Bosch FMM-100SAT2CK-Y, FMM-100SAT2CK-B, FMM-100SAT2CK-G Specsheet

Fire Alarm Systems | FMM‑100 Single‑action, Die‑cast Metal Manual Stations
FMM‑100 Single‑action, Die‑cast Metal Manual Stations
www.boschsecurity.com
u Terminal connections
u Gold‑plated alarm contacts for corrosion resistance
The FMM‑100 family are versatile, high‑quality, metal manual stations in blue, green, or yellow. These single‑action manual stations have two single-pole, double-throw (SPDT) contacts that are individually field‑configurable for normally-open (NO) or normally­closed (NC) operation. They come with a key lock and contain gold‑plated contacts to resist corrosion.
Functions
Operation
When the bar on the front of the manual station is pulled, it latches open and is easily visible from 50 ft (15 m). Reset the activation bar by opening the manual station with the key and placing the activation bar in its normal upright position. An optional scored acrylic break rod is available.
Certifications and approvals
Region Certification
USA UL UNIU: Boxes, Non-coded (UL38),
UNIU7: Boxes, Non-coded Certified for Canada (ULC-S528-M91)
u Optional labels
Installation/configuration notes
Compatibility Information
These manual stations are compatible with all Bosch Security Systems, Inc. control panels.
Mounting Considerations
These manual stations can be surface mounted on the FMM‑100BB Series Surface‑mount Back Boxes or flush mounted on a standard single‑gang back box. Mounting locations are subject to local regulations. To comply with ADA standards, the manual station must be less than 48 in. (1.2 m) above the floor for front wheelchair access and less than 54 in. (1.3 m) above the floor for side wheelchair access.
Parts included
The following parts are provided with each manual station in the FMM‑100 series:
Quant. Component
1 Manual station
1 D102 Key (1358 key)
2 | FMM‑100 Single‑action, Die‑cast Metal Manual Stations
1 FMM‑100GR Acrylic Break Rod
1 Hardware pack
1 Literature pack
1 Label pack (see following)
Each single‑action manual station is also supplied with a specific set of labels for the top and bottom of the manual station. Use these labels to customize the manual station for specific emergency warning applications. The label pack provided with each manual station contains the indicated labels:
Labels for Top
Blue Green Yellow
Alarm Alarm
Alert Alert
Open Door
Labels for Bottom
Blue Green Yellow
AFFF Release
Bosch
Door Release
Emergency
Extinguisher Release
HazMat
Manual Release
Medical
Police
Sprinkler Release
Suppression Release
Tornado
Technical specifications
Inputs
Switch Rating: 1 A at 30 VDC or 125 VAC
Ordering information
FMM‑100SAT2CK‑B Single‑action Manual Station (blue)
Versatile, high‑quality, single‑action metal manual station in blue with key lock and gold‑plated contacts
Order number FMM-100SAT2CK-B
FMM‑100SAT2CK‑G Single‑action Manual Station (green)
Versatile, high‑quality, single‑action metal manual station in green with key lock and gold‑plated contacts
Order number FMM-100SAT2CK-G
FMM‑100SAT2CK‑Y Single‑action Manual Station (yel­low)
Versatile, high‑quality, single‑action metal manual station in yellow with key lock and gold‑plated contacts
Order number FMM-100SAT2CK-Y
Accessories
D102 Replacement Key
Replacement key (#1358) for LOCK‑1358 and the D101 lock.
Order number D102
FMM‑100BB‑B Surface‑mount Back Box (blue)
Blue cast‑metal back box
Order number FMM-100BB-B
FMM‑100BB‑G Surface‑mount Back Box (green)
Green cast‑metal back box
Order number FMM-100BB-G
FMM‑100BB‑Y Surface‑mount Back Box (yellow)
Yellow cast‑metal back box
Order number FMM-100BB-Y
FMM‑100GR Scored Acrylic Break Rods
Scored acrylic rods (12 per package)
Order number FMM-100GR
Environmental
Relative Humidity: 90% at +100°F (+38°C)
Temperature (operating):
-40°F to +150°F (-40°C to +66°C)
Mechanical
Color: Blue: FMM‑100SAT2CK‑B
Dimensions (H x W x D): 4.75 in. x 3.25 in. x 1.1 in.
Material: Die‑cast metal
Green: FMM‑100SAT2CK‑G Yellow: FMM‑100SAT2CK‑Y
(12 cm x 8.3 cm x 2.8 cm)