Bosch 016519 Datasheet

Fire Alarm Systems - 016519 Flame detector flameproof Ex d, IR3
FLM-420/4-CON
016519
1 2
016519 Flame detector flameproof Ex d, IR3
u Suitable for explosive areas of the zones 1, 21, 2
and 22 (ATEX and IECEx certified)
u Sensitivity according to EN 54-10 Class 1: 0.1 m²
flames at 25m
u Low risk of false alarms due to different IR
wavelengths and a combination of filters and signal processing techniques
Flame detectors are used to detect open flames indoor and outdoor. They respond to the light emitted from flames during combustion. Flame detectors are especially suitable for smokeless liquid and gas fires not visible for the naked eye as well as for fires of materials that contain carbon with strong smoke emission. Typical areas of application are large industrial warehouses, airplane hangars, chemical facilities, oil refineries, machine rooms, ferries and freight ships, power plants, printing plants, wood warehouses, subway tunnels. Flameproof equipment is contained in an enclosure so strong that an internal explosion will neither damage the enclosure nor be transmitted outside of it. The surface remains cool enough not to ignite the explosive mixture.
u Reliable operation, even if the lens is
contaminated by a layer of oil, dust, water­vapour, or ice
u Selectable response time
u 2-wire or 4-wire configuration via DIP switch
settings
System overview
Pos.
1
2
Description
Non-Ex area
Ex area zone 1, 2, 21 or 22
Fire Alarm Systems - 016519 Flame detector flameproof Ex d, IR3
2 | 3
Functions
Most IR flame sensors respond to 4.3 µm light, emitted by hydrocarbon flames. By responding to 0.75 to 2.7 µm light emissions from fires almost all flickering flames can be detected. The flame detector has three IR sensors. The detector discriminates between flames and other light sources by responding only to particular optical wavelengths and flame flicker frequencies. False alarms due to factors as flickering sunlight are avoided by a combination of filters and signal processing techniques. Low-frequency detection enables the sensor to operate through a layer of oil, dust, water vapour, or ice. An alarm is transmitted via current amplification (2­wire) or relay contact (4-wire). The alarm is also indicated with the integrated alarm LED.
Certifications and approvals
Region Regulatory compliance/quality marks
Europe
CPR
2831-CPR-F0578 IR3 Exd
• The device cannot be used with an FPC-500 Conventional Fire Panel.
• No safety barrier is needed with this device.
• Detector replacement cycle: 10 years
Parts included
QuantityComponent
1
IR3 Flame Detector, flameproof, Red
Technical specifications
Dimensions
Detector (W x H x D)
Cable gland entries
146 x 150 x 137 mm
3 x 20 mm
Electrics
Terminal functions
1 – 2
Supply in connections or 2-Wire connections +IN and -IN
Germany
Europe
VdS
CE
G 212189 IR3FlameDetector
0165XX IR3 Flame Detector
Installation/configuration notes
• The device complies with EN 54-10 Class 1.
• Applications and locations to avoid: – ambient temperatures above +55 °C – close proximity to radio frequency sources – exposure to severe rain and ice – large amounts of flickering reflections – large IR sources for instance heaters, burners,
flares – obstructions to field of view – sunlight falling directly on the detector optics – spot lighting directly on the detector optics
• Latching mode is recommended (factory setting). Different alarm signalling modes can be set via DIP switches: current amplification (for 2-wire configuration) or relay contact (for 4-wire configuration).
• The device can be connected using an FLM-420/4­CON Conventional Interface Module to the Local Security Network LSN. The device can also be used in conjunction with a CZM 0004 A module. For connecting more than one IR3 Flame Detector use a four-wire connection with end of line element. Extended line monitoring is necessary for EN 54-13 compliant operation.
3 – 4
5 – 6
7 – 8
Operating voltage
Current consumption, 2-Wire configuration
Standby
Alarm
Current consumption, 4-Wire configuration
Standby
Alarm
Mechanics
Housing material
Housing color
Weight
Protection category (EN
60529)
Remote test input connections +R and -R
Alarm Relay RL1 connections
Fault Relay RL2 connections
14 to 30 V DC
4 mA
20 mA
8 mA
20 mA
Copper Free Aluminium Alloy (LM25)
Red
2.5 kg
IP66