Fire Alarm Systems - FMC‑300RW Single Action Call Points
FMC‑300RW Single Action Call Points
u Alarm triggering by pressing the black marking
or breaking the glass pane
u Protection against injury through foil-labeled
glass pane
u LED display for triggered alarm or inspection
evaluation
FMC‑300RW Single Action Call Points are used for
manual alarm triggering and are employed in
conventional technology.
Functions
Single action call points with glass pane:
Pressing the black marking (1) breaks the glass pane
(3), which triggers the alarm and causes the LED
display (2) to flash.
Single action call points can be reset with the test key
and by replacing the glass pane (3). The LED display
(2) switches off.
Resettable single action call points:
Pressing the black marking (1) triggers the alarm. The
alarm status is displayed by the red window color (4)
and the flashing LED display (2).
Single action call points can be reset using the test
key. The LED display (2) switches off.
The standby mode is indicated by the white window
color (4).
Certifications and approvals
Applies to EN54‑11:2001/A1:2005
Region Regulatory compliance/quality marks
Germany
Europe
VdS
CE
CE
CPD
G 207086 FMC-300RW
FMC-300RW-GSGRD, -GSRRD
FMC-300RW-GSGYE/BU, -GSRYE/BU
0786-CPD-20332 FMC-300RW
Installation/configuration notes
• Manual call points have to be mounted visibly along
escape and rescue routes (e.g. exits, passageways,
stairwells) and be easily accessible.
• An installation height of 1400mm ±200mm,
measured from the middle of the manual call point
to the floor, must be maintained.
• Manual call points must be illuminated sufficiently
with daylight or another light source (including
emergency lighting, if present).
• Max. one test detector may be used for primary
lines together with automatic detectors. The test
detector is connected at the end of the primary line.
• Further standards, guidelines and planning
recommendations regarding the installation location
etc., should also be taken into consideration.
• Regulations of local fire departments must be
observed.
Fire Alarm Systems - FMC‑300RW Single Action Call Points
2 | 3
Technical specifications
Electrical
Operating voltage
Current consumption
Alarm resistor
20VDC
(8.5VDC to 30VDC)
specified by the respective security
system
820Ω +/- 10%
(8.5VDC to 30VDC)
Mechanical components
Dimensions (H x W x D)
Housing material
Colors
• Red
• Blue
• Yellow
87mm x 87mm x 56mm (3.4 in. x
3.4 in. x 2.2 in.)
Plastic, ASA
RAL 3001
RAL 5005
RAL 1003
Environmental conditions
Protection category according to EN
60529
Permissible operating temperature
IP 54
-25°C to +70°C
Ordering information
FMC-300RW-GSGBU Manual call point, glass, blue
conventional manual call point with glass pane for indoor
use, direct alarm triggering (type A), surface-mounted,
blue
Order number FMC-300RW-GSGBU | F.01U.012.724
FMC-300RW-GSRBU Manual call point, resettable, blue
resettable conventional manual call point for indoor use,
direct alarm triggering (type A), surface-mounted, blue
Order number FMC-300RW-GSRBU | F.01U.012.770
FMC-300RW-GSGRD Manual call point glass surfacemnt, red
conventional manual call point with glass pane for indoor
use, direct alarm triggering (type A), surface-mounted,
red
Order number FMC-300RW-GSGRD | F.01U.012.771
FMC-300RW-GSRRD Manual call point reset surfacemnt, red
resettable conventional manual call point for indoor use,
direct alarm triggering (type A), surface-mounted, red
Order number FMC-300RW-GSRRD | F.01U.012.777
FMC-300RW-GSGYE Manual call point, glass, yellow
conventional manual call point with glass pane for indoor
use, direct alarm triggering (type A), surface-mounted,
yellow
Order number FMC-300RW-GSGYE | F.01U.012.778
FMC-300RW-GSRYE Manual call point, resettable,
yellow
resettable conventional manual call point for indoor use,
direct alarm triggering (type A), surface-mounted, yellow
Order number FMC-300RW-GSRYE | F.01U.012.779
Accessories
FMC-BEZEL-RD Bezel for manual call point, red
Frame for the flush-mounted variant of the RW call
points.
1 unit = 4 bezels
Order number FMC-BEZEL-RD | F.01U.073.045
FMC-BEZEL-WH Bezel for manual call point, white
Frame for the flush-mounted variant of the RW call
points.
1 unit = 4 bezels
Order number FMC-BEZEL-WH | F.01U.073.046
FMC-SEAL-RW Seal for manual call point
Seal for clear hinged flap
1 unit = 100 seals
Order number FMC-SEAL-RW | F.01U.073.214
FMC-SPACER-RWRD Spacer, red
For the flush-mounted variant of the RW call points. Its
use increases the storage room for the cables.
1 unit = 5spacers
Order number FMC-SPACER-RWRD | F.01U.013.460
FMC-SPGL-RW Spare glass
Spare glasses for all RW call points.
1 unit = 5 spare glasses
Order number FMC-SPGL-RW | F.01U.013.504
FMC-SIGN-RW Sign, out-of-order
Used instead of the glass pane when a call point is not
ready for use.
1 unit = 5 signs
Order number FMC-SIGN-RW | F.01U.028.195
FMC-KEY-RW Test key
The key can open, check, and reset manual call points.
1 unit = 1 key
Order number FMC-KEY-RW | F.01U.028.227
FMC-FLAP-RW Flap, transparent
To protect against accidental triggering; with seal.
1 unit = 5 flaps
Order number FMC-FLAP-RW | F.01U.028.194