Bosch D7030X-S8 Installation Guide

D7030X-S8
Installation Guide
EN
Eight-Zone LED Annunciator
D7030X-S8 | Installation Guide |
Notices
Notices
Install, test, and maintain the D7030X-S8 according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).
Follow the procedures in this guide to avoid personal injury and damage to the equipment. Failure to follow procedures can cause the D7030X-S8 to not operate properly. Bosch is not responsible for improperly installed, tested, or maintained devices.
1.0 Description
All eight zones of the D7030X-S8 are reserved for supervisory functions. This annunciator has power, trouble, and eight zone LEDs that can be individually labeled. It mounts in a standard three-gang box (Figure 1).
Figure 1: D7030X-S8 Features
3
16 LED ENABLE
6
68910 7
POWER
ON
SYSTEM
TROUBLE
FIRE SYSTEM
ANNUNCIATOR
1
18
Y G B R
16 LED 8 LED
2
1 - Front outside view 6 - LED enable jumpers 2 - Yellow zone LEDs (8) 7 - 8 and 16 zone selection 3 - Inside view 8 - To D7032 (optional) 4 - Address jumpers 9 - To FACP option bus 5 - To D7031 (optional) 10 - Remote LED pins
To CTRL-X
8
4
1
5
For the D7030X-S8 to operate with the D7024, use control panel firmware version 2.0 or greater.
Bosch | 11/04 | 48176D2
D7030X-S8 | Installation Guide | 4.0 Wiring
2.0 Setting the Address
Figure 2 shows the fifteen annunciator addresses you can select from when setting the D7030X-S8 address.
Figure 2: Address Settings
Address 1
1 | 2 | 4 | 8
Address 4
1 | 2 | 4 | 8
Address 7
1 | 2 | 4 | 8
Address 10
1 | 2 | 4 | 8
Address 13
1 | 2 | 4 | 8
Address 2
1 | 2 | 4 | 8
Address 5
1 | 2 | 4 | 8
Address 8
1 | 2 | 4 | 8
Address 11
1 | 2 | 4 | 8
Address 14
1 | 2 | 4 | 8
Address 3
1 | 2 | 4 | 8
Address 6
1 | 2 | 4 | 8
Address 9
1 | 2 | 4 | 8
Address 12
1 | 2 | 4 | 8
Address 15
1 | 2 | 4 | 8
The D7030X-S8 must have a unique address set within its address pins. This address cannot conflict with other annunciator addresses or other option bus device addresses. Program the D7030X-S8 at the control panel using the Update Bus option in the Programming Mode.
Each address can only support one device.
3.0 Setting the LED Jumpers
4.0 Wiring
Ensure all wiring is de-energized before routing.
Inform the operator and local AHJ before installing the D7030X-S8 in an existing
1. Remove AC power from the system at the dedicated
2. Remove the standby battery power before making
3. Route the wiring from the control panel (Option
Figure 4: D7030X-S8 Terminal Wiring
system. Also, disconnect all power to the FACP.
120 VAC breaker.
or removing any connections to the FACP.
Bus A or Option Bus B) through the three-gang box knockout and to the annunciator terminal strip (Figure 4).
1
RABA GA YA
2 3
RBBBGB YB
4
Y G B
R
Set the LED jumpers to 8 LED (zones) and 8 LED ENABLED as shown in Figure 3. When adding a D7032 Eight-Zone LED Expander, refer to the D7032 Installation Guide (P/N: 47169) for jumper settings.
Figure 3: Jumper Settings
18
Y G B R
16 LED 8 LED
1
16 LED 8 LED
16 LED ENABLE
16 LED ENABLE D
8
1
To CTRL-X
2
1 - 16 LED 8 LED (jumper setting for 8 zones) 2 - 16 LED ENABLED (jumper setting for 8 LEDs
enabled)
1 - Control panel option bus 3 - Option Bus B 2 - Option Bus A 4 - Terminal strip
Note: Connect to either bus.
To prevent the D7030X-S8 from operating improperly, do not use Bus A and Bus B simultaneously. Use one or the other.
3Bosch | 11/04 | 48176D