Bosch FMC210SM User Manual

Fire Alarm Systems | FMC‑210‑SM Single Action Call Points
2
23
3
4
5
FMC‑210‑SM Single Action Call Points
Alarm triggering by breaking of the glass pane
Automatic or manual detector addressing via rotary
switch possible
Indicator LED for alarm or for inspection evaluation
Call point query routines with evaluation and multiple
transmission
Individual call point identification
Maintains LSN loop functions in the event of wire
interruption or short-circuit thanks to two integrated isolators
The FMC‑210‑SM Single Action Call Points are used for manual triggering, and can be used in the Local SecurityNetwork LSN and LSN improved. The FMC‑210‑SM Single Action Call Points are designed for indoor deployment.

Functions

With single action call points, the alarm is triggered when the glass plate (2) is broken and the button (3) springs up.
This activates the microswitch for alarm triggering and the indicator LED (4) blinks.
The call point (3) can be reset after inserting a new glass pane (2) and closing the door of the single action call point (1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Individual call point identification with display of the call point address on the fire panel ensures the quick location of the triggered call point.

Certifications and Approvals

FMC‑210‑SM‑G‑R applies to
EN 54‑11:2001/A1:2005
EN 54‑17:2005
Region Certification
Germany VdS G 207008 FMC-210-SM-G-R
Europe CPD 0786-CPD-20316 FMC-210-SM-G-R

Installation/Configuration Notes

Manual call points must be mounted visibly along
escape and rescue routes (e. g. exits, passageways, stairwells) and be easily accessible. An installation height of 1400 mm ±200 mm, measured
from the middle of the manual call point to the floor, must be maintained. Manual call points must be adequately illuminated by
sunlight or another light source (including emergency lighting if present).
www.boschsecurity.com
2 | FMC‑210‑SM Single Action Call Points
135 mm
140 mm
2,5 mm
2 mm
139 mm
1
2
3
149,5 mm
12,5 mm
The maximum number of LSN elements that may be
connected depends on their current consumption from the LSN data line. The limit values should be taken from the product information supplied with the fire panel used. Further standards, guidelines and planning
recommendations regarding the installation location etc., should also be taken into consideration (see Fire Detection manual). The regulations of the local fire services must be
observed.
Installation notes in accordance with VdS/VDE
The distance between manual call points should not
be more than 100 m according to DIN 14675 or 80 m according to VdS. In high risk areas, manual call points should be
installed at a distance of max. 40 m (VDE 0833 Part 2, Point 7.2.6).
Installation
The cable duct can be surface-mounted or flush-
mounted.
Pos. Description
1 Installation depth version 1: ca. 40 mm
2 Installation depth version 2: 14 mm
3 Installation depth version 3: min. 30 mm

Parts Included

Installation in fire hose cabinets is possible in three
ways:
TypeNumber. Component
FMC‑210‑SM‑G‑B Form G, Blue
FMC‑210‑SM‑G‑R Form G, Red
Note The key must be ordered separately.
Single Action Call Point for indoor use, direct trig­gering (type A)
Single Action Call Point for indoor use, direct trig­gering (type A

Technical Specifications

Electrical
Operating voltage 15 V DC . . . 33 V DC
Current consumption 0.4 mA
Mechanics
Dimensions (H x W x D) 135 x 135 x 40 mm
Housing material Plastic, ASA
Colors
FMC-210-SM-G-R
FMC-210-SM-G-B
Weight Approx. 235 g
Red, RAL 3001
Blue, RAL 5005