Daikin ERHQ011BA, ERHQ014BA, ERHQ016BA, ERLQ011CA, ERLQ014CA Installer reference guide

...
INSTALLER
REFERENCE GUIDE
Daikin Altherma - Low Temperature Split
+
ERHQ011BA ERHQ014BA ERHQ016BA ERLQ011CA ERLQ014CA ERLQ016CA
EHVH16S18CA EHVH16S26CA EHVX16S18CA EHVX16S26CA
Table of contents
Table of contents
1 About the documentation 2
1.1 About this document ........................................................................ 2
2 General safety precautions 2
2.1 About the documentation ................................................................. 2
2.1.1 Meaning of warnings and symbols ....................................... 2
2.2 For the installer ................................................................................ 3
2.2.1 General.................................................................................3
2.2.2 Installation site...................................................................... 3
2.2.3 Refrigerant............................................................................ 3
2.2.4 Water.................................................................................... 3
2.2.5 Electrical............................................................................... 4
3 About the box 4
3.1 Indoor unit........................................................................................4
3.1.1 To unpack the indoor unit .....................................................4
3.1.2 To remove the accessories from the indoor unit................... 4
4 About the units and options 5
4.1 Identification.....................................................................................5
4.1.1 Identification label: Indoor unit..............................................5
4.2 Possible combinations of units and options..................................... 5
4.2.1 List of options for indoor unit ................................................ 5
4.2.2 Possible combinations of indoor unit and outdoor unit......... 6
5 Application guidelines 6
5.1 Overview: Application guidelines ..................................................... 6
5.2 Setting up the space heating/cooling system................................... 6
5.2.1 Single room .......................................................................... 7
5.2.2 Multiple rooms – One LWT zone .......................................... 8
5.2.3 Multiple rooms – Two LWT zones ...................................... 10
5.3 Setting up an auxiliary heat source for space heating ................... 11
5.4 Setting up the domestic hot water tank .......................................... 12
5.4.1 System layout – Integrated DHW tank ............................... 12
5.4.2 System layout – Standalone DHW tank ............................. 13
5.4.3 Selecting the volume and desired temperature for the DHW
tank..................................................................................... 13
5.4.4 Setup and configuration – DHW tank ................................. 13
5.4.5 Combination: Standalone DHW tank + Solar panels..........14
5.4.6 DHW pump for instant hot water ........................................ 14
5.4.7 DHW pump for disinfection................................................. 14
5.5 Setting up the energy metering...................................................... 14
5.5.1 Produced heat....................................................................14
5.5.2 Consumed energy..............................................................15
5.5.3 Normal kWh rate power supply .......................................... 15
5.5.4 Preferential kWh rate power supply ................................... 15
5.6 Setting up the power consumption control ..................................... 16
5.6.1 Permanent power limitation ................................................ 16
5.6.2 Power limitation activated by digital inputs......................... 16
5.6.3 Power limitation process .................................................... 17
5.7 Setting up an external temperature sensor .................................... 17
6 Preparation 18
6.1 Preparing installation site ............................................................... 18
6.1.1 Installation site requirements of the indoor unit.................. 18
6.2 Preparing water piping ................................................................... 18
6.2.1 Water circuit requirements.................................................. 18
6.2.2 Formula to calculate the expansion vessel pre-pressure... 19
6.2.3 To check the water volume ................................................. 19
6.2.4 Changing the pre-pressure of the expansion vessel .......... 20
6.2.5 To check the water volume: Examples ............................... 20
6.3 Preparing electrical wiring .............................................................. 20
6.3.1 About preparing electrical wiring ........................................ 20
6.3.2 About preferential kWh rate power supply ......................... 21
6.3.3 Overview of electrical connections except
external actuators ............................................................... 21
6.3.4 Overview of electrical connections for external and internal
actuators............................................................................. 21
7 Installation 22
7.1 Opening the units........................................................................... 22
7.1.1 To open the indoor unit and switch box cover.................... 22
7.2 Mounting the indoor unit ................................................................ 23
7.2.1 To install the indoor unit ..................................................... 23
7.3 Connecting the water piping .......................................................... 23
7.3.1 To connect the water piping ...............................................23
7.3.2 To connect the pressure relief valve to the drain................ 23
7.3.3 To fill the water circuit ......................................................... 24
7.3.4 To fill the domestic hot water tank ...................................... 24
7.3.5 To insulate the water piping................................................ 24
7.4 Connecting the electrical wiring ..................................................... 24
7.4.1 About electrical compliance ............................................... 24
7.4.2 To connect the electrical wiring on the indoor unit .............25
7.4.3 To connect the main power supply..................................... 25
7.4.4 To connect the backup heater power supply...................... 26
7.4.5 To connect the user interface.............................................27
7.4.6 To connect the shut-off valve ............................................. 28
7.4.7 To connect the electrical meters.........................................29
7.4.8 To connect the domestic hot water pump...........................29
7.4.9 To connect the alarm output...............................................29
7.4.10 To connect the space cooling/heating ON/OFF output ...... 29
7.4.11 To connect the changeover to external heat source .......... 29
7.4.12 To connect the power consumption digital inputs...............29
7.5 Finishing the indoor unit installation............................................... 30
7.5.1 To fix the user interface cover to the indoor unit ................ 30
7.5.2 To close the indoor unit ...................................................... 30
8 Configuration 30
8.1 Overview: Configuration ................................................................ 30
8.1.1 To connect the PC cable to the switch box ........................ 30
8.1.2 To access the most used commands................................. 30
8.1.3 To copy the system settings from the first to the second user
interface ............................................................................. 31
8.1.4 To copy the language set from the first to the second user
interface ............................................................................. 31
8.1.5 Quick wizard: Set the system layout after first
power ON ........................................................................... 31
8.2 Basic configuration ........................................................................ 32
8.2.1 Quick wizard: Language / time and date............................32
8.2.2 Quick wizard: Standard ...................................................... 32
8.2.3 Quick wizard: Options ........................................................ 34
8.2.4 Quick wizard: Capacities (energy metering) ...................... 35
8.2.5 Space heating/cooling control ............................................ 36
8.2.6 Domestic hot water control................................................. 39
8.2.7 Contact/helpdesk number .................................................. 40
8.3 Advanced configuration/optimization ............................................. 40
8.3.1 Space heating/cooling operation: advanced ...................... 40
8.3.2 Domestic hot water control: advanced ............................... 43
8.3.3 Heat source settings .......................................................... 46
8.3.4 System settings .................................................................. 48
8.4 Menu structure: Overview .............................................................. 51
8.5 Menu structure: Overview installer settings ................................... 52
9 Commissioning 53
9.1 Overview: Commissioning ............................................................. 53
9.2 Checklist before test run ................................................................ 53
9.3 Air purge function........................................................................... 53
9.3.1 To perform a manual air purge ........................................... 53
9.3.2 To perform an automatic air purge ..................................... 54
9.3.3 To interrupt air purge .......................................................... 54
9.4 To perform a test run ...................................................................... 54
9.5 To perform an actuator test run...................................................... 54
9.5.1 Possible actuator test runs ................................................. 54
9.6 Underfloor heating screed dryout .................................................. 54
9.6.1 To program an underfloor heating screed dryout
schedule............................................................................. 55
9.6.2 To start an underfloor heating screed dryout...................... 55
9.6.3 To readout the status of an underfloor heating
screed dryout ..................................................................... 55
9.6.4 To interrupt an underfloor heating screed dryout ...............55
10 Hand-over to the user 55
Installer reference guide
1
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
1 About the documentation
11 Maintenance and service 56
11.1 Overview: Maintenance.................................................................. 56
11.2 Maintenance safety precautions ....................................................56
11.2.1 Opening the indoor unit ......................................................56
11.3 Checklist for yearly maintenance for indoor unit ............................56
11.3.1 To drain the domestic hot water tank.................................. 57
12 Troubleshooting 57
12.1 Overview: Troubleshooting.............................................................57
12.2 General guidelines ......................................................................... 57
12.3 Solving problems based on symptoms .......................................... 57
12.3.1 Symptom: The unit is NOT heating or cooling as
expected .............................................................................57
12.3.2 Symptom: The compressor does NOT start (space heating
or domestic water heating) .................................................58
12.3.3 Symptom: The pump is making noise (cavitation).............. 58
12.3.4 Symptom: The pressure relief valve opens ........................58
12.3.5 Symptom: The water pressure relief valve leaks................ 58
12.3.6 Symptom: The space is NOT sufficiently heated at low
outdoor temperatures ......................................................... 58
12.3.7 Symptom: The pressure at the tapping point is temporarily
unusual high ....................................................................... 59
12.3.8 Symptom: Decoration panels are pushed away due to a
swollen tank........................................................................59
12.4 Solving problems based on error codes......................................... 59
12.4.1 Error codes: Overview........................................................59
13 Glossary 60
14 Technical data 61
14.1 Dimensions and service space ...................................................... 61
14.1.1 Dimensions and service space: Indoor unit ........................61
14.2 Components...................................................................................63
14.2.1 Components: Indoor unit ....................................................63
14.2.2 Components: Switch box (indoor unit)................................64
14.3 Functional diagrams.......................................................................65
14.3.1 Functional diagram: Indoor unit..........................................65
14.4 Piping diagram ...............................................................................66
14.4.1 Piping diagram: Indoor unit.................................................66
14.5 Wiring diagram ...............................................................................67
14.5.1 Wiring diagram – components: Indoor unit.........................67
14.6 Technical specifications.................................................................. 73
14.6.1 Technical specifications: Indoor unit ................................... 73
14.7 Operation range ............................................................................. 75
14.7.1 Operation range: Indoor unit...............................................75
14.8 ESP curve ...................................................................................... 78
14.8.1 ESP curve: Indoor unit........................................................78
14.9 Performance ...................................................................................79
14.10Combination table .......................................................................... 82
1 About the documentation
Document Contains… Format
General safety precautions
Indoor unit
Safety instructions that you must read before installing
Installation instructions
Paper (in the box of the indoor unit)
installation manual
Outdoor unit installation
Installation instructions Paper (in the box of the
outdoor unit)
manual
Installer reference guide
Preparation of the installation, technical specifications, good
CD/DVD in the box of the indoor unit)
practices, reference data,…
Addendum book for optional equipment
Additional info about how to install optional equipment
Paper (in the box of the indoor unit)
CD/DVD (in the box of the indoor unit)
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
2 General safety precautions
2.1 About the documentation
Q The original documentation is written in English. All other
languages are translations.
Q The precautions described in this document cover very
important topics, follow them carefully.
Q All activities described in the installation manual must be
performed by an authorized installer.
2.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
1.1 About this document
Target audience
Authorized installers
Documentation set
This document is part of a documentation set. The complete set consists of:
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
WARNING
Indicates a situation that could result in death or serious injury.
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Installer reference guide
2
2 General safety precautions
2.2 For the installer
2.2.1 General
If you are not sure how to install or operate the unit, contact your dealer.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
DANGER: RISK OF BURNING
Q Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Q Do NOT touch any accidental leaking refrigerant.
2.2.2 Installation site
Q Provide sufficient space around the unit for servicing and air
circulation.
Q Make sure the installation site withstands the unit’s weight and
vibration.
Q Make sure the area is well ventilated. Q Make sure the unit is level.
Do NOT install the unit in the following places:
Q In potentially explosive atmospheres. Q In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
Q In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
Q In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
2.2.3 Refrigerant
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are not subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
NOTICE
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminum fins of the unit.
NOTICE
Q Do NOT place any objects or equipment on top of the
unit.
Q Do NOT sit, climb or stand on the unit.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,… Also, at least, following information must be provided at an accessible place at the product:
Q Instructions for shutting down the system in case of an
emergency
Q Name and address of fire department, police and hospital Q Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Q Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
Q Toxic gas may be produced if refrigerant gas comes
into contact with fire.
WARNING
Always recover the refrigerants. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
2.2.4 Water
NOTICE
Make sure water quality complies with EU directive 98/83 EC.
Installer reference guide
3
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
3 About the box
2.2.5 Electrical
DANGER: RISK OF ELECTROCUTION
Q Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
Q Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage must be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Q Do NOT touch electrical components with wet hands.
Q Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If not factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, shall be installed in the fixed wiring.
WARNING
Q Only use copper wires.
Q All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
Q NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Q Make sure to install earth wiring. Do NOT earth the
unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Q Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
Q Make sure to install the required fuses or circuit
breakers.
Q Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
Q When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
3 About the box
Q At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier’s claims agent.
Q Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
3.1 Indoor unit
3.1.1 To unpack the indoor unit
3.1.2 To remove the accessories from the indoor unit
1 Remove the screws at the top of the unit. 2 Remove the top panel.
4x
Install power cables at least 1 meter away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 meter may not be sufficient.
WARNING
Q After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
Q Make sure all covers are closed before starting up the
unit.
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
3 Remove the accessories.
Installer reference guide
4
4 About the units and options
a
1x
b
1x
f
1x
a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e CD
f User interface kit: user interface, 4 fixing screws, 2 plugs g Shut-off valve h User interface cover
i Hinges for user interface cover
c
1x
g
2x
d
1x
h
1x 2x
e
1x
i
4 Reinstall the top panel.
4 About the units and options
4.1 Identification
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.
4.1.1 Identification label: Indoor unit
Location
Model identification
Example: E HV H 04 S 18 CA 3V
Code Description
E European model
HV HV=Floor-standing indoor unit with integrated tank
H
Q H=Heating only Q X=Heating/cooling
04 Capacity class:
Q 04=4.5 kW Q 08=7.5 kW Q 16=16 kW
S Integrated tank material:
S=Stainless steel
18 Integrated tank volume:
Q 18=180 l Q 26=260 l
CA Series
3V Backup heater model
Q 3V Q 9W
4.2 Possible combinations of units and options
4.2.1 List of options for indoor unit
User interface (EKRUCAL1, EKRUCAL2)
The user interface is delivered as an accessory with the unit. An additional user interface is optionally available. The additional user interface can be connected:
Q To have both:
Q control close to the indoor unit Q room thermostat functionality in the principal space to be
heated
Q To have an interface containing other languages
The additional user interface EKRUCAL1 contains the 6 common languages: English, German, French, Dutch, Italian, Spanish.
The additional user interface EKRUCAL2 contains other languages: English, Swedish, Norwegian, Czech, Turkish, Portuguese.
Languages on the user interface can be uploaded by PC software or copied from an user interface to the other.
For installation instructions, see "7.4.5 To connect the user interface" on page 27.
Installer reference guide
5
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide following signals:
Q Alarm output Q Space heating/cooling On/OFF output Q Changeover to external heat source Q Only for EHVH/X16 models: Control signal for bottom plate
heater kit EKBPHTH16A For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
5 Application guidelines
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB. For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room temperature on another location.
For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment.
INFORMATION
Q The remote indoor sensor can only be used in case
the user interface is configured with room thermostat functionality.
Q You can only connect either the remote indoor sensor
or the remote outdoor sensor.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature. As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour. For installation instructions, see the installation manual of the remote outdoor sensor.
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
PC configurator (EKPCCAB1)
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to upload different language files to the user interface and indoor parameters to the indoor unit. For the available language files, contact your local dealer.
The software and corresponding operating instructions are available on Daikin Extranet. For installation instructions, see the installation manual of the PC cable.
4.2.2 Possible combinations of indoor unit and outdoor unit
Indoor unit
Outdoor unit
ERHQ011BAV3 O O O O
ERHQ014BAV3 O O O O
ERHQ016BAV3 O O O O
ERLQ011CAV3 O O O O
ERLQ014CAV3 O O O O
ERLQ016CAV3 O O O O
ERHQ011BAW1 O O O O
ERHQ014BAW1 O O O O
ERHQ016BAW1 O O O O
ERLQ011CAW1 O O O O
ERLQ014CAW1 O O O O
ERLQ016CAW1 O O O O
EHVH16S18CA3V EHVX16S18CA3V EHVH16S26CA9W EHVX16S26CA9W
5 Application guidelines
5.1 Overview: Application guidelines
The purpose of the application guidelines is to give a glance of the possibilities of the Daikin heat pump system.
NOTICE
Q The illustrations in the application guidelines are
meant for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
Q For more information about the configuration settings
to optimize heat pump operation, see the configuration chapter.
This chapter contains applications guidelines for:
Q Setting up the space heating/cooling system Q Setting up an auxiliary heat source for space heating Q Setting up the domestic hot water tank Q Setting up the energy metering Q Setting up the power consumption Q Setting up an external temperature sensor
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
5.2 Setting up the space heating/cooling system
The Daikin heat pump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
Q How many rooms are heated (or cooled) by the Daikin
heat pump system?
Q Which heat emitter types are used in each room and what is
their design leaving water temperature?
Once the space heating/cooling requirements are clear, Daikin recommends to follow the setup guidelines below.
Installer reference guide
6
5 Application guidelines
B
A
a
B
A
b
a
5.2.1 Single room
Under floor heating or radiators – Wired room thermostat
Setup
A Main leaving water temperature zone B One single room
Q The under floor heating or radiators are directly connected to the
indoor unit.
Q The room temperature is controlled by the user interface, which
is used as room thermostat. Possible installations:
Q User interface (standard equipment) installed in the room
Q User interface (standard equipment) installed at the indoor
Configuration
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature zones:
Q #: [A.2.1.8] Q Code: [7-02]
Benefits
Q Cost effective. You do NOT need an additional external room
thermostat.
Q Highest comfort and efficiency. The smart room thermostat
functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation). This results in:
Q Stable room temperature matching the desired temperature
Q Less ON/OFF cycles (more quiet, higher comfort and
Q Lowest possible leaving water temperature (higher
Q Easy. You can easily set the desired room temperature via the
user interface:
Q For your daily needs, you can use preset values and
Q To deviate from your daily needs, you can temporarily
a User interface used as room thermostat
and used as room thermostat
unit and used for control close to the indoor unit + user interface (optional equipment EKRUCAL) installed in the room and used as room thermostat
Setting Val ue
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
0 (1 LWT zone): Main
(higher comfort)
higher efficiency)
efficiency)
schedules.
overrule the preset values and schedules, use the holiday mode…
Under floor heating or radiators – Wireless room thermostat
Setup
A Main leaving water temperature zone B One single room
a Receiver for wireless external room thermostat
Q The under floor heating or radiators are directly connected to the
indoor unit.
Q The room temperature is controlled by the wireless external
room thermostat (optional equipment EKRTR1).
Configuration
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature zones:
Q #: [A.2.1.8] Q Code: [7-02]
External room thermostat for the main zone:
Q #: [A.2.2.4] Q Code: [C-05]
Benefits
Q Wireless. The Daikin external room thermostat is available in a
wireless version.
Q Efficiency. Although the external room thermostat only sends
ON/OFF signals, it is specifically designed for the heat pump
system.
Q Comfort. In case of under floor heating, the wireless external
room thermostat prevents condensation on the floor during
cooling operation by measuring the room humidity.
b Wireless external room thermostat
Setting Valu e
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
Configure according to the setup:
Q 1 (Thermo ON/OFF): When
the used external room thermostat or heat pump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
Q 2 (C/H request): When the
used external room thermostat can send a separate heating/cooling thermo ON/OFF condition.
Installer reference guide
7
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
5 Application guidelines
B
A
a
B
A
a
M1
Heat pump convectors
Setup
A Main leaving water temperature zone B One single room
Q The heat pump convectors are directly connected to the indoor
a Remote controller of the heat pump convectors
unit.
Q The desired room temperature is set via the remote controller of
the heat pump convectors.
Q The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/1 and X2M/4).
Q The space operation mode is sent to the heat pump convectors
by one digital output on the indoor unit (X2M/33 and X2M/34).
INFORMATION
When using multiple heat pump convectors, make sure each one receives the infrared signal from the remote controller of the heat pump convectors.
Configuration
Setting Val ue
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
zones:
Q #: [A.2.1.8] Q Code: [7-02]
External room thermostat for the main zone:
Q #: [A.2.2.4] Q Code: [C-05]
1 (Thermo ON/OFF): When the used external room thermostat or heat pump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
Benefits
Q Cooling. The heat pump convector offers, besides heating
capacity, also excellent cooling capacity.
Q Efficiency. Optimal energy efficiency because of the interlink
function.
Q Stylish.
Combination: Under floor heating + Heat pump convectors
Q Space heating is provided by:
Q The under floor heating Q The heat pump convectors
Q Space cooling is provided by the heat pump convectors only.
The under floor heating is shut off by the shut-off valve.
Setup
A Main leaving water temperature zone B One single room
Q The heat pump convectors are directly connected to the indoor
a Remote controller of the heat pump convectors
unit.
Q A shut-off valve (field supply) is installed before the under floor
heating to prevent condensation on the floor during cooling operation.
Q The desired room temperature is set via the remote controller of
the heat pump convectors.
Q The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/1 and X2M/4)
Q The space operation mode is sent by one digital output (X2M/33
and X2M/34) on the indoor unit to:
Q The heat pump convectors Q The shut-off valve
Configuration
Setting Value
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
zones:
Q #: [A.2.1.8] Q Code: [7-02]
External room thermostat for the main zone:
Q #: [A.2.2.4] Q Code: [C-05]
1 (Thermo ON/OFF): When the used external room thermostat or heat pump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
Benefits
Q Cooling. Heat pump convectors provide, besides heating
capacity, also excellent cooling capacity.
Q Efficiency. Under floor heating has the best performance with
Altherma LT.
Q Comfort. The combination of the two heat emitter types
provides:
Q The excellent heating comfort of the under floor heating Q The excellent cooling comfort of the heat pump convectors
5.2.2 Multiple rooms – One LWT zone
If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same, you do NOT need a mixing valve station (cost effective).
Example: If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters.
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
8
5 Application guidelines
T
BC
A
a
M2M1
BC
A
aa
b
B
A
aa
C
Under floor heating or radiators – Thermostatic valves
If you are heating up rooms with under floor heating or radiators, a very common way is to control the temperature of the main room by using a thermostat (this can either be the user interface or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves, which open or close depending on the room temperature.
Setup
A Main leaving water temperature zone B Room 1 C Room 2
Q The under floor heating of the main room is directly connected to
the indoor unit.
Q The room temperature of the main room is controlled by the user
interface used as thermostat.
Q A thermostatic valve is installed before the under floor heating in
each of the other rooms.
Configuration
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature zones:
Q #: [A.2.1.8] Q Code: [7-02]
Benefits
Q Cost effective. Q Easy. Same installation as for one room, but with thermostatic
valves.
a User interface
NOTICE
Mind situations where the main room can be heated by another heating source. Example: Fireplaces.
Setting Val ue
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
0 (1 LWT zone): Main
Under floor heating or radiators – Multiple external room thermostats
Setup
A Main leaving water temperature zone B Room 1 C Room 2
a External room thermostat
Q For each room, a shut-off valve (field supplied) is installed to
b Bypass valve
avoid leaving water supply when there is no heating or cooling
demand.
Q A bypass valve must be installed to make water recirculation
possible when all shut-off valves are closed.
Q The user interface connected to the indoor unit decides the
space operation mode. Mind that the operation mode on each
room thermostat must be set to match the indoor unit.
Q The room thermostats are connected to the shut-off valves, but
do NOT have to be connected to the indoor unit. The indoor unit
will supply leaving water all the time, with the possibility to
program a leaving water schedule.
Configuration
Setting Valu e
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature
0 (LWT control): Unit operation is decided based on the leaving water temperature.
0 (1 LWT zone): Main
zones:
Q #: [A.2.1.8] Q Code: [7-02]
Benefits
Compared with under floor heating or radiators for one room:
Q Comfort. You can set the desired room temperature, including
schedules, for each room via the room thermostats.
Heat pump convectors
Setup
Installer reference guide
9
A Main leaving water temperature zone B Room 1 B Room 2
Q The desired room temperature is set via the remote controller of
a Remote controller of the heat pump convectors
the heat pump convectors.
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
5 Application guidelines
B
A
aa
C
E
D
b
c
Q The user interface connected to the indoor unit decides the
space operation mode.
Q The heating or cooling demand signals of each heat pump
convector are connected in parallel to the digital input on the indoor unit (X2M/1 and X2M/4). The indoor unit will only supply leaving water temperature when there is an actual demand.
NOTICE
To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump convector.
Configuration
Setting Val ue
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
zones:
Q #: [A.2.1.8] Q Code: [7-02]
Benefits
Compared with heat pump convectors for one room:
Q Comfort. You can set the desired room temperature, including
schedules, for each room via the remote controller of the heat pump convectors.
Combination: Under floor heating + Heat pump convectors
Setup
NOTICE
To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump convector.
Configuration
Setting Value
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
Number of water temperature
0 (LWT control): Unit operation is decided based on the leaving water temperature.
0 (1 LWT zone): Main
zones:
Q #: [A.2.1.8] Q Code: [7-02]
5.2.3 Multiple rooms – Two LWT zones
If the heat emitters selected for each room are designed for different leaving water temperatures, you can use different leaving water temperature zones (maximum 2). In this document:
Q Main zone = Zone with the lowest design temperature in
heating, and the highest design temperature in cooling
Q Additional zone = The other zone
CAUTION
When there is more than one leaving water zone, you must always install a mixing valve station in the main zone to decrease (in heating)/increase (in cooling) the leaving water temperature when the additional zone has demand.
Typical example:
A BC
M1
M1
b
a
A Main leaving water temperature zone B Room 1 C Room 2
a External room thermostat
Q For each room with heat pump convectors: The heat pump
b Remote controller of the heat pump convectors
convectors are directly connected to the indoor unit.
Q For each room with under floor heating: Two shut-off valves
(field supply) are installed before the under floor heating:
Q A shut-off valve to prevent hot water supply when the room
has no heating demand
Q A shut-off valve to prevent condensation on the floor during
cooling operation of the rooms with heat pump convectors
Q For each room with heat pump convectors: The desired room
temperature is set via the remote controller of the heat pump convectors.
Q For each room with under floor heating: The desired room
temperature is set via the external room thermostat (wired or wireless).
Q The user interface connected to the indoor unit decides the
space operation mode. Mind that the operation mode on each external room thermostat and remote controller of the heat pump convectors must be set to match the indoor unit.
Heat emitters: Design
Room (zone)
temperature
Living room (main zone) Under floor heating:
Q In heating: 35°C Q In cooling: 20°C (only
refreshment, no real cooling allowed)
Bed rooms (additional zone) Heat pump convectors:
Q In heating: 45°C Q In cooling: 12°C
Setup
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
10
5 Application guidelines
abcdefgh j
FHL1
FHL2
FHL3
M
h
i
il
k
f
m
n
A Additional leaving water temperature zone B Room 1 C Room 2 D Main leaving water temperature zone E Room 3
a Remote controller of the heat pump convectors b User interface
Q For the main zone:
Q A mixing valve station is installed before the under floor
c Mixing valve station
heating.
Q The pump of the mixing valve station is controlled by the
ON/OFF signal on the indoor unit (X2M/5 and X2M/7; normal closed shut-off valve output).
Q The room temperature is controlled by the user interface,
which is used as room thermostat.
Q For the additional zone:
Q The heat pump convectors are directly connected to the
indoor unit.
Q The desired room temperature is set via the remote
controller of the heat pump convectors for each room.
Q The heating or cooling demand signals of each heat pump
convector are connected in parallel to the digital input on the indoor unit (X2M/1 and X2M/4). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand.
Q The user interface connected to the indoor unit decides the
space operation mode. Mind that the operation mode on each remote controller of the heat pump convectors must be set to match the indoor unit.
Configuration
Setting Val ue
Unit temperature control:
Q #: [A.2.1.7] Q Code: [C-07]
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
Note:
Q Main room = user interface
used as room thermostat functionality
Q Other rooms = external
room thermostat functionality
Number of water temperature zones:
Q #: [A.2.1.8] Q Code: [7-02]
In case of heat pump convectors: External room thermostat for the
additional zone:
Q #: [A.2.2.5] Q Code: [C-06]
1 (2 LWT zones): Main + additional
1 (Thermo ON/OFF): When the used external room thermostat or heat pump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
Shut-off valve output Set to follow the thermo demand
of the main zone.
Shut-off valve If the main zone must be shut off
during cooling mode to prevent condensation on the floor, set it accordingly.
At the mixing valve station Set the desired main leaving
water temperature for heating and/or cooling.
Benefits
Q Comfort.
Q The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the actual room temperature (modulation).
Q The combination of the two heat emitter systems provides
the excellent heating comfort of the under floor heating, and the excellent cooling comfort of the heat pump convectors.
Q Efficiency.
Q Depending on the demand, the indoor unit supplies
different leaving water temperature matching the design temperature of the different heat emitters.
Q Under floor heating has the best performance with
Altherma LT.
5.3 Setting up an auxiliary heat source for space
heating
Q Space heating can be done by:
Q The indoor unit
Q An auxiliary boiler (field supply) connected to the system Q When the room thermostat requests heating, the indoor unit or
the auxiliary boiler starts operating depending on the outdoor
temperature (status of the changeover to external heat source).
When the permission is given to the auxiliary boiler, the space
heating by the indoor unit is turned OFF.
Q Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always
produced by the DHW tank connected to the indoor unit.
INFORMATION
Q During heating operation of the heat pump, the
heat pump operates to achieve the desired temperature set via the user interface. When weather­dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature.
Q During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water temperature set via the auxiliary boiler controller.
Setup
Q Integrate the auxiliary boiler as follows:
Installer reference guide
11
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
5 Application guidelines
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Shut-off valve
g Motorised 3-way valve (delivered with DHW tank)(field
supply)
h Non-return valve
i Shut-off valve j Collector (field supply)
k Auxiliary boiler (field supply)
l Aquastat valve (field supply)
m DHW tank (option)
n Heat exchanger coil
FHL1...3 Under floor heating
NOTICE
Q Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
Q Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
Q Make sure the return water to the heat pump does NOT exceed
55°C. To do so:
Q Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
Q Install an aquastat valve in the return water flow of the
heat pump.
Q Set the aquastat valve to close above 55°C and to open
below 55°C.
Q Install non-return valves. Q Make sure to only have one expansion vessel in the water
circuit. An expansion vessel is already is already premounted in the indoor unit.
Q Install the digital I/O PCB (option EKRP1HB). Q Connect X1 and X2 (changeover to external heat source) on the
PCB to the auxiliary boiler thermostat.
Q To setup the heat emitters, see setting up the space
heating/cooling application guidelines).
Q Setup: Connect the following field wiring:
L
H
Com
Indoor/Auto/Boiler
A
K2AK1A
Indoor
X2M
1234 XY
K2AK1A
N
BTIBoiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional) K1A Auxiliary relay for activation of indoor unit (field supply) K2A Auxiliary relay for activation of boiler (field supply)
Indoor Indoor unit
Auto Automatic
Boiler Boiler
NOTICE
Q Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between indoor unit and auxiliary boiler.
Q If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.
Q Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.
5.4 Setting up the domestic hot water tank
The DHW tank can be:
Q Integrated in the indoor unit Q Installed standalone as option
5.4.1 System layout – Integrated DHW tank
B
TI
Configuration
Via the user interface (quick wizard):
Q Set the use of a bivalent system as external heat source. Q Set the bivalent temperature and hysteresis.
NOTICE
Q Make sure the bivalent hysteresis has enough
differential to prevent frequent changeover between indoor unit and auxiliary boiler.
Q Because the outdoor temperature is measured by the
outdoor unit air thermistor, install the outdoor unit in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.
Q Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary contact
Q Only possible in external room thermostat control AND one
leaving water temperature zone (see setting up space heating/cooling application guideline).
Q The auxiliary contact can be:
Q An outdoor temperature thermostat Q An electricity tariff contact Q A manually operated contact Q
abcd hh if
M
e
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Motorised 3-way valve g DHW tank h Shut-off valve
i Collector (field supply)
FHL1...3 Under floor heating
UI User interface
UI
FHL1
FHL2
FHL3
g
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
12
5 Application guidelines
5.4.2 System layout – Standalone DHW tank
abcde hfg
M
f
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Shut-off valve g Motorised 3-way valve h Collector (field supply)
i DHW tank
j Heat exchanger coil
FHL1...3 Under floor heating
FHL1
ij
FHL2
FHL3
5.4.3 Selecting the volume and desired temperature for the DHW tank
People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C). Selecting the volume and desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the volume and desired temperature for the DHW
tank.
Possible DHW tank volumes
Typ e Possible volumes
Integrated DHW tank
Standalone DHW tank
Energy saving tips
Q If the DHW consumption differs from day to day, you can
program a weekly schedule with different desired DHW tank temperatures for each day.
Q The lower the desired DHW tank temperature, the more cost
effective. By selecting a larger DHW tank, you can lower the desired DHW tank temperature.
Q The heat pump itself can produce domestic hot water of
maximum 55°C (50°C if outdoor temperature is low). The electrical resistance integrated in the heat pump can higher this temperature. However, this consumes more energy. Daikin recommends to set the desired DHW tank temperature below 55°C to avoid using the electrical resistance.
Q The higher the outdoor temperature, the better the performance
of the heat pump.
Q 180 l Q 260 l
Q 150 l Q 200 l Q 300 l
Q If energy prices are the same during the day and the night,
Daikin recommends to heat up the DHW tank during the day.
Q If energy prices are lower during the night, Daikin
recommends to heat up the DHW tank during the night.
Q When the heat pump produces domestic hot water, it cannot
heat up a space. When you need domestic hot water and space heating at the same, Daikin recommends to produce the domestic hot water during the night when there is lower space heating demand.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent hot water volume at 40°C) using the typical water volumes:
Question Typical water volume
How many showers are needed per day?
How many baths are needed per
1 shower = 10 min x 10 l/min = 100 l
1 bath = 150 l
day?
How much water is needed at the
1sink = 2min x 5l/min = 10l
kitchen sink per day?
Are there any other domestic hot
water needs?
Example: If the DHW consumption of a family (4 persons) per day is as follows:
Q 3 showers Q 1 bath Q 3 sink volumes
Then the DHW consumption = (3x100 l) + (1x150 l) + (3x10 l) = 480 l
Determining the volume and desired temperature for the DHW tank
Formula Example
= V2 + V2x (T2- 40) / (40 - T1) If:
V
1
V
= V1 x (40 - T1)/ (T2-T1) If:
2
V1: DHW consumption (equivalent hot water volume at 40°C) V2: Required DHW tank volume if only heated once T2: DHW tank temperature T1: Cold water temperature
Q V
Q T
Q T
Then V
Q V
Q T
Q T
Then V
= 180 l
2
= 54°C
2
= 15°C
1
= 280 l
1
= 480 l
1
= 54°C
2
= 15°C
1
= 307 l
2
5.4.4 Setup and configuration – DHW tank
Q For large DHW consumptions, you can heat up the DHW tank
several times during the day.
Q To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
Q Thermodynamic cycle of the heat pump Q Electrical backup heater (for integrated DHW tank) Q Electrical booster heater (for standalone DHW tank) Q Solar panels
Q For more information about:
Q Optimizing the energy consumption for producing domestic
hot water, see the configuration chapter.
Q Connecting the electrical wiring of the standalone DHW
tank to the indoor unit, see the installation chapter.
Q Connecting the water piping of the standalone DHW tank to
the indoor unit, see the installation manual of the DHW tank.
Installer reference guide
13
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
5 Application guidelines
M
a
c
db
c.1
c.2
c.3
e
c.4
f
≥0.5 m
c
f
a
b
g
h
i
5.4.5 Combination: Standalone DHW tank + Solar panels
By connecting the DHW tank to solar panels, the DHW tank can be heated by solar energy.
For installation instructions, see the installation manual of the solar kit and addendum book for optional equipment.
a Solar panels b Solar pump station
c Solar pump station controller with temperature sensors c1 Tank temperature sensor c2 Return temperature sensor to solar panels c3 Supply temperature with flow meter from solar panels c4 Solar panel temperature sensor
d Solar kit
e DHW temperature sensor of the unit
f Solenoid 2-way valve (only for UK). Obligatory for
compliance to UK building regulation G3. Heating system Example of unit
5.4.6 DHW pump for instant hot water
Setup
5.4.7 DHW pump for disinfection
Setup
h
c
a
b
Q The DHW pump and the installation are field supply and the
i
d f
eg
a Indoor unit b DHW tank c DHW pump d Heater element e Non-return valve
f Shower g Cold water h Domestic hot water OUT
i Recirculation connection
responsibility of the installer.
Q For the integrated DHW tank, the temperature of the DHW tank
can be set to maximum 60°C. If applicable legislation requires higher temperature for disinfection, you can connect a DHW pump and heater element as shown above.
Q If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above.
Configuration
The indoor unit can control DHW pump operation. For more information, see the configuration chapter.
5.5 Setting up the energy metering
Q Via the user interface, you can read out the following energy
data:
Q Produced heat Q Consumed energy
Q You can read out the energy data:
Q For space heating Q For space cooling Q For domestic hot water production
Q You can read out the energy data:
Q Per month Q Per year
a Indoor unit b DHW tank c DHW pump
f Shower g Cold water h Domestic hot water OUT
i Recirculation connection
Q By connecting a DHW pump, instant hot water can be available
at the tap.
Q The DHW pump and the installation are field supply and the
responsibility of the installer.
Q For more information about connecting the recirculation
connection (for integrated DHW tank), see the installation chapter.
5.5.1 Produced heat
Q Applicable for all models. Q The produced heat is calculated internally based on:
Q The leaving and entering water temperature Q The flow rate Q The power consumption of the booster heater (if applicable)
in the domestic hot water tank
Q Setup and configuration:
Q No additional equipment needed. Q Only in case a booster heater is present in the system,
measure its capacity (resistance measurement) and set the capacity via the user interface. Example: If you measure a booster heater resistance of 17.1 , the capacity of the heater at 230 V is 3100 W.
Configuration
Q For more information, see the configuration chapter. Q You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference guide.
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
14
5 Application guidelines
b
5
8
0
1
5
0
0
0
cc
fed
g
ABC
a
b
5
8
0
1
5
0
0
0
gfe
h
ABC
ccd
a

5.5.2 Consumed energy
You can use the following methods to determine the consumed energy:
Q Calculating Q Measuring
NOTICE
You cannot combine calculating the consumed energy (example: for backup heater) and measuring the consumed energy (example: for outdoor unit). If you do so, the energy data will be invalid.
Calculating the consumed energy
Q Only applicable for EHBH/X04+08 and EHVH/X04+08. Q The consumed energy is calculated internally based on:
Q The actual power input of the outdoor unit Q The set capacity of the backup heater and booster heater Q The voltage
Q Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via the user interface for:
Q The backup heater (step 1 and step 2) Q The booster heater
Measuring the consumed energy
Q Applicable for all models. Q Preferred method because of higher accuracy. Q Requires external power meters. Q Setup and configuration:
Q For the specifications of each type of meter, see technical
data.
Q When using electrical power meters, set the number of
pulses/kWh for each power meter via the user interface. Consumed energy data for EHVH/X16 and EHBH/X16 models will only be available if this setting is configured.
NOTICE
When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters.
5.5.3 Normal kWh rate power supply
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/7 and X5M/8.
Power meter type
In case of… Use a… power meter
Q Single-phase outdoor unit Q Backup heater supplied
from a single-phase grid (i.e. the backup heater model is *3V or *9W connected to a single-phase grid)
In other cases (i.e. a three-phase outdoor unit and/or a 9W* backup heater model connected to a three-phase grid)
Single-phase
Three-phase
Example
Single-phase power meter Three-phase power meter
A Outdoor unit B Indoor unit C DHW tank a Electrical cabinet (L
/N)
/N)
1
/N)
1
/N)
1
1
b Power meter (L c Fuse (L
1
d Outdoor unit (L e Indoor unit (L f Backup heater (L g Booster heater (L
/N)
1
/N)
1
/N)
A Outdoor unit B Indoor unit C DHW tank a Electrical cabinet (L
b Power meter (L c Fuse (L d Fuse (L e Outdoor unit (L f Indoor unit (L g Backup heater (L
1/L2/L3
/N)
1
1/L2/L3
/N)
1/L2/L3
1/L2/L3
1/L2/L3
h Booster heater (L
1/L2/L3
/N)
/N)
1
/N)
/N)
/N)
/N)
Exception
Q You can use a second power meter if:
Q The power range of one meter is insufficient. Q The electrical meter cannot easily be installed in the
electrical cabinet.
Q 230V and 400V three-phase grids are combined (very
uncommon), because of technical limitations of power meters.
Q Connection and setup:
Q Connect the second power meter to X5M/9 and X5M/10. Q In the software the power consumption data of both meters
is added so you do NOT have to set which meter covers which power consumption. You only need to set the number of pulses of each power meter.
Q See preferential kWh rate power supply for an example with two
power meters.
5.5.4 Preferential kWh rate power supply
General rule
Q Power meter 1: Measures the outdoor unit. Q Power meter 2: Measures the rest (i.e. indoor unit, backup
heater and optional booster heater).
Setup
Q Connect power meter 1 to X5M/7 and X5M/8. Q Connect power meter 2 to X5M/9 and X5M/10.
Power meter types
Q Power meter 1: Single- or three-phase power meter according to
the power supply of the outdoor unit.
Q Power meter 2:
Q In case of a single-phase backup heater configuration, use
a single-phase power meter.
Q In other cases, use a three-phase power meter.
Installer reference guide
15
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
Example
5 8
0
1
5
0
0
0
eef
ihg
j
ABC
ba
d

5
8
0
1
5
0
0
0
c
P
i
t
DI
a
b
Single-phase outdoor unit with a three-phase backup heater:
A Outdoor unit B Indoor unit C DHW tank
a Electrical cabinet (L
/N): Preferential kWh rate power
1
supply
b Electrical cabinet (L
/N): Normal kWh rate power
1/L2/L3
supply
c Power meter (L
d Power meter (L
e Fuse (L
f Fuse (L
g Outdoor unit (L
h Indoor unit (L
i Backup heater (L
j Booster heater (L
/N)
1
1/L2/L3
/N)
1
1/L2/L3
/N)
/N)
1
1/L2/L3
1/L2/L3
/N)
/N)
/N)
/N)
1
5.6 Setting up the power consumption control
Q The power consumption control:
Q Is only applicable for EHBH/X04+08 and EHVH/X04+08. Q Allows you to limit the power consumption of the entire
system (sum of outdoor unit, indoor unit, backup heater and optional booster heater).
Q Configuration: Set the power limitation level and how it has
to be achieved via the user interface.
Q The power limitation level can be expressed as:
Q Maximum running current (in A) Q Maximum power input (in kW)
Q The power limitation level can be activated:
Q Permanently Q By digital inputs
5.6.1 Permanent power limitation
Permanent power limitation is useful to assure a maximum power or current input of the system. In some countries, legislation limits the maximum power consumption for space heating and DHW production. Example: The maximum power input depends on the area of the house and an annual fee has to be paid to the electrical company according to the size of the installed field fuse. By permanently limiting the maximum power or current of the system, you can install smaller field fuses.
NOTICE
When the current control is intended to reduce the installed field fuse sizes, the field fuse will trip to protect the field wires in case of overcurrents caused by the unit. Make sure the selection of the field fuse complies with applicable legislation.
5 Application guidelines
PiPower input
t Time
DI Digital input (power limitation level)
a Power limitation active b Actual power input
Setup and configuration
Q No additional equipment needed. Q Set the power consumption control settings in [A.7.2] via the
user interface (for the description of all settings, see configuration chapter):
Q Select full time limitation mode Q Select the type of limitation (power in kW or current in A) Q Set the desired power limitation level
NOTICE
Mind the following guidelines when selecting the desired power limitation level:
Q Set a minimum power consumption of ±3.6 kW to
guarantee defrost operation. Otherwise, if defrosting is interrupted several times, the heat exchanger will freeze up.
Q Set a minimum power consumption of ±3 kW to
guarantee space heating and DHW production by allowing at least one electrical heater (backup heater step 1 or booster heater).
5.6.2 Power limitation activated by digital inputs
Power limitation is also useful in combination with an energy management system. The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following:
Q Current (in A) Q Power input (in kW)
The energy management system (field supply) decides the activation of a certain power limitation level. Example: To limit the maximum power of the entire house (lighting, domestic appliances, space heating…).
D
a
5
4 3 2
A8P
1
b
ABC
c
A Outdoor unit B Indoor unit C DHW tank D Energy management system
a Power limitation activation (4 digital inputs) b Backup heater c Booster heater
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
16
5 Application guidelines
P
i
t
DI1
DI3
DI4
a
b
Then power consumption is limited as follows:
P
h
e
d
c
b
PiPower input
t Time
DI Digital inputs (power limitation levels)
a Power limitation active b Actual power input
Setup
Q Demand PCB (option EKRP1AHTA) needed. Q Maximum four digital inputs are used to activate the
corresponding power limitation level:
Q DI1 = strongest limitation (lowest energy consumption) Q DI4 = weakest limitation (highest energy consumption)
Q For the specification and the connection of the digital inputs, see
technical data > wiring diagram.
Configuration
Set the power consumption control settings in [A.7.2] via the user interface (for the description of all settings, see configuration chapter):
Q Select activation by digital inputs. Q Select the type of limitation (power in kW or current in A). Q Set the desired power limitation level corresponding to each
digital input.
5.6.3 Power limitation process
The outdoor unit has better efficiency than the electrical heaters. Therefore, the electrical heaters are limited and turned OFF first. The system limits power consumption in the following order:
1 Limits certain electrical heaters.
Then set the heater priority
If… has priority
Domestic hot water production Booster heater.
Space heating Backup heater.
2 Turns OFF all electrical heaters.
3 Limits the outdoor unit
4 Turns OFF the outdoor unit.
Example
If the configuration is as follows:
Q Power limitation level does NOT allow operation of both booster
heater and backup heater (step 1 and step 2).
Q Heater priority = Booster heater.
via the user interface to…
Result: The backup heater will be turned OFF first.
Result: The booster heater will be turned OFF first.
a
AB C
PhProduced heat C
e
A Outdoor unit B Booster heater C Backup heater
a Limited outdoor unit operation b Full outdoor unit operation c Booster heater turned ON d Backup heater step 1 turned ON e Backup heater step 2 turned ON
C
e
Consumed energy
5.7 Setting up an external temperature sensor
You can connect one external temperature sensor. It can measure the indoor or outdoor ambient temperature. Daikin recommends to use an external temperature sensor in the following cases:
Indoor ambient temperature
Q In room thermostat control, the user interface is used as room
thermostat and it measures the indoor ambient temperature. Therefore, the user interface must be installed on a location:
Q Where the average temperature in the room can be
detected
Q That is NOT exposed to direct sunlight Q That is NOT near a heat source Q That is NOT affected by outside air or air draught because
of, for example, door opening/closing
Q If this is NOT possible, Daikin recommends to connect a remote
indoor sensor (option KRCS01-1).
Q Setup: For installation instructions, see the installation manual of
the remote outdoor sensor.
Q Configuration: Select room sensor [A.2.2.B].
Outdoor ambient temperature
Q In the outdoor unit, the outdoor ambient temperature is
measured. Therefore, the outdoor unit must be installed on a location:
Q At the north side of the house or at the side of the house
where the most heat emitters are located
Q That is NOT exposed to direct sunlight
Q If this is NOT possible, Daikin recommends to connect a remote
outdoor sensor (option EKRSCA1).
Q Setup: For installation instructions, see the installation manual of
the remote outdoor sensor.
Q Configuration: Select outdoor sensor [A.2.2.B]. Q During suspend (see configuration), the outdoor unit is turned
down to reduce the standby energy losses. As a result, the outdoor ambient temperature is NOT read out.
Q If the desired leaving water temperature is weather dependent,
the full time outdoor temperature measurement is important. This is another reason to install the optional outdoor ambient temperature sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged or instantaneous) is used in the weather-dependent control curves and in the automatic heating/cooling changeover logic. To protect the outdoor unit, the internal sensor of the outdoor unit is always used.
Installer reference guide
17
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
6 Preparation
>500
>10>10
(mm)
M
M
FCU1
FCU2
FCU3
FHL1
FHL2
FHL3
a
b
cd
e f
gf h
i
i
i
i
jk
65°C
65°C
6 Preparation
6.1 Preparing installation site
Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered. Choose the installation location with sufficient place for carrying the unit in and out of the site.
6.1.1 Installation site requirements of the indoor unit
Q Mind the measurement guidelines:
Maximum refrigerant piping length between indoor unit and outdoor unit
Minimum refrigerant piping length between indoor unit and outdoor unit
Maximum height difference between indoor unit and outdoor unit
(a) Check the outdoor unit installation manual. (b) When <5 m, you need to recharge the outdoor unit (check the
Q Mind the following spacing installation guidelines:
outdoor unit installation manual).
75 m
3m
30 m
(a)
(b)
6.2 Preparing water piping
6.2.1 Water circuit requirements
Q Use the indoor unit only in a closed water system.
Using the system in an open water system will lead to excessive corrosion.
Q The maximum water pressure is 4 bar.
Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
Q All installed piping and piping accessories (valve,
connections,…) must withstand the following temperatures:
INFORMATION
The following illustration is an example and may NOT match your system layout.
Do NOT install the unit in places such as:
Q Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or water to leak.
Q Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom and the like), so that the operation noise will cause no trouble. Note: If the sound is measured under actual installation conditions, the measured value will be higher than the sound pressure level mentioned in Sound spectrum due to environmental noise and sound reflections.
Q The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full of water into account. Make sure, in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
Q In places with high humidity (max. RH=85%), for example a
bathroom.
Q In places where frost is possible. Ambient temperature around
the indoor unit should be >5°C.
Q The indoor unit is designed for indoor installation only and for
ambient temperatures ranging 5~35°C in cooling mode and 5~30°C in heating mode.
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Stop valve g Motorised 3-way valve h Motorised 2-way valve (field supply)
i Collector
j Domestic hot water tank k Heat exchanger coil
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
Q Make all water piping connections in accordance with the
applicable legislation and the outlook diagram that is delivered with the unit, respecting the water inlet and outlet.
Q Do NOT use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the unit.
Q Provide drain taps at all low points of the system in order to allow
complete drainage of the water circuit.
Q Provide a proper drain for the pressure relief valve to avoid
water dripping out of the unit. See "7.3.2 To connect the pressure relief valve to the drain" on page 23.
Q Provide air vents at all high points of the system, which must
also be easily accessible for servicing. An automatic air purge is provided in the indoor unit. Check that the air purge is NOT tightened too much, so that automatic release of air in the water circuit is possible.
Installer reference guide
18
6Preparation
FHL1
FHL2
FHL3
M1
T1
M2T2M3
T3
fdcba
f
g h
e
Q Only use materials that are compatible with water used in the
system and with the materials used in the indoor unit.
Q Check that all components in the field piping can withstand the
water pressure and water temperature.
Q When using non-brass metallic piping, insulate the brass and
non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Q Never use Zn-coated parts in the water circuit. Because the
unit's internal water circuit uses copper piping, excessive corrosion may occur.
Q Only use appropriate tooling to handle brass, which is a soft
material. If NOT, pipes will get damaged.
Q Select the water piping diameter in relation to the required water
flow and the available external static pressure of the pump. See "14 Technical data" on page 61 for the external static pressure curves of the indoor unit.
Q You can find the minimum required water flow for the indoor unit
operation in the following table. When the water flow is lower, flow error 7H will be displayed and the indoor unit will be stopped.
Model Minimum water flow (l/min)
04 5
08+16 11
Q When using a 2-way valve in the water circuit, the maximum
change-over time of the valve must be 60 seconds.
Q It is strongly recommended to install an additional filter on the
heating water circuit. Especially to remove metallic particles from the filed heating piping, it is advised to use a magnetic or cyclone filter, which can remove small particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump system.
Q If air, moisture or dust gets into the water circuit, problems may
occur. To prevent this:
Q Only use clean pipes Q Hold the pipe end downwards when removing burrs. Q Cover the pipe end when inserting it through a wall, to
prevent dust and/or particles entering the pipe.
Q Use a decent thread sealant to seal connections.
Q For safety reasons, it is NOT allowed to add any kind of glycol to
the water circuit.
Q To avoid stagnation of water, it is important that the storage
capacity of the domestic hot water tank meets the daily consumption of domestic hot water. In cases where during longer periods of time there is no consumption of hot water, the equipment must be flushed with fresh water before usage. The disinfection function provided on the equipment is specified in the operation manual of the indoor unit.
Q It is recommended to avoid long runs of piping between the
domestic hot water tank and the hot water end point (shower, bath,…) and to avoid dead ends.
Q The installation must be in compliance with the applicable
legislation and may require additional hygienic installation measures.
Q In accordance with the applicable legislation, it may be
necessary to install thermostatic mixing valves.
Q Immediately after installation, the domestic hot water tank must
be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.
Q In accordance with the applicable legislation, it may be required
to connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank.
ab
d
a Recirculation connection b Hot water connection c Shower d Recirculation pump
6.2.2 Formula to calculate the expansion vessel pre-pressure
c
The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)
6.2.3 To check the water volume
The indoor unit has an expansion vessel of 10 litre with a factory set pre-pressure of 1 bar. To make sure that the unit operates properly:
Q You must check the minimum and maximum water volume. Q You might need to adjust the pre-pressure of the expansion
vessel.
Minimum water volume
Check that the total water volume in the installation is minimum 20 liter, the internal water volume of the indoor unit NOT included.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be required.
NOTICE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Shut-off valve g Collector (field supply) h By-pass valve (field supply)
FHL1...3 Floor heating loop (field supply)
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control loop FHL1...3 (field
supply)
Installer reference guide
19
EHVH/X16
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
Maximum water volume
0.3
0.5
1
1.5
2
2.5
10050
0
20
150 200 250 300 350 400 450
a
b
a
Use the following graph to determine the maximum water volume for the calculated pre-pressure.
a Pre-pressure (bar) b Maximum water volume (l)
Example: Maximum water volume and expansion vessel pre­pressure
6 Preparation
a Schräder valve
6.2.5 To check the water volume: Examples
Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100 l. No actions or adjustments are required.
Installation
height
difference
(a)
280 l >280 l
7 m No pre-pressure
adjustment is required.
>7 m Do the following:
Q Increase the pre-
pressure.
Q Check if the water
volume does NOT exceed the maximum allowed water volume.
(a) This is the height difference (m) between the highest point of the
water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0 m.
6.2.4 Changing the pre-pressure of the expansion vessel
NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
When changing the default pre-pressure of the expansion vessel (1 bar) is required, take following guidelines into account:
Q Only use dry nitrogen to set the expansion vessel pre-pressure. Q Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder
Water volume
Do the following:
Q Decrease the pre-
pressure.
Q Check if the water
volume does NOT exceed the maximum allowed water volume.
The expansion vessel of the indoor unit is too small for the installation.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l. Actions:
Q Because the total water volume (350 l) is more than the default
water volume (280 l), the pre-pressure must be decreased.
Q The required pre-pressure is:
Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar=0.3 bar.
Q The corresponding maximum water volume at 0.3 bar is 410 l.
(See the graph in the chapter above).
Q Because 350 l is lower than 410 l, the expansion vessel is
appropriate for the installation.
6.3 Preparing electrical wiring
6.3.1 About preparing electrical wiring
WARNING
Q If the power supply has a missing or wrong N-phase,
equipment will break down.
Q Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
Q Install the required fuses or circuit breakers.
Q Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with the piping or sharp edges, particularly on the high-pressure side
Q Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
Q Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
valve of the expansion vessel.
WARNING
Q All wiring must be performed by an authorized
electrician and must comply with the applicable legislation.
Q Make electrical connections to the fixed wiring.
Q All components procured on the site and all electrical
construction must comply with the applicable legislation.
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
20
6Preparation
1
5 8
0
1
5
0
0
0
2
a
3
1
4
5
8
0
1
5
0
0
0
2
b
3
53
a
b
14
5
8 0
1
5
0
0
0
5 8
0
1
5 0
0
0
2
M
a
16
21
14
19
15
20
12
6
13
14
17
18
WARNING
The backup heater should have a dedicated power supply.
6.3.2 About preferential kWh rate power supply
Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ... This equipment allows for connection to such preferential kWh rate power supply delivery systems.
When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to:
Q interrupt power supply to the equipment for certain periods of
time;
Q demand that the equipment only consumes a limited amount of
electricity during certain periods of time. The indoor unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the outdoor unit compressor will not operate. Whether the power supply is interrupted or not, the wiring to the unit is different.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available, if any.
6.3.3 Overview of electrical connections except external actuators
Preferential kWh rate power supply
Normal power supply
Power supply is NOT interrupted Power supply is interrupted
During preferential kWh rate power supply activation, power supply is NOT interrupted. The outdoor unit is turned off by the control. Remark: The electricity company must always allow the power consumption of the indoor unit.
a Normal power supply b Preferential kWh rate power supply 1 Power supply for outdoor unit 2 Power supply and interconnection cable to indoor unit 3 Power supply for backup heater 4 Preferential kWh rate power supply (voltage free contact) 5 Normal kWh rate power supply (to power the indoor unit PCB in the event of power supply interruption of the preferential kWh rate power supply)
6.3.4 Overview of electrical connections for external and internal actuators
The following illustration shows the required field wiring.
INFORMATION
The following illustration is an example and may NOT match your system layout.
During preferential kWh rate power supply activation, power supply is interrupted immediately or after some time by the electricity company. In this case, the indoor unit must be powered by a separate normal power supply.
Installer reference guide
21
a Indoor unit
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
7Installation
4x
Item Description Wires
Outdoor unit and indoor unit power supply
1 Power supply for
outdoor unit
2 Power supply and
2+GND or 3+GND
3
(a)
(c)
interconnection cable to indoor unit
3 Power supply for
See table below. —
backup heater
4 Preferential kWh rate
2
(d)
power supply (voltage free contact)
5 Normal kWh rate power
26.3A
supply
User interface
6User interface 2
(e)
Optional equipment
11 Power supply for
2
(b)
bottom plate heater
12 Room thermostat 3 or 4
13 Outdoor ambient
2
100 mA
(b)
temperature sensor
14 Indoor ambient
2
(b)
temperature sensor
15 Heat pump convector 4
100 mA
Field supplied components
16 Shut-off valve 2
17 Electricity meter 2 (per meter)
18 Domestic hot water
2
(b)
(b)
(b)
pump
19 Alarm output 2
20 Changeover to external
2
(b)
(b)
heat source control
21 Space cool/heat
2
(b)
operation control
22 Power consumption
digital inputs
(a) Refer to name plate on outdoor unit. (b) Minimum cable section 0.75 mm². (c) Cable section 2.5 mm². (d) Cable section 0.75 mm² till 1.25 mm²; maximum length: 50 m.
Voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA.
(e) Cable section 0.75 mm² till 1.25 mm²; maximum length: 500 m.
Applicable for both single user interface and dual use interface connection.
Backup heater
type
Power supply
2 (per input signal)
Required number of
(b)
conductors
*3V 1x 230 V 2+GND
*9W 1x 230 V 2+GND + 2 bridges
3x 230 V 3+GND + 1 bridge
3x 400 V 4+GND
Maximum
running current
(b)
(b)
7 Installation
7.1 Opening the units
7.1.1 To open the indoor unit and switch box
1 Loosen and remove the screws at the bottom of the unit. 2 Slide the front panel of the unit downwards and remove it. 3 Loosen and remove the 4 screws that fix the top panel. 4 Remove the top panel from the unit.
5 Loosen and remove the 4 screws that fix the switch box cover. 6 Remove the switch box cover.
cover
3
4
4x
2
2x
1
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
22
7 Installation
≤1°
a
7.2 Mounting the indoor unit
7.2.1 To install the indoor unit
1 Lift the indoor unit from the pallet and place it on the floor.
3x
2 Slide the indoor unit into position. 3 Adjust the height of the leveling feet to compensate for floor
irregularities. The maximum allowed deviation is 1°.
1
2
120kg
7.3 Connecting the water piping
7.3.1 To connect the water piping
NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
NOTICE
To avoid damage to the surroundings in case of water leakage, it is recommended to close the cold water inlet stop valves during periods of absence.
2 Screw the indoor unit nuts on the shut-off valves. 3 Connect the domestic hot water in and out pipes to the indoor
unit.
NOTICE
Q A drain device and pressure relief device should be
installed on the cold water inlet connection of the domestic hot water cylinder.
Q To avoid back siphonage, it is recommended to install
a non-return valve on the water inlet of the domestic hot water tank in accordance with the applicable legislation.
Q It is recommended to install a pressure reducing valve
on the cold water inlet in accordance with the applicable legislation.
Q An expansion vessel should be installed on the cold
water inlet in accordance with the applicable legislation.
Q It is recommended to install the pressure relief valve
on higher position as top of the domestic hot water tank. Heating of the domestic hot water tank causes water to expand and without pressure relief valve the water pressure inside the tank can rise above the tank design pressure. Also the field installation (piping, tapping points, etc.) connected to the tank is subjected to this high pressure. To prevent this, a pressure relieve valve needs to be installed. The overpressure prevention depends on the correct operation of the field installed pressure relief valve. If this is NOT working correctly, overpressure will deform the tank and water leakage may occur. To confirm good operation, regular maintenance is required.
7.3.2 To connect the pressure relief valve to the drain
The blow out of the pressure relief valve is coming out of the backside of the unit.
To facilitate service and maintenance, 2 shut-off valves are provided. Mount the valves on the water inlet and on the water outlet. Mind their the position. Orientation of the integrated drain and fill valves is important for servicing.
1 Install the shut-off valves on the water pipes.
ac bd
a Space heating/cooling water out b Space heating/cooling water in c Domestic hot water out
Installer reference guide
d Domestic cold water in (cold water supply)
NOTICE
It is recommended to install shut-off valves to domestic cold water in and domestic hot water out connections. Shut-off valves are field supplied.
The blow out should be connected to an appropriate drain according to the applicable legislation. It is recommended to use a tundish.
23
a Pressure relief blow-out
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
7Installation
7.3.3 To fill the water circuit
1 Connect the water supply hose to the fill valve.
2 Open the fill valve. 3 Make sure that the automatic air purge valve is open (at least 2
turns).
INFORMATION
For location of the air purge valve, see Components: Indoor unit.
4 Fill the circuit with water until the manometer indicates a
pressure of ±2.0 bar.
5 Purge as much air as possible from the water circuit.
NOTICE
Q Air in the water circuit can cause malfunctioning of the
backup heater. During filling, it may not be possible to remove all the air from the circuit. Remaining air will be removed through the automatic air purge valves during the initial operating hours of the system. Additional filling with water afterwards may be required.
Q To purge the system, use the special function as
described in To perform an air purge. This function should be used to purge the heat exchanger coil of the domestic hot water tank.
7.4 Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
INFORMATION
More information about the legend and the location of the wiring diagram of the unit can be found in Wiring diagram.
7.4.1 About electrical compliance
Only for ERLQ006CAV3+ERLQ008CAV3
Equipment complying with EN/IEC 61000-3-12 (European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low­voltage systems with input current >16 A and ≤75 A per phase.).
Only for indoor units
See To connect the backup heater power supply.
6 Close the fill valve. 7 Disconnect the water supply hose from the fill valve.
NOTICE
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure shall remain above 1 bar to avoid air entering the circuit.
7.3.4 To fill the domestic hot water tank
1 Open every hot water tap in turn to purge air from the system
pipe work.
2 Open the cold water supply valve. 3 Close all water taps after all air is purged. 4 Check for water leaks. 5 Manually operate the field installed pressure relief valve to
ensure that free water flow through the discharge pipe.
7.3.5 To insulate the water piping
The piping in the complete water circuit must be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the sealing materials should be at least 20 mm to prevent condensation on the surface of the sealing.
EHVH/X16 Daikin Altherma - Low Temperature Split 4P313777-1 – 2012.05
Installer reference guide
24
7 Installation
X1M
123
123
X2M
X5M
X6YB
X6YA
X6Y
X1A X19A
30 31
a
7.4.2 To connect the electrical wiring on the indoor unit
1 To open the indoor unit, see To open the indoor unit. 2 Wiring should enter the unit from the top:
a b+c
Routing Possible cables (depending on unit type and installed options)
a Low voltage
b High voltage power supply
c High voltage control signal
Q User interface Q Power consumption digital inputs (field supply) Q Outdoor ambient temperature sensor (option) Q Indoor ambient temperature sensor (option) Q Electrical meters (field supply)
Q Interconnection cable Q Normal kWh rate power supply Q Preferential kWh rate power supply Q Power supply for backup heater Q Power supply for bottom plate heater (option)
Q Preferential power supply contact Q Heat pump convector (option) Q Room thermostat (option) Q Shut-off valve (field supply) Q Domestic hot water pump (field supply) Q Alarm output Q Changeover to external heat source control Q Space cool/heat operation control
3 Routing of the wiring inside the unit should be as follows:
a b+c
4 Fix the cable with cable ties to the cable tie mountings to ensure
strain relief and to make sure that it does NOT come in contact with the piping and sharp edges.
CAUTION
Do NOT push or place redundant cable length in the unit.
7.4.3 To connect the main power supply
1 Connect the main power supply.
In case of normal kWh rate power supply
Installer reference guide
25
Daikin Altherma - Low Temperature Split
4P313777-1 – 2012.05
EHVH/X16
Loading...
+ 58 hidden pages