Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could cause death and/or
property damage.
Disconnect gas piping from unit when leak testing at
pressure greater than
psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater
1
than
/2psig, it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
1
/2psig or less, a unit connected to such piping must be
isolated by manually closing the gas valve(s).
WARNING
WARNING
1
/2psig. Pressures greater than1/
2
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert
to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in
basepan of unit with insulation-side down. Seals around
openings must be tight. (See Fig. 1.)
1
Fig. 1 --- Horizontal Conversion Panels
Step 1 —Provide Unit Support
581B,C
Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. (See Fig. 2.) Install insulation,
cant strips, roofing felt, and counter flashing as shown. Ductworkmust be attached to curb, not to the unit. If electric control power
or gas service is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the basepan in
accordancewiththeaccessoryinstallationinstructions.
Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the roof
curb as shown in Fig. 2. Improperly applied gasket can result in
air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly.Refer to
Accessory Roof Curb Installation Instructions for additional
information as required.
Slab Mount (Horizontal Units
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of
condenser-coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Alternate Unit
When the curb or adapter cannot be used, support unit with
sleeper rails using unit curb or adapter support area. If sleeper
rails cannot be used, support the long sides of the unit with a
minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Support
Only)
Step 2 —Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, field-supplied isolation flanges should be attached to
horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire
codes.
C06108
A minimum clearance is not required around ductwork. Cabinet
return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer.
These units are designed for a minimum continuous return-air
temperature in heating of 50_F (dry bulb), or an intermittent
operation down to 45_F (dry bulb), such as when used with a
night setback thermostat.
To operate at lower return-air temperatures, a field-supplied
outdoor air temperature control must be used to initiate both
stages of heat when the temperature is below 45_F. Indoor
comfort may be compromised when these lower air temperatures
are used with insufficient heating temperature rise.
Step 3 —Install External Trap for Condensate
Drain
The unit’s3/4-in. condensate drain connections are located on the
bottom and side of the unit. Unit discharge connections do not
determine the use of drain connections; either drain connection
can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug
(Red) in the alternate bottom connection is tight before installing
the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-installed plug (Red) from the bottom
connection to the side connection. The center drain plug looks
like a star connection, however it can be removed with a
socket drive extension. (See Fig. 4.) The piping for the
condensate drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate drainage.
Install a trap 4-in. deep and protect against freeze-up. If drain line
is installed downstream from the external trap, pitch the line away
from the unit at 1 in. per 10 ft of run. Do not use a pipe size
smaller than the unit connection (
3
/4in.). (See Fig. 5.)
1
/2-in.
Step 4 —Rig and Place Unit
Inspect unit for transportation damage, and file any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit, and
rollers may be used to move unit across a roof. Level by using
unit frame as a reference. See Table 1 and 2 and Fig. 6 for
additional information. Operating weight is shown in Table 1 and
2 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 8 and 9.
Refer to rigging instructions on unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
Positioning
Maintain clearance around and above unit to provide minimum
distance from combustible materials, proper airflow, and service
access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are
maintained:
rail inside the front and rear, 0.0 in. clearance between the roof
curb and the base rail inside on the duct end of the unit. This will
result in the distance between the roof curb and the base rail
inside on the condenser end of the unit being approximately
equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air
inlets near exhaust vents or other sources of contaminated air.
1
WARNING
/4in. clearance between the roof curb and the base
2
1-4
[406]
DALT
DRAIN
HOLE
13/4
[44.5]
GASPOWERCONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1-9
11
[551]
/16
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest
on curb).
6. Service clearance: 4 ft on each side.
1-2
[356]
2-0
[610]
A
581B036-072
581C024-060
UNIT
SIZE
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01
and 002A01 are for thru-the-curb type gas.
Packages CRBTMPWR003A01 and 004A01
are for thru-the-bottom type gas connections.
581B,C
Fig. 2 --- Roof Curb Details
3
C06345
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 3 --- Unit Leveling Tolerances
Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet.
581B,C
Unit may be installed directly on wood flooring or on Class A, B,
or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from
an adjacent building or combustible material. When unit is
located adjacent to public walkways, flue assembly must be at
least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge
deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that
flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American
National Standards Institute) Z223.1-1984 and addendum
Z223.1a-1987. In Canada, installation must be in accordance with
the CAN1.B149.1 and CAN1.B149.2 installation codes for gas
burning appliances.
Flue vent discharge must have a minimum horizontal clearance of
4 ft from electric and gas meters, gas regulators, and gas relief
equipment.
After unit is in position, remove shipping materials and rigging
skids.
Step 5 —Install Flue Hood
Flue hood is shipped screwed to the burner compartment access
panel. Remove from shipping location and, using screws
provided, install flue hood in location shown in Fig. 8 and 9.
For units being installed in California Air Quality Management
Districts which require NOx emissions of 40 nanograms/joule or
less, a low NOx unit must be installed.
NOTE: Low NOx units are available for 2 to 5 ton units.
C06110
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
Step 6 —Install Gas Piping
Unit is equipped for use with type of gas shown on nameplate.
Refer to localbuilding codes, or in the absence of local codes,
to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled
National Fuel Gas Code. In Canada, installation must be in
accordancewiththeCAN1.B149.1andCAN1.B149.2
installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas connection
must not be less than 4 in. wg or greater than 13 in. wg while the
unit is operating. On 581B036 --072 and 581C036--060 high-heat
units, the gas pressure at unit gas connection must not be less than
5 in. wg or greater than 13 in. wg while the unit is operating. For
propane applications, the gas pressure must not be less than 5 in.
wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop.
Do not use supply pipe smaller than unit gas connection.
4
NOTES:
OPERATING
OPERATING
B
1. Place unit on curb as close as possible to the duct end.
2. Dimensionin( )isinmillimeters.
3. Hook rigging shackles through holes in base rail as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid
when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.
5. Weights include base unit without the Perfect Humidityt adaptive dehumidification system. See Table 1 for unit operating weights with th e Perfect Humidityt
system.
Support gas piping as shown in the table in Fig. 11. For example,
3
/4-in. gas pipe must have one field-fabricated support beam
a
every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams, and a 48-ft long pipe would have a
minimum of 6 support beams.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
See Fig. 11 for typical pipe guide and locations of external
manual gas shutoff valve.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas
connection piping. The power wiring, control wiring and gas
piping can be routed through field-drilled holes in the basepan.
The basepan is specially designed and dimpled for drilling the
access connection holes.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent damage
to the valve.
5
581B,C
C06363
COMPRESSOR
ACCESS PANEL
CONTROL BOX
Fig. 8 --- 581B 036 --072 Base Unit Dimensions
6
C06364
581B,C
COMPRESSOR
ACCESS PANEL
Fig. 9 --- 581C 024 --060 Base Unit Dimensions
7
Fig. 10 --- Flue Hood Details
*
581B,C
LEGEND
NFGC — National Fuel Gas Code
Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER (in.)
1
/
3
/4or 1
1
/4or larger
1
2
Fig. 11 --- Gas Piping Guide (With Accessory
Thru--the--Curb Service Connections)
Step 7 —Make Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground
may consist of electrical wire connected to unit ground
lug in control compartment, or conduit approved for
electrical ground when installed in accordance with
NEC (National Electrical Code), ANSI/NFPA (National
Fire Protection Association), latest edition, and local
electrical codes. Do not use gas piping as an electrical
ground.
WARNING
SPACING OF SUPPORTS
X DIMENSION (ft)
6
8
10
C06114
C06115
Field Power Supply
All units except 208/230-v units are factory wired for the voltage
shown on the nameplate. If the 208/230-v unit is to be connected
to a 208-v power supply, the transformer must be rewired by
moving the black wire from the 230-v terminal on the
transformer and connecting it to the 200-v terminal from the
transformer.
Refer to unit label diagram for additional information. Pigtails
are provided for field service. Use factory-supplied splices or UL
(Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC.
Allfield wiringmustcomplywithNECand local
requirements.
Install conduit through side panel openings indicated in Fig. 8.
Route power lines through connector to terminal connections as
shown in Fig. 12.
Voltage to compressor terminals during operation must be within
voltage range indicated on unit nameplate (also see Tables 3 and
4). On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown in
Tables 3 and 4, Note 3 to determine the percent voltage
imbalance. Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Bryant warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas connection
piping. The power wiring, control wiring and gas piping can be
routed through field-drilled holes in the basepan. The basepan is
specially designed and dimpled for drilling the access connection
holes.(SeeFig.2.)
Field Control W
iring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the accessory.
Locate thermostat assembly on a solid wall in the conditioned
space to sense average temperature in accordance with thermostat
installation instructions.
Route thermostat cable or equivalent single leads of colored wire
from subbase terminals through connector on unit to low-voltage
connections (shown in Fig. 13 and 14).
Connect thermostat wires to matching screw terminals of
low-voltage connection board. (See Fig. 13 and 14.)
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in thecorner
post; then feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the control box.
(See Fig. 15). The raceway provides the UL required clearance
between high and low-voltage wiring.
Heat Anticipator
Settings
Set heat anticipator settings at 0.14 amp for first stage and 0.14
for second stage heating, when available.
8
Table 1—Physical Data 581B
A
/B(
)
MotorPulleyPitchDiameterA/B(i
n.)
f
SpeedChangeperFullTurno
f
MovablePulleyMaximumFul
l
BASE UNIT 581B036048060072
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Perfect Humidity Adaptive Dehumidification System
EconoMi$er IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Perfect Humidity Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
Unit with Perfect Humidity Adaptive Dehumidification System
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous BhpStd
Hi-Static
Motor RPMStd
Hi-Static
Motor Frame SizeStd
Hi-Static
Fan Rpm RangeStd
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Motor PulleyPitch Diameter
in.
Hi-Static
Nominal Motor Shaft Diameter (in.)Std
Hi-Static
Fan Pulley Pitch Diameter (in.)Std
Hi-Static
Belt — Type...Length (in.)Std
Hi-Static
Pulley Center Line Distance (in.)
Speed Changeper Full Turn o
Movable Pulley Flange (rpm)
Movable PulleyMaximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns OpenStd
Hi-Static
Factory Speed Setting (rpm)Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
LEGEND
Bhp — Brake Horsepower
Std
Std
Std
3456
530540560635
15232529
50505050
115115115115
Scroll
1111
42535060
R-22
Acutrol Metering Device
5-810-210-012- 8
12-518-820-523-14
Propeller
1...221...221...221...22
3500350041004100
1
/4...825
1
/4...825
1
/4...1100
1
/4...1100
180180320320
3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
1...172...172...172...17
14.616.516.521.3
3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...152...154...154...15
5.55.55.57.3
1...172...172...172...17
3.93.93.95.2
Centrifugal Type, Belt Drive
1...10 x 101...10 x 101...10 x 101...10 x 10
1200160020002400
1.20
2.40
1620
1725
48
56
680-1044
1075-1455
1.201.30/2.40*2.40
2.402.902.90
162017251725
172517251725
4848/56*56
565656
770-11851035-14601119-1585
1075-14551300-16851300-1685
BallBallBallBall
2100210021002100
1.9/2.9
2.8/3.8
1/
2
5
/
8
4.5
4.5
1...A...36
1...A...39
1.9/2.02.4/3.42.4/3.4
2.8/3.83.4/4.43.4/3.4
1
/
2
5
/
8
4.04.04.0
5
/
8
5
/
8
5
7
4.04.54.5
1...A...361....4...401...A...38
1...A...391...A...401...A...40
10.0-12.410.0-12.414.7-15.514.7-15.5
65
65
5
6
3
1
3
826
1233
5
/
/
2
8
707595
656060
565
655
333
31/
2
93612481305
123313961396
5
/
8
31/
2
5
/
8
31/
5
581B,C
/
8
/
8
2
/
8
9
Table 1 — Physical Data 581B (cont)
UNIT SIZE 581B036048060072
FURNACE SECTION
Rollout Switch Cutout Temp (F)†195195195195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas —Std071/072.113...33.113...33.113...33.113...33
Thermostat Heat Anticipator Setting (amps)
208/230/460 v
First Stage.14.14.14.14
Second Stage.14.14.14.14
Gas Input (Btuh)
First Stage/Second Stage (3---phase units)07250,000/ 72,00050,000/ 72,00050,000/ 72,00050,000/ 72,000
Manifold Pressure (in. wg)
Natural Gas —Std3.53.53.53.5
Propane —Alt††3.53.53.53.5
Maximum Static Pressure (in. wg)1.01.01.01.0
Field Gas Connection Size (in.)1/21/21/21/2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
Cleanable. Screen quantity and size varies with option selected.
2...16 x 25 x 24...16 x 16 x 2
Throwaway
LEGEND
Bhp — Brake Horsepower
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh
Heat input units have 3 burners.
††A propane kit is available as an accessory. Kit may be used at elevations as high as
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be
removed a nd the units will no longer be classified as Lo w NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating wi th heating input val ues.
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
10
Table 2—Physical Data 581C
A
/B(
)
MotorPulleyPitchDiameterA/B(i
n.)
f
SpeedChangeperFullTurno
f
MovablePulleyMaximumFul
l
BASE UNIT 581C024036048072
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Perfect Humidity Adaptive Dehumidification System
EconoMi$er IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Perfect Humidity Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
Unit with Perfect Humidity Adaptive Dehumidification System
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous BhpStd
Hi-Static
Motor Frame SizeStd
Hi-Static
Motor Rpm
Fan Rpm RangeStd
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Motor PulleyPitch Diameter
in.
Hi-Static
Nominal Motor Shaft Diameter (in.)Std
Hi-Static
Fan Pulley Pitch Diameter (in.)Std
Hi-Static
Belt — Type...Length (in.)Std
Hi-Static
Pulley Center Line Distance (in.)
Speed Changeper Full Turn o
Movable Pulley Flange (rpm)
Movable PulleyMaximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns OpenStd
Hi-Static
Factory Speed Setting (rpm)Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
Std
Std
Std
2345
530540560635
13152325
50505050
115115115115
Scroll
1111
25425653
R-22
Acutrol Metering Device
5 --- 37 --- 1 18 --- 812---11
1 0 --- 214 --- 014--- 1321 --- 0
Propeller
1...221...221...221...22
3000350035004100
1
/8...825
1
/8...825
1
/8...825
1
/4...1100
180180180320
3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
1...171...172...172...17
14.614.616.516.5
3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...152...152...154...15
4.25.55.55.5
1...171...172...172...17
3.53.93.93.9
Centrifugal Type, Belt Drive
1...10 x 101...10 x 101...10 x 101...10 x 10
800120016002000
0.58
1.201.201.30/2.40*
2.402.402.90
48
484848/56*
565656
1620162016201725
400-1000
680-1044770-11851035-1460
1075-14551075-14551300-1685
BallBallBallBall
1620210021002100
2.4/3.2
5
/
8
7
/
8
4.0
4.5
1...A...36
1.9/2.91.9/2.02.4/3.4
2.8/3.82.8/3.83.4/4.4
1/
2
5
/
8
4.54.04.0
1
/
2
5
/
8
5
5
4.54.04.5
1...A...361...A...361....4...40
1...A...391...A...391...A...40
10.0---12.410.0-12.410.0-12.414.7-15.5
60
657075
656560
5
556
665
333
31/
2
8269361248
123312331396
5
/
8
31/
2
5
/
8
31/
5
756
5
3
/
8
581B,C
/
8
/
8
2
/
8
11
Table 2 — Physical Data 581C (cont)
UNIT SIZE 581C024036048060
FURNACE SECTION
Rollout Switch Cutout Temp (F)†195195195195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas —Std071/072.113...33.113...33.113...33.113...33
Thermostat Heat Anticipator Setting (amps)
208/230/460 v
First Stage.14.14.14.14
Second Stage.14.14.14.14
Gas Input (Btuh)
First Stage/Second Stage (3---phase units)07250,000/ 72,00050,000/ 72,00050,000/ 72,00050,000/ 72,000
Manifold Pressure (in. wg)
Natural Gas —Std3.53.53.53.5
Propane —Alt††3.53.53.53.5
Maximum Static Pressure (in. wg)1.01.01.01.0
Field Gas Connection Size (in.)1/21/21/21/2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
Cleanable. Screen quantity and size varies with option selected.
2...16 x 25 x 24...16 x 16 x 2
Throwaway
LEGEND
Bhp — Brake Horsepower
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh
Heat input units have 3 burners.
††A propane kit is available as an accessory. Kit may be used at elevations as high as
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be
removed a nd the units will no longer be classified as Lo w NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating wi th heating input values.
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
12
BLK
BLK
TO COMP
BLK
TO COMP
1123
C
2321
208/230-1-60
(SIZES 581B036-060,
581C024-060)
1123
C
2321
208/230-3-60
460-3-60
(SIZES 581B060, 072,
581C0060)
YEL
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLK
YEL
BLU
FIELD POWER SUPPLY
DISCONNECT
PER NEC
EQUIP
GND
TO COMP
14
IFC
63
1123
YELBLU
C
2321
208/230-3-60
480-3-60
(SIZES 581B036,048
581C036,048)
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLK
1113
YELBLU
C
2321
FIELD POWER SUPPLY
575-3-60
(SIZES 581B060, 072)
DISCONNECT
PER NEC
Fig. 12 --- Power Wiring Connections
(SIZES 581B036,048
581C036,048)
TO TB2
1123
C
575-3-60
YEL
2321
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLU
581B,C
C06346
Y1
Y2
W1
W2
IPD/X
R
G
C
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
A
LEGEND
NOTE: Un derlined letter indicates ac tive therm ostat output wh en
configured for A/C operation.
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
B
C
Field Wiring
D
Fig. 13 --- Low --Voltage Connections With or
Without Economizer or Two--Position Damper
C06008
LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
Fig. 14 --- Field Control Wiring
C06125
13
IFM
208
/23
0
1
6
0
S
TD1
8
72541109631070620
024
208
/23
0
1
6
0
S
TD1
8
2
110.96310.70.6
2.0
208
/23
0
-
--1--
-60
S
TD1
8
725411688107064
9
/
S
T
D
4
9
208
/23
0
-
--3--
-60
1
8
725411037710706
/
H
S
5
8
S
T
D
2
2
4
6
0
---3-
--6
0
4
1
4508151391040
3
036
H
S
2
6
(3ton
s
)
S
T
D
1
9
104
5
7
5
---3-
--60HS5
1
863214231
03†20
104†26†
P
erfec
t
208
/23
0
-
--1--
-60
S
TD1
9
72541211151150649
/
S
T
D
4
9
208
/23
0
-
--3--
-60
1
8
725411419511506
/
H
S
5
8
S
T
D
2
2
4
6
0
---3-
--6
0
4
1
4508171451080
3
048
H
S
2
6
(4ton
s
)
S
T
D
1
9
106
5
7
5
---3-
--60HS5
1
863216138
03†20
108†26†
P
erfec
t
208
/23
0
-
--1--
-60
S
TD1
8
72541251501150666
/
S
T
D
5
8
208
/23
0
-
--3--
-60
1
8
725411731231150
6
/
H
S
7
5
S
T
D
2
6
4
6
0
---3-
--6
0
4
1
45081847010803†
060
H
S
3
4
(5ton
s
)
S
T
D
2
0
106
5
7
5
---3-
--60HS5
1
863217153
03†28
119†34†
P
erfec
t
581B,C
MINIMUM UNIT
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
IFM
FAN MOTOR
COMBUSTION
FLA
FLALRA
MOCP**
MCA
NO16.32015.669
NO25.63024.8101
NO18.52518.390
NO19.42519.3120
NO9.0158.946
NO9.4159.360
NO7.6107.536
NO7.7107.643
NO7.7108.048
NO32.74031.5130
NO24.03023.6110
NO24.93024.6140
NO11.91511.653
NO12.31512.167
NO10.1159.944
NO10.21510.051
NO10.31510.156
NO39.45038.1187
NO28.93528.3168
NO30.63530.2187
NO13.92013.692
NO14.72014.5102
NO11.51511.266
NO12.31512.175
YES22.32521.273
YES31.63530.4106
YES24.53023.895
YES25.43024.9124
YES11.71511.448
YES12.11511.863
YES9.7159.538
YES9.8159.644
YES9.8159.650
YES38.74537.0135
YES30.03529.1115
YES30.93530.1145
YES14.62014.155
YES15.02014.670
YES12.31511.946
YES12.41512.052
YES12.51512.158
YES45.46043.6191
YES34.94033.8173
YES36.64035.8192
YES16.62016.195
YES17.42017.0104
4.9
2.2
1.9
10.4
4.9
2.2
1.9
10.4†2.6†
10.6
5.8
2.6
10.8†2.6†
NO12.21512.079
YES13.61513.267
YES14.42014.176
YES14.42014.080
2.0
10.6
11.9†3.4†
Table 3—Electrical Data 581C
VOLTAGE
COMPRESSOROFM
RANGE
581C024--- 060
NOMINAL
IFM TYPEMinMaxQTYRLALRAQTYFLAFLA
V --- P H --- H z
UNIT SIZE
024
54
7
---
---
---
---
(2 tons)
2 3 0 --- 1 --- 6 0STD1872541168810.70.64.9
208
STD
187254110.37710.70.6
2 3 0 --- 3 --- 6 0
208
41450815.13910.40.3
HS5.8
HS2.6
STD
STD
Perfect
Humidity
036
4 6 0 --- 3 --- 6 0
(3 tons)
5 7 5 --- 3 --- 6 0HS51863214.2310.3†2.0
2 3 0 --- 1 --- 6 0STD19725412111511.50.64.9
208
STD
187254114.19511.50.6
2 3 0 --- 3 --- 6 0
208
41450817.14510.80.3
HS5.8
HS2.6
STD
STD
Perfect
Humidity
048
4 6 0 --- 3 --- 6 0
(4 tons)
5 7 5 --- 3 --- 6 0HS51863216.1380.3†2.0
2 3 0 --- 1 --- 6 0STD18725412515011.50.66.6
208
STD
187254117.312311.50.6
2 3 0 --- 3 --- 6 0
208
41450818.47010.80.3†
HS7.5
HS3.4
STD
STD
Perfect
Humidity
060
4 6 0 --- 3 --- 6 0
(5 tons)
5 7 5 --- 3 --- 6 0HS51863217.1530.3†2.8
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA --- Full Load Amps
{ 460v motor
NOTES:
14
MINIMUM UNI
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
16881070649
/
S
T
D49
208
/23
0
-
-
-36
0
1
8
725
4
1
103771070
6
/
H
S
5
2
S
T
D22
036(3
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
513910403
H
S
2
6
S
T
D19
10403
†
5
7
5
-
--3---6
0
H
S51
863
2
1
423
1
2
0
104†09†26
†
P
erfec
t
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
2371261070649
/
S
T
D49
208/2
3
0
---3---
6
0
1
8
725
4
1
135931070
6
/
H
S
5
8
S
T
D22
048(4
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
644651040
3
H
S
2
6
S
T
D19
10403
†
5
7
5
-
--3---6
0
H
S51
863
2
1
644
0
2
0
10409
†26
†
P
erfec
t
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
2881691150666
/
S
T
D58
208/2
3
0
---3---
6
0
1
8
725
4
1
17312311506
/
H
S
7
5
S
T
D26
060(5
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
9621080
3
H
S
3
4
S
T
D20
0603†
H
S51
863
2
1
71501
2
8
5
7
5
3
6
0
08†03
†34
†
P
erfec
t
S
TD0
658
208/2
3
0
---3---
6
0
1
8
725
4
1
205156114
/
H
S
0
675
S
TD0
326
4
6
0
-
--3---6
0
4
1
450
8
1
9675106
072(6
Ton
s
)
H
S
0
334
S
T
D20
0803†
5
7
5
-
--3---6
0
H
S51
863
2
1
77561
2
8
06†03
†34
†
P
erfec
t
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
FLA
IFM
FAN MOTOR
COMBUSTION
FLALRA
MOCP**
NO25.63025101
YES31.63530106
NO18.5251890
NO19.42519120
NO9.015946
NO9.415960
NO7.610736
NO7.710843
NO8.310852
NO35.24534139
NO22.53022106
NO23.43023136
NO10.6151054
NO11.0151168
NO10.3151045
NO10.4151052
NO11.0151161
NO44.16042206
NO28.93528168
NO30.63530187
NO14.7201484
NO15.5201594
NO11.5151163
NO12.3151272
NO12.2151276
NO32.84032200
NO34.54034219
NO15.2201597
NO16.02016107
NO12.4151269
NO13.2201379
YES24.5302495
YES25.43025124
YES11.7151148
YES12.1151263
YES9.715938
YES9.8151044
YES10.4151054
YES41.25039144
YES28.53527111
YES29.43529140
YES13.3151356
YES13.7151370
YES12.5151247
YES12.6151253
YES13.2151363
YES50.16048210
YES34.94034173
YES36.64036192
YES17.4201787
YES18.2201896
YES13.6151364
YES14.4201473
YES14.4201477
YES38.84537205
YES40.54539224
YES17.9201799
YES18.72518109
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
2.0
0.65.8
0.32.6
NO12.8151381
YES14.6201470
YES15.4201580
YES15.0201583
2.0
581B,C
Table 4—Electrical Data 581B
VOLTAGE
COMPRESSOR (each)OFM (each)
RANGE
IFM TYPEMinMaxQTYRLALRAQTYFLAFLAMCA
STD
0.60.3†
0.8†0.3†3.4†
10.40.3†
10.4†0.9†2.6†
187254110.37710.70.6
41450815.13910.40.3
HS5.2
HS2.6
STD
STD
Perfect
Humidity
STD
187254113.59310.70.6
HS5.8
STD
10.40.3†
10.40.9†2.6†
41450816.446.510.40.3
HS2.6
STD
Perfect
Humidity
STD
187254117.312311.50.6
414508196210.80.3
HS7.5
HS3.4
STD
HS51863217.15012.8
STD
187254120.515611.4
HS0.67.5
STD
Perfect
Humidity
STD
0.80.3†
0.6†0.3†3.4†
41450819.67510.6
STD
Perfect
Humidity
581B036---072
NOMINAL
V --- P H --- H z
UNIT SIZE
2 3 0 --- 1 --- 6 0STD1872541168810.70.64.9
208
208
036 (3 Tons)46 0 --- 3 --- 6 0
2 3 0 --- 1 --- 6 0STD187254123.712610.70.64.9
208
2 3 0 --- 3 --- 6 0
208
048 (4 Tons)46 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0HS51863214.2312.0
2 3 0 --- 1 --- 6 0STD187254128.816911.50.66.6
208
2 3 0 --- 3 --- 6 0
208
5 7 5 --- 3 --- 6 0
060 (5 Tons)46 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0HS51863216.4402.0
2 3 0 --- 3 --- 6 0
208
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0HS51863217.75612.8
072 (6 Tons)HS0.33.4
230--- 3 60
15
Step 8 —Adjust Factory--Installed Options
Perfect Humidity Adaptive Dehumidification
System
Perfect Humidity system operation can be controlled by field
installation of a Bryant--approved humidistat. (See Fig. 15.)
NOTE: A light commercial Thermidistat device (Fig. 16) can
be used instead of the humidistat if desired. The Thermidistat
device includes a thermostat and a humidistat. The humidistat is
normally used in applications where a temperature sensor is
already provided.
581B,C
% RELATIVE HUMIDITY
Fig. 15 --- Accessory Field--Installed Humidistat
Fig. 16 --- Light Commercial Thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 14). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low-- voltage
wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 17.
C06358
C06359
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 14). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low-- voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat and the Humidi-Mizer circuit (recommended
relay: HN61KK324). (See Fig. 18.) The relay coil is
connected between the DEHUM output and C (common)
of the unit. The relay controls thePerfect Humidity
solenoid valve and must be wired between the Perfect
Humidity fuse and the low-pressure switch. Refer to the
installation instructions included with the Bryant Light
Commercial Thermidistat device for more information.
Manual Outdoor
Damper
The outdoor--air hood and screen are attached to the basepan at
the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
(See Fig. 19.)
3. Remove evaporator coil access panel. Separate hood and
screen from basepan by removing the 4 screws securing
them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 20 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.21.)
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. (See Fig. 28 and 21.) Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by
adjusting the manual outdoor-air adjustment screws on the
front of the damper blade. (See Fig. 19.) Slide blade
vertically until it is in the appropriate position determined
by Fig. 22. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. (See
Fig. 21.)
Convenience
Outlet
An optional convenience outlet provides power for rooftop use.
For maintenance personnel safety, the convenience outlet power
is off when the unit disconnect is off. Adjacent unit outlets may
be used for service tools.
Fig. 17 --- Typical Perfect Humidityt Adaptive Dehumidification System
LEGEND
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Humidistat Wiring (208/230--V Unit Shown)
C06128
581B,C
LCT
R
C
Y1
Y2
G
W1
W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB— Circuit Breaker
LCT — Light Commercial Thermidistat™ Device
LLSV — Liquid Line Solenoid Valve
LT LO — Low Temperature Lockout
Fig. 18 --- Typical Rooftop Unit with Perfect Humidity
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
R1
R1
ROOF TOP UNIT
R
C
Y1
Y2
G
W1
W2
PINK
PINK
CB
3.2 AMPS
LTL O
PERFECT HUMIDITY SYSTEM
RED
24 V
PINK
FROM
PERFECT HUMIDITY SYSTEM
LLSV
C06360
Fig. 19 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 20 --- Outdoor-- Air Hood Details
17
A
581B,C
Fig. 21 --- Outdoor-- Air Damper With
Hood Attached
Fig. 22 --- Outdoor-- Air Damper Position Setting
ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS
CTUATOR
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
C06131
C06132
Optional Economi$er
IV
See Fig. 23 for EconoMi$er IV component locations.
NOTE:These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV when
field installing an EconoMi$er IV accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. (See
Fig. 24.)
2. The box with the economizer hood components is shipped
in the compartment behind the economizer. The
EconoMi$er IV controller is mounted on top of the
EconoMi$er IV. To remove the component box from its
shipping position, remove the screw holding the hood box
bracket to the top of the economizer. Slide the hood box
out of the unit. (See Fig. 25.)
IMPORTANT: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. (See Fig. 26.)
4. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. (See Fig. 27.)
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See
Fig. 28 and 29.) Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. (See Fig. 28.)
8. Caulk the ends of the joint between the unit top panel and
the hood top. (See Fig. 26.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 29.
Barometric flow capacity is shown in Fig. 30. Outdoor air
leakage is shown in Fig. 33. Return air pressure drop is shown in
Fig. 32.
FILTER ACCESS PANEL
C06021
Fig. 23 --- EconoMi$er IV Component Locations
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 24 --- Typical Access Panel Locations
C06023
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.