Fire Alarm Systems | FMC‑210‑SM Single Action Call Points
11
2
23
3
4
5
FMC‑210‑SM Single Action Call Points
Alarm triggering by breaking of the glass pane
▶
Automatic or manual detector addressing via rotary
▶
switch possible
Indicator LED for alarm or for inspection evaluation
▶
Call point query routines with evaluation and multiple
▶
transmission
Individual call point identification
▶
Maintains LSN loop functions in the event of wire
▶
interruption or short-circuit thanks to two integrated
isolators
The FMC‑210‑SM Single Action Call Points are used for
manual triggering, and can be used in the Local
SecurityNetwork LSN and LSN improved. The
FMC‑210‑SM Single Action Call Points are designed for
indoor deployment.
Functions
With single action call points, the alarm is triggered when
the glass plate (2) is broken and the button (3) springs
up.
This activates the microswitch for alarm triggering and the
indicator LED (4) blinks.
The call point (3) can be reset after inserting a new glass
pane (2) and closing the door of the single action call
point (1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Individual call point identification with display of the call
point address on the fire panel ensures the quick location
of the triggered call point.
Certifications and Approvals
FMC‑210‑SM‑G‑R applies to
EN 54‑11:2001/A1:2005
•
EN 54‑17:2005
•
RegionCertification
GermanyVdSG 207008 FMC-210-SM-G-R
EuropeCPD0786-CPD-20316 FMC-210-SM-G-R
Installation/Configuration Notes
Manual call points must be mounted visibly along
•
escape and rescue routes (e. g. exits, passageways,
stairwells) and be easily accessible.
An installation height of 1400 mm ±200 mm, measured
•
from the middle of the manual call point to the floor,
must be maintained.
Manual call points must be adequately illuminated by
•
sunlight or another light source (including emergency
lighting if present).
www.boschsecurity.com
Page 2
2 | FMC‑210‑SM Single Action Call Points
135 mm
140 mm
2,5 mm
2 mm
139 mm
1
2
3
149,5 mm
12,5 mm
The maximum number of LSN elements that may be
•
connected depends on their current consumption
from the LSN data line. The limit values should be
taken from the product information supplied with the
fire panel used.
Further standards, guidelines and planning
•
recommendations regarding the installation location
etc., should also be taken into consideration (see Fire
Detection manual).
The regulations of the local fire services must be
•
observed.
Installation notes in accordance with VdS/VDE
The distance between manual call points should not
•
be more than 100 m according to DIN 14675 or 80 m
according to VdS.
In high risk areas, manual call points should be
•
installed at a distance of max. 40 m (VDE 0833 Part 2,
Point 7.2.6).
Installation
The cable duct can be surface-mounted or flush-
•
mounted.
Pos.Description
1Installation depth version 1: ca. 40 mm
2Installation depth version 2: 14 mm
3Installation depth version 3: min. 30 mm
Parts Included
Installation in fire hose cabinets is possible in three
•
ways:
TypeNumber.Component
FMC‑210‑SM‑G‑B
Form G, Blue
FMC‑210‑SM‑G‑R
Form G, Red
NoteThe key must be ordered separately.
Single Action Call Point for indoor use, direct triggering (type A)
Single Action Call Point for indoor use, direct triggering (type A
Technical Specifications
Electrical
Operating voltage15 V DC . . . 33 V DC
Current consumption0.4 mA
Mechanics
Dimensions (H x W x D)135 x 135 x 40 mm
Housing materialPlastic, ASA
Colors
FMC-210-SM-G-R
•
FMC-210-SM-G-B
•
WeightApprox. 235 g
Red, RAL 3001
Blue, RAL 5005
Page 3
Environmental Considerations
Protection class as per EN 60529IP 52
Permissible operating temperature -10 °C. . . +55 °
Ordering Information
FMC‑210‑SM‑G‑B Form G, Blue
Single Action Call Point for indoor use, direct
triggering (type A), for LSN improved
FMC‑210‑SM‑G‑R Form G, Red
Single Action Call Point for indoor use, direct
alarm triggering (type A), for LSN improved