![](/html/ff/ff05/ff057ff497de1ff1720f8a9fff73d596f0c5379cbd9b46245fdc6535ce448907/bg1.png)
Fire Alarm Systems | D7030X LED Annunciators
D7030X LED Annunciators
www.boschsecurity.com
u Use with the FPA‑1000 Analog Addressable Fire
Panels or FPD‑7024 FACPs
u LED indicates power and trouble conditions
u LED annunciates eight individual zones expandable
to 64 zones
The D7030X LED Annunciators are used with the
FPA‑1000 Analog Addressable Fire Panels or the
FPD-7024 Fire Alarm Control Panels (FACPs). These
annunciators include the:
• D7030X that establishes the location of fire alarms for
up to eight zones
• D7030X-S2 with two of its eight LEDs dedicated to
indicating supervisory conditions
• D7030X-S8 with all eight of its LEDs dedicated to
indicating supervisory conditions
The eight zone LEDs on these annunciators can be
individually labeled for quick zone identification. Two
LEDs are labeled for power and trouble indication.
The D7032 Eight-Zone LED Annunciator Expander adds
an additional eight zones that are easily enabled by
jumper pins.
The D7030X LED Annunciator and D7032 LED
Annunciator Expander should be mounted in
entryways in plain view.
u Remote control panel reset and notification
appliance silencing capabilities
u Low profile, aesthetically appealing appearance
Certifications and approvals
Region Certification
USA UL UOJZ: Control Units, System (ANSI/UL
864) and UOXX: Control Unit Accessories, System (ANSI/UL 864)
FM D7030X Family
CSFM see our website
FDNY-
#6101
CoA
FDNY-
#6173
CoA
Installation/configuration notes
Compatible Products
The following products are compatible with the
D7030X LED Annunciators:
Category Product ID Product Description
Control Panels FPA_1000-V2 Analog Addressable Fire Panel
FPA‑1000‑UL Compact Fire Panel
FPD-7024 FACP
![](/html/ff/ff05/ff057ff497de1ff1720f8a9fff73d596f0c5379cbd9b46245fdc6535ce448907/bg2.png)
2 | D7030X LED Annunciators
D7024 FACP
D7024-EXP FACP for export
Expander D7032 LED annunciator expander
Notice
The D7024 and D7024‑EXP are not listed under
UL864, 9th edition.
Mounting
These annunciators mount on a standard three‑gang
box.
Wiring
Wiring the annunciators to the Control Panel
Four wires connect the annunciator terminal strip to
the option bus on the control panel as a Class B
(Style 4) communication circuit.
Notice
Do not share annunciator option bus wiring with
multiplex, telephone, or notification appliance
wiring.
D7032 Wiring
When using a D7032 Remote LED Expander:
• The D7032 must be mounted in the same room as the
annunciator.
• The D7032 must be within 20 ft (6 m) of the
annunciator.
• All wiring connecting the D7032 to the annunciator
must be in conduit.
Power Requirements
Current (alarm): 255 mA maximum
(includes remote LED current).
Use 190 mA for battery calculation.
Current (standby): 45 mA maximum
(use 34 mA for battery calculation).
Voltage (operating): 12 VDC nominal
Ordering information
D7030X LED Annunciator
Eight zone LEDs indicate alarm conditions.
Order number D7030X
D7030X‑S2 LED Annunciator
Two LEDs indicate supervisory conditions; six indicate
alarm conditions.
Order number D7030X-S2
D7030X‑S8 LED Annunciator
All eight zone LEDs indicate supervisory conditions.
Order number D7030X-S8
Accessories
D7032 Eight‑zone LED Annunciator Expander
Use with D7030X LED Annunciators
Order number D7032
Notice
A wiring harness is supplied with the D7032.
Parts included
Quant. Component
1 Annunciator
1 Hardware pack
1 Literature pack
Technical specifications
Environmental Considerations
Environment: Indoor, dry
Mechanical Properties
Dimensions (HxWxD): 4.5 in. x 6.5 in. x 1.5 in.
(11.4 cm x 16.5 cm x 3.8 cm)