252 TO 505
MBH INPUT
8082%
THERMAL
EFFICIENCY
Series 8H/8HE
CAST IRON GAS FIRED
COMMERCIAL WATER BOILER
30 OR 50 PSI
CAST IRON
SECTIONAL
DESIGN
ATMOSPHERIC
VENT
MODULAR/
MULTIPLE BOILER
CONFIGURATIONS
AVAILABLE

Series 8H/8HE EFFICIENT CAST IRON COMMERCIAL WATER BOILER
High Performance & Long Term Reliability
Burnham Commercial’s commitment to quality and dependability
continues with the Series 8H/8HE. The features and eciency of the
8H/8HE boiler make it ideal for single and multiple boiler applications.
Oering space heating, or a combination of heating and domestic
hot water, the Series 8H/8HE has a compact design which easily
adapts to existing piping arrangements, boiler room requirements,
and system heating needs.
American-Made Cast Iron Construction
Burnham Commercial’s unique cast iron
formula has an extremely high silicon
content, making it stronger and more
exible. It oers better thermal shock
resistance and greater heat transfer
capabilities than other cast iron products.
• MANUFACTURED WITH QUALITY
Casting Solutions operates a state-ofthe-art foundry, in Zanesville, Ohio,
ensuring quality and availability of
boiler sections.
• CAST IRON NIPPLE DIFFERENCE
The gaskets that other manufacturers
use to connect boiler sections can
break down if they come in contact
with oils, boiler ue gases, corrosion
inhibitors, pump lubricants, and
antifreeze. Burnham Commercial is
committed to safety, reliability and
durability. That’s why the Series 8H/8HE
uses cast iron nipples instead of
gaskets. The Series 8H/8HE’s cast iron
nipples remain unaected by those elements, ensuring long life and
eliminating costly repairs. Cast iron nipples expand and contract
with the sections they connect, ensuring the overall integrity of
the section assembly.
• HEAT EXCHANGER DESIGN
The cast iron heat exchanger on the
Series 8H/8HE features a pinned
heating surface. These multi-faceted
pins allow the heat generated from the
combustion process to be transferred to
the cast iron from a number of angles, which contributes to the
boiler’s overall eciency. A vertical ue design extracts heat while
maintaining low draft losses.
• DELUXE INSULATED JACKET
The jacket on the Series 8H/8HE is lined
with three inches of insulation. This
serves to reduce jacket and standby heat
losses, further conserving energy. The
jacket itself is powder coated, insuring a
scratch resistant, long lasting nish.
Two Packaging Options
Knockdown 8H/8HE units are easy to
handle and maneuver at the job site.
Knockdown units are supplied in a crate
which includes an assembled block with
separate cartons containing jackets and
components (shown). Packaged and wired
units are ready to install out of the crate.
A reinforced shipping container protects
against damage.

Series 8H/8HE STANDARD EQUIPMENT
Pressure/Temperature
Gauge
Rugged Cast Iron
Nipples
Assembled with cast iron
nipples for durability and
reliability
High Limit Control
Honeywell L4080D
50 VA Transformer
Aluminized Steel Burners
Provide optimized air flow for
maximum efficiency, smooth
ignition and long life.
Safety Relief Valve
50 PSI (standard)
30 PSI (optional)
Gas Manifold
With plugged pressure
tapping, saves on
installation time and
money.
Top Mounted Drafthood
High Limit Control Manual Reset
Honeywell L4006E (Packaged only)
Step Opening Gas Valve
Provides smooth ignition
Blocked Vent Switch
Automatically shuts down
boiler in the event that the
chimney or venting system
become restricted.
Stainless Steel Flue Baffles
Durable Cast Iron Sections
For long term durability and reliability
Ignition Module
Honeywell S8610
Deluxe Jacket
with 3" Insulation
Decreases operating losses
and gives a lasting finish
Flame Rollout Switch
Safely shuts down the boiler if the flue
passages become blocked or restricted.
Modular Optional Equipment
Water Manifolds
Factory fabricated manifolds are available as
a convenience to the installer. The manifolds
are lightweight and forgiving of minor piping
misalignments common to multiple boiler
installations. Available as two-module or
three-module manifolds. For installations of
four or more modules in a row, the manifolds
can be joined together as required. Applicable
to primary-secondary or parallel piping
arrangements.
Flex Couplings
Easy to install ex couplings are available to
facilitate piping connections. They accommodate
misalignments between pipes and permit up
to a total of 8º angular misalignment at each
connection while maintaining a leakproof seal.
Flex couplings reduce installation time and
reduce labor costs.
Staging Controls
Go to www.burnhamcommercial.com to view the
selection of staging controls we oer from Tekmar
Control Systems.

Dimensions and Specications
DIMENSIONS INCHES
Boiler Model ‘A’ ‘B’ ‘C’ ‘D’ ‘E’
805H
806H
807HE
808HE
809HE
810HE
All dimensions are in inches
20
23-3/4
27-1/2
31-1/4
35
38-3/4
10
11-7/8
13-3/4
15-5/8
17-1/2
19-3/8
7
8
8
9
10
10
24-13/16
27-13/16
27-13/16
30-13/16
33-1/2
33-1/2
Series 8H/8HE Ratings* Natural and LP Gas
16-1/8
18
18
20
22
22
4.5
4.5
4.5
4.5
5.0
5.0
Recommended
Chimney Size
(Round)
7" dia. x 15ft.
8" dia. x 15ft.
8" dia. x 15ft.
8" dia. x 15ft.
10" dia. x 15ft.
10" dia. x 15ft.
APPROX. SHIPPING
WEIGHT LBS.
Water
Content
(Gallons) Packaged Knock-down
11.9
13.9
15.9
17.9
19.9
21.9
600
690
770
880
970
1060
680
770
870
950
1040
1140
RATINGS
MINIMUM NATURAL GAS
PRESSURE INCHES
I=B=R Net
Boiler
Model (1)
805H
806H
807HE
808HE
809HE
810HE
*Ratings shown are for installations at sea level and elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should be reduced at the rate of four percent (4%) for each 1,000 feet above sea level.
1. When ordering, use prex P for packaged and K for knocked-down. Use sux NSP for natural gas, standing pilot; NEI for natural gas, electronic ignition; PSP for LP gas, standing pilot; PEI for LP gas, electronic ignition.
2. Net I=B=R ratings shown are based on normal I=B=R piping and pickup allowance of 1.15. Consult the Burnham Commercial website for installations having unusual piping and pickup requirements such as intermittent
system of operation, extensive piping systems, etc.
3. 15 foot height is measured from top of drafthood to top of chimney.
4. 805H Eciency is AFUE.
Maximum allowable working pressure: 50 PSI Water only; 50 PSI Safety Relief Valve - Standard; 30 PSI Safety Relief Valve - Optional
Input
(MBH)
252
315
340
410
460
505
Gross Output
(MBH)
208
253
275
328
370
406
Rating Water
(MBH) (2)
181
220
239
285
322
353
Thermal
Eciency(4) 24V EI
82.7
80.2
81.0
80.1
80.4
80.5
N/A
4.5
5.0
N/A
N/A
N/A
Standard Equipment
Cast Iron Section Assembly
Deluxe Jacket with 3 inch Insulation
100% Shut-O Gas Controls
Boiler Drain Valve
50VA Transformer and Junction Box
Packaged units are shipped packaged and wired in a reinforced cardboard container, for added protection. Drafthood, trim carton, low water cut-o and damper; when supplied, are shipped in separate cartons. Knocked-down
units are shipped in a stackable container with sections assembled and mounted on the base with manifold and burners installed. Controls, trim, drafthood, and jacket are shipped together in the same container as the boiler.
Aluminized Steel Burners
1" Gas Connection
2" Supply and Return Connections
50 PSI Safety Relief Valve
Stainless Steel Flue Baes
Blocked Vent Switch (BVS) - All Sizes
Flame Roll-Out Switch (FRS) - All Sizes
L4080D High Limit Control
High Limit Control with Manual Reset -
L4006E (in addition to L4080) - Packaged Boilers Only
751P-MT-120 Probe LWCO - 808HE-810HE Only
Electronic Ignition on 805H & 808HE - 810HE for Natural or LP Gas
24V Standing Pilot on 806H & 807HE for Natural or LP Gas
Pressure Temperature Gauge
Optional Equipment
Intermittent circulation—24V-R8285D relay in lieu of AT150D1001 (80160155)
30 psi relief valve in lieu of standard 50 psi relief valve (specify on order)
Vent damper (Optional on 806H + 807HE - 810HE, not available with “EP” or “OP” control sets)—(Standard on 805H)
NOTE: NOT FOR DIRECT INSTALLATION ON COMBUSTIBLE FLOORING. A HEAT SHIELD IS REQUIRED AND AVAILABLE FOR COMBUSTIBLE FLOOR INSTALLATION AND CONCRETE INSTALLATION WHICH IS OVER A MATERIAL
THAT IS SUBJECT TO MELTING (PVC, PEX RADIANT TUBING ETC.). NOT FOR INSTALLATIONS ON CARPET, EVEN WITH A COMBUSTIBLE FLOOR SHIELD.
©2014 Burnham Commercial • P.O. Box 3939, Lancaster, PA 17604
Phone: 888.791.3790 • www.burnhamcommercial.com
Form No. PL81401161000-1/14-2.5Ms Printed in the U.S.A.
Electronic Control Sets to Meet CSD-1
Deduct 751P-MT-120 low water cut-o (on 808HE thru 810HE)
Combustible oor shield (Required r installation on combustible ooring)