Bosch FMC‑300RW Datasheet

Fire Alarm Systems - FMC‑300RW Single Action Call Points
1
2
3
1
2
4
FMC‑300RW Single Action Call Points
u Alarm triggering by pressing the black marking
or breaking the glass pane
u Protection against injury through foil-labeled
glass pane
u LED display for triggered alarm or inspection
evaluation
Functions
Single action call points with glass pane:
Pressing the black marking (1) breaks the glass pane (3), which triggers the alarm and causes the LED display (2) to flash. Single action call points can be reset with the test key and by replacing the glass pane (3). The LED display (2) switches off.
Resettable single action call points:
Pressing the black marking (1) triggers the alarm. The alarm status is displayed by the red window color (4) and the flashing LED display (2). Single action call points can be reset using the test key. The LED display (2) switches off. The standby mode is indicated by the white window color (4).
Certifications and approvals
Applies to EN54‑11:2001/A1:2005
Region Regulatory compliance/quality marks
Germany
Europe
VdS
CE
CE
CPD
G 207086 FMC-300RW
FMC-300RW-GSGRD, -GSRRD
FMC-300RW-GSGYE/BU, -GSRYE/BU
0786-CPD-20332 FMC-300RW
Installation/configuration notes
• Manual call points have to be mounted visibly along escape and rescue routes (e.g. exits, passageways, stairwells) and be easily accessible.
• An installation height of 1400mm ±200mm, measured from the middle of the manual call point to the floor, must be maintained.
• Manual call points must be illuminated sufficiently with daylight or another light source (including emergency lighting, if present).
• Max. one test detector may be used for primary lines together with automatic detectors. The test detector is connected at the end of the primary line.
• Further standards, guidelines and planning recommendations regarding the installation location etc., should also be taken into consideration.
• Regulations of local fire departments must be observed.
Fire Alarm Systems - FMC‑300RW Single Action Call Points
2 | 3
Technical specifications
Electrical
Operating voltage
Current consumption
Alarm resistor
20VDC
(8.5VDC to 30VDC)
specified by the respective security system
820Ω +/- 10%
(8.5VDC to 30VDC)
Mechanical components
Dimensions (H x W x D)
Housing material
Colors
Red
Blue
Yellow
87mm x 87mm x 56mm (3.4 in. x
3.4 in. x 2.2 in.)
Plastic, ASA
RAL 3001
RAL 5005
RAL 1003
Environmental conditions
Protection category according to EN 60529
Permissible operating temperature
IP 54
-25°C to +70°C
Ordering information
FMC-300RW-GSGBU Manual call point, glass, blue
conventional manual call point with glass pane for indoor use, direct alarm triggering (type A), surface-mounted, blue Order number FMC-300RW-GSGBU | F.01U.012.724
FMC-300RW-GSRBU Manual call point, resettable, blue
resettable conventional manual call point for indoor use, direct alarm triggering (type A), surface-mounted, blue Order number FMC-300RW-GSRBU | F.01U.012.770
FMC-300RW-GSGRD Manual call point glass surface­mnt, red
conventional manual call point with glass pane for indoor use, direct alarm triggering (type A), surface-mounted, red Order number FMC-300RW-GSGRD | F.01U.012.771
FMC-300RW-GSRRD Manual call point reset surface­mnt, red
resettable conventional manual call point for indoor use, direct alarm triggering (type A), surface-mounted, red Order number FMC-300RW-GSRRD | F.01U.012.777
FMC-300RW-GSGYE Manual call point, glass, yellow
conventional manual call point with glass pane for indoor use, direct alarm triggering (type A), surface-mounted, yellow Order number FMC-300RW-GSGYE | F.01U.012.778
FMC-300RW-GSRYE Manual call point, resettable, yellow
resettable conventional manual call point for indoor use, direct alarm triggering (type A), surface-mounted, yellow Order number FMC-300RW-GSRYE | F.01U.012.779
Accessories
FMC-BEZEL-RD Bezel for manual call point, red
Frame for the flush-mounted variant of the RW call points. 1 unit = 4 bezels Order number FMC-BEZEL-RD | F.01U.073.045
FMC-BEZEL-WH Bezel for manual call point, white
Frame for the flush-mounted variant of the RW call points. 1 unit = 4 bezels Order number FMC-BEZEL-WH | F.01U.073.046
FMC-SEAL-RW Seal for manual call point
Seal for clear hinged flap 1 unit = 100 seals Order number FMC-SEAL-RW | F.01U.073.214
FMC-SPACER-RWRD Spacer, red
For the flush-mounted variant of the RW call points. Its use increases the storage room for the cables. 1 unit = 5spacers Order number FMC-SPACER-RWRD | F.01U.013.460
FMC-SPGL-RW Spare glass
Spare glasses for all RW call points. 1 unit = 5 spare glasses Order number FMC-SPGL-RW | F.01U.013.504
FMC-SIGN-RW Sign, out-of-order
Used instead of the glass pane when a call point is not ready for use. 1 unit = 5 signs Order number FMC-SIGN-RW | F.01U.028.195
FMC-KEY-RW Test key
The key can open, check, and reset manual call points. 1 unit = 1 key Order number FMC-KEY-RW | F.01U.028.227
FMC-FLAP-RW Flap, transparent
To protect against accidental triggering; with seal. 1 unit = 5 flaps Order number FMC-FLAP-RW | F.01U.028.194
Loading...