CAME ZM3E-ZM3EC INSTALLATION MANUAL

Page 1
h
Z SERIES
CONTROL PANEL FOR 230V OPERATORS
INSTALLATION MANUAL
ZM3E - ZM3EC
Englis
Page 2
2
319U75
2.0
“IMPORTANT INSTALLATION, SAFETY INSTRUCTIONS”
“CAUTION: IMPROPER INSTALLATION MAY CAUSE SERIOUS DAMAGE, FOLLOW ALL INSTALLATION INSTRUCTIONS CAREFULLY”
“THIS MANUAL IS ONLY FOR PROFESSIONAL INSTALLERS OR QUALIFIED PERSONS”
1 Legend of symbols
This symbol indicates sections to be read with particular care.
This symbol indicates sections concerning safety.
This symbol indicates notes to communicate to users.
ENGLISH
2 Intended use and application
2.1 Intended use
The ZM3 control panel is designed to command the following swing-gate operators ATI, AXO, FAST, FERNI, FROG, KRONO. The ZM3EC control panel is engineered to command CBX - F4000 industrial doors. It comes with its own safety release and buttons.
The use of this product for purposes other than as described above and installation executed in a manner other than as
instructed in this technical manual are prohibited.
2.2 Application
Make sure you respect the distances and cable diameters as shown in “cable types and minimal thicknesses” table. The overall power of the motors must not exceed 750 W.
3 Reference Standards
For its quality processes management Came Cancelli Automatici is ISO 9001:2000 certified, and for its environmental management it is ISO 14001 certified. Came designs and manufactures entirely in Italy. This product complies with the following standards: see Declaration of Compliance.
4 Description
This product is engineered and manufactured by CAME cancelli automatici s.p.a. and complies with current safety regulations. Guaranteed 24 months if not tampered with.
The control panel works on 230V a.c. of power, 50/60Hz frequency.
Both command and control devices and accessories are 24V powered. Warning! Accessories must not exceed 35 W overall.
All connections are protected by quick fuses, see table.
The input and output contact functions, the timing settings and users’ management, are set and viewed on the display, which is run by software.
TECHNICAL FEATURES
Power supply 230V - 50/60Hz
max. rated power 750W
Power draw when idling 85mA
Max power of 24V accessories 35W
Insulation rating II
Material ABS
Protection rating IP54
operating temperature -20 / +55°C
FUSES
protection: fuse type:
Electrolock 3.15A-F
Electronic board (power supply line) 5A-F
Accessories 1.6A-F
Control devices 630mA-F
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
2 - Manual code:
Pag.
Page 3
#!-%
3
319U75
2.0
4.1 Dimensions, spans and anchoring holes
(mm)

  
4.2 Main components
1 - Transformer 2 - M1 gearmotor condenser (black wires) 3 - M2 gearmotor condenser (red wires) 4 - Card fuse 5 - Accessories fuse 6 - Electrolock fuse 7 - Display 8 - Display lighting adjustment trimmer 9 - Memory roll card connector 10 - AF card connector 11 - R700 card connector 12 - Open contact error - warning LED 13 - Programming buttons 14 - Terminal board for connecting 15 - Terminal board for 230V a.c. power grid 16 - Line fuse 17 - 230V-power signalling LED 18 - STOP button 19 - CLOSE button 20 - OPEN button 21 - Safety block
ZM3EC
{
17
16
15
ZM3C

1

ZM3EC

!02%
#()5$%

 
2
4
3
2
1
6
4
5
3
7
ENGLISH
8
9
10
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
Manual code
3 -
Pag.
21
#!-%
14
20
19
11
12
13
18
Warning! Before acting on the machinery, cut off the
main power supply and disconnect any emergency batteries.
Page 4
4
319U75
2.0
5 Installation
Installation must be carried out by expert qualified personnel and in full observance of regulations in force.
5.1 Preliminary checks
Before installing do the following:
• Check that the panel’s anchoring point is protected from possible blows, and that the anchoring surface is solid. Also check that the anchoring is done using the appropriate bolts, screws etc.;
• Make sure you have a suitable omnipolar cut-off device with contacts more than 3 mm apart, and independent (sectioned off) power supply;
ENGLISH
Make sure that any connections inside the case (that provide continuance to the protective circuit) are fitted with extra insulation as compared to the other conductive parts inside;
• Make sure you have suitable tubing and conduits for the electrical cables to pass through and be protected against mechanical
damage.
5.2 Tools and materials
Make sure you have all the tools and materials you will need for the installation at hand to work in total safety and compliance with the current standards and regulations. The following figure illustrates the minimum equipment needed by the installer. Here are some examples.
5.3 Fixing and mounting the box
1) Fix the base of the panel in a protected area; we suggest
using round top Phillips recessed head screws of max. 6mm in diameter.


3) Assemble the pressure hinges.
2) Perforate the pre-punched holes and insert the cable glands with the corrugated tubing for the electrical cables to travel through.
N.B.: diameter of the pre-punched holes: 20 mm.
!!
4) Insert the pressure hinges into the box (on the left or right as you wish) and set them using the provided screws and washers.
They must slide in order to tum
15 mm~
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
4 - Manual code:
Pag.
Page 5
5
319U75
2.0
5) Snap the cover into place onto the hinges. Close it and fix it using the provided screws.
6 Electrical connections
6.1 Cable and type and section
6) After the adjustments and settings, fix the cover using the provided screws.
ENGLISH
Connections
Type
of cable
Control panel power supply
Motor power supply 3G x 1,5 mm
flashing lamp 2 x 1,5 mm
Transmitter photocells 2 x 0,5 mm
Receiver photocells 4 x 0,5 mm
FROR CEI
20-22
CEI EN
50267-2-1
Power supply to accessories 2 x 0,5 mm
Control and safety devices 2 x 0,5 mm
Length of cable
1 < 10 m
3G x 1,5 mm
Length of cable 10 < 20 m
2
2
2
2
2
2
2
3G x 1,5 mm
3G x 1,5 mm
2 x 1,5 mm
2 x 0.5 mm
4 x 0,5 mm
2 x 0,5 mm
2 x 0,5 mm
2
2
2
2
2
2
2
Length of cable
20 < 30 m
3G x 2,5 mm
3G x 2,5 mm
2 x 1,5 mm
2 x 0,5 mm
4 x 0,5 mm
2 x 1 mm
2 x 0,5 mm
2
2
2
2
2
2
2
Encoder connection 2402C 22AWG max. 30 m
Antenna connection RG58 max. 10 m
N.B.: If the cable length differs from that specified in the table, then you must determine the proper cable diameter based on the actual power draw from the connected devices and according to the CEI EN 60204-1 standards. For connections that require several, sequential loads, the sizes given on the table must be re-evaluated based on actual power draw and distances.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
When connecting products that are not specified in this manual, please follow the documentation provided with said products.
6.2 Electrical connections
Power supply to accessories
Terminals for powering the following accessories
- 24V A.C. Overall power allowed: 20W
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
Manual code
5 -
Pag.
Power supply
230V (A.C.) 50/60 Hz
:
+
-
Electrolock connection (12V - 15W max)
Possible output of the radio
receiver’s second channel
(N.O. socket).
Socket rating: 1A-24V (D.C.).
,
" "
Page 6
6
319U75
2.0
Signalling and Lighting devices
Signal Flasher (socket rating: 230V
- 25W max.) Flashes during opening and closing phases.
Cycle lamp: (contact rating: 230V – 60W max.) It lights up the driving area and stays on from the
ENGLISH
moment the gate begins to open until it is fully closed (including the automatic closing time). If automatic closing is not activated, the lamp stays on only during movement or for a set time of 5 minutes if used as a courtesy lamp.
Command devices
LT001 - Magnetic card reader
TSP00 - Transponder sensor
Open gate indicator-light
(socket rating: 24V - 3W max.).
Turns on when the gate is ajar or open.
It turns off when the gate is closed.
N.B.: insert the R700 emcoding card for the TSP00 sensors and LT001 card readers to be recognised.
ACCESS CONTROL
CAME
Stop button (N.C. contact) - Button to stop gate while excluding the automatic closing cycle. For movement to resume you must press the command button or transmitter button. N.B.: if contact is unused, select Disabled on the “FUNCTIONS” menu.
Key selector and/or opening button (N.O. contact) -
Gate opening command.
Key selector and/or partial opening button (N.O. contact) - Partial gate opening for pedestrian access.
Key selector and/or closing button (N.O. contact) - Gate closing command.
Black
Red
3'.$
CANCELLI AUTOMATICI
R700
Antenna with RG58
cable for the remote
control.
Key selector and/or commands button (N.O. contact) - Commands for opening and closing the gate – pressing the button or turning the key­switch, inverts the gate’s movement or stops it depending on how it is set on the 2-7 command in the “FUNCTIONS” menu.
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
6 - Manual code:
Pag.
Page 7
7
319U75
2.0
Gearmotor, mechanical stops
M1 - 230V A.C. gearmotor featuring delayed action on opening M2 - 230V A.C. gearmotor featuring delayed action on closing
FROG A
ATI
F4000
FERNI
F7001
Gearmotor, encoder
M1 - 230V A.C. gearmotor featuring delayed action on opening
FROG AE
White
Brown Green
KRONO
FROG A
KRONO
&!&# &!&#

ENCODER BENCODER A
M2 - 230V A.C. gearmotor featuring delayed action on closing
Green
Brown White
FERNI
ATI
F7001
ENGLISH
CBX
F4000
FROG AE
F7001E
Safety devices
Confi gure either (N.C.) contacts CX, CY or CZ, input for safety devices such as photocells, that comply with EN 12978 standards. See CX, CY or CZ input functions in:
- C1 «re-open during closing phase», When the gate leaf is closing, opening the contact triggers the inversion of the direction of movement until the gate leaf is fully open.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
- C2 «re-close during opening phase», When gate is opening, if the contact is opened it triggers an inversion of the direction until gate is fully closed;
- C3 «partial stop», Halts moving gate leaves and causes them to automatically close (if this functions has been selected);
- C4 «stand-by Obstacle», Halts the moving gate leaves causing them to start moving again once obstacle is removed.
- Deactivated, if contact is unused.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
AXOAXO
DIR photocells
RX
RX TX
./ # .#
DOC photocells
F7001E
TX

319U75
:
Manual code
7 -
Pag.
Page 8
8
319U75
2.0
Confi gure either (N.C.) contacts CX, CY or CZ,
input for EN 12978 compliant safety devices such as sensitive edges. See CX input functions in:
- C7 «Open while closing»,
During gate closing,
opening the contact causes inversion of movement until gate is fully open;
- C8 «close while opening», During gate opening, opening the contact causes inversion of movement until gate is fully close.
ENGLISH
- Deactivated, if contact is unused.
DF
DF with DFI connections monitor card
6.3 Electrical connection for the photocells functions test
(DOC)
./
#
.#

(DIR)
  48
&53)"),%M!
#
.#
48 
48
At each opening and closing command, the control board assesses the effi ciency status of the control devices (photocells). Any anomaly found is signalled with the fl ashing of the LED on the control panel. Consequently it cancels any commands coming from the remote control or the button.
Electrical connection to enable the photocell safety test:
- the transmitter and the receiver, must be connected as per the diagram;
- from the functions menu, select “safety tests” and select either CX - CY - CZ input/s to activate the test
.
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
8 - Manual code:
Pag.
Page 9
9
319U75
2.0
7 Programming
7.1 Description of display commands
The ESC key is for:
- exiting the menu;
- cancelling modifications.
- shifting from one menu item to another;
- increase or decrease values.
{
The < > keys are for:
7.2 Browsing the menu
To enter the menu, keep the ENTER key pressed for at least one second.
Lingua
Italiano
Þß
the <...> symbols on the display are for:
-pointing out the currently, selected item
{
The ENTER key is for:
- entering the menu;
{
- confirming and memorising set values.
{
Þß
LANGUAGE
English
ENGLISH
To select a menu item, mode using the greater than-lesser than keys...
also use the greater than-lesser than keys for the “sub-menus”...
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
If the <> are on the TIME
Cycle Time
Þß
01/2009 © CAME cancelli automatici s.p.a. -
2.0
Þß
ver.
90s
Cycle Time
100s
function, you may modify the value.
...then press ENTER to confirm...
Þß
Þß
LANGUAGE
English
Þß
Þß
FUNCTIONS
English
TIMING ADJ.
Þß
A.C.T.
90s
Cycle Time
90s
...to exit the menu, wait 30 seconds, or press ESC, until start screen is displayed.
...then press ENTER
...then press ENTER
To increase or reduce values, use the greater than-lesser than keys...
319U75
:
Manual code
9 -
Pag.
N.B.: when the menu is active, the system cannot be used.
Page 10
10
319U75
2.0
7.3 Menu structure
< LANGUAGE >
< FUNCTIONS >
< ENCODER >
< TIMING ADJ >
ENGLISH
< USERS >
ENTER
>
ENTER
>
ENTER
>
ENTER
>
ENTER
< Add User >
>
<English> <Francais>
>
See detailed functions on pages 17, 18, 19 and 20 (the “ENCODER” function, appears only if selected from the “Config.” function in the FUNCTIONS menu.
confirm? (no)
ENTER
>
confirm? (yes)
>
>
< T.C.A. >
>
<Pedestrian ACT>
>
<Deutsch>
>
<Espanol><Italiano>
ENTER
>
ENTER
>
< 0s. >
>
< 0s. >
>
< 300s.>
>
< 300s.>
>
Choose User
<001:-U001->
< Mod. name >
>
< Mod. Code >
>
<Relate d Fu nc.>
>
>
< Remove Usr. >
>
ENTER
ENTER
ENTER
ENTER
>
Sel.Utente
<002:-U002->
Choose User
<001:-U001->
>
Sel.Utente
<002:-U002->
Choose User
<001:-U001->
>
Sel.Utente
<002:-U002->
Choose User
<001:-U001->
>
Sel.Utente
<002:-U002->
>
< Cycle Time >
>
< Op. Delay M1 >
>
>
< Cl. Delay M2 >
>
>
<Preflashing T.>
>
>
< Lock time >
>
ENTER
ENTER
ENTER
ENTER
ENTER
< 10s. >
>
< 150s.>
< 1s. >
>
< 1s. >
>
< 1s. >
>
< 1s. >
>
>
>
< 10s. >
>
< 60s >
>
< 60s.>
>
< 5s. >
<Res tore backup>
< INFO >
>
< TEST MOT. >
<D elete all U s r>
>
< Backup data >
>
>
ENTER
ENTER
ESC
confirm? (no)
ENTER
>
confirm? (yes)
confirm? (no)
ENTER
>
confirm? (yes)
confirm? (no)
ENTER
>
confirm? (yes)
< Version >
fw. 3.0
TEST MOT.
< <=M1 M2=> >
>
>
>
< No. of Runs >
>
>
< Ram hit time >
< Ped.opening >
<Slow down time>
16480
< System Reset >
ENTER
>
ENTER
>
ENTER
>
< Standby Msg. >
>
< 1s. >
>
< 5s. >
>
< 0s. >
>
>
>
< 10s. >
>
< 60s.>
>
< 30s.>
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
10 - Manual code:
Pag.
Page 11
11
319U75
2.0
< AutoClose >
>
ENTER
< Turn on > < Disabled >
>
>
<M ain tain e d Act>
>
< Obstacle Det. >
>
< Safety d.Te s t >
>
< Preflashing >
>
<Ram hit funct.>
>
< Total Stop >
>
< CX Input >
>
< CY Input >
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
< Disabled > < Turn on >
< Turn on > < Disabled >
< Disabled >
>
<CX+ CY+C Z>
< Turn on > < Disabled >
< Turn on > < Disabled >
< Turn on > < Disabled >
< Disabled >
< C8 >
< Disabled >
>
>
>
< CX >
>
< CY+CZ >
>
>
>
>
>>
>
>
< C1 >
< C7 >
< C1 >
>
< CY >
>
< CX+CZ >
>
>
>
>
< C2 >
>
>
< C2 >
>
<when close>
>
< CZ >
>
< C4 >
>
>
< CX+CY >
< C3 >
< C3 >
>
>
ENGLISH
>
>>
>
< CZ Input >
>
< Cl. Thrust >
>
< Lock >
>
< Config. >
>
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
< endstop >
>
< cmd 2-7 >
>
< cmd 2-3P >
>
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
< Slow run >
<Op.-Stop- Cl.>
<Pedestrian>
< C8 >
< Disabled >
< C8 >
< Turn on > < Disabled >
< Turn on > < Disabled >
>
>
>
<Lim it s witch>
< N.C. > < N.A. >
>
>
>
< C7 >
>
< C1 >
>>
< C7 >
< Fcap-RallCh >
>>
<Open-Close>
< Partial >
>
>
>
< C2 >
>
>
>
< C4 >
< C4 >
< encoder >
< Time of Run >
>
>
>
>
>
< C3 >
>
>
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
Manual code
11 -
Pag.
< lamp E3 >
<output B1-B2>
< No. Motors >
>
<Slow Down Spd>
ENTER
>
ENTER
>
ENTER
>
ENTER
< Cycle >
<Monostable>
< M1 + M2 >
-ooo+
<
>
< Courtesy >
>
<Bistable>
>
< M2 >
>
>
-ooo+
<
>
>
>
>
>
Page 12
12
319U75
2.0
7.4 Main menu
FUNCTIONS
TIMING ADJ.
USERS
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
h
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
TEST MOT.
< LANGUAGE >
English
Press ENTER for 1 second
< TEST MOT. >
ENGLISH
7.5 Language menu
Select language: selects among the languages displayed.
< LANGUAGE >
English
LANGUAGE
< English >
< FUNCTIONS >
It appears only if selected from the “Config.”
Section in the FUNCTIONS menu.
< INFO >
LANGUAGE
< Francais >
LANGUAGE
< Italiano >
< ENCODER >
< TIMING ADJ. >
< USERS >
250
Max. 250 users
LANGUAGE
< Deutsch >
LANGUAGE
< Espanol >
7.6 Functions menu
Automatic Closing: activates or deactivates the automatic closing function. The automatic closing timer activates at each opening endpoint. The predetermined time may be adjusted, and is in any case dependent on any safety devices that may activate; and it does not activate after a total safety “stop” or during a power outage.
< AutoClose >
FUNCTIONS
Turn on
X 2
Maintained action: the gate works by keeping the button pressed (button 2-3 for opening, button 2-4 for closing, or if set to the “On Closing” function, only with button 2-4.
AutoClose
< Turn on >
AutoClose
< Disabled >
FUNCTIONS
<M ain tain e d Act>
Disabled
X 2
Maintained Act
< Disabled >
Maintained Act
< when close >
Maintained Act
< Turn on >
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
12 - Manual code:
Pag.
Page 13
13
319U75
2.0
Obstacle detected: when motor is stopped (gate closed or after a total stop command) it prevents any movement if safety devices,
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
TIMING ADJ.
USERS
O
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
<
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
such as photocells, detect any obstacles.
X 2
Obstacle Det.
< Disabled >
FUNCTIONS
<Obstacle Det.>
Disabled
X 2
Obstacle Det.
< Turn on >
Safety test: allows the card to check the efficiency of any safety devices (i.e. photocells) after every opening or closing command.
LANGUAGE >
FUNCTIONS
X 3
<Safety d.Test>
Disabled
Safety d.Tes t < Disabled >
Safety d.Tes t
< CX+CY+CZ >
Safety d.Tes t
< CX >
Safety d.Tes t
< CY >
ENGLISH
X 2
Safety d.Tes t
< CX+CZ >
Safety d.Tes t
< CX+CY >
Safety d.Tes t
< CZ >
Pre-flashing: after an opening or closing command, the flashing light, connected to W-E, starts flashing before the gate begins its run (to set the time, see “Pre-flashing timing” from the Adjust Timings menu
X 4
Preflashing
< Disabled >
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
FUNCTIONS
< Preflashing >
Disabled
X 2
Ram blow: before any opening run, the gate leaves will press onto the mechanical endstop for a few seconds, to help release the elec­trolock (to set the time, see “Starting ram timing” in the Adjust Timings menu).
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
FUNCTIONS
X 5
<Ram hit funct.>
Disabled
Ram hit funct.
< Disabled >
X 2
Manual code
13 -
Pag.
NF
Page 14
14
319U75
2.0
Total Stop: this function stops the gate and consequently excludes any automatic closing cycle; for movement to resume, you need to
< LANGUAGE >
EnglishEnglish
TIMING ADJ.
IMING ADJ
USERS
TEST MOT.
TEST MOT.
< LANGUAGE >
EnglishEnglish
TIMING ADJ.
IMING ADJ
USERS
TEST MOT.
TEST MOT.
< LANGUAGE >
EnglishEnglish
TIMING ADJ.
IMING ADJ
USERS
TEST MOT.
TEST MOT.
use the keypad or transmitter. Insert safety device on [1-2]; Insert the safety device on [1 -2]; if unused, select “Deactivated”
X 6
FUNCTIONS
< Total Stop >
Turn on
Total Stop
< Turn on >
X 2
Total Stop
ENGLISH
< Disabled >
CX input: the N.C. safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when
opening), C3 (partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges) or, be deactivated. See safety devices on electrical connections.
X 7
CX Input
< C1 >
< C2 >
FUNCTIONS
NFO
< CX Input >
Disabled
CX Input
< Disabled >
CX Input
< C8 >
CX Input
X 2
CX Input
< C7 >
CX Input
< C4 >
CX Input
< C3 >
CY input: safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when opening), C3
(partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges) or, be deactivated. See safety devices on electrical connections.
X 8
CY Input
< C1 >
CY Input
< C2 >
FUNCTIONS
< CY Input >
Disabled
CY Input
< Disabled >
CY Input
< C8 >
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
X 2
CY Input
< C7 >
CY Input
< C4 >
CY Input
< C3 >
319U75 ver.
14 - Manual code:
Pag.
Page 15
15
319U75
2.0
CZ input: safety contact input can take on the following functions: C1 (re-opening when closing), C2 (re-closing when opening), C3
< LANGUAGE >
English
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
h
TIMING ADJ.
USERS
< LANGUAGE >
English
TIMING ADJ.
USERS
< LANGUAGE >
English
h
TIMING ADJ.
TEST MOT.
TEST MOT
(partial stop), C4 (obstacle stall), C7 (re-opening when closing, for sensitive edges), C8 (re-closing when opening, for sensitive edges) or, be deactivated. See safety devices on electrical connections.
X 9
< CZ Input >
Disabled
FUNCTIONS
CZ Input
< Disabled >
CZ Input
< C1 >
CZ Input
< C8 >
CZ Input
< C2 >
X 2
CZ Input
< C7 >
CZ Input
< C4 >
CZ Input
< C3 >
Closing thrust: at the endpoint stage during closing, the gearmotors perform a final closing-thrust of the doors for a few seconds.
X 10
FUNCTIONS
< Cl. Thrust. >
Disabled
Cl. Thrust.
< Disabled >
X 2
Cl. Thrust.
< Turn on >
Lock: to lock the gate leaves. Required for gate leaves longer than 2.50 m.
ENGLISH
X 11
< Lock >
FUNCTIONS
Disabled
< Disabled >
X 2
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Deceleration configuration: configuring decelerations when opening or closing:
- slow run: decelerations when opening and closing;
- Fcap-RallCh.: end stop when opening and deceleration when closing;
- ecoder: managing decelerations, obstacle detection and sensitivity; (FROG-AE)
- Time of Run: timed end stop (default function); (FROG-A, FERNI 230V, ATI 230V, FAST 230V and KRONO)
- Limit switch (endstop): opening and closing endstop. (C-BX and F4000)
X 12
Config.
< Slow run >
Config.
<Lim it s witch>
<Time of Run>
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
Manual code
15 -
Pag.
< Config. >
Slow run
FUNCTIONS
USERS
X 2
Lock
Lock
< Turn on >
Config.
< Fcap-RallCh >
Config.
< encoder >
Config.
Page 16
16
319U75
2.0
Endstop: configure the endpoints are normally closed or open contacts.
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
N.B.: this function appears only if selected from the “Config.” function in the FUNCTIONS menu.
X 13
< endstop >
FUNCTIONS
N.C
endstop
< N.C >
X 2
endstop
< N.A >
ENGLISH
Command 2-7: setting the 2-7 contact to step-by- step mode (open-close) or sequential (open-stop-close-stop).
X 14
cmd 2-7
<Op.-Stop- Cl.>
FUNCTIONS
< cmd 2-7 >
Op.-Stop-Cl.
X 2
cmd 2-7
<Open-Close>
Command 2-3P: setting the 2-3P contact to pedestrian opening (second gate leaf opens fully) or partial (second gate leaf opens partially depending on the time set on “Partial opening” from the Adjust Times menu).
< LANGUAGE >
FUNCTIONS
X 15
< cmd 2-3P >
Pedestrian
cmd 2-3P
< Pedestrian >
X 2
E3 lamp: configuring the lamp connected to E-E3:
- cycle: outdoor lamp, which can be positioned at leisure, for better illumination in the parking/driveway area. It stays on from the moment the gate leaf begins to open, until it is fully closed (including automatic closing time). In case the automatic closing function is not inserted, it stays on only during gate movement.
- courtesy: outdoor lamp, which can be positioned at leisure, for better illumination in the parking/driveway area. It stays on for a set time of 5 minutes.
X 16
FUNCTIONS
< lamp E3 >
Cycle
lamp E3
< Cycle >
cmd 2-3P
< Partial >
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
X 2
lamp E3
< Courtesy >
319U75 ver.
16 - Manual code:
Pag.
Page 17
17
319U75
2.0
B1-B2 output: setting contact B1-B2 to MONO-STABLE or BI-STABLE (switch) mode.
< LANGUAGE >
English
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
TIMING ADJ.
USERS
TEST MOT.
TEST MOT
X 17
FUNCTIONS
< output B1-B2 >
Monostable
X 2
output B1-B2
< Monostable
output B1-B2
< Bistable >
Slow Down: setting the deceleration speed when opening or closing, or, only when closing if said deceleration is configured as (Fcap­RallCh.). N.B.: this function only appears if the decelerations are selected.
X 18
FUNCTIONS
X 2
<Slow Down Spd.>
-ooo+
Slow Down Spd.
<
-ooo+
Slow Down Spd.
<
>
-ooo+
ENGLISH
>
Number of motors: setting the number of motors, either one or two, depending on the number of gate leaves installed on the system.
X 19
FUNCTIONS
< No. Motors >
M1 + M2
No. Motors
< M1 + M2 >
X 2
No. Motors
< M2 >
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Motor Type: setting up the type of swing gate motor installed in the system.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
< Motor Type >
FROG
FUNCTIONS
Motor Type
< FROG >
Motor Type
< AXO >
319U75
:
Manual code
17 -
Pag.
X 2
Motor Type
< FAST >
Page 18
18
319U75
2.0
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
EnglishEnglish
FUNCTION
TIMING ADJ.
USERS
English
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
English
FUNCTION
TIMING ADJ.
USERS
7.7 Encoder Menu (the ENCODER menu, appears only if selected from the “Config.” function in the FUNCTIONS menu.)
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
N.B.: before setting the functions in the encoder menu, run the gearmotor checks to verify the proper turning direction.
Sensitivity: the obstacle detection function is activated during gate operation and deceleration.
Se n sibility
< Turn on >
ENGLISH
ENCODER
< Se n s ibility >
Turn on
X 2
Gate operation sensitivity: this adjusts the obstacle detection sensitivity during opening and closing gate operation. N.B.: this function appears only if the “sensitivity” function is activated in the ENCODER menu.
Sensib. Run
-oooooooo+
<
ENCODER
< Sensib. Run >
-oooooooo+
X 2
Deceleration sensitivity: it adjusts the obstacle detection sensitivity during opening and closing gate deceleration. N.B.: this function appears only if the “sensitivity” function is activated in the ENCODER menu.
X 2
Se n sibility
<Disabled>
>
Sensib. Run
-oooooooo+
<
>
Sensib. Decel.
-oooooooo+
<
>
ENCODER
<Sensib. Decel.>
-oooooooo+
X 2
Sensib. Decel.
-oooooooo+
<
Encoder Deceleration: this activates the opening and closing deceleration starting points.
< LANGUAGE >
X 3
Slow run Enc
< ON
>
ENCODER
< Slow run Enc >
ON
X 2
Slow run Enc
< OFF
M1 opening deceleration%: this adjusts the (M1) first motor’s deceleration starting point before the opening endpoint. The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28. N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 4
>
>
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
ENCODER
X 2
< M1 Slow.AP.% >
10
M1 Slow.A P.%
< 10
>
M1 Slow.A P.%
< 11
319U75 ver.
18 - Manual code:
>
Pag.
Page 19
19
319U75
2.0
M1 closing deceleration%: this adjusts the (M1) first motor’s deceleration starting point before the closing endpoint.
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERSNFO
< LANGUAGE >
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
USERS
The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28. N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 5
M1 Slow.CH %
< 10
>
ENCODER
< M1 Slow.CH % >
10
X 2
M1 Slow.CH %
< 11
M2 opening deceleration%: this adjusts the (M2) second motor’s deceleration starting point before the opening endpoint. The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28. N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 6
M2 Slow.AP %
< 10
>
ENCODER
< M2 Slow.AP % >
10
X 2
M2 Slow.AP %
< 11
ENGLISH
>
>
M2 closing deceleration %: this adjusts the (M2) second motor’s deceleration starting point before the closing endpoint. The deceleration starting point is calculated as a percentage (from 1% to 40% of a full gate run). See illustration on page 28. N.B.: this function appears only if it is activated in the “decel. Enc” function in the ENCODER menu.
X 7
M2 Slow.CH %
< 10
>
ENCODER
< M2 Slow.CH % >
10
X 2
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
M2 Slow.CH %
< 11
M1 closing acceleration %: this adjusts the (M1) first motor’s percentage rate of approach to the final closing and opening points before reaching the opening and closing endpoints. The percentage rate of approach to (goes from 1% to 15% of the full gate run). See illustration on page 28.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
Manual code
19 -
Pag.
ENCODER
X 2
X 8
< M1 Appr.CH % >
5
M1 Appr.CH %
< 5
>
M1 Appr.CH %
< 6
>
>
Page 20
20
319U75
2.0
M2 closing acceleration %: this adjusts the (M2) second motor’s percentage rate of approach to the final closing and opening points
< LANGUAGE >
EnglishEnglish
FUNCTION
TIMING ADJ.
USERS
TEST MOT.
< LANGUAGE >
EnglishEnglish
FUNCTION
TIMING ADJ.
USERS
TEST MOT.
< LANGUAGE >
English
h
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
h
FUNCTION
USERS
TEST MOT.
TEST MOT
before reaching the opening and closing endpoints. The percentage rate of approach to (goes from 1% to 15% of the full gate run). See illustration on page 28.
X 8
ENGLISH
ENCODER
ENCODER
X 2
X 2
X 9
< M2 Appr.CH % >
5
< Set Encoder >
M2 Appr.CH %
< 5
Set Encoder
<confirm?(no)>
M2 Appr.CH %
< 6
Set Encoder
<confirm?(yes)>
>
See detailed description on page 28
>
7.8 Time setting menu
Automatic closing: to set the waiting time when gate is in the open position. Once this time is elapsed, the gate closes automatically. The waiting time can be set to between 0” and 300”.
< A.C.T. >
TIMING ADJ.
10s.
X 2
Automatic Pedestrian Closing: waiting time of the (M2) second gate leaf when in the open position. Once this time interval has elapsed, the gate automatically closes. The waiting time interval can go anywhere from 0” to 300”.
TIMING ADJ.
<Pedestrian ACT>
10s.
A.C.T.
< 10s. >
A.C.T.
< 11s. >
Pedestrian ACT
< 10s. >
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
X 2
Pedestrian ACT
< 11s. >
20 - Manual code:
Pag.
Page 21
21
319U75
2.0
Cycle time: the working time of the motor during opening or closing phases is anywhere from 10” to 150”.
< LANGUAGE >
English
English
FUNCTIONS
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTIONS
FUNCTION
USERS
TEST MOT.
TEST MOT
<
English
English
FUNCTIONS
FUNCTION
U
S
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTIONS
FUNCTION
USERS
TEST MOT.
TEST MOT
X 2
TIMING ADJ.
< Cycle Time >
90s.
Cycle Time
< 90s. >
X 2
NFO
Cycle Time
< 91s. >
M1 delayed opening: the waiting time of the (M1) first gate lead, unlike the (M2) second one, after each opening command. The waiting time can be set to between 0” and 10”.
X 3
TIMING ADJ.
< Op. Delay M1 >
2s
Op. Delay M1
< 2s >
X 2
Op. Delay M1
< 3s >
ENGLISH
M2 delayed closing: the waiting time of the (M2) second gate leaf, unlike the (M1) first one, after each closing command. the waiting
time can be set to between 0” and 60”.
LANGUAGE >
X 4
TIMING ADJ.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
SER
< Cl. Delay M2 >
2s
X 2
Cl. Delay M2
< 2s >
Cl. Delay M2
< 3s >
Pre-flashing time: after an opening or closing command is given, the flasher connected to “W-E), flashes for between 1” and 60”, before the gate begins to move.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
TIMING ADJ.
319U75
:
X 5
<Preflashing T.>
5s.
Preflashing T.
< 5s. >
X 2
Preflashing T.
Manual code
21 -
Pag.
< 6s. >
Page 22
22
319U75
2.0
Lock time: the time required for releasing the electro-lock after each opening command. The time of operation can be set to between
< LANGUAGE >
English
English
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTION
USERS
TEST MOT.
TEST MOT
< LANGUAGE >
LANGUAG
English
FUNCTION
NS
USERS
TEST MOT.
1” and 5”.
X 6
TIMING ADJ.
< Lock time >
2s.
Lock time
< 2s. >
X 2
ENGLISH
Lock time
< 3s. >
Ram hit time: the gearmotor’s thrust time when fully closing after each opening command. The thrust time can be set to between 1” and 10”.
X 7
TIMING ADJ.
NFO
< Ram hit time >
2s.
X 2
Ram hit time
< 2s. >
Ram hit time
< 3s. >
Partial opening: the opening time of the (M2) second gate leaf. The time can be set to between 5” and 60”.
X 8
TIMING ADJ.
< Ped. opening >
5s.
X 2
Ped. opening
< 5s. >
Ped. opening
< 6s. >
Slow down time: the gate leaf’s deceleration time before every endpoint. The time can be set to between 0” and 30”. N.B.: this function only appears if the decelerations are selected.
X 9
TIMING ADJ.
< Slow down time >
5s.
Slow down time
< 5s. >
X 2
Slow down time
< 6s. >
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
22 - Manual code:
Pag.
Page 23
23
319U75
2.0
7.9 Users Radio Menu
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
TEST MOT.
TEST MOT
<
English
English
FUNCTION
TIMING ADJ.
TEST MOT.
TEST MOT
< LANGUAGE >
English
English
FUNCTION
TIMING ADJ.
TEST MOT.
TEST MOT
Add User: to create a new user and assigned function (max. 250 users).
< Add User >
X 2
USERS
Mod. Name: to change a user number or existing name to another name.
LANGUAGE >
< Mod. name >
X 2
USERS
Add User
<confirm? (no) >
ENGLISH
Add User
<confirm? (yes)>
See detailed description on page 26
Choose User
< 001:--001-- >
Choose User
< 002:--002-- >
Mod. Code: to change a user’s current code.
X 2
< Mod. Code >
X 2
USERS
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
Related Function: to change the function assigned to the user.
X 3
< Related Func >
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
USERS
X 2
See detailed description on page 26
Choose User
< 001:--001-- >
Choose User
< 002:--002-- >
See detailed description on page 27
Choose User
< 001:--001-- >
Choose User
< 002:--002-- >
Manual code
23 -
Pag.
See detailed description on page 27
Page 24
24
319U75
2.0
Remove user: to remove an exisiting user. Confirm the use you wish to remove with the ENTER key.
< LANGUAGE >
English
FUNCTIONS
TIMING ADJ.
TEST MOT.
< LANGUAGE >
English
English
FUNCTIONS
TIMING ADJ.
TEST MOT.
TEST MOT.
< LANGUAGE >
English
English
FUNCTIONS
TIMING ADJ.
TEST MOT.
< LANGUAGE >
English
English
FUNCTIONS
TIMING ADJ.
TEST MOT.
X 4
< Remove Usr. >
Choose User
< 001:--001-- >
X 2
USERS
ENGLISH
Delete all user: to cancel all registered users. Confirm cancellation of all users with ENTER.
X 5
<D elete all U s r>
Dele te all U sr
<confirm? (no) >
X 2
Choose User
< 002:--002-- >
Remove Usr.
<confirm? (no) >
Remove Usr.
<confirm? (yes)>
USERS
Dele te all U sr
<confirm? (yes)>
Backup data: to save the users in the memory roll. Confirm saving of users on the memory roll with ENTER.
X 6
< Backup data >
Backup data
<confirm? (no) >
X 2
USERS
Backup data
<confirm? (yes)>
Restore backup: to load the data saved on the memory roll onto card.
X 7
Backup data
WRITE:250
USERS
<Restore backu p>
X 2
Restore backu p
<confirm? (no) >
Restore backu p
<confirm? (yes)>
Restore backu p
READ:250
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
24 - Manual code:
Pag.
Page 25
C
A
M
E
25
319U75
2.0
7.10 nfo Menu
< LANGUAGE >
English
FUNCTION
TIMING ADJ.
USERS
< LANGUAGE >
English
FUNCTION
TIMING ADJ.
USERS
TEST MOT.
Version: to view software version. Number of gate runs: to view the number of runs performed by the gate. Starting Mssg: to view the starting message, confirm with ENTER to change text. Use the ENTER key to move the cursor forward, ESC
to move it backwards and <> to select the letter of number. Confirm the text by pressing the ENTER key for a few seconds.
System reset: it resets the system to its original settings. Press ENTER key to confirm.
< Version >
fw : 3.0
< System Reset >
INFO
7.11 Motor test menu
TEST MOT.: Test to check the proper direction of the gearmotors.
Gate leaf opening
run of the first (M1)
gearmotor. If the
direction is wrong,
invert the motor’s
phases.
< No. of Runs >
< TEST MOT. >
<=M1 M2=>
10
ENGLISH
< Standby Msg. >
- WWW.CAME.IT ZM3E
Gate leaf opening run of the second (M2) gearmotor. If the direction is wrong, invert the motor’s phases.
TEST MOT.
7.12 Decoding card
Connect the required (R700, AF43S cards) to insert, change, remove and command the operator via transmitter, card or transponder. Insert the memory roll to save and load all setting including users registered by another card.
AF Card
TFM
TOP
ATOMO / TWIN
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
319U75
:
Manual code
25 -
Pag.
ACCESS CONTROL
TSP00 LT001
Lingua
Italiano
Þß
R700
CANCELLI AUTOMATICI
R700 Card
Memory roll
Frequency/MHz Card Transmitter
FM 26.995 AF130 TFM
FM 30.900 AF150 TFM
AM 26.995 AF26 TOP
AM 30.900 AF30 TOP
AM 433.92 AF43S TAM / TOP
AM 433.92 AF43TW TWIN
AM 40.685 AF40 TOUCH
AM 868.35 AF868 TOP
TAM
CA
TWIN
ATOMO
E
M
TOUCH
Page 26
26
319U75
2.0
7.13 Inputting users
1) From the Users menu, select “Add User”. Press ENTER to confirm.
ENGLISH
3) Choose which function to assign to
the user....
Þß
Add User
2) Select “ confirm (yes)” and press ENTER key to confirm.
Related Func.
Þß
2-7
4) .... will ask to input
a code. Send the code with the radio­command button or slide-through card or transponder.
Add User
confirm? (yes)
Þß
Waiting Code
>>>>
ACCESS CONTROL
5) ... once the code is inputted, the user name will come up showing the type of command that was memorised...
7.14 Changing users
1) From the Users menu, choose “Mod. name”. Press ENTER to confirm.
--001--
radio
... or if the code is already inputted, “Existing Code” will appear.
Mod. name
Þß
2) Choose the user number or name you wish to change the text of and press ENTER to confirm.
Code exist
001:--001--
Choose User
001:--U001--
Þß
3) Use the ENTER key to move the cursor forward, ESC to move it backwards and < > to select the letter or number.
Mod. name
--001--
4) Confirm the text by pressing the ENTER key for a few seconds.
Mod. name
JOHN
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
26 - Manual code:
Pag.
Page 27
27
319U75
2.0
7.15 Changing code
1) From the Users menu, choose “Mod. Code”. Press ENTER to confirm.
3) .... you will be
asked to input a code. Send the code using the transmitter button or the slide ­through card or the transponder.
Mod. Code
Waiting Code
>>>>
Choose User
2) Choose the user name for which you wish to change the
001:--U001--
Þß
Choose User
002:--U002--
Þß
code and press ENTER to confirm.
ENGLISH
4) .. once the code is inputted, the user name will come up
--002--
radio
showing the type of command that was
ACCESS CONTROL
memorised...
7.16 Function assigned to the user
1) From the Users menu, choose “Related Fuc.”. Press ENTER to confirm.
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
3) Choose the new function to assign to the user. Press ENTER to confirm.
01/2009 © CAME cancelli automatici s.p.a. -
2.0
ver.
Þß
Þß
Þß
Related Func.
Related Func.
2-7
Related Func.
open
5) Select “ confirm (yes)” and press ENTER key to confirm.
2) Choose the user name fo which you wish to change the command function and press ENTER to confirm.
4) Choose “confirm (yes)” and press ENTER to confirm.
Mod. Code
confirm? (yes)
Þß
Choose User
001:--U001--
Þß
Choose User
002:--U002--
Þß
Related Func.
confirm? (yes)
Þß
319U75
:
Manual code
27 -
Pag.
Page 28
28
319U75
2.0
7.17 Gate run calibration
N.B. before calibrating the gate run, check that the manoeuvring area is free of any obstacles and check the proper direction of rotation of the gearmotors. (para. 7.11)
1) From the Encoder menu, select “Set Encoder”. Press ENTER to confirm.
ENGLISH
3) the gate leaf of the first motor will perform a closing run until fully
closed.....
5) …then, the gate leaf of the second motor, will perform and opening run until fully open…
Set Encoder
Þß
2) Select “confirm (yes) and press ENTER to confirm.
Set Encoder
Close 1
4) …then, the gate leaf of the
0
0
second motor will perform the same manoeuvre…
Set Encoder
Open 2
6) ...after which,
0
0
the gate leaf of the first motor will perform the same manoeuvre…
Set Encoder
confirm? (no)
Þß
0
0
Set Encoder
confirm? (yes)
<>
Set Encoder
Close 2
0
Set Encoder
Open 1
0
7) When the procedure is finished, the display will show “Set Encoder ok” for a few
Set Encoder
OK
seconds.
7.18 Error messages
-“encoder ERROR”: check proper connections or functionality of the device and possibly even the motor’s torque”
-“safety d. test ERROR”: malfunctioning of safety devices, check proper functioning of connections and functionalities;
-“end stop ERROR”: check proper connections on end point connections or functionality of devices;
-“cycle time ERROR”: check the working time settings, the set time may be insufficient to complete the duty cycle.
- Safety STOP, C1, C3, C4”: check proper functioning of connections and functionalities of devices.
2.0 01/2009 © CAME cancelli automatici s.p.a. - The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
319U75 ver.
28 - Manual code:
Pag.
Page 29
29
319U75
2.0
7.19 Illustration depicting the areas and points of deceleration and final opening and closing approaches per encoder device.
Note: the areas and points of deceleration and fi nal opening and closing approaches are tested according to the parameters set forth by Technical Norms EN12445 and EN12453 regarding compatibility of impact forces generated by moving gate leaves.
A = Area of movement at normal speed B* = Run zone at decelerated speed C = Encoder intervention zone with
0
movement inversion
D= Encoder intervention zone with
movement stop
B
E = Opening deceleration beginning point
(M1 Open Deceler %)
F = Closing deceleration beginning point
(M1 Close Deceler %)
G = Opening deceleration beginning point
(M2 Open Deceler %)
B
A
C
H = Closing deceleration beginning point
(M2 Close Deceler %)
I** = Closing and opening fi nal phase
beginning point (M1 Final Close %)
L** = Closing and opening fi nal phase
beginning point (M2 Final Close %)
D
E
M
I
M= endstops
* Minimum 600 mm from the Final full stop. **Set the function’s fi nal phase % “M1 Final Close” for the fi rst (M1) mtors and “M2 Final Close” for the second (M2) motor from the
“ENCODER” menu so as to obtain a distance of between 1 and 50 mm maximum from the fi nal full stop.
M
D
I
F H
D
L
B
A
C
B
G
L
0
ENGLISH
D
M
8 Demolition and disposal
In its premises, CAME CANCELLI AUTOMATICI S.p.A. implements an Environmental Management System certifi ed in
compliance with the UNI EN ISO 14001 standard to ensure environmental protection. Please continue our efforts to protect the environment—which CAME considers one of the cardinal elements in the development of its operational and market strategies—simply by observing brief recommendations as regards disposal:
DISPOSAL OF PACKAGING
The packaging components (cardboard, plastic, etc.) are all classifi able as solid urban waste products and may be disposed of easily, keeping in mind recycling possibilities. Prior to disposal, it is always advisable to check specifi c regulations in force in the place of installation.
PLEASE DISPOSE OF PROPERLY!
PRODUCT DISPOSAL
Our products are made up of various types of materials. Most of them (aluminium, plastics, iron, electrical wires, etc.) may be disposed of in normal garbage collection bins and can be recycled by disposing of in specifi c recyclable material collection bins and disposal in authorized centres. Other components (electrical boards, remote control batteries, etc.), however, may contain polluting substances. They should therefore be removed and given to qualifi ed service companies for proper disposal. Prior to disposal, it is always advisable to check specifi c regulations in force in the place of disposal.
PLEASE DISPOSE OF PROPERLY!
The data and information reported in this installation manual are susceptible to change at any time and without obligation on CAME cancelli automatici s.p.a. to notify users.
9 Manufacturer’s warranty
MANUFACTURER’S DECLARATION OF CONFORMITY
CAME Cancelli Automatici S.p.A.
via Martiri della Libertà, 15 31030 Dosson di Casier - Treviso - ITALY tel (+39) 0422 4940 - fax (+39) 0422 4941 internet: www.came.it - e-mail: info@came.it
Declares under its own responsibility that the equipments for automatic garage doors and gates listed below:
01/2009 © CAME cancelli automatici s.p.a. -
… comply with the National Law related to the following European Directives and to the applicable parts of the following Standards.
2.0
ver.
2006/95/EC L 2004/108/EC ELECTROMAGNETIC COMPATIBILITY DIRECTIVE EN 60335-1 EN 61000-6-2
319U75
:
EN 13241-1 EN 61000-6-3
ZM3E - ZM3EC
OW VOLTAGE DIRECTIVE
Pursuant to the Low Voltage Directive 2006/95/EC
Do not use the equipment specifi ed here above, before
In full compliance with the Machinery Directive 98/37/EC
IMPORTANT WARNING!
completing the full installation
MANGING DIRECTOR
Mr. Andrea Menuzzo
Manual code
29 -
Reference code to request a true copy of the original: DDF L EN Z002e
Pag.
Page 30
CAME F ra nce S.a.
CAME France S.a.
Nanter re Cedex -
CAME G mb h Seefeld
Seefel d
CAME A ut omatismes S.a.
Marsei ll e -
CAME G mb h
Korn ta l
CAME A ut omatismos S.a.
Madri d -
CAME A me ricas Aut omation L lc
Sunris e
CAME A ut omatismos Cataluny a S.a.
Sant Vi cenc Del Horts -
CAME M id dle East Fzco
Dubai -
Paf - CA ME
Rio D e Mouro -
CAME P ol ska Sp.Zo .o
Warsza wa -
CAME U ni ted Kingd om Ltd.
Nottin gh am
S.c. C AM E Romania S.r.l.
Bucare st -
CAME B el gium Sprl
Lessi ne s -
CAME R us sia
Moskva
CAME C an celli Aut omatici S .p .a.
Dosso n Di Casier
CAME N or d s.r.l.
Colog no Monzese
CAME S er vice Ital ia S.r.l.
Dosso n Di Casier
Assist en za Tecnic a 800 295 83 0
CAME S ud s.r.l.
Napol i
En glish
119EU 7 5
2.0
7, Rue Des Haras Z.i. Des Hautes Patures 92737
Nanterre Cedex - FRANCE
(+33) 1 46 13 05 05
(+33) 1 46 13 05 00
CAME Gmbh Seefeld
Akazienstrasse, 9
16356
Seefeld
Bei Berlin - DEUTSCHLAND
(+49) 33 3988390
(+49) 33 39883985
CAME Automatismes S.a. 3, Rue Odette Jasse 13015
Marseille - FRANCE
(+33) 4 95 06 33 70
(+33) 4 91 60 69 05
CAME Automatismos S.a. C/juan De Mariana, N. 17-local 28045
Madrid - SPAIN
(+34) 91 52 85 009
(+34) 91 46 85 442
CAME Automatismos Catalunya S.a. P.i. Moli Dels Frares N. 23 C/a 08620
Sant Vicenc Del Horts - SPAIN
(+34) 93 65 67 694
(+34) 93 67 24 505
Paf - CAME Estrada Nacional 249-4 Ao Km 4,35 Cabra Figa - Trajouce 2635-047
Rio De Mouro - PORTUGAL
(+351) 219 257 471
(+35) 219 257 485
Kornwestheimer Str. 37
Munchingen Bei Stuttgart - DEUTSCHLAND
(+49) 71 5037830
(+49) 71 50378383
CAME Americas Automation Llc
1560 Sawgrass Corporate Pkwy, 4th Floor
Sunrise, FL 33323 - U.S.A
(+1) 305 433 3307 (+1) 305 396 3331
CAME Middle East Fzco
Po Box 17131 Warehouse N. Be02
South Zone - Jebel Ali Free Zone -
(+971) 4 8860046 (+971) 4 8860048
CAME Polska Sp.Zo.o
01-237
Warszawa - POLAND
(+48) 22 8365076 (+48) 22 8363296
CAME Gmbh
70825
Korntal
Dubai - U.A.E.
Ul. Ordona 1
CAME United Kingdom Ltd. Unit 3 Orchard Business Park Town Street, Sandiacre Nottingham - Ng10 5du - UNITED KINGDOM
2.0 01/2009 © CAME cancelli automatici s.p.a.
119EU75 ver.
(+44) 115 9210430
(+44) 115 9210431
CAME Belgium Sprl Zoning Ouest 7 7860
Lessines - BELGIUM
Buftea, Judet Ilfov
(+32) 68 333014
(+32) 68 338019
S.c. CAME Romania S.r.l.
B-dul Mihai Eminescu, Nr. 2, Bloc R2
Scara A, Parter, Ap. 3
Bucarest - ROMANIA
(+40) 21 3007344 (+40) 21 3007344
CAME Russia
Leningradskij Prospekt, Dom 80
Pod’ezd 3, offi ce 608
125190,
Moskva - RUSSIA (+7) 495 937 33 07 (+7) 495 937 33 08
English - Manual code:
The data and information repor ted in this installation manual are susceptible to change at any time and without obligation on CA ME cancelli automatici s.p.a. to notify users.
CAME Cancelli Automatici S.p.a. Via Martiri Della Libertà, 15 31030
Dosson Di Casier (Tv)
(+39) 0422 4940
(+39) 0422 4941
20093
CAME Nord s.r.l.
Piazza Castello, 16
Cologno Monzese (MI)
(+39) 02 26708293 (+39) 02 25490288
Informazioni Commerciali 800 848095 www.came.it
CAME Service Italia S.r.l. Via Della Pace, 28 31030
Dosson Di Casier (Tv)
(+39) 0422 383532
(+39) 0422 490044
Assistenza Tecnica 800 295830
CAME Sud s.r.l.
Via F. Imparato, 198
Cm2 Lotto A/7
80146
Napoli (+39) 081 7524455 (+39) 081 7529109
Loading...