Bosch FLM-325-2I4 Specsheet

Fire Alarm Systems | FLM‑325‑2I4 Dual Input Monitor
FLM‑325‑2I4 Dual Input Monitor
www.boschsecurity.com
u Two independent contact monitoring circuits
u Monitors Normally Open (NO) or Normally
Closed (NC) contacts
configured with or without EOL resistor
The FLM‑325‑2I4 Dual Input Monitor Module provides two independent contact monitoring circuits while only utilizing one address on the SLC loop. The module can be programmed to monitor Normally Open (NO) or Normally Closed (NC) dry contact types of fire alarm and supervisory devices such as pull stations or water flow devices. It fits into a standard 4‑inch square or double‑gang electrical back box.
Functions
Status display
The DIMM has a bi‑colored LED that flashes every time the module is polled and can be switched on steady when the module goes into active condition.
Certifications and approvals
Region Certification
USA UL UOXX: Control Unit Accessories, System
(ANSI/UL 864)
CSFM see our website
FDNY-
#6101
CoA
u Module address programming with the D5070
Analog Device Programmer between 1‑127
u Bicolored LED provides module status
Installation/configuration notes
Compatibility Information
The following products are compatible with the FLM‑325‑2I4 Dual Input Monitor Module:
Category Product ID Product Description
Fire Panels FPA‑1000 Analog Addressable Fire Panels
Programmer D5070 Analog Device Programmer
Wiring
Install the FLM‑325‑2I4 Dual Input Monitor Module with the following maximum distances to the EOL resistor depending on the wirings:
Wirings Distances
14 AWG (ISO 2.5 mm2) 1500 ft (457 m)
16 AWG (ISO 1.5 mm2) 900 ft (274 m)
18 AWG (ISO 0.75 mm2) 550 ft (167 m)
Parts included
Quant. Component
1 FLM‑325‑2I4 Dual Input Monitor Module
2 | FLM‑325‑2I4 Dual Input Monitor
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2690678027 | en, V6, 24. Jul 2014
2 EOL resistor 22 kΩ
1 Wall plate
1 Literature pack
Technical specifications
Electrical
Operating Voltage 17 VDC to 41 VDC
Current Consumption
• Standby 0.6 mA
• Active (without LED) 0.6 mA
• Active (LED on) 30 mA
Mechanical
Dimensions (H x W x D) 4.7 in. x 4.2 in. x 1.4 in.
(11.9 cm x 10.7 cm x 3.6 cm)
Bicolored LED Red and green
Environmental
Operating Temperature +32°F to +120°F (0°C to +49°C)
Relative Humidity 90 %, non‑condensing
Ordering information
FLM‑325‑2I4 Dual Input Monitor
Provides two independent contact monitoring circuits to monitor Normally Open (NO) or Normally Closed (NC) dry contact types of fire alarm devices
Order number FLM-325-2I4