D7030X-S8
Installation Guide
EN
Eight-Zone LED
Annunciator
![](/html/15/1533/153324ef11143f5f631b6eff8115a15cf831b0c16154b72c833dc797222fb60e/bg2.png)
D7030X-S8 | Installation Guide |
Notices
Notices
This guide coves the installation of the D7030X-S8 Eight-Zone LED Annunicator in a fire system supervised by a
D7024 Fire Alarm Control Panel (FACP).
Install, test, and maintain the D7030X-S8 according to these instructions, NFPA 72, local codes, and the Authority
Having Jurisdiction (AHJ).
Follow the procedures in this guide to avoid personal injury and damage to the equipment. Failure to
follow procedures can cause the D7030X-S8 to not operate properly. Bosch is not responsible for
improperly installed, tested, or maintained devices.
1.0 Description
All eight zones of the D7030X-S8 are reserved for supervisory functions. This annunciator has power, trouble, and
eight zone LEDs that can be individually labeled. It mounts in a standard three-gang box (Figure 1).
Figure 1: D7030X-S8 Features
3
16 LED ENABLE
6
68910 7
POWER
ON
SYSTEM
TROUBLE
FIRE SYSTEM
ANNUNCIATOR
1
18
Y
G
B
R
16 LED 8 LED
2
1 - Front outside view 6 - LED enable jumpers
2 - Yellow zone LEDs (8) 7 - 8 and 16 zone selection
3 - Inside view 8 - To D7032 (optional)
4 - Address jumpers 9 - To FACP option bus
5 - To D7031 (optional) 10 - Remote LED pins
To CTRL-X
8
4
1
5
For the D7030X-S8 to operate with the D7024, use control panel firmware version 2.0 or greater.
Bosch | 11/04 | 48176D2
![](/html/15/1533/153324ef11143f5f631b6eff8115a15cf831b0c16154b72c833dc797222fb60e/bg3.png)
D7030X-S8 | Installation Guide | 4.0 Wiring
2.0 Setting the Address
Figure 2 shows the fifteen annunciator addresses you can
select from when setting the D7030X-S8 address.
Figure 2: Address Settings
Address 1
1 | 2 | 4 | 8
Address 4
1 | 2 | 4 | 8
Address 7
1 | 2 | 4 | 8
Address 10
1 | 2 | 4 | 8
Address 13
1 | 2 | 4 | 8
Address 2
1 | 2 | 4 | 8
Address 5
1 | 2 | 4 | 8
Address 8
1 | 2 | 4 | 8
Address 11
1 | 2 | 4 | 8
Address 14
1 | 2 | 4 | 8
Address 3
1 | 2 | 4 | 8
Address 6
1 | 2 | 4 | 8
Address 9
1 | 2 | 4 | 8
Address 12
1 | 2 | 4 | 8
Address 15
1 | 2 | 4 | 8
The D7030X-S8 must have a unique address set within
its address pins. This address cannot conflict with other
annunciator addresses or other option bus device
addresses. Program the D7030X-S8 at the control panel
using the Update Bus option in the Programming Mode.
Each address can only support one device.
3.0 Setting the LED Jumpers
4.0 Wiring
Ensure all wiring is de-energized before
routing.
Inform the operator and local AHJ before
installing the D7030X-S8 in an existing
1. Remove AC power from the system at the dedicated
2. Remove the standby battery power before making
3. Route the wiring from the control panel (Option
Figure 4: D7030X-S8 Terminal Wiring
system. Also, disconnect all power to the
FACP.
120 VAC breaker.
or removing any connections to the FACP.
Bus A or Option Bus B) through the three-gang box
knockout and to the annunciator terminal strip
(Figure 4).
1
RABA GA YA
2 3
RBBBGB YB
4
Y
G
B
R
Set the LED jumpers to 8 LED (zones) and 8 LED
ENABLED as shown in Figure 3. When adding a D7032
Eight-Zone LED Expander, refer to the D7032
Installation Guide (P/N: 47169) for jumper settings.
Figure 3: Jumper Settings
18
Y
G
B
R
16 LED 8 LED
1
16 LED 8 LED
16 LED ENABLE
16 LED ENABLE D
8
1
To CTRL-X
2
1 - 16 LED 8 LED (jumper setting for 8 zones)
2 - 16 LED ENABLED (jumper setting for 8 LEDs
enabled)
1 - Control panel option bus 3 - Option Bus B
2 - Option Bus A 4 - Terminal strip
Note: Connect to either bus.
To prevent the D7030X-S8 from operating
improperly, do not use Bus A and Bus B
simultaneously. Use one or the other.
3Bosch | 11/04 | 48176D