Bosch FMM-325A-D Specsheet

Fire Alarm Systems | FMM‑325A Analog Manual Stations
FMM‑325A Analog Manual Stations
www.boschsecurity.com
u Digital data communications and power provided
over two-wire circuit
u EEPROM addressing in module unit
construction
These manual stations are used in the polling circuit of the Bosch Security Systems, Inc.'s FPA‑1000 Analog Addressable Fire Panels, and the D9024, D8024, and D10024A Fire Alarm Control Panels (FACP). They communicate with the control panel (both power and data) over a two‑wire polling circuit. The manual station's address on the polling circuit is set by programming an EEPROM microchip. The D5070 Analog Device Programmer is required to set the address. All commercial buildings use manual stations. These manual stations allow people evacuating a building to initiate an alarm. The FACP identifies the alarm point on the polling circuit and the alarm lever latches in the pulled position.
Certifications and approvals
ADA Complies with Americans with
Disabilities Act ADA 4.28.3
NFPA Complies with National Fire Protection
Association NFPA 72
u Single‑gang mounting
u Latching alarm lever
Region Certification
USA UL UNIU: Boxes, Non-Coded (UL38)
CSFM see our website
Installation/configuration notes
Compatibility Information
The following table lists products compatible with these manual stations:
Active products:
FPA-1000 Analog Addressable Control Panel
D5070 Programmer
Legacy products:
FPA-1000-UL Compact Fire Panel
D10024A, D9024, and D8024 Fire Alarm Control Panels
Mounting Considerations
These manual stations are for indoor use only. They have die-cast housings that flush mount on a single­gang back box. For surface mounting, use an FMM‑100BB‑R Surface‑mount Back Box.
2 | FMM‑325A Analog Manual Stations
Parts included
Quant. Component
1 Manual station
1 FLM-325-IM Point Contact Module
1 FMM‑100GR Scored Acrylic Breakrod
1 D102 Key (#1358)
1 Literature pack
Technical specifications
Electrical
Current
Alarm: 28 mA
Polling: 22 mA ± 20%
Standby: 0.35 mA typical
Voltage
Input: 24 VDC nominal
Operating: 17 VDC to 41 VDC
Environmental
Accessories
D102 Replacement Key
Replacement key (#1358) for LOCK‑1358 and the D101 lock.
Order number D102
FMM‑100BB‑R Surface‑mount Back Box (red)
Red cast‑metal back box
Order number FMM-100BB-R
FMM‑100GR Scored Acrylic Break Rods
Scored acrylic rods (12 per package)
Order number FMM-100GR
Temperature (operating):
+14°F to +120°F (-10°C to +49°C)
Mechanical
Activation Force: 5 lb (2.3 kg)
Dimensions (H x W x D):
Material: Painted die‑cast metal
4.75 in. x 3.2 in. x 0.875 in. (12.1 cm x 8.1 cm x 2.2 cm)
Ordering information
FMM‑325A Single‑action Manual Station
The single‑action manual station is UL listed for commercial fire applications and meets Americans with Disabilities Act (ADA) requirements. Its address on the polling circuit is set by programming an EEPROM microchip with the D5070 Analog Device Programmer.
Order number FMM-325A
FMM‑325A‑D Double‑action Manual Station
The double‑action manual station is UL listed for commercial fire applications and meets Americans with Disabilities Act (ADA) requirements. Its address on the polling circuit is set by programming an EEPROM microchip with the D5070 Analog Device Programmer.
Order number FMM-325A-D