Fire Alarm Systems | FLM‑325‑2I4 Dual Input Monitor
FLM‑325‑2I4 Dual Input Monitor
www.boschsecurity.com
u Two independent contact monitoring circuits
u Monitors Normally Open (NO) or Normally
Closed (NC) contacts
u Monitored Normally Open (NO) contacts can be
configured with or without EOL resistor
The FLM‑325‑2I4 Dual Input Monitor Module provides
two independent contact monitoring circuits while
only utilizing one address on the SLC loop. The
module can be programmed to monitor Normally Open
(NO) or Normally Closed (NC) dry contact types of fire
alarm and supervisory devices such as pull stations or
water flow devices.
It fits into a standard 4‑inch square or double‑gang
electrical back box.
Functions
Status display
The DIMM has a bi‑colored LED that flashes every time
the module is polled and can be switched on steady
when the module goes into active condition.
Certifications and approvals
Region Certification
USA UL UOXX: Control Unit Accessories, System
(ANSI/UL 864)
CSFM see our website
FDNY-
#6101
CoA
u Module address programming with the D5070
Analog Device Programmer between 1‑127
u Bicolored LED provides module status
Installation/configuration notes
Compatibility Information
The following products are compatible with the
FLM‑325‑2I4 Dual Input Monitor Module:
Category Product ID Product Description
Fire Panels FPA‑1000 Analog Addressable Fire Panels
Programmer D5070 Analog Device Programmer
Wiring
Install the FLM‑325‑2I4 Dual Input Monitor Module
with the following maximum distances to the EOL
resistor depending on the wirings:
Wirings Distances
14 AWG (ISO 2.5 mm2) 1500 ft (457 m)
16 AWG (ISO 1.5 mm2) 900 ft (274 m)
18 AWG (ISO 0.75 mm2) 550 ft (167 m)
Parts included
Quant. Component
1 FLM‑325‑2I4 Dual Input Monitor Module
2 | FLM‑325‑2I4 Dual Input Monitor
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2690678027 | en, V6, 24. Jul 2014
2 EOL resistor 22 kΩ
1 Wall plate
1 Literature pack
Technical specifications
Electrical
Operating Voltage 17 VDC to 41 VDC
Current Consumption
• Standby 0.6 mA
• Active (without LED) 0.6 mA
• Active (LED on) 30 mA
Mechanical
Dimensions (H x W x D) 4.7 in. x 4.2 in. x 1.4 in.
(11.9 cm x 10.7 cm x 3.6 cm)
Bicolored LED Red and green
Environmental
Operating Temperature +32°F to +120°F (0°C to +49°C)
Relative Humidity 90 %, non‑condensing
Ordering information
FLM‑325‑2I4 Dual Input Monitor
Provides two independent contact monitoring circuits
to monitor Normally Open (NO) or Normally Closed
(NC) dry contact types of fire alarm devices
Order number FLM-325-2I4