Fire Alarm Systems | Conventional Manual Call Points for Ex Areas
Conventional Manual Call Points for Ex Areas
www.boschsecurity.com
The Conventional Manual Call Points for Ex Areas are used to manually activate the alarm in zones 1 and 2 at risk of explosion. The K type call points are encapsulated, intrinsically safe call points and do not require any safety barriers. The DM 1103 B‑Ex Manual Call Points for ex zones must be connected via a Safety Barrier SB 3 incl. Input/Output Module DCA1192 (see system overview).
System Overview
For DM 1103 B‑Ex:
Pos. Description
1 Non-ex area
2 Ex area zone 1 or 2
Page 2
2 | Conventional Manual Call Points for Ex Areas
Functions
In the event of an alarm, the glass pane (2) is broken first, then the pushbutton (3) is pressed hard. Thus the switch triggers the alarm. A locking mechanism holds the pressed manual call point. The pushbutton can be reset with the reset lever. This does not reset the alarm on the fire panel.
Certifications and Approvals
Region Certification
Europe CE DM 1103
CE DKM2014
Germany VdS G 297060 DKM 2014/2-ex/-GLU
VdS G 295036 DM 1103 B-Ex
PTB 97 ATEX 3197 DKM 2014/2 / DKM
2014/2-GLU
Europe BASEE-FAEx 98E2304 DM 1103 B-Ex
Installation/Configuration Notes
• Manual call points must be illuminated sufficiently with daylight or another light source (including emergency lighting, if present).
• An installation height of 1400 mm ±200 mm, measured from the middle of the manual call point to the floor, must be maintained.
• Manual call points must be installed along escape and rescue routes (e.g. exits, passageways, stairwells).
• Further standards, guidelines and planning recommendations regarding the installation location etc., should also be taken into consideration (see Fire Detection manual).
• Regulations of local fire departments must be observed.
Installation/configuration notes in accordance with VdS/VDE
• The distance between manual call points should not exceed 100 m according to DIN 14675 or 80 m according to VdS.
• In high risk areas, manual call points should be installed at a distance of max. 40 m (VDE 0833 Part 2, Point 7.2.6).
• According to VdS, up to 10 manual call points can be connected to a primary line.
DKM 2014/2‑ex Manual Call Point Type K
• For connection to the LSN, an NBK 100 LSN Fire Interface is required.
• Can be connected directly to the following conventional control panels:
– BZ 1012 – BZ 1060 – UEZ 1000 GLT.
• With an NBK 100 LSN Fire Interface, can be connected to the following control panels:
– BZ 500 LSN
– UEZ 1000 LSN – UEZ 2000 LSN – UGM 2020 LSN
DKM 2014/2‑ex‑UGM Manual Call Point Type K, for Connection to UGM Conventional
• Can be connected directly to the UGM‑GLT Universal Danger Detection System
DM 1103 B-Ex manual call point for ex area
• For connection to the LSN, an NBK 100 LSN interface is required.
• For use in explosive areas of zones 1 and 2, a safety barrier and an input/output module are required, which must be mounted in front of the ex area.
• Cables can be inserted surface-mounted or flush­mounted
Parts Included
Type Qty.Components
DKM 2014/2‑ex 1 Manual Call Point Type K, for ex areas,
DKM 2014/2‑ex‑UGM1 Manual Call Point Type K, for
DM 1103 B-Ex 1
for surface mounting
Connection to UGM Conventional, for ex areas, for surface mounting
DM 1103 B-Ex manual call point, color
1
red
2
Key for DM1103B-Ex manual call point PG11 cable screws
Technical Specifications
DKM 2014/2‑ex Manual Call Point Type K DKM 2014/2‑ex‑UGM Manual Call Point Type K, for Connection to UGM Conventional
Operating voltage 24 V DC
Switch contact Type 366 (encapsulated), II 2 G
Maximum contact load 5 A / 250 V AC
Cable entry • 1x M16 x 1.5 tightening
Housing material Polyester, glass fiber reinforced
Colors Red, RAL 3001
Dimensions (W x H x D) 136 x 138 x 88 mm
Weight Approx. 1800 g
Protection class as per EN 60529 IP 66
Permissible operating temperature
Ex classification Eex emd IIC T6
EEx d II C
0,25 A / 250 V DC
diameter 4‑8 mm, EEx e II
• Blind plug: 1x M16 x1.5 EEx e II
-25 °C to +40 °C
Page 3
3 | Conventional Manual Call Points for Ex Areas
Test certificate / PTB No. 97-37001
ATEX approval no. PTB 97 ATEX 3197
DM 1103 B‑Ex Manual Call Point
Operating voltage 16V DC to 28V DC
Cable duct PG11 screws (2x)
Connection terminals 0.2 mm to 1.5 mm
Housing material Plastic, PC
Color Red, RAL 3000
Dimensions (W x H x D) 134.4 x 134.4 x 43.5 mm
Weight Approx. 200 g
Protection class as per EN 60529 IP 54
Permissible operating
-25 °C to +60 °C
temperature
Permissible storage temperature -30 °C to +75 °C
Permissible relative humidity ≤100% at T≤34 °C
Ex classification EEx ib IIC T4
Ordering Information
DKM 2014/2‑ex Manual Call Point Type K
for ex area, surface-mounted, indirect alarm triggering, conventional technology
Order number DKM 2014/2-ex
Key for Fire Detector Type K
Order number FMX-7743.0.0500
DKM 2014/2‑ex‑UGM Manual Call Point Type K, for Con­nection to UGM Conventional
for ex area, surface-mounted, indirect alarm triggering
Order number DKM 2014/2-ex-UGM
Key for Fire Detector Type K
Order number FMX-7743.0.0500
DM 1103 B‑Ex Manual Call Point
for zone 1 and 2 areas at risk of explosion, conventional technology
Order number DM1103B-Ex
SB3 Safety Barrier incl. DCA1192 Input/Output Module
limits the electrical energy between non-inherently safe and inherently safe circuits
Order number SB3
Accessories
FMC‑SPGL‑DEIL Spare Glasses
For manual call points of Series DM, DKM, SKM, FMC‑120 and FMC‑210. 1 unit = 5 spare glasses
Order number FMC-SPGL-DEIL
Page 4
4 | Conventional Manual Call Points for Ex Areas
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 al.securitysystems@bosch.com www.boschsecurity.com
© Bosch Security Systems 2012 | Data subject to change without notice 1292017419 | en, V4, 25. Sep 2012