Fire Alarm Systems | FMM‑7045 Multiplex Addressable Manual Stations
FMM‑7045 Multiplex Addressable Manual
Stations
www.boschsecurity.com
u Easy addressing with rotary switches
u Terminal connections and low current draw
The FMM‑7045 Multiplex Manual Stations are UL
Listed fire alarm initiating devices that can be
connected along with other multiplex devices on the
D7039 Multiplex Expansion Module. The FPD‑7024 or
D7024 Addressable Fire Alarm Control Panel (FACP)
supervises the entire multiplex loop, including the
FMM‑7045 or FMM‑7045‑D manual stations, for
troubles, alarms, and ground fault conditions. Because
each manual station occupies only one address on the
multiplex bus, it can be addressed for any point within
the 9 to 255 range allowed by the multiplex expansion
module.
These manual stations are generally installed near
building exits such as stairways and doors, allowing
persons evacuating the building to activate the fire
alarm. They have optional scored acrylic breakrods and
a pull handle that locks in the activated position, to
allow easy identification of alarm activation points.
These manual stations are high‑quality units
constructed entirely of non‑toxic materials. They have
a low profile and rounded edges to fit most design
applications. All components are painted or have
plated surfaces to inhibit corrosion. Non-corroding
screw terminals are provided for wire connections.
u Key‑lock reset
u Replaceable scored acrylic break rod option
u UL Listed and ADA compliant
They are manufactured in conformance with the
standards set forth in the Americans with Disabilities
Act (ADA).
Functions
Alarm Action
The single‑action FMM‑7045 has a white pull‑down
lever in its center. The dual‑action FMM‑7045‑D has a
white push lever above the white pull‑down lever in its
center. Pulling down the pull‑down lever latches it into
place and sends an alarm signal to the control panel
over the multiplex bus. The pull‑down lever cannot be
reset unless the correct key is inserted into the manual
station's lock and the unit is opened. The latching
lever can then be restored to its normal position.
2 | FMM‑7045 Multiplex Addressable Manual Stations
Certifications and approvals
Region Certification
USA UL UNIU: Boxes, Non-Coded (UL38)
CSFM see our website
FDNYCoA
#6173
Installation/configuration notes
Compatibility Information
The following table lists control panels compatible
with the FMM‑7045 and FMM-7045-D manual stations:
Control Panels
Active products:
FPD-7024
Legacy products:
D7024*
* with firmware revision 2.0 or greater and with a D7039 Multiplex
Expansion module
Addressing
Addresses are set using three rotary switches.
For programming information, refer to the D7024 FACP
Operation and Installation Guide or the FPD‑7024
Operation and Installation Guide and the FMM-7045,
FMM-7045-D Multiplex Addressable Manual Stations
Installation Instructions.
Mounting
The manual stations are for indoor use only.
Parts included
Quant. Component
1 Manual station
1 FMM‑100GR Scored Acrylic Breakrod
1 D102 Key (1358)
1 Literature pack
Technical specifications
Environmental Considerations
Environment: Dry, indoor
Radio Frequency
Interference (RFI)
Immunity:
Temperature
(Operating):
No alarm on critical frequencies in the
range from 26 MHz to 950 MHz at field
strengths less than 30 V/m.
+32°F to +120°F (0°C to +49°C)
Mechanical Properties
Dimensions (H x W x D): 4.75 in. x 3.75 in. x 3.25 in.
Material: Die cast zinc alloy and steel
(12 cm x 9.5 cm x 8.2 cm)
Power Requirements
Current Draw (Mux Bus
Average):
Voltage (Operating): 12 VDC nominal (provided by the MUX
Alarm: 0.55 mA
Standby: 0.55 mA
bus)
Ordering information
Notice
If a pull station is needed for outdoor use or in an
unheated area, use an FMM‑100 Family Pull
Station rated for the environment and wired to a
multiplex module within the interior of the
building.
The FMM‑7045 manual stations flush or surface mount
on a standard four‑inch square back box with a
single‑gang mud ring so that the total depth of the box
is at least 2.25 in. (5.7 cm).
Notice
These manual stations do not fit an FMM‑100BB‑R
Back Box.
Wiring
The terminal block accepts wiring up to 12 AWG (ISO
4 mm2) in diameter.
For multiplex wiring information, refer to the D7039
Installation Instructions.
FMM‑7045 Single‑Action Manual Station
The single‑action manual station is UL listed and meets
Americans with Disabilities Act (ADA) requirements. Its
address on the polling circuit is easily set with rotary
switches. The pull handle locks in the activated
position and is reset by opening the unit with a key
and then relocking it.
Order number FMM-7045
FMM‑7045‑D Double‑Action Manual Station
The double‑action manual station is UL listed and
meets Americans with Disabilities Act (ADA)
requirements. Its address on the polling circuit is
easily set with rotary switches. The pull handle locks in
the activated position and is reset by opening the unit
with a key and then relocking it.
Order number FMM-7045-D
Accessories
D102 Replacement Key
Replacement key (#1358) for LOCK‑1358 and the
D101 lock.
Order number D102