Fire Alarm Systems | TRUTEST801 Smoke detector sensitivity tester
TRUTEST801 Smoke detector sensitivity tester
www.boschsecurity.com
The TRUTEST801 introduces a measured amount of smoke aerosol (SMOKE400, not supplied) into the installed smoke detector’s smoke chamber. It operates using a precision closed-loop system that measures the smoke obscuration and feeds information back to a controlling microprocessor. It then displays the sensitivity reading in %/ft. on a liquid crystal display (LCD) screen.
Certifications and approvals
No Climb Products Ltd. holds these Listings and Approvals:
Region |
Regulatory compliance/quality marks |
|
|
|
|
USA |
UL |
UL 268, Smoke Detectors for Fire Alarm |
|
|
Systems |
|
|
|
Installation/configuration notes
The TRUTEST801 requires either the SOLO100 Telescopic pole (1-3.38 m) or the SOLO101 Extension pole (1 m). Neither is supplied.
uCompatible with analog-addressable, addressable, or conventional ionization and photoelectric detectors
uAutomatic self-calibration before each test
uTelescopic adjustment to over 20 ft (6 m) with the optional SOLO100 Telescopic Access Pole
uLightweight and portable
uEasy to use
Parts included
Quantity |
Component |
1 |
Main unit |
|
|
1 |
Control unit |
|
|
2 |
Interconnecting cables (different lengths) |
|
|
1 |
Height adjustment clamp |
|
|
2 |
Membrane seals (different apertures) |
|
|
1 |
Battery charger |
|
|
1 |
Carry case |
|
|
1 |
Literature pack |
|
|
2 | TRUTEST801 Smoke detector sensitivity tester
Technical specifications
Environmental
Relative Humidity: |
|
up to 85%, non condensing |
|
|
|
Temperature (operating): |
+50°F to +95°F (+10°C to +35°C) |
|
|
|
|
Temperature (storage): |
+15°F to +120°F (-10°C to +50°C) |
|
|
|
|
Mechanical |
|
|
|
|
|
Dimensions |
0.870 m x 0.381 m x 0.254 m (34.25 in. x 15 in. x |
|
(LxWxH) |
10 in.) |
|
|
|
|
Weight |
|
|
gross |
11.250 kg (24.8 lb.) |
|
net |
9.885 kg (21.8 lb.) |
|
|
|
|
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
TRUTEST801 Smoke detector sensitivity tester
Uses a precision closed-loop system to measure smoke obscuration. Then displays the sensitivity reading in %/ft. on a liquid crystal display (LCD) screen
Order number TRUTEST801
Accessories
SOLO100 Telescopic access pole
Enables the installation and replacement of fire detectors at high ceilings. Expandable with up to three SOLO101 Fixed extension poles. In the Americas, the product is labelled SOLO100. Elsewhere, the product is labelled SOLO106-126.
Order number SOLO100
SOLO101 Extension pole
Enables the installation and replacement of fire detectors on ceilings. Expandable with other fixed extension poles. Can be used to extend the SOLO100 Telescopic access pole.
Order number SOLO101
Represented by: |
|
|
|
Europe, Middle East, Africa: |
Germany: |
North America: |
Asia-Pacific: |
Bosch Security Systems B.V. |
Bosch Sicherheitssysteme GmbH |
Bosch Security Systems, Inc. |
Robert Bosch (SEA) Pte Ltd, Security Systems |
P.O. Box 80002 |
Robert-Bosch-Ring 5 |
130 Perinton Parkway |
11 Bishan Street 21 |
5600 JB Eindhoven, The Netherlands |
85630 Grasbrunn |
Fairport, New York, 14450, USA |
Singapore 573943 |
Phone: + 31 40 2577 284 |
Germany |
Phone: +1 800 289 0096 |
Phone: +65 6571 2808 |
emea.securitysystems@bosch.com |
www.boschsecurity.com |
Fax: +1 585 223 9180 |
Fax: +65 6571 2699 |
emea.boschsecurity.com |
|
onlinehelp@us.bosch.com |
apr.securitysystems@bosch.com |
|
|
www.boschsecurity.us |
www.boschsecurity.asia |
© Bosch Security Systems 2018 | Data subject to change without notice 2741676043 | en, V5, 05. Dec 2018