Burnham 8H, 8HE Brochure

Page 1
252 TO 505
MBH INPUT
8082%
THERMAL
EFFICIENCY
Series 8H/8HE
CAST IRON GAS FIRED COMMERCIAL WATER BOILER
CAST IRON
SECTIONAL
DESIGN
ATMOSPHERIC
VENT
MODULAR/ MULTIPLE BOILER CONFIGURATIONS
AVAILABLE
Page 2
2
PAG E
Series 8H/8HE EFFICIENT CAST IRON COMMERCIAL WATER BOILER
High Performance & Long Term Reliability
Burnham Commercial’s commitment to quality and dependability continues with the Series 8H/8HE. The features and eciency of the 8H/8HE boiler make it ideal for single and multiple boiler applications. Oering space heating, or a combination of heating and domestic hot water, the Series 8H/8HE has a compact design which easily adapts to existing piping arrangements, boiler room requirements, and system heating needs.
American-Made Cast Iron Construction
Burnham Commercial’s unique cast iron formula has an extremely high silicon content, making it stronger and more exible. It oers better thermal shock resistance and greater heat transfer capabilities than other cast iron products.
MANUFACTURED WITH QUALITY
Casting Solutions operates a state-of­the-art foundry, in Zanesville, Ohio, ensuring quality and availability of boiler sections.
CAST IRON NIPPLE DIFFERENCE
The gaskets that other manufacturers use to connect boiler sections can break down if they come in contact with oils, boiler ue gases, corrosion inhibitors, pump lubricants, and antifreeze. Burnham Commercial is committed to safety, reliability and durability. That’s why the Series 8H/8HE uses cast iron nipples instead of gaskets. The Series 8H/8HE’s cast iron nipples remain unaected by those elements, ensuring long life and eliminating costly repairs. Cast iron nipples expand and contract with the sections they connect, ensuring the overall integrity of the section assembly.
HEAT EXCHANGER DESIGN
The cast iron heat exchanger on the Series 8H/8HE features a pinned heating surface. These multi-faceted pins allow the heat generated from the combustion process to be transferred to the cast iron from a number of angles, which contributes to the boiler’s overall eciency. A vertical ue design extracts heat while maintaining low draft losses.
DELUXE INSULATED JACKET
The jacket on the Series 8H/8HE is lined with three inches of insulation. This serves to reduce jacket and standby heat losses, further conserving energy. The jacket itself is powder coated, insuring a scratch resistant, long lasting nish.
Two Packaging Options
Knockdown 8H/8HE units are easy to handle and maneuver at the job site. Knockdown units are supplied in a crate which includes an assembled block with separate cartons containing jackets and components (shown). Packaged and wired units are ready to install out of the crate. A reinforced shipping container protects against damage.
Page 3
3
PAG E
Series 8H/8HE STANDARD EQUIPMENT
Pressure/Temperature Gauge
Rugged Cast Iron Nipples
Assembled with cast iron nipples for durability and reliability
High Limit Control
Honeywell L4080D
50 VA Transformer
Aluminized Steel Burners
Provide optimized air flow for maximum efficiency, smooth ignition and long life.
Safety Relief Valve
50 PSI (standard) 30 PSI (optional)
Gas Manifold
With plugged pressure tapping, saves on installation time and money.
Top Mounted Drafthood
High Limit Control Manual Reset
Honeywell L4006E (Packaged only)
Step Opening Gas Valve
Provides smooth ignition
Blocked Vent Switch
Automatically shuts down boiler in the event that the
chimney or venting system become restricted.
Stainless Steel Flue Baffles
Durable Cast Iron Sections
For long term durability and reliability
Ignition Module
Honeywell S8610
Deluxe Jacket with 3" Insulation
Decreases operating losses and gives a lasting finish
Flame Rollout Switch
Safely shuts down the boiler if the flue passages become blocked or restricted.
Modular Optional Equipment
Water Manifolds
Factory fabricated manifolds are available as a convenience to the installer. The manifolds are lightweight and forgiving of minor piping misalignments common to multiple boiler installations. Available as two-module or three-module manifolds. For installations of four or more modules in a row, the manifolds can be joined together as required. Applicable to primary-secondary or parallel piping arrangements.
Flex Couplings
Easy to install ex couplings are available to facilitate piping connections. They accommodate misalignments between pipes and permit up to a total of 8º angular misalignment at each connection while maintaining a leakproof seal. Flex couplings reduce installation time and reduce labor costs.
Staging Controls
Go to www.burnhamcommercial.com to view the selection of staging controls we oer from Tekmar Control Systems.
Page 4
Dimensions and Specications
4
PAG E
DIMENSIONS INCHES
Boiler Model ‘A’ ‘B’ ‘C’ ‘D’ ‘E’
805H
806H 807HE 808HE 809HE 810HE
All dimensions are in inches
20 23-3/4 27-1/2 31-1/4
35 38-3/4
10 11-7/8 13-3/4 15-5/8 17-1/2 19-3/8
7 8 8
9 10 10
24-13/16 27-13/16 27-13/16 30-13/16
33-1/2 33-1/2
Series 8H/8HE Ratings* Natural and LP Gas
16-1/8
18 18 20 22 22
4.5
4.5
4.5
4.5
5.0
5.0
Recommended
Chimney Size
(Round)
7" dia. x 15ft. 8" dia. x 15ft. 8" dia. x 15ft.
8" dia. x 15ft. 10" dia. x 15ft. 10" dia. x 15ft.
APPROX. SHIPPING
WEIGHT LBS.
Water
Content
(Gallons) Packaged Knock-down
11.9
13.9
15.9
17.9
19.9
21.9
600 690 770 880 970
1060
680 770 870
950 1040 1140
RATINGS
MINIMUM NATURAL GAS
PRESSURE INCHES
I=B=R Net
Boiler
Model (1)
805H
806H 807HE 808HE 809HE 810HE
*Ratings shown are for installations at sea level and elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should be reduced at the rate of four percent (4%) for each 1,000 feet above sea level.
1. When ordering, use prex P for packaged and K for knocked-down. Use sux NSP for natural gas, standing pilot; NEI for natural gas, electronic ignition; PSP for LP gas, standing pilot; PEI for LP gas, electronic ignition.
2. Net I=B=R ratings shown are based on normal I=B=R piping and pickup allowance of 1.15. Consult the Burnham Commercial website for installations having unusual piping and pickup requirements such as intermittent system of operation, extensive piping systems, etc.
3. 15 foot height is measured from top of drafthood to top of chimney.
4. 805H Eciency is AFUE.
Maximum allowable working pressure: 50 PSI Water only; 50 PSI Safety Relief Valve - Standard; 30 PSI Safety Relief Valve - Optional
Input
(MBH)
252 315 340 410 460 505
Gross Output
(MBH)
208 253 275 328 370 406
Rating Water
(MBH) (2)
181 220 239 285 322 353
Thermal
Eciency(4) 24V EI
82.7
80.2
81.0
80.1
80.4
80.5
N/A
4.5
5.0 N/A N/A N/A
Standard Equipment
Cast Iron Section Assembly Deluxe Jacket with 3 inch Insulation 100% Shut-O Gas Controls Boiler Drain Valve 50VA Transformer and Junction Box
Packaged units are shipped packaged and wired in a reinforced cardboard container, for added protection. Drafthood, trim carton, low water cut-o and damper; when supplied, are shipped in separate cartons. Knocked-down units are shipped in a stackable container with sections assembled and mounted on the base with manifold and burners installed. Controls, trim, drafthood, and jacket are shipped together in the same container as the boiler.
Aluminized Steel Burners 1" Gas Connection 2" Supply and Return Connections 50 PSI Safety Relief Valve Stainless Steel Flue Baes
Blocked Vent Switch (BVS) - All Sizes Flame Roll-Out Switch (FRS) - All Sizes L4080D High Limit Control High Limit Control with Manual Reset - L4006E (in addition to L4080) - Packaged Boilers Only
751P-MT-120 Probe LWCO - 808HE-810HE Only Electronic Ignition on 805H & 808HE - 810HE for Natural or LP Gas 24V Standing Pilot on 806H & 807HE for Natural or LP Gas Pressure Temperature Gauge
Optional Equipment
Intermittent circulation—24V-R8285D relay in lieu of AT150D1001 (80160155) 30 psi relief valve in lieu of standard 50 psi relief valve (specify on order) Vent damper (Optional on 806H + 807HE - 810HE, not available with “EP” or “OP” control sets)—(Standard on 805H)
NOTE: NOT FOR DIRECT INSTALLATION ON COMBUSTIBLE FLOORING. A HEAT SHIELD IS REQUIRED AND AVAILABLE FOR COMBUSTIBLE FLOOR INSTALLATION AND CONCRETE INSTALLATION WHICH IS OVER A MATERIAL THAT IS SUBJECT TO MELTING (PVC, PEX RADIANT TUBING ETC.). NOT FOR INSTALLATIONS ON CARPET, EVEN WITH A COMBUSTIBLE FLOOR SHIELD.
©2014 Burnham Commercial P.O. Box 3939, Lancaster, PA 17604
Phone: 888.791.3790 www.burnhamcommercial.com
Form No. PL81401161000-1/14-2.5Ms Printed in the U.S.A.
Electronic Control Sets to Meet CSD-1 Deduct 751P-MT-120 low water cut-o (on 808HE thru 810HE) Combustible oor shield (Required r installation on combustible ooring)