Carrier TM016-028, 50HJQ004-016, TM004-014, 48-50TJ, 48-50TF User Manual

...
48/50HJ004-024
*Where “XX” will be “04,” “16,” or “32.”
Fig. 1 — Carrier TEMP System Components
HVAC —
Heating, Ventilation, and Air Conditioning
50TFQ004-012, 48/50TF,TM004-014
50HJQ004-016, 48/50TJ,TM016-028
Apollo Control
Installation, Operation, and
Troubleshooting Instructions
SAFETY CONSIDERATIONS
Read these instructions entirely before modifying the base
Before beginning any modification, make sure all power is disconnected to the unit and locked out. Fai lure to discon­nect power supply prior to servicing may result in serious injury. All wiring must comply with applicable national and local codes.
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of replacing filters. All other operations should be performed by trained service personnel. When working on air­conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
When removing panels from the unit, be careful not to damage the roof or other surfaces with the panels.
GENERAL
The Apollo control is a relay pack which is factory wired and mounted in the Carrier rooftop unit. The Apollo control allows the unit to be connected to a thermostat and a communi­cation bus. The rooftop unit can then be used as part of a system which is controlled by devices on the communication bus. The thermostat and communication bus wiring must be field installed.
The TEMP System thermostat maintains proper tempera­tures by controlling the amount of heated or cooled air supplied to the area in which it is installed or the area it controls (if using a remote room sensor).
Each thermostat is responsible for controlling the tempera­ture conditions in its space. Each thermostat w ill maintain its own independent occupied/unoccupied time schedule and heat­ing (if applicable) and cooling set points. This allows the user to program the TEMP S ystem thermost at so t hat it will mai n­tain different temperature ranges at different times.
TEMP System Components —
System consists of one or more thermostats that communicate by way of a communication bus. Each thermostat controls an Apollo control which in turn controls the Carrier rooftop unit. See Fig. 1.
Each thermostat can be connected to others to provide com­munication between thermostats. Only one thermostat per sys­tem can have a timeclock that will broadcast time to the rest of the system. Se e Fig . 2.
TEMP SYSTEM THERMOSTATS — The 33CSTMT-01, or 33CSVMT-XX (with timeclock) and 33CSTM-01 or 33CSVM-XX (without timeclock) TEMP System thermostats (see Fig. 3) have the following features:
• controls temperature to user- defin ed set points
• eliminates the need for external timeclocks, manual
override timer, night low limit thermostat, battery
backup, or unit time guard
• operates with 3 system switch es for supply-air fan and
the unit heating (if applicable) and cooling stages NOTE: For 33CSVM(T)-XX thermostats, the “XX” will be
either “04,” “16,” or “32.”
The Carrier TEMP
Do not turn on unit power until Apollo control and thermo­stat have been installed. Unit is shipped with loose leads which may cause electrical shock or death.
Carrier TEMP System —
usually consists of more than one thermostat and can be ex­panded to meet whatever number of single zone systems are required.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 111444 Tab 1a1b5a5a6a6b
PC 111 Catalog No. 534-80082 Printed in U.S.A. Form 48/50H,T-15SI Pg 1 8-01 Replaces: 48/50H,T-2SI
The Carrier TEMP System
APOL L O CO NT R OL — The Apollo control (see Fig. 4) has
Fig. 5 — Apollo Control Factory-Installed
In Typical Unit
the following features:
• serves as interface between thermostat, Carrier rooftop unit, and any external field-supplied sensors
• powered by 24 vac/10 va; supplies thermostat with 10 vdc. This power is supplied by the Carrier rooftop unit.
The Apollo control must be used in conjunction with a
Carrier 33CSTM(T)-01 or 33CSVM(T)-XX master thermo­stat. Figure 5 shows the Apollo control factory-installed in a rooftop unit.
*Where “XX” will be “04,” “16,” or “32.”
Fig. 2 — TEMP System Communication
WIRING TO THERMOSTAT
APOLLO CONTROL
CONTROL WIRING
Fig. 3 — TEMP System Thermostat
(With Timeclock Shown)
NOTE: The indicator lights verify each mode of operation.
Fig. 4 — Apollo Control
INSTALLATION
Wiring Requirements —
the TEMP Syst em a re: THERMOSTAT TO THERMOSTAT COMMUNICATION
BUS — Use field-supplied, 18 gage, 3-conductor, shielded, stranded wire, color coded (red, black, green), plenum rated (if required by code). Be sure wire is long enough t o run from thermostat to thermostat in daisy-chain configuration.
THERMOSTAT TO APOLLO CONTROL — Use field­supplied, 18 gage, 5-conductor, shielded, stranded wire, color-coded (red, white, blue, yellow , gr een), plenum rated (if required by code). Be sure wire is long enough to run from thermostat to the Apollo control. The Apollo control is easily accessible in the Carrier rooftop unit. It is found in the unit control box.
IMPORTANT: Do not run the thermostat communication bus and the control wire in the same conduit for more than 5 ft. Never run wires near any c able carrying AC voltage. For further wiring information, consult your local Carrier distributor.
Factory-supplied power required by each Apollo control is 24 vac/10 va. T ypical wiring is 18-gage thermostat wire. Power to the Apollo control may be wired to the Carrier rooftop unit transformer if transformer is of sufficient va capacity. Other­wise, a dedicated transformer has been factory provi ded. The maximum load of a relay contact is 24 vac, 1 amp. A short in the field wiring or Carrier rooftop unit will cause non-warranty damage to the relay board. Test wiring before attaching to Apollo control.
Call your local Carrier representative for more information about wiring the Apollo control as needed.
2
The wiring requirements for
Thermostat Installation —
stallation by determining where the thermostat will be located. In most cases, this will be pre-determined by the building plans.
Locate the thermostat on an interior wall, about 5 ft from the ground. The thermostat should be located away from direct sunlight, drafts, or interior heat sources which may influence temperature readings.
The thermostat may also be m ounted in a re mote location with the use of an optional remote room sensor. Refer to the specific thermostat information for more details on thermostat installatio n.
Begin the thermostat in-
Wiring Connections
Electric shock can cause injury or death. Ensure power to the rooftop unit has been disconnected, before wiring.
WIRE APOLLO CONTROL TO THERMOSTAT — Wire each thermostat to its respective Apollo control as shown in Fig. 6. Make wiring connections at the wiring connector board of the thermostat.
WIRE THERMOSTAT TO COMMUNICATION BUS — The thermostat is connected to the communication bus through the thermostat wiring connection block. Connect the black, red, and green wires from the communication bus to the thermostat wiring connection block. See Fig. 6. To connect other devices to the communication bus, refer to the application manual for that device.
Provide Power To Apollo Control —
ing has been completed, provide power to the Apollo control. Once power has been provided, the Apollo control will power the thermostat. The heating (if applicable) and/ or cooling set points will appear on the thermostat display screen. The ther­mostat is now ready to be programmed. If the display is blank or blinking, recheck the wiring connections between the ther­mostat and Apollo control.
After the wir-
OPERATION
There are 3 system switches which are used to control oper­ation at the thermostat: Heat, Cool, and Fan. The Heat and Cool switches can be set to either AUTO. or OFF position. The Fan switch can be set to either AUTO or ON position. When the fan is running, the F AN indicator will be shown on the ther­mostat display screen. When Cooling mode is energized, the COOL indicator will be shown on the thermostat display screen. When Heating mode is energized, the H EAT indicator will be shown on the thermostat display screen. When the second stage of heating or cooling is energized, a decimal point is displayed between the heating and cooling set points.
AUTO. Fan Mode —
system energizes heating or cooling. The only exception is when the thermostat controls a gas heating rooftop unit. In this application, the thermostat will allow the rooftop unit to control the fan during Heating mode, and the fan will run in Cooling mode.
ON Fan Mode —
ing the occupied mode. In unoccupied mode, t he fan wil l only operate when a system mode is energized.
AUTO. Heating Mode —
AUTO. position, the Apollo control will energize heating when the heating demand is 1.5° F or greater. The second stage of heating will energize when the demand becomes 2.0° F or greater.
OFF Heating Mode —
OFF position, the Apollo control will not allow the rooftop unit to energize heating.
AUTO. Cooling Mode —
to AUTO. position, the Apollo control will energize cooling when the cooling demand is 1.5° F or greater. The second stage of cooling will energize when the demand becomes 2.0° F or greater.
OFF Cooling Mode —
OFF position, the Apollo control will not allow the rooftop unit to energize cooling.
Temperature Trend Staging —
ture Trend Staging option has been configured at the thermo­stat, the thermostat tracks the tempera tures at regular interva ls in each cooling or heating mode. As long as the space tempera­ture is improving, the Apollo control will not allow the second stage to be energized. If the space temperature stays the s ame or the demand becomes greater, the second stage will energize.
Heating Lockout —
ture set point has been configured, and the heating lockout op­tion has been configured to ON, the Apollo control will not al­low heating to energize when the outdoor-air temperature rises above the heating lockout set point.
Cooling Lockout —
ture set point has been configured, and the cooling lockout op­tion has been configured to ON, the Apollo control will not al­low cooling to energize when the outdoor-air temperature drops below the cooling lockout set point.
Time-Delay Relay —
control utilize a 5-minute time delay between the different modes of operation for the rooftop unit. When a mode of oper­ation is deenergized, another mode cannot begin for 5 minutes.
The fan will energize any time the
The fan will operate continuously dur-
When the Heat switch is set to
When the Heat switch is set to
When the Cool switch is set
When the Cool switch is set to
When the Tempera-
When the heating lockout tempera-
When the cooling lockout tempera-
The thermostat and the Apollo
3
Loading...
+ 5 hidden pages