These instructions are the >> translation of the
original version << in your language.
All the activities required for operation and
setting the parameters are described in this instruction manual. All parameters needed for
trouble-free operation have been configured at
the factory.
● Please read through this manual carefully
before operating the heating system or before
adjusting the settings for it.
● Make a note of the preset values before you
make any changes to the unit configuration.
Relevant documents
– Daikin Altherma M ECH
O:
2
– Installation and maintenance instructions
– Operating instructions for the user/owner
– Commissioning checklist
– the operating manual for the user/owner
– Outdoor unit for Daikin Altherma M ECH
2
O:
the respective installation and operating
instructions.
– On connection of a Daikin solar system: the
respective installation and operating instructions.
– On connection of a Daikin FWXV-ATV3: the
respective installation and operating instructions.
– For connecting to another Daikin heat gener-
ator or optional accessories: the associated
installation and operating instructions.
1.2 Warning signs and explanation of
symbols
1.2.1 Meaning of the warnings
Warnings in this manual are classified according
into their severity and probability of occurrence.
DANGER!
Draws attention to imminent danger.
Disregarding this warning can lead to serious
injury or death.
WARNING!
Indicates a potentially dangerous situation.
Disregarding this warning may result in serious
physical injury or death.
CAUTION!
Indicates a situation which may cause possible
damage.
Disregarding this warning may cause damage
to property and the environment.
This symbol identifies user tips and particularly useful information, but not
warnings or hazards.
The guides are included in the scope of supply
for the individual units.
Operating instructions
4
Special warning signs
Some types of danger are represented by
special symbols:
Electric current
Risk of burning or scalding
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
1.2.2 Validity
1 x Safety
Some information in this manual has limited validity. The validity is highlighted by a symbol.
Only valid for Daikin Altherma M ECH2O
with cooling function
Only valid/available with a connected
room station (EHS157034)
Only valid/available with a connected
mixer module (EHS157068)
1.2.3 Handling instructions
● Handling instructions are shown as a list.
Actions for which the sequential order must be
maintained are numbered.
Results of actions are identified with an
arrow.
Display readouts of the RoCon controller
Entry into a setting procedure
Exit from a setting procedure
Certain screen displays or menu items may deviate from those shown in these instructions depending on the national or equipment variant of
the Daikin Altherma M ECH
O or the user status
2
logged onto the controller.
1.3 Avoiding danger
WARNING!
This equipment must only be used by children
aged 8 and above and by persons with restricted physical, sensory or mental capabilities
or with a lack of experience and knowledge, if
they are under supervision or if they have been
instructed in the safe use of the equipment and
understand the dangers arising therefrom.
Children must not play with the equipment.
Cleaning or user maintenance must not be
carried out by children without supervision.
1.4 Use as intended
The RoCon mb controller must only be used in
Daikin Altherma M ECH
O heat pumps that are
2
approved for the Daikin RoCon regulating
system. The Daikin RoCon mb must only be operated as per the data in these instructions.
Any other use outside the intended use is considered as improper. The operator alone shall
bear responsibility for any resulting damage.
For any work on the equipment, which extends
above and beyond the operation of the regulating system, you must observe the details provided in the supplementary documents, particularly with regard to safety instructions.
The Daikin Altherma M ECH
O is built according
2
to the state-of-the-art and the recognised technical rules. However, improper use may result in
serious physical injuries or death, as well as
property damage.
To avoid hazards, only operate the Daikin
Altherma M ECH
O:
2
– as stipulated and in perfect condition,
– with an awareness of safety and the hazards
involved.
This assumes knowledge and use of the contents of this manual, of the relevant accident prevention regulations as well as the recognised
safety-related and occupational health rules.
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
5
2 x Product description
2Product description
The RoCon mb controller is part of the Daikin
Altherma M ECH
O.
2
It consists of the RoCon BM1 printed circuit board, to
which the actuators, sensors and further components of the
Daikin RoCon regulating system are connected, and the
RoConB1 control panel.
In this instruction manual we explain just the functions and
setting possibilities of the control unit. More detailed information
on the Daikin Altherma M ECH
O and other device components
2
can be found in the other applicable documents.
Depending on heater unit, the electronic, digital controller automatically regulates all heating, cooling and hot water functions for
a direct heating circuit, a storage tank charging circuit and, via
mixer modules that can be optionally connected, also further
heating circuits.
It undertakes all safety management for the Daikin Altherma M
ECH
O. This executes a safety switch-off in the event of a water
2
shortage or undefined operating states. A corresponding error
message shows the operator all the information for fault causes.
All function settings for the Daikin Altherma M ECH
O and the
2
optional RoCon devices that are connected via the data bus are
undertaken with the controls of the integrated RoCon B1 control
panel and shown on the plain text display with coloured backlighting.
The following additional, optional devices can be connected to
the Daikin Altherma M ECH
The RoCon mb control unit contains a timer which can be used
to set:
– 2 individual adjustable switching time programs
heating and room cooling
(direct heating circuit),
2)
for room
– 2 individually-adjustable timer programs for hot water gener-
ation,
– 1 individually-adjustable timer program for an optional circu-
lation pump.
2) Use of the switching time programs for room cooling only in combination with a
connected room thermostat
Initial commissioning of the heating system is described in the installation instructions for the Daikin Altherma M ECH
O.
2
Certain menu items of the RoCon mb control unit are only accessible for the heating expert. This security measure ensures that
no undesirable malfunctions arise during operation of the system
through incorrect settings.
The EHS157034 room station has the same user interface as the
Daikin Altherma M ECH
O's integrated RoCon B1 control panel.
2
All settings for the allocated heating circuit can be carried out in
the same way as the operating unit. With activated terminal
function, all operating possibilities that are available on the integrated operating unit are available, with the exception of certain
special functions (e.g. Manual Operation).
After corresponding assignment, a connected EHS157068 mixer
module is also operated using the RoCon B1 control panel and/or
the EHS157034 room station.
In addition, the RoCon mb controller has a frost protection
function for the direct heating circuit and the storage tank
charging circuit as well as an automatic function for heating
support (integration of an additional heat source such as a woodburning boiler or solar system).
The potential-free AUX switching contact can be used to carry out
different control functions in conjunction with external devices
(demand from an external heat generator, switching to bivalent
operating mode, external status display, etc.).
Several inputs for evaluating external control contacts are also
available (external operating mode switching or heat request,
Smart Grid and off-peak EVU functions
1) Utility company (EVU) outputs signals that are used to control power grid capacity utilisation and influence the electricity price and availability.
1)
.
With the optional EKRSC1 outside temperature sensor that is installed on the north side of the building, weather-dependent T-HS
control can be further optimised.
If the optional EHS157056 gateway is installed and connected to
the Internet, the Daikin Altherma M ECH
O can be conveniently
2
monitored and operated by remote control using a mobile phone
(app).
Operating instructions
6
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3Operation
3 x Operation
3.1General
DANGER!
If electrical components come into contact with
water, this can cause an electric shock as well
as cause potentially fatal burns or injuries.
● The displays and the keys of the control unit
must be protected against the effects of
moisture.
● To clean the control unit, use a dry cotton
cloth. Using aggressive cleaning agents
and other fluids can cause damage to
devices or lead to an electric shock.
Maximum energy exploitation
The Daikin Altherma M ECH2O makes the most effective use of energy at the lowest possible return and
target hot water temperature.
If an external heat generator (e.g. the optional backup heater)
is activated at target feed temperatures over 50 °C, the efficiency (COP) of the Daikin Altherma M ECH
(depending on the outside temperature).
O can deteriorate
2
3.2.1 Display
All operating steps are supported by corresponding displays on a
coloured backlit plain text display.
The menu guidance can be displayed 7 languages (see
chap. 3.4.8).
Malfunctions are generally indicated by a fault code and
a clear text fault message on the display.
For troubleshooting instructions, see Chapter 7.
The colour of the backlighting indicates the operational status
and the operating mode:
White:Standard lighting, normal operating display.
Red:Fault status; depending on the type of fault, the
Daikin Altherma M ECH
restrictions.
Green:Operating mode with operator authorisation.
Blue:Operating mode with expert authorisation.
O continues to operate with
2
3.2Display and operating elements
1Clear text display
2Setting: Configuration
3Setting: Remote Param
4Rotary switch
5Setting: Info
6Setting: Operating Mode
Fig. 3-1 Arrangement of display and operating elements
7Setting: Set Temp Day
8Setting: Set Temp Night
9Setting: DHW Set Temp
10Rotary button
11Setting: DHW Install
12Setting: Time Program
13Exit key
1Display date
2Refrigerant compressor
status
3Status display (e.g. techni-
cian access rights active)
4Display time
5Current feed temperature
6Heating circuit status
Fig. 3-2 Display of the control unit - standard display
7Current outside temperature
8Active operating mode
9Hot water generation status
10Current storage temperature
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
7
3 x Operation
Explanation of symbols
Item
fig. 3-2
2
2
3
2 / 3
2 / 3
2 / 3
2 / 3
2 / 3
2 / 3
2 / 3
2 / 3
5
5
5
6Heating circuit status
7External temperature sensor
IconExplanation
Flashing: heat pump request active
Permanently on: refrigerant compressor operating
No connection to the heat pump outdoor
unit
Expert access rights active (see
chap. 3.6.1)
Air purge active (see chap. 3.6.10)
Terminal function active (see chap. 3.4.9)
Frost protection function active (see
chap. 3.6.5)
Temporary time program "Party" active (see
chap. 3.4.7)
Temporary time program "Away" active
(see chap. 3.4.7)
Temporary time program "Holiday" active
(see chap. 3.4.7)
Temporary time program "Vacation" active
(see chap. 3.4.7)
Screed program active (see chap. 3.6.13)
Direct heating circuit
The current feed temperature t
played beneath this.
Mixer circuit
The current T-HS of the assigned heating
circuit is displayed underneath.
Room temperature sensor
The current room temperature is displayed
underneath.
– Heating circuit active (room heating
function)
– Heating circuit active (room cooling
function)
– Heating circuit not active (currently no
thermal transport in the heating circuit)
The current outside temperature is displayed underneath.
V, BH
is dis-
Item
fig. 3-2
8Current operating mode (see chap. 3.4.2)
9
10
Tab. 3-1 Explanation of display symbols
IconExplanation
Standby active
Reducing active
Heating active
Cooling active
Summer active
Automatic 1 active
Automatic 2 active
Hot water generation active
Hot water generation not active
Hot water heating circuit status
The current storage tank temperature t
is displayed beneath this.
DHW
3.2.2 Controls
CAUTION!
Never operate the operating elements of the
control unit with a hard, pointed object. This can
cause damage and can cause the control to
malfunction.
If special key combinations or long key presses are required for
certain functions, these are referred to separately in the respective section of this manual.
Rotary switch
Frequently required functions and setting options can be quickly
and directly selected using the rotary switch (main function level).
Irrespective of the rotary switch position, the Daikin
Altherma M ECH
ating mode which has been set in the "Operating Mode"
program.
ActionResult
Turning
O operates according to the oper-
2
switch position or activated by a special
Operating instructions
8
Direct selection of the main function level
assigned to this switch position.
Tab. 3-2 Function of the rotary switch
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3 x Operation
Rotary button
The rotary button can be used to navigate in the respective level,
to select or change the setting value and to accept this change
with a short key press.
This key can be used to jump back to the previous display within
a menu item or to cancel a function/input.
The special level can also be called up using this key (see
chap. 3.5).
ActionResult
Touch briefly.
Press for longer
than 5 seconds.
Tab. 3-4 Functions of the Exit key
– Return to the previous display or the pre-
vious level or
– cancel a special function or an active,
temporary time program.
– A special level is called up.
3.3Operating concept
The operating concept of the RoCon mb control unit is designed
so that frequently required setting options can be accessed
quickly and directly at the main function level (selection by
means of rotary switch) and less frequently required setting options are arranged on a lower lying parameter level.
1Info (chap. 3.4.1)
2Operating Mode (chap. 3.4.2)
3Set Temp Day (chap. 3.4.3)
4Set Temp Night (chap. 3.4.4)
5DHW Set Temp (chap. 3.4.5)
6DHW Install (chap. 3.4.6)
7Time Program (Chap. 3.4.7)
8Configuration (Chap. 3.4.8)
9Remote Param (Chap. 3.4.9)
Fig. 3-3 Illustration of the main function level (rotary switch position)
Certain functions and parameters are restricted by access rights
and can only be configured by a heating expert (see chap. 3.6.1).
In normal operation, the rotary switch should be in the position.
After switching on and successful initialisation, the standard
display automatically shows the display for the rotary switch
setting
During initial start-up, the setting for the language selection is first
displayed.
● Select the language with the rotary button.
● Confirm the selection with a brief push of the rotary button.
.
Adaptations to the special system configuration are
made in the "Configuration"
rotary switch setting
(see chap. 3.4.8).
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
If the system is switched on, the defaults set in the RoCon mb
control unit fully automatically control the operation of the
– room heating, room cooling and
– hot water generation plumbing.
Irrespective of the rotary switch position, the Daikin
Altherma M ECH
O operates according to the oper-
2
ating mode which has been set in the "Operating Mode"
switch position or activated by a special
program.
If the user sets a value manually, this setting remains active until
the user changes it or until the timer program forces a different
mode of operation.
Operating instructions
9
3 x Operation
The operating modes can be affected by additional functions
such as:
– Weather-dependent T-HS control
– Switching time program
– Setting the temperature target value
– Setting on the room station
– Setting on the room thermostat
– Switch status on the EXT input (external operating mode
changeover)
– Switch status at the EBA input (external requirement request)
– Whisper mode
– Interlink function
– Switch status at the Smart Grid input (EVU function
Smart Grid)
– Switch status at the EVU input (EVU function HT/NT (off-
peak) or Smart Grid)
– Defrost function
– Frost protection function
– Screed function
– Air purge
– Manual operation
– EHS emergency operation
Keylock
The control panel of the RoCon mb can be locked against inadvertent operation (see fig. 3-4).
It is unlocked in the same way.
Precondition for this function is that the [Keylock Function] parameter at the "Setup" level is set to "On" (see chap. 6.2.1,
tab. 6-1).
Keylock Function
On
Keylock Function
3.4Basic functions and operating modes
If the storage tank temperature falls below specific
minimum values, the Daikin Altherma M ECH
safety settings prevent the heat pump from being
operated at low outside temperatures:
– Outside temperature < -2 °C, minimum storage tank
temperature = 30 °C
– Outside temperature < 12 °C, minimum storage tank
temperature = 23 °C.
Without backup heater:
The storage tank water must be heated to the required
minimum storage tank temperature with an external heater
booster.
With backup heater (EKBUxx):
At an outside temperature of < 12 °C and a storage tank temperature of < 35 °C, the backup heater (EKBUxx) is automatically switched on to heat the storage tank water to at least
35 °C.
● To speed up the heating process with backup heater,
temporarily set
– parameter [Function Heating Rod] = "1" and
– parameter [Power DHW] to the maximum value of the
backup heater.
– Set the rotary switch to
operating mode, and set the
parameter [1x Hot Water] to "On".
Automatic defrost function
At low outdoor temperatures and corresponding humidity, the
heat pump outdoor unit may ice up. This icing impairs efficient operation. The system detects this status automatically and starts
the defrost function.
While the defrost function is active, heat is drawn from the hot
water storage tank, and the backup heater is activated if necessary. Depending on the heat required for the defrost function,
heating the direct heating circuit may be temporarily interrupted
during the defrosting process.
After a maximum of 8 minutes, the system switches back to
normal operation.
2
O's
Keylock Function
Fig. 3-4 Activating (1.) and deactivating (4.) the key lock
Operating instructions
10
Off
3.4.1 System information (Info)
In this rotary switch position, the rotary button can be used to
query all system temperatures, the Daikin Altherma M ECH
O
2
type, various software information and the operating states of all
system components in succession. The number of displayed parameters depends on which components are connected.
No adjustments can be made to these values.
● Set the rotary switch to the "Info"
position.
Standard display is shown (see fig. 3-2).
● Press the rotary button briefly.
Parameter overview is displayed.
● Use the rotary button to select the desired information level.
● Confirm the selection with a brief push of the rotary button.
Value is displayed (example, see fig. 3-6).
● Use the rotary button to select the individual information.
Further explanations on, and possible display values for, this rotary switch position
can be found in tab. 3-5 and chap. 6.10.
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3 x Operation
Displaying the operating data overview
On the "Overview" information level, the RoCon mb controller's
display shows the current operating data for the Daikin
Altherma M ECH
The display of the operating data is split over several screen
pages. Adjust the rotary button to navigate between the screen
pages.
Short des-
ignation
Mode Current heat pump mode:
ExtCurrent heat pump energy mode:
Page 1
RTParameter [Room thermostat] / [Interlink fct]
Pump Current status of the internal heating circulation
VActual flow rate in the heating system
EHSCurrent output of the backup heater in kW
TVCurrent feed temperature downstream of the plate
TVBH Current heating feed temperature, poss. down-
TRCurrent temperature of heating return (t
Page 2
Tdhw Current temperature in the hot water storage tank
TACurrent outside temperature (measured by the
Psyst Current water-side pressure in the heating system
O.
2
Explanation of the display value
- - -: No heat or cooling request
: Heating
: Cooling
: Hot water generation
: Automatic defrost function active
LT: EVU function HT/NT active and off-peak.
HT: EVU function HT/NT active and peak.
SGN: EVU function Smart Grid active, normal
operation.
SG1: EVU function Smart Grid active, shut-off: no
heat pump operation, no frost protection function.
SG2: EVU function Smart Grid active, switch-on
recommendation, operation at higher target
temperatures, inexpensive electricity.
SG3: EVU function Smart Grid active, switch-on
command and storage tank charging to 70 °C,
inexpensive electricity
- - -: No external mode active, heat pump operates
in standard mode.
= Off: - - -
Parameter [Room thermostat] = On:
–: Heat or cooling request
–
: No heat requirement
Parameter [Interlink fct] = On (priority):
– - - -: Frost protection only
– IL1: Normal target feed temperature
– IL2:
– In heating mode, increased target feed
temperature
– In cooling mode, reduced target feed tem-
perature
pump
heat exchanger (t
V1
)
stream of the heating support heat exchanger
(t
)
V, BH
)
R1
)
(t
DHW
heat pump outdoor unit temperature sensor)
Short des-
Explanation of the display value
ignation
BPVCurrent position of mixing valve 3UVB1
(100% = A, 0% = B)
3UVD Current position of mixing valve 3UV DHW
(100% = B, 0% = A)
TA2Current outside temperature (measured by the op-
Page 3
Tliq2Current refrigerant temperature (t
tional outside temperature sensor EKRSC1)
)
L2
quietIndicates the whisper mode status
Glycol Glycol present: 0 (No) / 1 (Yes)
Tab. 3-5 Explanation of the operating data displayed as an overview
Info
Overview
Water Pressure
Mode:
Ext:
RT:
TV:
TVBH:
TR:
BPV:
3UVD:
TA2:
Fig. 3-5 Displaying the operating data overview
- - -
- - -
44°C
0%
2°C
Pump:
V:
EHS:
Tdhw:
TA:
Psyst:
Tliq2:
quiet:
Glycol:
On
1205 l/h
3 kW
48°C42°C
1°C
1,9 bar36°C
46°C0%
On
0
At low return flow temperatures and with glycol in the
system, only "ffff" is displayed as the volumetric flow, no
current value.
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
11
3 x Operation
Displaying the water pressure
On the RoCon mb control unit, the system pressure (water
pressure) of the internal circuit (direct heating circuit) can be displayed when it is switched on. The water pressure is the first info
parameter available after the operating data overview (see
fig. 3-6).
The permissible water pressure range during operation is dependent on the Daikin Altherma M ECH
system. The target values and thresholds may only be set by the
heating expert. If the water pressure drops below the minimum
value (set parameter value), it must be increased by topping up
the system (see Daikin Altherma M ECH
tions, chapter entitled "Inspection and maintenance").
The pressure limits for safety shut-off and the target
pressure can be set in the parameter setting on the
"System Configuration" level.
O and the heating
2
O installation instruc-
2
3.4.2 Setting the operating mode
The operating mode in which the Daikin Altherma M ECH2O is to
operate is selected using the rotary switch in the "Operating Mode"
The selected operating mode is activated by briefly pressing the
rotary button.
Operating Mode
Standby
Reducing
position.
Operating Mode
Heating
Cooling
Summer
Operating Mode
Summer
Automatic 1
Automatic 2
Info
Overview
Water Pressure
T-HS
Water Pressure
Fig. 3-6 Displaying info values (e.g. system pressure)
Operating Mode
Summer
Automatic 1
Automatic 2
Fig. 3-7 Changing the operating mode
(e.g. from "Standby" to "Automatic 1")
● Set the rotary switch to the "Operating Mode"
position.
An overview is displayed.
● Use the rotary button to select the required operating mode.
● Confirm the selection with a brief push of the rotary button.
Daikin Altherma M ECH
O operates according to the set
2
operating mode.
The current operating mode is indicated by an appropriate
symbol on the standard display.
Operating mode Standby (Stand-by)
CAUTION!
A heating system that is not protected against
frost can freeze in the event of frost and thus be
damaged.
Operating instructions
12
● Add glycol to the heating water circuit (see
installation and maintenance instructions)
● Alternatively, drain the heating system on the
water side if there is a danger of frost.
● If the heating system is not drained, the
power supply must be ensured and the
external main switch must remain switched
on if there is a danger of frost.
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3 x Operation
In this operating mode, the Daikin Altherma M ECH2O is
switched to Stand-by mode. The frost protection function (see
chap. 3.6.5) is maintained. In order to maintain this function, the
system may not be disconnected from the mains.
All controllers integrated in the RoCon system via the CAN bus
are primarily also switched to the "Standby" operating mode.
Fig. 3-8 Standard display in the "Standby" operating mode
(above the frost limit temperature)
Operating mode Reducing
Reduced heating mode (lower target room temperature) according to the target feed temperature set for reducing mode in
the parameter [T-Reduced] (see chap. 3.4.4).
Hot water preparation according to the set target hot water temperatures and switching cycles in the hot water time program
[DHW Program 1] (see chap. 3.4.5).
Heating, Cooling
Heating, cooling mode according to the target room temperature
set in the parameter [T-Room 1 Setpoint] (see chap. 3.4.3).
A connected outside temperature sensor (weather-dependent THS control) or a connected room station also influence the target
feed temperature (prerequisite: parameter [HC Function] = On).
Hot water preparation according to the set target hot water temperatures and switching cycles in the hot water time program
[DHW Program 1] (see chap. 3.4.5).
Operating mode Summer
Hot water preparation according to the set target hot water temperatures and switching cycles in the hot water time program
[DHW Program 1] (see chap. 3.4.5).
All controllers integrated in the RoCon system via the CAN bus
are primarily also switched to the "Summer" operating mode.
Operating mode Automatic 1 (time program)
Automatic heating and setback mode according to the permanent
time programs (see chap. 3.4.7):
– [HC Program 1]
– [DHW Program 1]
Operating mode Automatic 2 (time program)
Automatic heating and setback mode according to the permanent
time programs (see chap. 3.4.7):
– [HC Program 2]
– [DHW Program 2]
If the hot water readiness is in setback mode in the
active operating mode,
heating" can be set with the rotary switch setting
without having to change other standard settings (see
chap. 3.4.6).
a temporary "DHW Re-
Switching contact for external operating mode
switch-over
A potential-free switching contact connected via Daikin
Altherma M ECH2O connection J8 at the "EXT" terminals and
wired with a resistor can also be used to switch the operating
mode from an external device (e.g. modem, …).
In this case, the switching contact functionality is dependent on
the parameter [Function BSC]:
– [Function BSC] = 0 (default setting): evaluation of the resist-
ance values (see tab. 3-6)
– [Function BSC] = 1: evaluation as a burner blocking contact.
If the switching contact is closed, the external heat generator
has priority.
Operating mode ResistanceTolerance
Standby< 680 Ω
Heating1200 Ω
Reducing1800 Ω
Summer2700 Ω
± 5 %
Automatic 14700 Ω
Automatic 28200 Ω
Tab. 3-6 Resistance values for evaluating the EXT signal
The resistances specified in tab. 3-6 function in a toler-
ance field of 5%. Resistances outside this tolerance
field are interpreted as an open input. The heat gener-
ator switches back to the previously active operating
mode.
The input is not considered for resistance values greater than
the value for "Automatic 2".
If several switching contacts are to be connected to the Daikin
Altherma M ECH
O (e.g. Smart Grid, room thermostat), the re-
2
lated functions may have a higher priority than external operating mode switch-over. The operating mode requested by the
EXT switching contact is then possibly not activated, or is only
activated later.
Besides these operating modes, different temporary heating programs (see tab. 3-7) are available that are carried out with priority
after activation.
Temporary
time program
DHW InstallDHW Install
Party
Away
Holiday
Setting/Activa-
tion in the level
Time Program
Rotary switch
setting
Information
Chap. 3.4.6
Chap. 3.4.7
Vacation
Configuration >
Screed*
HC Configura-
Chap. 3.6.13
tion
* only with technician code.
Tab. 3-7 Overview of temporary time programs
If a temporary time program (DHW Install, Party, Away,
Holiday, Vacation, Screed) is started during the se-
lected operating mode, control is carried out primarily
according to the settings for this time program.
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
13
3 x Operation
3.4.3 Temperature setting of daytime room
temperature
In rotary switch position , the target room temperatures during
the day for room heating are defined.
● Set the rotary switch to the "Set Temp Day" position.
An overview is displayed.
The last digits of the parameter designations (1 - 3)
within this rotary switch setting mark the affiliation to
the respective cycle of the time program.
● Select the temperature block to be set with the rotary button.
● Confirm the selection with a brief push of the rotary button.
Settings are displayed.
● Set the temperature.
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
Detailed explanations and possible setting values for this rotary switch setting can
be found in chap. 6.5.
3.4.4 Temperature setting of setback mode
In rotary switch position , the target room temperatures in reducing mode for room heating are defined.
● Set the rotary switch to the "Set Temp Night" position.
An overview is displayed.
● Select the parameter to be set with the rotary button.
● Confirm the selection with a brief push of the rotary button.
– [T-Reduced]: Setting value for "Reducing" operating
mode or reduction through permanent time program.
– [T-Absence]: Setting value for temporary heating/cooling
programs ("Away" and "Vacation").
Settings are displayed.
● Set the temperature.
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
Detailed explanations and possible setting values for this rotary switch setting can
be found in chap. 6.6.
3.4.5 Temperature setting of hot water generation
In rotary switch position , the target hot water temperatures
for hot water preparation for the respective time programs are defined.
● Set the rotary switch to the "DHW Set Temp"
position.
The last digits of the parameter designations (1 - 3)
within this rotary switch setting mark the affiliation to
the respective cycle of the time program.
● Select the temperature block to be set with the rotary button.
● Confirm the selection with a brief push of the rotary button.
Settings are displayed.
● Set the temperature.
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
Detailed explanations and possible setting values for this rotary switch setting can
be found in chap. 6.7.
3.4.6 Unscheduled hot water preparation
In rotary switch position the hot water can be recharged
manually, outside of a hot water time program, to the target temperature set as default in the parameter [T-DHW Setpoint 1]. The
heating up is carried out with priority and independent of other
heating programs.
● Set the rotary switch to the "DHW Install"
position.
An overview is displayed.
● Select the parameter to be set with the rotary button.
– [1x Hot Water]: Activation of one-time hot water genera-
tion.
● Confirm the selection with a brief push of the rotary button.
● Set the parameter.
● Confirm the selection with a brief push of the rotary button.
The unscheduled hot water generation starts.
After this temporary function has elapsed, the control
unit automatically jumps back to the previously active
operating mode. The rotary switch should therefore be
brought back into the "Info"
position after the
function has been activated.
The function is subject to time limitations.
At the latest, it is cancelled after the maximum loading time set
in the parameter [Max DHW loading time], and can be restarted
at the earliest after the blocking time set in the parameter [DHW
Off Time] has expired (see chap. 6.2.4).
Detailed explanations and possible setting values for this rotary switch setting can
be found in chap. 6.3.
3.4.7 Switching time program
For comfortable and individual room and hot water temperature
control, different (but freely adjustable) time programs preset at
the factory can be selected.
The switching time programs control the assigned heating circuit,
the storage charging circuit as well as an optionally connected
circulation pump according to the specified switching times.
Setting
In the rotary switch setting, the time intervals for the
heating circuit, integrated hot water generation and the optional
circulation pump are set.
● Set the rotary switch to the "Time Program"
position.
An overview is displayed.
● Use the rotary button to select the time program to be set.
● Confirm the selection with a brief push of the rotary button.
Settings are displayed.
● Use the rotary button to select and change the value to be
adjusted.
● Confirm the selection with a brief push of the rotary button.
More detailed explanations and possible setting values for this rotary switch position
can be found in chap. 6.8.
Operating instructions
14
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3 x Operation
Permanent time programs
Time programs control the heating circuit temperatures or the operating times of the circulation pump according to the specified
switching cycles for the connected heating circuits and the
storage charging circuit. The switching cycles are saved in time
blocks for which different target temperatures can be set.
In the switching cycles, the heating system is controlled differently according to day and reducing mode.
The target temperatures for these time programs are set in the
rotary switch positions "Set Temp Day"
and "DHW Set Temp".
The following switching time programs are available:
– 2 time programs for the heating circuit, each with 3 possi-
ble switching cycles
– [HC Program 1]
– [HC Program 2]
The times can be entered separately for each individual
weekday or in blocks of "Monday to Friday", "Saturday
to Sunday" and "Monday to Sunday".
ProgramTime periodSwitching cycle
HC Program 1
HC Program 2
Tab. 3-8 Menu structure of heating circuit/time program
Individual weekday
(Monday, Tuesday …)
Working week
(Monday to Friday)
Weekend
(Saturday to Sunday)
Whole week
(Monday to Sunday)
See
HC Program 1
, "Set Temp Night"
1.
06:00 -> 22:00
2.
--:-- -> --:--
3.
--:-- -> --:--
1.
06:00 -> 22:00
2.
--:-- -> --:--
3.
--:-- -> --:--
1.
07:00 -> 23:00
2.
--:-- -> --:--
3.
--:-- -> --:--
1.
06:00 -> 22:00
2.
--:-- -> --:--
3.
--:-- -> --:--
1.
2.
3.
See
HC Program 1
Time settings for a switching cycle in a weekday or
block program will also be accepted for other time periods as long as they are for the same weekdays. Examples referring to tab. 3-8:
a) The starting time in the 1st switching cycle is changed from
06:00 am to 05:00 am for the individual weekday "Monday".
The 1st switching cycle is also automatically changed
from 06:00 am to 05:00 am for the "working week" and
"whole week" time periods.
b) The starting time in the 1st switching cycle is changed from
07:00 am to 08:00 am for the "weekend" time period.
The 1st switching cycle is also automatically changed
from 07:00 am to 08:00 am for the individual weekdays
"Saturday" and "Sunday".
c) The end time in the 1st switching cycle is changed from
10:00 pm to 9:30 pm for the "whole week" time period.
The 1st switching cycle is also automatically changed
from 10:00 pm to 9:30 pm in all weekday or block programs.
– 2 time programs for the hot water circuit, each with 3 pos-
sible switching cycles
– [DHW Program 1]
– [DHW Program 2]
The setting and the entry structure of the time programs
are identical with those for the heating circuit time
program (see also tab. 3-8).
– 1 time program for an optionally connected circulation
pump, each with 3 possible switching cycles
– [Circulation Time]
The setting and the entry structure of the time program
are identical with those for the heating circuit time program (see also tab. 3-8).
For further information on settings for an optional circulation
pump, see chap. 3.6.15.
Saved switching time programs can be changed at any time. For
a better overview, it is recommended to write down and safely
store the programmed switching cycles (see chap. 9.1.1).
The permanent time programs are preset according to tab. 3-9.
Tab. 3-9 Factory setting of the permanent switching time programs
Temporary time programs
4 temporary time programs are available for special situations,
which make the permanent time programs or the currently set
operating mode ineffective for the duration of their validity.
The symbol of the temporary time program is displayed in the
header of the standard display for as long as the time program is
active.
The following temporary time programs can be cancelled at any time due to the manual changing of the
operating mode.
1.
2.
[Party]: Immediate one-off extension of room heating.
a) If an automatic program is activated, the last valid
switching cycle is always extended. In the time prior to
switching cycle 1, control is carried out according to the
target room temperature set in the parameter [T-Room 1
Setpoint].
b) In all other operating modes, control is carried out accord-
ing to the target room temperature set in the parameter [T-
Room 1 Setpoint].
– The hot water generation is not affected.
– The time program runs for the set time period from activa-
tion.
[Away]: Immediate one-time setback up to 6 hours.
– In reducing mode, control is carried out according to the
target room temperature set in the "Set Temp Night"
rotary switch position in the parameter [T-Absence].
– The hot water generation is not affected.
– The time program runs for the set time period from activa-
tion.
3.
[Holiday]: One-time calendar-controlled presence.
– Control is carried out only according to the settings for
"Sunday" in the [HC Program 1].
– The hot water generation is only controlled according to
the settings for "Sunday" in the [DHW Program 1].
4.
[Vacation]: One-time calendar-controlled setback.
– In reducing mode, control is carried out exclusively
according to the target room temperature set in the "Set Temp Night"
rotary switch position in the parameter
[T-Absence].
– Hot water generation according to the set target tempera-
tures and switching cycles in the [DHW Program 1] hot
water time program (see chap. 3.4.5).
– The calendar-controlled [Vacation] program is not
started if the "Standby" or "Manual Operation" operating
mode is active on the set start date.
Operating instructions
16
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3 x Operation
3.4.8 System settings
In the "Configuration" rotary switch position, basic setting
of the RoCon mb controller and system configuration for the
installation environment of the Daikin Altherma M ECH
O, the
2
direct heating circuit, hot water preparation and any optionally
connected components are carried out.
Depending on the access authorisation (user or expert), different
parameters are available. Several parameters can only be accessed by the heating expert.
Setting the LCD display, language, date, time
An internally pre-programmed calendar ensures an automatic timeshift for the annually repeating summertime/wintertime changeover dates.
● Set the rotary switch to the "Configuration"
position.
An overview is displayed.
● Use the rotary button to select the "Setup" level.
An overview is displayed.
● With the rotary button, select the parameters [LCD
Brightness] and [LCD Illum Time], and change them if
desired.
● With the rotary button, select and confirm the parameters
[Language], [Date] or [Time].
● Use the rotary button to select and change the value to be
changed within the respective display.
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
Detailed explanations and possible setting values of this rotary switch setting can be
found in chap. 3.6 and in chap. 6.2.
The different application and parametrisation options for the use
of the devices and control units in the RoCon system connected
via the CAN bus are described in chap. 4.3.
Remote Param
Bus - Scan
No selection
Remote Param
Contr BM1/BE1 #X
Mix Valve #X
3.4.9 Terminal function
In the "Remote Param" rotary switch setting, other devices
(mixer module control unit or heat generator control components)
integrated in the RoCon system via the CAN bus can also be operated and parametrised as long as the respective control unit
has the required authorisation (see also chap. 4.3).
A list of the recognised devices
is displayed for selection on the
display after activation of the
"Bus - Scan" (external devices
and local device).
After selection and confirmation of an external device,
the terminal function for this
device is activated and the associated standard display for
this device is shown on the
display.
The operating component is
then in terminal operation.
The local control unit functions as a remote control for the external device. In this case, all the control functions are performed
and saved 1:1 as on the external device.
Remote Param
Bus - Scan
No selection
Fig. 3-9 Display of the "Remote
Param" level during
commissioning or after
interim disconnection
from the mains
Remote Param
Bus - Scan
No selection
Remote Param
No selection
Contr BM1/BE1 #X
Mix Valve #X
B1RoCon B1 control panel of the Altherma M ECH2O
BusCAN bus (connection line between RoCon devices
and control units)
H
1
H
2
M1EHS157068 mixer module
U1EHS157034 room station
WE1Heat generator Altherma M ECH2O
Fig. 3-10 Example of "Bus - Scan" on a heating system with 1 heat gen-
erator, 1 mix valve, 1 room station and activation of the terminal function for remote control of the mixer module
Remote Param
Contr BM1/BE1 #X
Mix Valve #X
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
17
3 x Operation
If the terminal function is activated, the #X symbol is displayed in the header of the display as additional information on
the remote-controlled device, where "X" is the set device identification of the remote-controlled device.
The displayed values and symbols are always accepted by the
selected device (e.g. mixer circuit T-HS of the EHS157068 mix
valve module with device identification 1).
Fig. 3-11 Example of the display for the remote-controlled mixer module
In order to operate the local device, it must be activated again in
the selection list ([No selection] parameter).
If the "n.A." message is displayed in the rotary switch
setting
the control unit until now.
If the "n.A." message is still displayed, it may be necessary to
update the device software in order to use the terminal function.
Contact the Daikin Service Team for this.
, no valid terminal ID has been assigned to
Activating/deactivating terminal operation
Prerequisite: a valid terminal ID has been assigned to the
RoCon B1 control panel of the Daikin Altherma M ECH
EHS157034 room station.
For setting the terminal ID of optionally connected
devices, see chap. 4.4 or the respective operating
instructions that are supplied.
O or the
2
After an interim disconnection from the power supply,
the display always appears at the "Remote Param"
level, as shown in fig. 3-9.
To be able to use the terminal function for connected devices, a
repeat Bus - Scan must be carried out.
Communication between the RoCon system components also
continues to function without a Bus - Scan, and previously undertaken settings remain active.
The terminal function is activated as shown in fig. 3-10, but after
confirmation of the "Bus - Scan" display, the [New scan?] parameter must be selected with the rotary button and confirmed
with "Yes".
3.4.10 Operation with glycol
Frost can damage the system. To prevent the hydraulic components from freezing, the software is equipped with special frost
protection functions, that include the activation of pump, internal
heaters, and/or backup heater operation in case of low temperatures.
However, in case of a power failure, these functions cannot guarantee protection. It is therefore recommended to add glycol to the
water circuit. To do this, observe the installation and maintenance instructions.
If glycol has been added to the system, the RoCon controller
setting must be adapted accordingly.
● Set the rotary switch to the "Configuration"
position.
An overview is displayed.
● Use the rotary button to select the "Setup" level.
An overview is displayed.
● Use the rotary button to select the [Glycol] parameter.
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
3.4.11 Whisper mode
● Set the rotary switch to the "Remote Param"
position.
The "Remote Param" level is displayed.
● Use the rotary button to select the [Bus - Scan] parameter.
● Confirm the selection with a brief push of the rotary button.
The context menu is displayed.
● Use the rotary button to select the [Bus - Scan] parameter and
confirm with "Yes".
Bus - Scan is performed.
An overview of all the devices found is displayed (for an
example, see fig. 3-10).
● Use the rotary button to select the device for which the
terminal function should be carried out.
● Confirm the selection with a brief push of the rotary button.
The local control unit functions as a remote control for the
external device.
To endterminal operation and to switch back to the control unit
for the operation of the assigned device, the [No selection] pa-
rameter must be selected and confirmed at the "Remote
Param" level.
Operating instructions
18
Whisper mode means that the heat pump outdoor unit operates
at reduced output. This reduces the operating noise generated by
the heat pump outdoor unit.
CAUTION!
During active whisper mode, the output in room
heating and room cooling mode decreases such
that it may no longer be possible to achieve preset target temperature values.
● With outside temperatures below freezing,
there is a risk of material damage caused by
frost.
Activating / deactivating whisper mode
● Set the rotary switch to the "Configuration" position.
An overview is displayed.
● Use the rotary button to select the "System Configuration"
level.
An overview is displayed.
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
3 x Operation
● Use the rotary button to select the [Quite Mode] parameter.
● Confirm the selection with a brief push of the rotary button.
The setting of the parameter is displayed.
● Set the parameter.
– Parameter [Quite Mode] = 0: deactivated
– Parameter [Quite Mode] = 1: permanently activated
– Parameter [Quite Mode] = 2: only activated at night
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
Detailed explanations and possible setting values of this function can be found in
chap. 6.2.2.
3.4.12 Smart Grid (SG)
WARNING!
There is a danger of scalding at target hot water
temperatures over 60 °C. This is possible, as
the utility company (EVU) is entitled to control
current draw optimised according to supply and
demand in the definitions for Smart Grid.
Due to such forced charging, the target hot
water temperature in the hot water storage tank
can exceed 60 °C.
This storage tank charging is carried out even
when "Standby" operating mode is set.
● Install scald protection in the hot water distribution line (e.g. VTA32 + Screw set 1").
A special electricity meter with SG receiver, to which the Daikin
Altherma M ECH
function.
As soon as the function is activated by the parameter [SMART
GRID] = 1, the heat pump is set to an operating mode as per
tab. 3-10 depending on the utility company signal.
2)
Signal
EVUSGDomestic hot
10
00NormalNormal operationNormal operation
01LowSwitch-on recom-
11Very low Switch-on command,
O must be connected, is required to use this
2
Electric-
ity costs
- - -
water
No operation
mendation, and tar-
get storage tank
temperature value is
increased depending
on the parameter
[Mode SG]
and target storage
tank temperature val-
ue is set to 70 °C
Effect on
Heating installa-
1)
No operation
Switch-on recom-
mendation, and target feed temperature
is increased depending on the parameter
[Mode SG]
Switch-on command
for storage tank
tions
charging
1)
3.4.13 EHS emergency operation
If the heat pump fails, the backup heater can be used as emergency heating, and can undertake all heating requirements either
automatically or non-automatically.
Activation of emergency automatic operation ensures
that heating and hot water requirements are reliably
met even if the heat pump fails. However, the risk is run
that the user only notices the system malfunction after
a certain time, and that electricity consumption is thus increased.
If emergency automatic operation is deactivated (default
setting), it must be activated as described below to meet heating
and hot water requirements in the event that the outdoor unit
fails.
● Confirm the selection with a brief push of the rotary button.
Change has been accepted. Jump back to previous dis-
play.
1) No frost protection function (see chap. 3.6.5).
2) Switching contacts at input J8 of the RoCon BM1 printed circuit board closed
(1) or opened (0).
Tab. 3-10 Use of the SG signal
Detailed explanations and possible setting values of this function can be found in
chap. 6.2.1.
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
19
3 x Operation
3.5Special functions
At the "Special Level", different functions (mostly useful functions for the heating expert) can be carried out.
The following special functions are possible:
– Manual operation (see chap. 3.5.1).
– Displaying messages (see chapter 7)
– Reset to factory settings (see chap. 3.6.12)
Detailed explanations of these functions can be found in chap. 6.11.
Special Level
Manual Operation
FA failure
The calling-up of the special functions does not depend
on the rotary switch setting.
● Push the Exit button for at least 5 s.
Menu "Special Level" is displayed.
● Use the rotary button to select the program to be started.
● Confirm the selection with a brief push of the rotary button.
The selected program starts.
● Cancellation and jump back by:
– pressing the Exit key again or
– touching the rotary button or
– selecting another menu using the rotary switch.
3.5.1 Manual operation
Manual operation is used to manually control the Daikin
Altherma M ECH
O to a specific feed temperature. Manual oper-
2
ation should only be used for diagnostic purposes.
With hydraulically controlled priority operation for hot water preparation, it must be ensured that the target feed temperature set in
manual mode is sufficient to achieve the stored target hot water
temperature (parameter [T-DHW Setpoint 1]).
● Push the Exit button for at least 5 s.
Menu "Special Level" is displayed.
● Use the rotary button to select the "Manual Operation"
program.
● Confirm the selection with a brief push of the rotary button.
"Manual Operation" is active.
● Use the rotary button to set the target feed temperature.
Do not confirm this setting with the rotary button,
as the program is otherwise ended.
Manual Operation
Set Point
Special Level
Fig. 3-12 Symbolic brief instructions for manual operation
Current Value
Attention!
Actual mode:
3.5.2 3-way switching valves reference travel
The positions of the two 3-way switch valves 3UVB1 and
3UV DHW in the Daikin Altherma M ECH
tinuously between their two basic settings for optimised energy
utilisation (e.g. heating support function).
To ensure this function, the two 3-way switch valves are always
moved automatically to their basic position (bypass - path AB-A
open) at 11:00 hours.
This function can take up to 5 minutes. It is programmed as
standard and cannot be changed.
O are controlled con-
2
During active manual mode, the storage tank temperature
is permanently regulated to the first target hot water temperature parameter value ([T-DHW Setpoint 1]).
The key lock (if it was activated prior to the start of this
function) is reactivated within 2 s to prevent undesired
cancellation of the function through operation of the
RoCon mb controller.
● Cancellation and jump back by:
– pressing the Exit key again or
– touching the rotary button or
– selecting another menu using the rotary switch.
If manual operation is ended, the RoCon mb control unit
automatically switches to "Standby" operating mode.
Operating instructions
20
Daikin Control unit
008.1446899_00 – 07/2019 – EN
RoCon mb
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.