“CAUTION: IMPROPER INSTALLATION MAY CAUSE SERIOUS DAMAGE, FOLLOW ALL INSTALLATION INSTRUCTIONS CAREFULLY”
“THIS MANUAL IS ONLY FOR PROFESSIONAL INSTALLERS OR QUALIFIED PERSONS”
1 Legend of symbols
This symbol indicates sections to be read with particular care.
This symbol indicates sections concerning safety.
This symbol indicates notes to communicate to users.
ENGLISH
2 Intended use and application
2.1 Intended use
The ZM3 control panel is designed to command the following swing-gate operators ATI, AXO, FAST, FERNI, FROG, KRONO.
The ZM3EC control panel is engineered to command CBX - F4000 industrial doors.It comes with its own safety release and buttons.
The use of this product for purposes other than as described above and installation executed in a manner other than as
instructed in this technical manual are prohibited.
2.2 Application
Make sure you respect the distances and cable diameters as shown in “cable types and minimal thicknesses” table.
The overall power of the motors must not exceed 750 W.
3 Reference Standards
For its quality processes management Came Cancelli Automatici is ISO 9001:2000 certified, and for its environmental management it is
ISO 14001 certified. Came designs and manufactures entirely in Italy.
This product complies with the following standards: see Declaration of Compliance.
4 Description
This product is engineered and manufactured by CAME cancelli automatici s.p.a. and complies with current safety regulations.
Guaranteed 24 months if not tampered with.
The control panel works on 230V a.c. of power, 50/60Hz frequency.
Both command and control devices and accessories are 24V powered. Warning! Accessories must not exceed 35 W overall.
All connections are protected by quick fuses, see table.
The input and output contact functions, the timing settings and users’ management, are set and viewed on the display, which is run by
software.
1 - Transformer
2 - M1 gearmotor condenser (black wires)
3 - M2 gearmotor condenser (red wires)
4 - Card fuse
5 - Accessories fuse
6 - Electrolock fuse
7 - Display
8 - Display lighting adjustment trimmer
9 - Memory roll card connector
10 - AF card connector
11 - R700 card connector
12 - Open contact error - warning LED
13 - Programming buttons
14 - Terminal board for connecting
15 - Terminal board for 230V a.c. power grid
16 - Line fuse
17 - 230V-power signalling LED
18 - STOP button
19 - CLOSE button
20 - OPEN button
21 - Safety block
ZM3EC
{
17
16
15
ZM3C
1
ZM3EC
!02%
#()5$%
2
4
3
2
1
6
4
5
3
7
ENGLISH
8
9
10
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Warning! Before acting on the machinery, cut off the
main power supply and disconnect any emergency
batteries.
Page 4
4
319U75
2.0
5 Installation
Installation must be carried out by expert qualified personnel and in full observance of regulations in force.
5.1 Preliminary checks
Before installing do the following:
• Check that the panel’s anchoring point is protected from possible blows, and that the anchoring surface is solid. Also check that the
anchoring is done using the appropriate bolts, screws etc.;
• Make sure you have a suitable omnipolar cut-off device with contacts more than 3 mm apart, and independent (sectioned off) power
supply;
ENGLISH
• Make sure that any connections inside the case (that provide continuance to the protective circuit) are fitted with extra insulation
as compared to the other conductive parts inside;
• Make sure you have suitable tubing and conduits for the electrical cables to pass through and be protected against mechanical
damage.
5.2 Tools and materials
Make sure you have all the tools and materials you will need for the installation at hand to work in total safety and compliance with the
current standards and regulations. The following figure illustrates the minimum equipment needed by the installer.
Here are some examples.
5.3 Fixing and mounting the box
1) Fix the base of the panel in a protected area; we suggest
using round top Phillips recessed head screws of max.
6mm in diameter.
3) Assemble the pressure hinges.
2) Perforate the pre-punched holes and insert the cable
glands with the corrugated tubing for the electrical
cables to travel through.
N.B.: diameter of the pre-punched holes: 20 mm.
!!
4) Insert the pressure hinges into the box (on the left or right as you
wish) and set them using the provided screws and washers.
5) Snap the cover into place onto the hinges. Close it and fix it
using the provided screws.
6 Electrical connections
6.1 Cable and type and section
6) After the adjustments and settings, fix the cover
using the provided screws.
ENGLISH
Connections
Type
of cable
Control panel power supply
Motor power supply3G x 1,5 mm
flashing lamp2 x 1,5 mm
Transmitter photocells2 x 0,5 mm
Receiver photocells4 x 0,5 mm
FROR CEI
20-22
CEI EN
50267-2-1
Power supply to accessories2 x 0,5 mm
Control and safety devices2 x 0,5 mm
Length of cable
1 < 10 m
3G x 1,5 mm
Length of cable
10 < 20 m
2
2
2
2
2
2
2
3G x 1,5 mm
3G x 1,5 mm
2 x 1,5 mm
2 x 0.5 mm
4 x 0,5 mm
2 x 0,5 mm
2 x 0,5 mm
2
2
2
2
2
2
2
Length of cable
20 < 30 m
3G x 2,5 mm
3G x 2,5 mm
2 x 1,5 mm
2 x 0,5 mm
4 x 0,5 mm
2 x 1 mm
2 x 0,5 mm
2
2
2
2
2
2
2
Encoder connection2402C 22AWGmax. 30 m
Antenna connectionRG58max. 10 m
N.B.: If the cable length differs from that specified in the table, then you must determine the proper cable diameter based on the actual
power draw from the connected devices and according to the CEI EN 60204-1 standards.
For connections that require several, sequential loads, the sizes given on the table must be re-evaluated based on actual power draw
and distances.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
When connecting products that are not specified in this manual, please follow the documentation provided with said products.
- 25W max.) Flashes during opening
and closing phases.
Cycle lamp: (contact rating: 230V – 60W max.)
It lights up the driving area and stays on from the
ENGLISH
moment the gate begins to open until it is fully closed
(including the automatic closing time). If automatic
closing is not activated, the lamp stays on only during
movement or for a set time of 5 minutes if used as a
courtesy lamp.
Command devices
LT001 - Magnetic card reader
TSP00 - Transponder sensor
Open gate indicator-light
(socket rating: 24V - 3W max.).
Turns on when the gate is ajar or open.
It turns off when the gate is closed.
N.B.: insert the R700 emcoding card for the
TSP00 sensors and LT001 card readers to be
recognised.
ACCESS CONTROL
CAME
Stop button (N.C. contact) - Button to stop gate while
excluding the automatic closing cycle. For movement to
resume you must press the command button or transmitter
button.
N.B.: if contact is unused, select Disabled on the
“FUNCTIONS” menu.
Key selector and/or commands button (N.O. contact) - Commands for opening and closing the
gate – pressing the button or turning the keyswitch, inverts the gate’s movement or stops it
depending on how it is set on the 2-7 command in
the “FUNCTIONS” menu.
M1 - 230V A.C. gearmotor featuring delayed action on openingM2 - 230V A.C. gearmotor featuring delayed action on closing
FROG A
ATI
F4000
FERNI
F7001
Gearmotor, encoder
M1 - 230V A.C. gearmotor featuring
delayed action on opening
FROG AE
White
Brown
Green
KRONO
FROG A
KRONO
&!&#&!&#
ENCODER BENCODER A
M2 - 230V A.C. gearmotor featuring
delayed action on closing
Green
Brown
White
FERNI
ATI
F7001
ENGLISH
CBX
F4000
FROG AE
F7001E
Safety devices
Confi gure either (N.C.) contacts CX, CY or CZ, input
for safety devices such as photocells, that comply
with EN 12978 standards. See CX, CY or CZ input
functions in:
- C1 «re-open during closing phase», When the
gate leaf is closing, opening the contact triggers the
inversion of the direction of movement until the gate
leaf is fully open.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
- C2 «re-close during opening phase», When gate
is opening, if the contact is opened it triggers an
inversion of the direction until gate is fully closed;
- C3 «partial stop», Halts moving gate leaves and
causes them to automatically close (if this functions
has been selected);
- C4 «stand-by Obstacle», Halts the moving gate
leaves causing them to start moving again once
obstacle is removed.
input for EN 12978 compliant safety devices such
as sensitive edges. See CX input functions in:
- C7 «Open while closing»,
During gate closing,
opening the contact causes inversion of movement
until gate is fully open;
- C8 «close while opening», During gate opening,
opening the contact causes inversion of movement
until gate is fully close.
ENGLISH
- Deactivated, if contact is unused.
DF
DF with DFI connections
monitor card
6.3 Electrical connection for the photocells functions test
(DOC)
./
#
.#
(DIR)
48
&53)"),%M!
#
.#
48
48
At each opening and closing command, the control board assesses the effi ciency status of the control devices (photocells). Any
anomaly found is signalled with the fl ashing of the LED on the control panel. Consequently it cancels any commands coming from the
remote control or the button.
Electrical connection to enable the photocell safety test:
- the transmitter and the receiver, must be connected as per the diagram;
- from the functions menu, select “safety tests” and select either CX - CY - CZ input/s to activate the test
To enter the menu, keep the
ENTER key pressed for at least one
second.
Lingua
Italiano
Þß
the <...> symbols on the display are for:
-pointing out the currently, selected item
{
The ENTER key is for:
- entering the menu;
{
- confirming and memorising set values.
{
Þß
LANGUAGE
English
ENGLISH
To select a menu item,
mode using the greater
than-lesser than keys...
also use the greater
than-lesser than keys
for the “sub-menus”...
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Select language: selects among the languages displayed.
< LANGUAGE >
English
LANGUAGE
< English >
< FUNCTIONS >
It appears only if selected from the “Config.”
Section in the FUNCTIONS menu.
< INFO >
LANGUAGE
< Francais >
LANGUAGE
< Italiano >
< ENCODER >
< TIMING ADJ. >
< USERS >
250
Max. 250 users
LANGUAGE
< Deutsch >
LANGUAGE
< Espanol >
7.6 Functions menu
Automatic Closing: activates or deactivates the automatic closing function.
The automatic closing timer activates at each opening endpoint. The predetermined time may be adjusted, and is in any case
dependent on any safety devices that may activate; and it does not activate after a total safety “stop” or during a power outage.
< AutoClose >
FUNCTIONS
Turn on
X 2
Maintained action: the gate works by keeping the button pressed (button 2-3 for opening, button 2-4 for closing, or if set to the “On
Closing” function, only with button 2-4.
Obstacle detected: when motor is stopped (gate closed or after a total stop command) it prevents any movement if safety devices,
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
TIMING ADJ.
USERS
O
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
<
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
such as photocells, detect any obstacles.
X 2
Obstacle Det.
< Disabled >
FUNCTIONS
<Obstacle Det.>
Disabled
X 2
Obstacle Det.
< Turn on >
Safety test: allows the card to check the efficiency of any safety devices (i.e. photocells) after every opening or closing command.
LANGUAGE >
FUNCTIONS
X 3
<Safety d.Test>
Disabled
Safety d.Tes t
< Disabled >
Safety d.Tes t
< CX+CY+CZ >
Safety d.Tes t
< CX >
Safety d.Tes t
< CY >
ENGLISH
X 2
Safety d.Tes t
< CX+CZ >
Safety d.Tes t
< CX+CY >
Safety d.Tes t
< CZ >
Pre-flashing: after an opening or closing command, the flashing light, connected to W-E, starts flashing before the gate begins its run
(to set the time, see “Pre-flashing timing” from the Adjust Timings menu
X 4
Preflashing
< Disabled >
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
FUNCTIONS
< Preflashing >
Disabled
X 2
Ram blow: before any opening run, the gate leaves will press onto the mechanical endstop for a few seconds, to help release the electrolock (to set the time, see “Starting ram timing” in the Adjust Timings menu).
Total Stop: this function stops the gate and consequently excludes any automatic closing cycle; for movement to resume, you need to
< LANGUAGE >
EnglishEnglish
TIMING ADJ.
IMING ADJ
USERS
TEST MOT.
TEST MOT.
< LANGUAGE >
EnglishEnglish
TIMING ADJ.
IMING ADJ
USERS
TEST MOT.
TEST MOT.
< LANGUAGE >
EnglishEnglish
TIMING ADJ.
IMING ADJ
USERS
TEST MOT.
TEST MOT.
use the keypad or transmitter. Insert safety device on [1-2]; Insert the safety device on [1 -2]; if unused, select “Deactivated”
X 6
FUNCTIONS
< Total Stop >
Turn on
Total Stop
< Turn on >
X 2
Total Stop
ENGLISH
< Disabled >
CX input: the N.C. safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when
opening), C3 (partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for
sensitive edges) or, be deactivated. See safety devices on electrical connections.
X 7
CX Input
< C1 >
< C2 >
FUNCTIONS
NFO
< CX Input >
Disabled
CX Input
< Disabled >
CX Input
< C8 >
CX Input
X 2
CX Input
< C7 >
CX Input
< C4 >
CX Input
< C3 >
CY input: safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when opening), C3
(partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges)
or, be deactivated. See safety devices on electrical connections.
CZ input: safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when opening), C3
< LANGUAGE >
English
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
h
TIMING ADJ.
USERS
< LANGUAGE >
English
TIMING ADJ.
USERS
< LANGUAGE >
English
h
TIMING ADJ.
TEST MOT.
TEST MOT
(partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges)
or, be deactivated. See safety devices on electrical connections.
X 9
< CZ Input >
Disabled
FUNCTIONS
CZ Input
< Disabled >
CZ Input
< C1 >
CZ Input
< C8 >
CZ Input
< C2 >
X 2
CZ Input
< C7 >
CZ Input
< C4 >
CZ Input
< C3 >
Closing thrust: at the endpoint stage during closing, the gearmotors perform a final closing-thrust of the doors for a few seconds.
X 10
FUNCTIONS
< Cl. Thrust. >
Disabled
Cl. Thrust.
< Disabled >
X 2
Cl. Thrust.
< Turn on >
Lock: to lock the gate leaves. Required for gate leaves longer than 2.50 m.
ENGLISH
X 11
< Lock >
FUNCTIONS
Disabled
< Disabled >
X 2
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Deceleration configuration: configuring decelerations when opening or closing:
- slow run: decelerations when opening and closing;
- Fcap-RallCh.: end stop when opening and deceleration when closing;
- ecoder: managing decelerations, obstacle detection and sensitivity; (FROG-AE)
- Time of Run: timed end stop (default function); (FROG-A, FERNI 230V, ATI 230V, FAST 230V and KRONO)
- Limit switch (endstop): opening and closing endstop. (C-BX and F4000)
Endstop: configure the endpoints are normally closed or open contacts.
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TESTMOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
N.B.: this function appears only if selected from the “Config.” function in the FUNCTIONS menu.
X 13
< endstop >
FUNCTIONS
N.C
endstop
< N.C >
X 2
endstop
< N.A >
ENGLISH
Command 2-7: setting the 2-7 contact to step-by- step mode (open-close) or sequential (open-stop-close-stop).
X 14
cmd 2-7
<Op.-Stop- Cl.>
FUNCTIONS
< cmd 2-7 >
Op.-Stop-Cl.
X 2
cmd 2-7
<Open-Close>
Command 2-3P: setting the 2-3P contact to pedestrian opening (second gate leaf opens fully) or partial (second gate leaf opens
partially depending on the time set on “Partial opening” from the Adjust Times menu).
< LANGUAGE >
FUNCTIONS
X 15
< cmd 2-3P >
Pedestrian
cmd 2-3P
< Pedestrian >
X 2
E3 lamp: configuring the lamp connected to E-E3:
- cycle: outdoor lamp, which can be positioned at leisure, for better illumination in the parking/driveway area.
It stays on from the moment the gate leaf begins to open, until it is fully closed (including automatic closing time).
In case the automatic closing function is not inserted, it stays on only during gate movement.
- courtesy: outdoor lamp, which can be positioned at leisure, for better illumination in the parking/driveway area.
It stays on for a set time of 5 minutes.
B1-B2 output: setting contact B1-B2 to MONO-STABLE or BI-STABLE (switch) mode.
< LANGUAGE >
English
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
X 17
FUNCTIONS
< output B1-B2 >
Monostable
X 2
output B1-B2
< Monostable
output B1-B2
< Bistable >
Slow Down: setting the deceleration speed when opening or closing, or, only when closing if said deceleration is configured as (FcapRallCh.).
N.B.: this function only appears if the decelerations are selected.
X 18
FUNCTIONS
X 2
<Slow Down Spd.>
-ooo+
•
Slow Down Spd.
•
<
-ooo+
•
Slow Down Spd.
<
>
-ooo+
•
•
ENGLISH
>
Number of motors: setting the number of motors, either one or two, depending on the number of gate leaves installed on the system.
X 19
FUNCTIONS
< No. Motors >
M1 + M2
No. Motors
< M1 + M2 >
X 2
No. Motors
< M2 >
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Motor Type: setting up the type of swing gate motor installed in the system.
7.7 Encoder Menu (the ENCODER menu, appears only if selected from the “Config.” function in the FUNCTIONS menu.)
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
N.B.: before setting the functions in the encoder menu, run the gearmotor checks to verify the proper turning direction.
Sensitivity: the obstacle detection function is activated during gate operation and deceleration.
Se n sibility
< Turn on >
ENGLISH
ENCODER
< Se n s ibility >
Turn on
X 2
Gate operation sensitivity: this adjusts the obstacle detection sensitivity during opening and closing gate operation.
N.B.: this function appears only if the “sensitivity” function is activated in the ENCODER menu.
Sensib. Run
-oooooooo+
<
•
ENCODER
< Sensib. Run >
-oooooooo+
•
X 2
Deceleration sensitivity: it adjusts the obstacle detection sensitivity during opening and closing gate deceleration.
N.B.: this function appears only if the “sensitivity” function is activated in the ENCODER menu.
X 2
Se n sibility
<Disabled>
>
Sensib. Run
-oooooooo+
<
•
•
>
Sensib. Decel.
-oooooooo+
<
•
>
ENCODER
<Sensib. Decel.>
-oooooooo+
•
X 2
Sensib. Decel.
-oooooooo+
<
•
•
Encoder Deceleration: this activates the opening and closing deceleration starting points.
< LANGUAGE >
X 3
Slow run Enc
< ON
>
ENCODER
< Slow run Enc >
ON
X 2
Slow run Enc
< OFF
M1 opening deceleration%: this adjusts the (M1) first motor’s deceleration starting point before the opening endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
M1 closing deceleration%: this adjusts the (M1) first motor’s deceleration starting point before the closing endpoint.
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERSNFO
< LANGUAGE >
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERS
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 5
M1 Slow.CH %
< 10
>
ENCODER
< M1 Slow.CH % >
10
X 2
M1 Slow.CH %
< 11
M2 opening deceleration%: this adjusts the (M2) second motor’s deceleration starting point before the opening endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 6
M2 Slow.AP %
< 10
>
ENCODER
< M2 Slow.AP % >
10
X 2
M2 Slow.AP %
< 11
ENGLISH
>
>
M2 closing deceleration %: this adjusts the (M2) second motor’s deceleration starting point before the closing endpoint.
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28.
N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 7
M2 Slow.CH %
< 10
>
ENCODER
< M2 Slow.CH % >
10
X 2
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
M2 Slow.CH %
< 11
M1 closing acceleration %: this adjusts the (M1) first motor’s percentage rate of approach to the final closing and opening points
before reaching the opening and closing endpoints. The percentage rate of approach to (goes from 1% to 15% of the full gate run). See
illustration on page 28.
M2 closing acceleration %: this adjusts the (M2) second motor’s percentage rate of approach to the final closing and opening points
< LANGUAGE >
EnglishEnglish
FUNCTION
TIMING ADJ.
USERS
TEST MOT.
< LANGUAGE >
EnglishEnglish
FUNCTION
TIMING ADJ.
USERS
TEST MOT.
< LANGUAGE >
English
h
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
h
FUNCTION
USERS
TEST MOT.
TEST MOT
before reaching the opening and closing endpoints. The percentage rate of approach to (goes from 1% to 15% of the full gate run). See
illustration on page 28.
X 8
ENGLISH
ENCODER
ENCODER
X 2
X 2
X 9
< M2 Appr.CH % >
5
< Set Encoder >
M2 Appr.CH %
< 5
Set Encoder
<confirm?(no)>
M2 Appr.CH %
< 6
Set Encoder
<confirm?(yes)>
>
See detailed
description on
page 28
>
7.8 Time setting menu
Automatic closing: to set the waiting time when gate is in the open position.
Once this time is elapsed, the gate closes automatically. The waiting time can be set to between 0” and 300”.
< A.C.T. >
TIMING ADJ.
10s.
X 2
Automatic Pedestrian Closing: waiting time of the (M2) second gate leaf when in the open position. Once this time interval has
elapsed, the gate automatically closes. The waiting time interval can go anywhere from 0” to 300”.
Cycle time: the working time of the motor during opening or closing phases is anywhere from 10” to 150”.
< LANGUAGE >
English
English
FUNCTIONS
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTIONS
FUNCTION
USERS
TEST MOT.
TEST MOT
<
English
English
FUNCTIONS
FUNCTION
U
S
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTIONS
FUNCTION
USERS
TEST MOT.
TEST MOT
X 2
TIMING ADJ.
< Cycle Time >
90s.
Cycle Time
< 90s. >
X 2
NFO
Cycle Time
< 91s. >
M1 delayed opening: the waiting time of the (M1) first gate lead, unlike the (M2) second one, after each opening command. The
waiting time can be set to between 0” and 10”.
X 3
TIMING ADJ.
< Op. Delay M1 >
2s
Op. Delay M1
< 2s >
X 2
Op. Delay M1
< 3s >
ENGLISH
M2 delayed closing: the waiting time of the (M2) second gate leaf, unlike the (M1) first one, after each closing command. the waiting
time can be set to between 0” and 60”.
LANGUAGE >
X 4
TIMING ADJ.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
SER
< Cl. Delay M2 >
2s
X 2
Cl. Delay M2
< 2s >
Cl. Delay M2
< 3s >
Pre-flashing time: after an opening or closing command is given, the flasher connected to “W-E), flashes for between 1” and 60”,
before the gate begins to move.
Lock time: the time required for releasing the electro-lock after each opening command. The time of operation can be set to between
< LANGUAGE >
English
English
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
LANGUAG
English
FUNCTION
NS
USERS
TEST MOT.
1” and 5”.
X 6
TIMING ADJ.
< Lock time >
2s.
Lock time
< 2s. >
X 2
ENGLISH
Lock time
< 3s. >
Ram hit time: the gearmotor’s thrust time when fully closing after each opening command. The thrust time can be set to between 1”
and 10”.
X 7
TIMING ADJ.
NFO
< Ram hit time >
2s.
X 2
Ram hit time
< 2s. >
Ram hit time
< 3s. >
Partial opening: the opening time of the (M2) second gate leaf. The time can be set to between 5” and 60”.
X 8
TIMING ADJ.
< Ped. opening >
5s.
X 2
Ped. opening
< 5s. >
Ped. opening
< 6s. >
Slow down time: the gate leaf’s deceleration time before every endpoint. The time can be set to between 0” and 30”.
N.B.: this function only appears if the decelerations are selected.
Add User: to create a new user and assigned function (max. 250 users).
< Add User >
X 2
USERS
Mod. Name: to change a user number or existing name to another name.
LANGUAGE >
< Mod. name >
X 2
USERS
Add User
<confirm? (no) >
ENGLISH
Add User
<confirm? (yes)>
See detailed
description on
page 26
Choose User
< 001:--001-- >
Choose User
< 002:--002-- >
Mod. Code: to change a user’s current code.
X 2
< Mod. Code >
X 2
USERS
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Related Function: to change the function assigned to the user.
Version: to view software version.
Number of gate runs: to view the number of runs performed by the gate.
Starting Mssg: to view the starting message, confirm with ENTER to change text. Use the ENTER key to move the cursor forward, ESC
to move it backwards and <> to select the letter of number. Confirm the text by pressing the ENTER key for a few seconds.
System reset: it resets the system to its original settings. Press ENTER key to confirm.
< Version >
fw : 3.0
< System Reset >
INFO
7.11 Motor test menu
TEST MOT.: Test to check the proper direction of the gearmotors.
Gate leaf opening
run of the first (M1)
gearmotor. If the
direction is wrong,
invert the motor’s
phases.
< No. of Runs >
< TEST MOT. >
<=M1 M2=>
10
ENGLISH
< Standby Msg. >
- WWW.CAME.IT
ZM3E
Gate leaf opening run
of the second (M2)
gearmotor. If the
direction is wrong,
invert the motor’s
phases.
TEST MOT.
7.12 Decoding card
Connect the required (R700, AF43S cards) to insert, change, remove and command the operator via transmitter, card or transponder.
Insert the memory roll to save and load all setting including users registered by another card.
AF Card
TFM
TOP
ATOMO / TWIN
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
1) From the Users
menu, choose
“Mod. Code”.
Press ENTER to
confirm.
3) .... you will be
asked to input a
code. Send the code
using the transmitter
button or the slide through card or the
transponder.
Mod. Code
Waiting Code
>>>>
Choose User
2) Choose the user
name for which you
wish to change the
001:--U001--
Þß
Choose User
002:--U002--
Þß
code and press ENTER
to confirm.
ENGLISH
4) .. once the code
is inputted, the user
name will come up
--002--
radio
showing the type of
command that was
ACCESS CONTROL
memorised...
7.16 Function assigned to the user
1) From the Users
menu, choose
“Related Fuc.”.
Press ENTER to
confirm.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
3) Choose the new
function to assign
to the user. Press
ENTER to confirm.
5) Select “ confirm (yes)”
and press ENTER key to
confirm.
2) Choose the user
name fo which you
wish to change the
command function
and press ENTER to
confirm.
4) Choose “confirm
(yes)” and press
ENTER to confirm.
Mod. Code
confirm? (yes)
Þß
Choose User
001:--U001--
Þß
Choose User
002:--U002--
Þß
Related Func.
confirm? (yes)
Þß
319U75
:
Manual code
27 -
Pag.
Page 28
28
319U75
2.0
7.17 Gate run calibration
N.B. before calibrating the gate run, check that the manoeuvring area is free of any obstacles and check the proper direction of rotation of the
gearmotors. (para. 7.11)
1) From the Encoder
menu, select “Set
Encoder”. Press ENTER
to confirm.
ENGLISH
3) the gate leaf of the
first motor will perform
a closing run until fully
closed.....
5) …then, the gate leaf
of the second motor, will
perform and opening run
until fully open…
Set Encoder
Þß
2) Select “confirm
(yes) and press ENTER
to confirm.
Set Encoder
Close 1
4) …then, the
gate leaf of the
0
0
second motor will
perform the same
manoeuvre…
Set Encoder
Open 2
6) ...after which,
0
0
the gate leaf of
the first motor will
perform the same
manoeuvre…
Set Encoder
confirm? (no)
Þß
0
0
Set Encoder
confirm? (yes)
<>
Set Encoder
Close 2
0
Set Encoder
Open 1
0
7) When the procedure is
finished, the display will show
“Set Encoder ok” for a few
Set Encoder
OK
seconds.
7.18 Error messages
-“encoder ERROR”: check proper connections or functionality of the device and possibly even the motor’s torque”
-“safety d. test ERROR”: malfunctioning of safety devices, check proper functioning of connections and functionalities;
-“end stop ERROR”: check proper connections on end point connections or functionality of devices;
-“cycle time ERROR”: check the working time settings, the set time may be insufficient to complete the duty cycle.
- Safety STOP, C1, C3, C4”: check proper functioning of connections and functionalities of devices.
7.19 Illustration depicting the areas and points of deceleration and final opening and closing approaches per encoder device.
Note: the areas and points of deceleration and fi nal opening and closing approaches are tested according to the parameters set forth by
Technical Norms EN12445 and EN12453 regarding compatibility of impact forces generated by moving gate leaves.
A = Area of movement at normal speed
B* = Run zone at decelerated speed
C = Encoder intervention zone with
0
movement inversion
D= Encoder intervention zone with
movement stop
B
E = Opening deceleration beginning point
(M1 Open Deceler %)
F = Closing deceleration beginning point
(M1 Close Deceler %)
G = Opening deceleration beginning point
(M2 Open Deceler %)
B
A
C
H = Closing deceleration beginning point
(M2 Close Deceler %)
I** = Closing and opening fi nal phase
beginning point (M1 Final Close %)
L** = Closing and opening fi nal phase
beginning point (M2 Final Close %)
D
E
M
I
M= endstops
* Minimum 600 mm from the Final full stop.
**Set the function’s fi nal phase % “M1 Final Close” for the fi rst (M1) mtors and “M2 Final Close” for the second (M2) motor from the
“ENCODER” menu so as to obtain a distance of between 1 and 50 mm maximum from the fi nal full stop.
M
D
I
F H
D
L
B
A
C
B
G
L
0
ENGLISH
D
M
8 Demolition and disposal
In its premises, CAME CANCELLI AUTOMATICI S.p.A. implements an Environmental Management System certifi ed in
compliance with the UNI EN ISO 14001 standard to ensure environmental protection.
Please continue our efforts to protect the environment—which CAME considers one of the cardinal elements in the development of its
operational and market strategies—simply by observing brief recommendations as regards disposal:
DISPOSAL OF PACKAGING
The packaging components (cardboard, plastic, etc.) are all classifi able as solid urban waste products and may be disposed of easily,
keeping in mind recycling possibilities.
Prior to disposal, it is always advisable to check specifi c regulations in force in the place of installation.
PLEASE DISPOSE OF PROPERLY!
PRODUCT DISPOSAL
Our products are made up of various types of materials. Most of them (aluminium, plastics, iron, electrical wires, etc.) may be disposed
of in normal garbage collection bins and can be recycled by disposing of in specifi c recyclable material collection bins and disposal in
authorized centres. Other components (electrical boards, remote control batteries, etc.), however, may contain polluting substances.
They should therefore be removed and given to qualifi ed service companies for proper disposal.
Prior to disposal, it is always advisable to check specifi c regulations in force in the place of disposal.
PLEASE DISPOSE OF PROPERLY!
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
9 Manufacturer’s warranty
MANUFACTURER’S DECLARATION OF CONFORMITY
CAME Cancelli Automatici S.p.A.
via Martiri della Libertà, 15
31030 Dosson di Casier - Treviso - ITALY
tel (+39) 0422 4940 - fax (+39) 0422 4941
internet: www.came.it - e-mail: info@came.it
Declares under its own responsibility that the equipments for automatic garage doors and gates listed below:
Moskva - RUSSIA
(+7) 495 937 33 07
(+7) 495 937 33 08
English - Manual code:
The data and information repor ted in this installation manual are susceptible to change at any time and without obligation on CA ME cancelli automatici s.p.a. to notify users.
CAME Cancelli Automatici S.p.a.
Via Martiri Della Libertà, 15
31030
Dosson Di Casier (Tv)
(+39) 0422 4940
(+39) 0422 4941
20093
CAME Nord s.r.l.
Piazza Castello, 16
Cologno Monzese (MI)
(+39) 02 26708293
(+39) 02 25490288
Informazioni Commerciali 800 848095
www.came.it
CAME Service Italia S.r.l.
Via Della Pace, 28
31030
Dosson Di Casier (Tv)
(+39) 0422 383532
(+39) 0422 490044
Assistenza Tecnica 800 295830
CAME Sud s.r.l.
Via F. Imparato, 198
Cm2 Lotto A/7
80146
Napoli
(+39) 081 7524455
(+39) 081 7529109
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.