Floor-standing indoor unit with integrated tank |
|
|
Z |
Dual-zone model |
|
|
03 |
Capacity class |
|
|
S |
Integrated tank material: Stainless steel |
|
|
18 |
Integrated tank volume |
|
|
DJ |
Model series |
|
|
3V |
Backup heater model |
|
|
INFORMATION
Certain options might not be available in your country.
Outdoor unit |
Indoor unit |
|
EHFZ03S18DJ3V |
ERLA03DAV3 |
O |
|
|
Bottom plate heater (EKBPHT03D)
▪Prevents freeze-up of the bottom plate.
▪Recommended in areas with low ambient temperature and high humidity.
▪Required in areas with ambient temperatures between –7°C and –15°C when the
outdoor unit is installed between 1000 m and 2000 m altitude. See "6.1.2 Additional installation site requirements of the outdoor unit in cold climates" [439] for more information.
▪For installation instructions, see the installation manual of the bottom plate heater.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
20 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
4 | About the units and options
User interface used as room thermostat (BRC1HHDA)
▪The user interface used as room thermostat can only be used in combination with the user interface connected to the indoor unit.
▪The user interface used as room thermostat needs to be installed in the room that you want to control.
For installation instructions, see the installation and operation manual of the user interface used as room thermostat.
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HBAA)
The digital I/O PCB is required to provide following signals:
▪Alarm output
▪Space heating On/OFF output
▪Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room temperature on another location.
For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the user interface is configured with room thermostat functionality.
▪You can only connect either the remote indoor sensor or the remote outdoor sensor.
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
21 |
4P596821-1A – 2020.05 |
4 | About the units and options
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor sensor and the addendum book for optional equipment.
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
PC cable (EKPCCAB4)
The PC cable makes a connection between the switch box of the indoor unit and a
PC. It gives the possibility to update the software of the indoor unit.
For installation instructions, see the installation manual of the PC cable.
Pipe bend kit (EKHVTC)
When the indoor unit is installed in a place with limited space, a pipe bend kit can be installed to facilitate the connection to the refrigerant liquid and gas connections of the indoor unit.
For installation instructions, see the instruction sheet of the pipe bend kit.
Heat pump convector (FWXV)
For providing space heating, it is possible to use heat pump convectors (FWXV).
For installation instructions, see the installation manual of the heat pump convectors, and the addendum book for optional equipment.
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
▪Control the system via a smartphone app.
▪Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN adapter.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the LAN adapter.
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
22 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
5 | Application guidelines
5.1 |
Overview: Application guidelines ........................................................................................................................................... |
23 |
|
5.2 |
Setting up the space heating system ..................................................................................................................................... |
23 |
|
|
5.2.1 |
Multiple rooms – Two LWT zones ......................................................................................................................... |
24 |
5.3 |
Setting up the domestic hot water tank ................................................................................................................................ |
26 |
|
|
5.3.1 |
System layout – Integrated DHW tank .................................................................................................................. |
26 |
|
5.3.2 |
Selecting the desired temperature for the DHW tank .......................................................................................... |
26 |
|
5.3.3 |
Setup and configuration – DHW tank .................................................................................................................... |
27 |
|
5.3.4 |
DHW pump for instant hot water .......................................................................................................................... |
28 |
|
5.3.5 |
DHW pump for disinfection ................................................................................................................................... |
28 |
5.4 |
Setting up the energy metering ............................................................................................................................................. |
29 |
|
|
5.4.1 |
Produced heat ........................................................................................................................................................ |
29 |
|
5.4.2 |
Consumed energy .................................................................................................................................................. |
29 |
|
5.4.3 |
Normal kWh rate power supply............................................................................................................................. |
30 |
|
5.4.4 |
Preferential kWh rate power supply...................................................................................................................... |
31 |
5.5 |
Setting up the power consumption control........................................................................................................................... |
32 |
|
|
5.5.1 |
Permanent power limitation.................................................................................................................................. |
32 |
|
5.5.2 |
Power limitation activated by digital inputs .......................................................................................................... |
33 |
|
5.5.3 |
Power limitation process ....................................................................................................................................... |
34 |
5.6 |
Setting up an external temperature sensor........................................................................................................................... |
34 |
The purpose of the application guidelines is to give a glance of the possibilities of the heat pump system.
NOTICE
▪ The illustrations in the application guidelines are meant for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
▪For more information about the configuration settings to optimize heat pump operation, see "9 Configuration" 4[ 96].
This chapter contains application guidelines for:
▪Setting up the domestic hot water tank
▪Setting up the energy metering
▪Setting up the power consumption control
▪Setting up an external temperature sensor
5.2Setting up the space heating system
The heat pump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
▪ How many rooms are heated by the heat pump system?
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
23 |
4P596821-1A – 2020.05 |
5 | Application guidelines
▪Which heat emitter types are used in each room and what is their design leaving water temperature?
Once the space heating requirements are clear, we recommend to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on user interface of the unit is turned ON.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set auto emergency [A.6.C] to 1.
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations.
This unit is designed to deliver water at 2 different temperatures. A typical installation consists of underfloor heating at a lower temperature and radiators at a higher water temperature.
In this document:
▪Main zone = Zone with the lowest design temperature
▪Additional zone = Zone with the highest design temperature Typical example:
Room (zone) |
Heat emitters: Design temperature |
Living room (main zone) |
Underfloor heating: 35°C |
|
|
Bed rooms (additional zone) |
Heat pump convectors: 45°C |
|
|
Setup
B |
C |
|
A |
|
|
a |
|
a |
|
E |
b |
|
|
|
D |
|
|
AAdditional leaving water temperature zone
BRoom 1
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
24 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
5 | Application guidelines
CRoom 2
DMain leaving water temperature zone
ERoom 3
aRemote controller of the heat pump convectors
bUser interface used as room thermostat
▪For the main zone: the room temperature is controlled by the user interface, which is used as room thermostat (optional equipment EKRUDAS).
▪For the additional zone:
-The external thermostat is directly connected to the indoor unit.
-The desired room temperature is set via the external thermostat and the thermostatic valves of the radiators in each room.
-The heating demand signal from the external thermostat is connected to the digital input on the indoor unit (X2M/35a and X2M/30). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand.
▪The user interface connected to the indoor unit decides the space operation mode. Mind that the operation mode on each remote controller of the heat pump convectors must be set to match the indoor unit.
Configuration
|
Setting |
Value |
|
Unit temperature control: |
2 (RT control): Unit operation is |
||
▪ |
#: [A.2.1.7] |
decided based on the ambient |
|
▪ |
Code: [C-07] |
temperature of the user interface. |
|
Note: |
|||
|
|
||
|
|
▪ Main room = user interface used as |
|
|
|
room thermostat functionality |
|
|
|
▪ Other rooms = external room |
|
|
|
thermostat functionality |
|
|
|
||
Number of water temperature zones: |
1 (2 LWT zones): Main + additional |
||
▪ |
#: [A.8] |
|
|
▪ |
Code: [7-02] |
|
|
|
|
||
In case of heat pump convectors: |
1 (Thermo ON/OFF): When the used |
||
External room thermostat for the |
external room thermostat or heat pump |
||
convector can only send a hermos ON/ |
|||
additional zone: |
|||
▪ |
#: [A.8] |
OFF condition. No separation between |
|
heating or cooling demand. |
|||
▪ |
Code: [C-06] |
||
|
|||
|
|
||
Shut-off valve output |
Set to follow the hermos demand of the |
||
|
|
main zone. |
|
|
|
|
Benefits
▪Comfort. The smart room thermostat functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation).
▪Efficiency.
-Depending on the demand, the indoor unit supplies different leaving water temperature matching the design temperature of the different heat emitters.
-Underfloor heating has the best performance with the heat pump system.
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
25 |
4P596821-1A – 2020.05 |
5 | Application guidelines
a
b
A
A Domestic hot water
aCold water IN
bHot water OUT
People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the desired temperature for the DHW tank consists of:
1Determining the DHW consumption (equivalent hot water volume at 40°C).
2Determining the desired temperature for the DHW tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent hot water volume at 40°C) using typical water volumes:
Question |
Typical water volume |
How many showers are needed per |
1 shower = 10 min×10 l/min = 100 l |
day? |
|
|
|
How many baths are needed per day? |
1 bath = 150 l |
|
|
How much water is needed at the |
1 sink = 2 min×5 l/min = 10 l |
kitchen sink per day? |
|
|
|
Are there any other domestic hot water |
— |
needs? |
|
|
|
Example: If the DHW consumption for 2 persons per day is as follows:
▪1 showers
▪1 bath
▪2 sink volumes
Then the DHW consumption = (1×100 l)+(1×150 l)+(2×10 l)=270 l
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
26 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
|
|
|
|
5 | Application guidelines |
|
Determining the desired temperature for the DHW tank |
|||
|
|
|
|
|
|
|
Formula |
|
Example |
|
V1=V2+V2×(T2−40)/(40−T1) |
If: |
||
|
|
|
▪ |
V2=180 l |
|
|
|
▪ |
T2=54°C |
|
|
|
▪ |
T1=15°C |
|
|
|
Then V1=280 l |
|
|
|
|
|
|
|
V1 |
DHW consumption (equivalent hot water volume at 40°C) |
||
|
V2 |
Required DHW tank volume if only heated once |
||
|
T2 |
DHW tank temperature |
|
|
|
T1 |
Cold water temperature |
|
|
DHW tank volume
Integrated DHW tank volume: 180 l (=V2)
Energy saving tips
▪If the DHW consumption differs from day to day, you can program a weekly schedule with different desired DHW tank temperatures for each day.
▪The lower the desired DHW tank temperature, the more cost effective. By selecting a larger DHW tank, you can lower the desired DHW tank temperature.
▪The heat pump itself can produce domestic hot water of maximum 55°C (50°C if
outdoor temperature is low). The electrical resistance integrated in the heat pump can increase this temperature. However, this consumes more energy. We recommend to set the desired DHW tank temperature below 55°C to avoid using the backup heater.
▪The higher the outdoor temperature, the better the performance of the heat pump.
-If energy prices are the same during the day and the night, we recommend to heat up the DHW tank during the day.
-If energy prices are lower during the night, we recommend to heat up the DHW tank during the night.
▪When the heat pump produces domestic hot water, it cannot heat up a space. In case you need domestic hot water and space heating at the same, we recommend to produce the domestic hot water during the night when there is lower space heating demand.
▪For large DHW consumptions, you can heat up the DHW tank several times during the day.
▪To heat up the DHW tank to the desired DHW tank temperature, you can use the following energy sources:
-Thermodynamic cycle of the heat pump
-Electrical backup heater
▪For more information about optimizing the energy consumption for producing domestic hot water, see "9 Configuration" [496].
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
27 |
4P596821-1A – 2020.05 |
5 | Application guidelines
Setup
a |
|
|
b |
d |
c |
aCold water IN
bHot water OUT (shower (field supply))
cDHW pump (field supply)
dRecirculation connection
▪By connecting a DHW pump, instant hot water can be available at the tap.
▪The DHW pump and the installation are field supply and the responsibility of the
installer. For the electrical wiring, see "8.3.6 To connect the domestic hot water pump" [487].
For more information about connecting the recirculation connection, see "7.6.4 To connect the recirculation piping" [471].
Configuration
▪For more information, see "9 Configuration" [496].
▪You can program a schedule to control the DHW pump via the user interface. For more information, see the user reference guide.
Setup
|
b |
|
c |
a |
d |
|
|
|
e |
aCold water IN
bHot water OUT (shower (field supply))
cDHW pump (field supply)
dHeater element (field supply)
eNon-return valve (field supply)
▪The DHW pump is field-supplied and its installation is the responsibility of the
installer. For the electrical wiring, see "8.3.6 To connect the domestic hot water pump" [487].
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
28 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |
5 | Application guidelines
▪If the applicable legislation requires a higher temperature than the maximum tank setpoint during disinfection (see [2-03] in the field settings table), you can connect a DHW pump and heater element as shown above.
▪If applicable legislation requires disinfection of the water piping until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above.
▪To ensure a complete disinfection, you have to open the tapping point.
WARNING
When opening the tapping point, the water temperature can be up to 55°C.
Configuration
The indoor unit can control DHW pump operation. For more information, see "9 Configuration" [496].
▪Via the user interface, you can read out the following energy data:
-Produced heat
▪You can read out the energy data:
-For space heating
-For domestic hot water production
▪You can read out the energy data:
-Per month
-Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
▪The produced heat is calculated internally based on:
-The leaving and entering water temperature
-The flow rate
▪Setup and configuration: No additional equipment needed.
5.4.2Consumed energy
You can use the following methods to determine the consumed energy:
▪Calculating
▪Measuring
ERLA03DAV3 + EHFZ03S18DJ3V |
Installer reference guide |
Daikin Altherma 3 R F |
29 |
4P596821-1A – 2020.05 |
5 | Application guidelines
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater) and measuring the consumed energy (example: for outdoor unit). If you do so, the energy data will be invalid.
Calculating the consumed energy
▪The consumed energy is calculated internally based on:
-The actual power input of the outdoor unit
-The set capacity of the backup heater
-The voltage
▪Setup and configuration: To get accurate energy data, measure the capacity (resistance measurement) and set the capacity via the user interface for the backup heater (step 1).
Measuring the consumed energy
▪Preferred method because of higher accuracy.
▪Requires external power meters.
▪Setup and configuration: When using electrical power meters, set the number of pulses/kWh for each power meter via the user interface.
INFORMATION
When measuring the electrical power consumption, make sure ALL power input of
the system is covered by the electrical power meters.
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/5 and X5M/6. See "8.3.5 To connect the electricity meters" [486].
Power meter type
In case of… |
Use a… power meter |
▪ Single-phase outdoor unit |
Single-phase |
▪Backup heater supplied from a singlephase grid (i.e. the backup heater model is *3V connected to a singlephase grid)
Installer reference guide |
ERLA03DAV3 + EHFZ03S18DJ3V |
30 |
Daikin Altherma 3 R F |
4P596821-1A – 2020.05 |