Check the power supply: Voltage, frequency, and phase
must correspond to that specified on the unit rating plate.
The power supply must be able to handle the additional elec
trical load imposed by this equipment.
The Model 38GP Condensing Unit does not have a trans
former; therefore, the fan-coil or blower package trans
former (or another source) must be used as a low-voltage
supply. The low-voltage supply must have an additional
capacity of 15VA to handle the load imposed by this
equipment.
The compressor motor is equipped with em internal protec
tor. Excessive current or temperature wiU cause the protec
tor to open, giving the indication of an open circuit in the
motor winding. Sufi&cient time should be allowed for the
overload to reset before assuming the compressor has an
open winding.
The compressor motor is designed to start under low-load
conditions only (high- and low-side pressures equalized) and
within the specified operating voltage range. Make sure
that system pressures have equahzed before attempting to
start the unit. Equahzation takes approximately 3 minutes.
The owner should be informed not to short-cycle the unit
with the thermostat as this wiU cause the compressor to
tripout on overload.
Each condensing unit is shipped with a refrigerant charge
that is adequate for most systems using matching coils and
refrigerant tubing kits. This charge is adequate for up to 25
feet of interconnecting tubing. For tube lengths greater or
less than 25 feet, the refrigerant charge must be adjusted.
See Table II for charge quantity and refer to refrigeranttube sizing. Tables IV through VII, for the adjustment re
quirements.
NOTE: If additional refrigerant is needed, a crankcase heater
wül probably be required. (Refer to the appropriate refriger
ant-tube sizing table.) When a crankcase heater is used,
inform the homeowner that power must be turned on to the
air conditioning unit at least 12 hours before the thermostat
is turned to the COOLING position for spring startup.
A filter-drier is not normally required in the system when a
complete system is used (condensing unit, refrigerant tub
ing, and evaporator coil). For exceptions to this rule, see
Section II, “Installing Refrigerant Tubing,” of the Stand
ard Installation Practices booklet packaged with the unit.
To obtain optimum performance and efficiency with match
ing or mix-matched evaporator coils, it may be necessary to
change the metering device. See Table IX for necessary
changes.
^Carrier International Corporation 1984
38GP
(50-HZ)
Figure 1—Model 38GP
GENERAL
The condensing unit, as shipped from the factory, includes:
a compressor, a condenser fan and motor, hquid and suction
service valves, an air-cooled condenser coil, and all neces
sary electriceil controls.
The condensing unit is designed for use with matching
evaporator coils. An expansion valve is not required. How
ever, the unit can be used with a suitable evaporator coil
that uses an expansion valve with a pressure equalization
feature during the off cycle. Expansion valves with this fea
ture.are available from your Distributor.
Installation comprises the following steps (sections):
I. Locating the Unit
II. InstaUing Refrigerant Tubing
III. Leak Testing
IV. Purging (if required)
V. Evacuation (if required)
VI. Electrical Connections
VII. Checking Charge
VIII. Adjusting Charge
38GP-C12SI-CIC
AIR IN
NOTE: Fan position on motor shaft should be as close to motor as possible without touching.
♦Refer to appropriate refrigerant tube sizing table to determine correct liquid- and suction-tube diameters.
047
3/8
3/4
230
054
R-22
6-11
3/8
3/4
232
TABLE III—ELECTRIC CONNECTIONS
Nameplate
Size025040
Volts—Phase (60-Hertz)230—1—50
Operating Voltage Range
207-253360-440360-440360-440360-440
400—3—50
400—3—50
Unit Ampacity for Elec
trical Conductor Sizing.18.56.79.214.1
Total Unit Amps15.15.67.6
Min Branch Circuit
Wire Size
Copper
Conductor^
AWG No.
Max Length
In Ftt
12141414
94321236156228
Largest Wire Size
Terminal Will
, Accommodate
Type Conn
AWG No.6
ScrewScrew
6666
Screw
Max Branch. Circuit
Fuse Sizet
Amps25
10
15
NOTE: Use copper wire only between disconnect switch and unit.
♦If other than 75° C copper conductor is used, determine size from unit-ampacity and the National Electric Code. Voltage drop of wire must be less
than 2% of unit rated voltage.
fLength shown is as measured one way along the wire path between the unit and service panel-for minimum 2% voltage drop.
$Sing)e-phase units may use fuses or HACFI-type circuit breakers of same size as noted.
047054
400—3—50400—3—50
15.4
11.512.5
12
ScrewLug
2020
All of the above steps are covered in general by the likenumbered sections of the Standard Installation Practices in
the back of this manual; therefore, this Installation Instruc
tion will contain only supplementary information applicable
to installing the condensing unit. It should be noted that
evacuation and purging are not normally required when a
complete matching system is installed. However, if any of
the component parts are subject to contamination, or if tub
ing kits and matching coUs are not used, the system must
be purged or evacuated.
NOTE; Be sure to adjust system airflow per requirements of
the fan-coil, evaporator coil, and condensing unit
combination.
In addition, the following sections should be reviewed by
the equipment owner;
IX. Sequence of Operation
X. Care and Maintenance
I. LOCATING THE UNIT
(Supplementary Instructions)
Select a location for the unit where water, ice, emd snow will
not fall from an overhang and damage the unit top or fan
blade. Care must be exercised to maintain the clearance
requirements listed on page 2 to assure proper access for
servicing and to avoid recirculation of condenser air.
II. INSTALLING REFRIGERANT TUBES
(Supplementary Instructions)
A. Determining Liquid-Tube Diameter
The correct liquid-tube diameter cem be determined by using
the appropriate table as described in steps 1 through 7
which follow. Be certain to use only the hquid-tube table
that matches the size unit being installed. (See Tables IV
thru VII.)
1. Measure total one-way horizontal distance for intended
tubing path.
2. Measure total one-way vertical distance for intended
tubing path.
3. At left-hand end of table, select value that matches
measured vertical length. Be sure to note that upper
section of table is used if coohng coü is above unit,
whereas lower section is used if cooUng coil is below
unit.
4. Move across this Une towards right-hand side until cor
rect vertical column is reached for measured horizontal
length.
5. Correct diameter will be indicated at intersection of
these lines.
6. If point of intersection falls within shaded area, crank
case heater must be added.
7. For apphcations where coohng coil is to be placed more
than 50 feet below unit, see your Distributor for spe
cific recommendations.
Here is an example; Unit is size 025. Coohng coil is located
43 feet above unit. Horizontal distance is 72 feet.
First, in the section marked “Coü Above Unit,” find the hne
showing measurement of 41-50 feet. Follow this line
towards the right until it intersects the vertical colunrn
marked 71-80 feet. The correct tube size is 5/16-inch OD,
and the fact that the 5/16-inch size falls in the shaded area
means that the unit wih require a crankcase heater.
B. Instructions for Total System Charge
The total system refrigerant charge includes the condensing
unit, the evaporator coü, and the interconnecting tubing.
The factory charge is sufficient for a system using 25 feet of
interconnecting tubing and a matching evaporator coil. For
systems using tubing lengths other than 25 feet, adjust the
charge in accordance with the notes under the proper table
(IV through VII).
TABLE IV—UNIT SIZE 025
Vertical
Distancetototo
(Ft)10203040
Coil
Above21 to 301/4 1/4
Unit
Coil
Below
Unit
41 to 50
31 to 40,1/4
11 to 201/4 1
Oto 10
Oto 10
11 to 20
21 to 30
31 to 401/4
41 to 501/4 1/4 51«; /3«,
(1) Unit charge adequate for 3/8-in. OD tube lengths up to 25 ft. For lengths
(2) Unit charge adequate for 1/4-in. OD tube lengths up to 75 ft. For lengths
(3) Unit charge adequate for 5/16-in. OD tube lengths up to 40 ft. For lengths
(4) If tube size falls within shaded area, add crankcase heater.
41 to 50
Oto 10
Oto 10
11 to 20
21 to 30
31 to 40
41 to 50 5/16
below or above 25 ft, adjust charge at rate of 0.6 oz/ft. This may be done by
using superheat charging label.
above 75 ft, adjust charge at rate of 0.2 oz/ft.
above 40 ft, adjust charge at rate of 0.4 oz/ft.
10
3/8 3/8 3/8 3/8
5/ 16
' ’
Horizontal Distance— Feet
304050
20
t
5.'16] 5/ 1 6
5/16|5/16|5/16|5/16|5/163/8 3/8 3/8 3/8
3 5
1'
i J
7080 90
60
3./8 3/8 3/8 3,'8 3/8
5/16
5 1 6
1
i
6
...
4
100
—3—
TABLE Vili—RECOMMENDED
SUCTION-TUBE DIAMETERS
Suction-Tube
Size
0250 to 1205/8
040Oto 60
047
0540 to 651-1/8
NOTE: The above table is based on a tube loss of 2°F. Longer lengths
can be used in each diameter listed, or smaller diameters may
be used, but the result will be larger tube losses with a lower
unit capacity and efficiency rating. Refer to your Distributor for
specific details.
Length (Feet)
120 to 1507/8
60 to 1357/8
Oto 857/8
85 to 1501-1/8
65 to 1501-3/8
Recommended
Diameter (inches)
3/4
TABLE IX—REQUIRED PISTON SIZE FOR
INDOOR COIL
Condensing
Unit Size
025
04076
047
05488
NOTE: The piston sizes listed in this table are for systems where the
vertical separations between indoor and outdoor units do not
exceed 10 feet. For vertical separations exceeding 10 feet,
consult the factory for the proper piston sizes.
Piston
identification No.
59
82
If other than matching interconnecting tubing or evapora
tor coU is being used, use an accurate scale or volumetric
charging cylinder (such as a Dial-A-Charge) and weigh in the
refrigerant until the desired superheat temperature is
obtained. See the superheat charging label attached to each
condensing unit.
When system charging has been completed, stamp the total
amount of refrigerant in the block provided on the condens
ing unit rating plate. The total system charge is the same as
the field charge.
C. Determining Suction-Tube Diameter
The correct suction-tube diameter can be determined by
using Table VIII as follows:
1. Measure total length (vertical and horizontal) of
intended tubing path.
2. Find correct unit size at left of table.
The tube lengths are shown in the center of the table
with the appropriate diameters on the right.
iX. SEQUENCE OF OPERATiON
When the thermostat “calls for cooling,” the thermostat
contacts close, energizing contactor holding coil 2D or 2M
from a 24-volt external power source. The contactor closes,
energizing compressor motor 3F or 3J and condenser fan
motor 3C or 3D with supply voltage.
When the thermostat is satisfied, the contacts open,
deenergizing contactor holding coil 2D or 2M and, in turn,
breaking the supply voltage circuit. AH motors should stop.
Optional Start Assist (When Used)
Start thermistor 4K is wired in parallel to run capacitor 4G
on single-phase units. Its purpose is to provide additional
start assist. When compressor 3J starts, start thermistor
4K builds its internal resistance to a level where it effec
tively removes itself electrically from circuit. When contac
tor 2D or 2M is deenergized, start thermistor 4K will auto
matically reset itself in approximately 3 to 5 minutes.
Start Kit 2K and 4D
The start kit consists of start relay 2K and start capacitor
4D. Start capacitor 4D helps compressor 3J start. When the
compressor starts, start relay 2K disconnects start capaci
tor 4D from the circuit, allowing compressor 3J to run on
run capacitor 4A or 4G. When contactor 2D or 2M deener
gizes, start relay 2K reconnects the start capacitor in the
circuit, making it ready for the next compressor start.
X. CARE AND MAINTENANCE
For continuing high performance, and to rnmirnize possible
equipment failure, it is essential that periodic maintenance
be performed on this equipment. Consult your local Dealer
for the proper frequency or maintenance and the availability
of a maintenance contract.
The air for the condenser coil is drawn into the unit on four
sides and discharged out the top. Keep the air inlet and out
let grilles unplugged and clear of any obstructions at all
times. Never cover the unit or lean anything against it
which might restrict airflow or cause hot air from the top
grille to recirculate into the sides. Keep trash and debris
away from the uiut at all times. Never stand on the unit or
use it as a support for ladders, etc.
The refrigerant tubing connecting this unit with the coohng
coil is easily crushed or crimped. Therefore, do not hang or
stand anything on it. Do not move the unit after it has been
installed, as this may crimp the tubing and cause the unit to
malfunction.
The ability to properly perform maintenance on this equip
ment requires certain mechanical skills and tools. If you do
not possess these, contact your Distributor for
maintenance.
The minimum maintenance that should be performed on
this equipment is as follows:
1. Check condenser coü for cleanliness each month during
cooling season. Clean as necessary, but at least once at
the beginning of each cooling season. To insure reliable
performance in sea coast or contaminated atmosphere
installations, the unit must be kept free of debris and
the condenser coil flushed with fresh water at least
once a month. See Section X, item A, for proper
procedures.
—4—
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.