Bosch D7030X-S2 Installation Guide

D7030X-S2

Installation Guide

EN Eight-Zone LED

Annunciator

D7030X-S2 | Installation Guide | Notices

Notices

This guide covers the installation of the D7030X-S2 Eight-Zone LED Annunicator in a fire system supervised by a D7024 Fire Alarm Control Panel (FACP).

Install, test, and maintain the D7030X-S2 according to this guide, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).

Follow the procedures in this guide to avoid personal injury and damage to the equipment. Failure to follow procedures can cause the D7030X-S2 to not operate properly. Bosch is not responsible for improperly installed, tested, or maintained devices.

1.0Description

Two of the D7030X-S2’s eight zones are reserved for supervisory functions. This annunciator has power, trouble, and eight zone LEDs that can be individually labeled. The D7030X-S2 mounts in a standard three-gang box (Figure 1).

Figure 1: D7030X-S2 Features

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

9

 

 

TROUBLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIRE SYSTEM

 

 

 

 

 

 

 

 

 

 

8

 

ANNUNCIATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

1

8

 

Y

 

 

G

 

 

B

 

8

R

 

4

 

 

 

 

1

 

 

5

 

16 LED 8 LED

16 LED ENABLE To CTRL-X

 

7

6

1 -

Front outside view

6 -

LED enable jumpers

2

-

Yellow supervisory LEDs (2)

7 -

8 and 16 zone selection

3 -

Inside view

8 -

To D7032 (optional)

4 -

Address jumpers

9 - To FACP option bus

5 -

To D7031 (optional)

10 - Remote LED pins

 

 

 

 

 

 

 

 

 

 

 

 

For the D7030X-S2 to operate with the D7024, use control panel firmware version 2.0 or greater.

 

 

 

 

 

 

2

Bosch | 11/04 | 48177D

Bosch D7030X-S2 Installation Guide

D7030X-S2 | Installation Guide | 4.0

Wiring

 

 

2.0Setting the Address

Figure 2 shows the fifteen annunciator addresses you can select from when setting the D7030X-S2 address.

Figure 2: Address Settings

Address 1

Address 2

Address 3

1 | 2 | 4 | 8

1 | 2 | 4 | 8

1 | 2 | 4 | 8

 

Address 4

 

 

Address 5

 

 

Address 6

 

1 |

2 |

4 |

8

1 |

2 |

4 |

8

1 |

2 |

4 |

8

 

 

Address 7

 

 

 

 

Address 8

 

 

 

 

Address 9

 

 

1

|

2

|

4

|

8

1

|

2

|

4

|

8

1

|

2

|

4

|

8

 

 

Address 10

 

 

 

Address 11

 

 

 

 

Address 12

 

1

|

2

|

4

|

8

1

|

2

|

4

|

8

1

|

2

|

4

|

8

 

 

Address 13

 

 

 

Address 14

 

 

 

Address 15

 

1 |

2 |

4 |

8

1 |

2 |

4 |

8

1 |

2 |

4 |

8

The D7030X-S2 must have a unique address set within its address pins. This address cannot conflict with other annunciator addresses or other option bus device addresses. Program the D7030X-S2 at the control panel using the Update Bus option in the Programming Mode.

Each address can only support one device.

3.0Setting the LED Jumpers

Set the LED jumpers to 8 LED (zones) and 8 LED ENABLED as shown in Figure 3. When adding a D7032 Eight-Zone LED Expander, refer to the D7032 Installation Guide (P/N: 47169) for jumper settings.

Figure 3: Jumper Settings

1

8

 

 

Y

 

 

 

G

 

 

8

B

 

 

R

 

 

 

 

 

 

1

 

16 LED 8 LED

16 LED ENABLE

To CTRL-X

 

 

1

2

 

 

16 LED 8 LED

16 LED ENABLED

1 -

16

LED 8 LED (jumper setting for 8 zones)

2 -

16

LED ENABLED (jumper setting for 8 LEDs

 

enabled)

 

4.0Wiring

Ensure all wiring is de-energized before routing.

Inform the operator and local AHJ before installing the D7030X-S2 in an existing system. Also, disconnect all power to the FACP.

1.Remove AC power from the system at the dedicated 120 VAC breaker.

2.Remove the standby battery power before making or removing any connections to the FACP.

3.Route the wiring from the control panel (Option Bus A or Option Bus B) through the three-gang box knockout and to the annunciator terminal strip (Figure 4).

Figure 4:

D7030X-S2 Terminal Wiring

 

 

1

 

 

 

 

RA BAGA YA RB BBGB YB

 

4

 

2

 

 

 

 

 

3

 

 

 

 

Y

 

 

 

 

G

 

 

 

 

B

 

 

 

 

R

1 -

Control panel option bus

3 -

Option Bus B

2 -

Option Bus A

4 -

Terminal strip

Note: Connect to either bus.

To prevent the D7030X-S2 from operating improperly, do not use Bus A and Bus B simultaneously. Use one or the other.

Bosch | 11/04 | 48177D

3

Loading...
+ 5 hidden pages