D7030X
Installation Guide
EN
Eight-Zone LED
Annunciator
D7030X | Installation Guide |
Notices
Notices
This guide covers the installation of the D7030X Eight-Zone LED Annunicator in a fire system supervised by a
D7024 Fire Alarm Control Panel (FACP).
Install, test, and maintain the D7030X according to the procedures in this guide, NFPA 72, local codes, and the
Authority Having Jurisdiction (AHJ).
Follow the procedures in this guide to avoid personal injury and damage to the equipment. Failure to
follow procedures can cause the D7030X to not operate properly. Bosch is not responsible for
improperly installed, tested, or maintained devices.
1.0 Description
The D7030X has power, trouble, and eight-zone LEDs that can be individually labeled. Mount the D7030X in a
standard three-gang box (Figure 1).
Figure 1: D7030X Features
POWER
ON
SYSTEM
TROUBLE
FIRE SYSTEM
ANNUNCIATOR
1
9
8
18
Y
G
B
R
7
16 LED 8 LED 16 LED ENABLE
2
6
5
1 - Front outside view 6 - 8 and 16 zone selection
2 - Inside view 7 - To D7032 (optional)
3 - Address jumpers 8 - To FACP option bus
4 - To D7031 (optional) 9 - Remote LED pins
5 - LED enable jumpers
For the D7030X to operate with the D7024, use control panel firmware version 2.0 or greater.
To CTRL-X
8
3
1
4
Bosch | 11/04 | 47292E2
D7030X | Installation Guide | 4.0 Wiring
Ensure all wiring is de-energized before
routing.
Inform the operator and the local AHJ before
installing the D7030X in an existing system.
Disconnect all power to the FACP.
2.0 Setting the Address
Figure 2 shows the 15 possible annunciator addresses you
can select when setting the D7030X address.
Figure 2: Address Settings
Address 1
1 | 2 | 4 | 8
Address 4
1 | 2 | 4 | 8
Address 7
1 | 2 | 4 | 8
Address 10
1 | 2 | 4 | 8
Address 13
1 | 2 | 4 | 8
The D7030X must have a unique address set within its
address pins. This address cannot conflict with other
annunciator addresses or other option bus device
addresses. Program the D7030X at the control panel
using the Update Bus option in the Programming Mode.
Each address can only support one device.
Address 2
1 | 2 | 4 | 8
Address 5
1 | 2 | 4 | 8
Address 8
1 | 2 | 4 | 8
Address 11
1 | 2 | 4 | 8
Address 14
1 | 2 | 4 | 8
Address 3
1 | 2 | 4 | 8
Address 6
1 | 2 | 4 | 8
Address 9
1 | 2 | 4 | 8
Address 12
1 | 2 | 4 | 8
Address 15
1 | 2 | 4 | 8
4.0 Wiring
1. Remove the AC power from the system at the
dedicated 120 VAC breaker.
2. Remove the standby battery power before making
or removing any connections to the FACP.
3. Route wiring from the control panel (Option Bus A
or Option Bus B) through the three-gang box
knockout to the annunciator terminal strip
(Figure 4).
Figure 4: D7030X Terminal Wiring
1
RABAGA YA
2 3
RBBBGBYB
4
Y
G
B
R
3.0 Setting the LED Jumpers
Set the LED jumpers to 8 LED (zones) and 8 LED
ENABLED as shown in Figure 3. When adding a D7032
Eight-Zone LED Expander, refer to the D7032
Installation Guide (P/N: 47169) for jumper settings.
Figure 3: Jumper Settings
18
Y
G
B
R
16 LED 8 LED
16 LED ENABLE
1
16 LED 8 LED
16 LED ENABLED
1 - 16 LED 8 LED (jumper setting for 8 zones)
2 - 16 LED ENABLED (jumper setting for 8 LEDs
enabled)
8
1
To CTRL-X
2
1 - Control panel option bus 3 - Option Bus B
2 - Option Bus A 4 - Terminal strip
Note: Connect to either bus.
To prevent the D7030X from operating
improperly, do not use Option Bus A and
Option Bus B simultaneously. Use one or
the other.
3Bosch | 11/04 | 47292E