warning triangle printed against a grey background.
Keywords at the start of a warning indicate the type and seriousness
of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defi ned and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor to moderate injury.
NOTICE is used to address practices not related to personal injury.
1.2 Safety
Please read safety precautions before installation
WARNING:
Improper installation, set-up, modification, operation or
maintenance of the heating system can cause personal injury
and property damage.
Follow these instructions precisely.
If you require assistance or further information, contact a
9Anti Cycle Period
10Anti Cycle Temperature Diff erential
11Ramp Delay Step Modulation
14Maximum Power Central Heating
15Minimum Power Central Heating / DHW
19Design Supply Temperature
20Design Outdoor Temperature
21Baseline Supply Temperature
22Baseline Outdoor Temperature
23Design Supply Minimum Limit
24Design Supply Maximum Limit
25Warm Weather Shutdown
26Boost Temperature Increment
27Boost Time Delay
28Night Setback Temperature
29Weather Setpoint
35Domestic Hot Water Mode
36Domestic Hot Water Tank Diff erential DOWN
37Domestic Hot Water Tank Diff erential UP
38Domestic Hot Water Tank Supply Extra
42Domestic Hot Water Priority
43Domestic Hot Water Priority Time
44Domestic Hot Water Pump Overrun
48Domestic Hot Water Tank Setpoint
72Permit Emergency Mode
73Boiler Address
74Emergency Setpoint
75Delay Period Start Next Boiler
76Delay Period Stop Next Boiler
77Diff erential DOWN Start Boiler
78Diff erential UP Stop Boiler
79Maximum Setpoint Off set DOWN
80Maximum Setpoint Off set UP
81Start Modulation Delay Factor
82Next Boiler START Rate
83Next Boiler STOP Rate
84Boiler Rotation Intervale
85Domestic Hot Water Boiler Assign
89Frost Protection
90Frost Protection Setpoint
91Domestic Hot Water Maximum Limit
92Fan Speed Maximum
93Fan Speed Minimum
94Fan Speed Ignition
97Appliance Model
98Gas Type
99Flue Length Range
There are 6 onboard CH Mode settings which may be selected with the SSB Boiler.
1. CH Mode = “0” [default mode] Setpoint control of the boiler using dry
contacts (TT)
2. CH Mode = “1” Outdoor Reset using ON/OFF control of the boiler using dry
contacts (TT)
3. CH Mode = “2” Full Outdoor reset with no heat demand
4. CH Mode = “3” Permanent Setpoint Demand
5. CH Mode = “4” Analog control (0-10Vdc) of set point temperature
6. CH Mode = “5” Analog control (0-10Vdc) of Boiler Power (%)
Central Heating Mode 0 [default mode]
(Setpoint control of the boiler using dry contacts #11 and #12)
CH Mode “0” - Boiler demand is generated thru a call for heat on low voltage contacts
#11 and #12 (dry contacts only). The Boiler will then target a temperature equal to
“CH Setpoint” (par.#3) at the Supply Temperature Sensor. If Temperature exceeds
the target Setpoint temperature by “CH Hysteresis” (par.#7) the burner will shut off
until the Supply Temperature Sensor drops the value of “CH Hysteresis” below the
target Setpoint Temperature.
Example:
If “CH Setpoint” is set for 140°F and CH Hysteresis is set for 10°F and there is a call
for heat on #11 and #12 the burner will start when the Boiler Supply Temperature
(System Supply Temperature sensor for cascade) reads a temperture of 130°F or less
and will remain operating until the call for heat is satisifi ed or until the sensor reads
a temperature of 150°F or greater. As long as the call for heat remains the Boiler and
CH Pump contacts will remain energized. The Burner will remain off until temperature
falls to 130°F.
Central Heating Mode 1
(On/Off with Outdoor Reset using dry contacts #11 and #12)
CH Mode “1” - Boiler demand is generated thru a call for heat on low voltage
contacts #11 and #12 (dry contacts only). Boiler will target a system supply water
temperature equal to the corresponding point on the installer programmed heating
curve. (See page 7 for details on how-to program the heating curve). If the System
Temperature sensor exceeds the calculated heating curve temperature by “CH Hysteresis” (par.#7) the burner will shut off until the System Temperature sensor
reads “CH Hysteresis” below the target Setpoint Temperature.
Example:
Based on the heating curve programmed by the installer, the calculated supply water
temperature on a 32°F degree day outside corresponds with a target boiler water
temperature of 140°F. If CH Hysteresis is set for 10°F, and there is a call for heat
on #11 and #12, then the burner will turn on when the Boiler Supply Temperature
sensor (System Supply Temperature sensor for cascade) reads a temperture of
130°F or less and will remain operating until the call for heat is satisifi ed or until the
sensor reads a temperature of 150°F or greater. As long as the call for heat remains
the Boiler and CH Pump contacts will remain energized. The Burner will remain off
until temperature measured at the system supply sensor falls to 130°F
Central Heating Mode 2
(Full Outdoor reset with no heat demand)
CH Mode“2” - Boiler demand is generated when the outdoor temperature falls
below the value of “Weather Setpoint” (par.#29). When this occurs the Boiler and
CH pump contacts are energized and the Boiler will target a system supply water
temperature corresponding to a point on the installer programmed heating curve.
(See “How to Program the Heating Curve” for details). If the System Temperature
sensor exceeds the calculated heating curve temperature by “CH Hysteresis”
(par.#7) the burner will shut off until the System Temperature sensor reads “CH
Hysteresis” below the target Setpoint Temperature. This CH Mode is for constant
circulation applications. The Boiler and CH pump contacts will remain energized
as long as the outdoor temperature is less than the value of “Weather Setpoint”
(par.#29). Using the low voltage contacts #11 and #12 it is possible to apply a
set-back to the heating curve. “Night Setback Dif” (par.# 28) controls the parallel
temperature shift that is applied to the curve when #11 and #12 contacts are
“closed” using a clock or switch.
Example:
“Weather Setpoint” is programmed for 60°F. The outdoor temperature falls below
this value. The boiler energizes Boiler and CH pump contacts. Based on the heating
curve programmed by the installer in this application, the calculated supply water
temperature on this particular temperature day corresponds to a target boiler
water temperature of 140°F. If CH Hysteresis is set for 10°F, and and the outdoor
temperature remains below the value of “Weather Setpoint”, then the burner will turn
on when the Boiler Supply Temperature sensor (System Supply Temperature sensor
for cascade) reads a temperature of 130°F or less and will remain operating until
the outdoor temperature exceeds the value of “Weather Setpoint” or if the sensor
reads a temperature of 150°F or greater. As long as the outdoor temperature remains
below the value of “Weather Setpoint” the Boiler and CH Pump contacts will remain
energized. The burner will remain off until the system supply temperature falls to
130°F.
Central Heating Mode 3
(Permanent set point demand)
CH Mode“3” - Boiler demand is always “ON” in CH Mode 3 – “Permanent Demand
Mode”. In this mode the Boiler and CH Pump contacts will always be energized. When
the Supply Temperature Sensor falls below the value of “CH Setpoint” (par.#3)
minus the value of “CH Hysteresis” (par.#7), the burner will turn on. The burner
will remain on as long as the supply temperature remains below the value of “CH
Setpoint” plus “CH Hysteresis”. Using the low voltage contacts #11 and #12 it is
possible to apply a set-back to the “CH Setpoint” target temperature. “Night Setback Dif” (par.# 28) controls the temperature shift that is applied to the “CH Setpoint”
when #11 and #12 contacts are “closed” using a clock or switch.
Example:
With both Boiler and CH Pump contacts energized, the boiler will monitor the Supply
Temperature Sensor. The application calls for a setpoint of 140°F with and Hysteresis
setting of 10°F. When the temperature of the Boiler Supply Temperature sensor
(System Supply Temperature sensor for cascade) falls below 130°F ( the value of
“CH Setpoint” minus “CH Hysteresis”) the burners will turn on. Burners will remain
on as long as the sensor does not exceed 150°F ( the value of “CH Setpoint” plus
“CH Hysteresis”). In the evening the application calls for a reduced supply water
temperature of 120°F. A timer/clock is installed and wired to contacts #11 and #12
of the boiler and these contacts are “closed” between the hours of 10 pm and 5 am.
During that time period the “CH Setpoint” is reduced by the value programmed into
“Night Setback Dif”. In this example the value is set for 20°F.
Central Heating
(CH) Mode
CH Mode = “3”
Table 5
Description
Permanent
Setpoint
Demand
Set these Parameters
Parameter #DescriptionDefaultRange
3CH Setpoint176°F68 - 194°F
4System pump overrun300 sec.0 – 900 sec.
5Boiler pump overrun300 sec.0 – 900 sec.
7CH Hysteresis5.4°F