The hood should completely cover the unit with an
overhang of at least 6" (15 cm) on all sides not adjaĆ
cent to a wall. The distance from the floor to the
lower edge of the hood should not exceed 7' (2.1
m). The ventilation system should replace 80% of
the exhaust volume with fresh make up air.
TABLE 1 should be used as a guideline.
SingleDoubleTriple
CFM400Ć500900Ć10001200Ć1500
M3/min14 Ć 1728Ć3442Ć51
TABLE 1
L1
N
L2
ELECTRICAL SPECIFICATIONS
NOTE: Three Phase hookup is not permitted on
gas models.
Installations within the U.S.
The MT1828G requires a 15 Amp, 60HZ, 1F,
208Ć240VAC, 4 wire service consisting of L1, L2,
neutral and ground. See FIGURE 1. Use 90C wire
and size to National Electric or local codes.
The MT1828E is available in either 1F or 3F modĆ
els. Single phase models require a 60Hz,
208/240VAC, 3 wire service consisting of L1, L2
and ground. Three phase models require a 60Hz,
208/240VAC, 4 wire service consisting of L1, L2, L3
and ground. See FIGURE 1. Wiring from the power
source to any of these units must be a minimum of
#8 AWG copper stranded wire or larger for 3 phase
and #4 AWG for 1 phase.
120
120
208Ć240
OvenSupply
MT1828G
L1
L2
208/240
OvenSupply
L1
L2
L3
208/240
MT1828E Single PhaseMT1828E Three Phase Delta System
FIGURE 1
OvenSupply
1
MT1828
Installations outside the U.S.
The MT1828G requires a 15 Amp, 50Hz, 1F, 240
VAC, 3 wire service consisting of L1, neutral and
ground. See FIGURE 2. Use 90C wire and size
wire according to local codes.
The MT1828E is available in either 1F or 3F modĆ
els. Single phase models require a 50 Hz,
220/240VAC, 3 wire service consisting of L1, L2
and ground. Three phase models are available in
either Delta or WYE configurations. Delta models
require 50Hz, 208/240VAC, 4 wire service consistĆ
ing of L1, L2, L3 and ground. WYE models require
50 Hz, 220/240 VAC, 5 wire service consisting of
L1
N
240
OvenSupply
MT1828G Export Installations
L1
L2
L3
208/240
OvenSupply
L1, L2, L3, neutral and ground. See FIGURE 2. Use
2
a minimum of 8.37 mm
copper stranded wire or
larger for 3 phase and 21.15 mm2 for 1 phase.
CE approved installations
The MT1828G requires 15 Amp, 50Hz, 1F, 230
VAC, 3 wire service consisting of L1, neutral and
ground. Connect exhaust fan connector 1 and 2.
See FIGURE 2. Use 90C wire and size according
to local codes.
The MT1828G requires 50 Hz, 3F, 230VAC, 5 wire
service consisting of L1, L2, L3, neutral and
ground. See FIGURE 2. Use 90C wire and size
according to local codes.
L1
L2
220/230/240
OvenSupply
MT1828E Single Phase Export Installations
L1
L2
L3
N
415/400*/380
415/400*/380
415/
400*/
380
240/
230*/
220
OvenSupply
MT1828E Three Phase Delta System
Export Installations
L3
L2
L1
N
Blodgett
Connector
N
L
Connector
L1
N
230
1
2
OvenSupply
MT1828G CE Approved Installations
FIGURE 2
* - CE Approved Installations
MT1828E Three Phase WYE System
Export and CE Installations
2Ć4Ć92
A1
Relay A
1
Fan
s
2
A2
21Air Pressure Regulator
Burner Control Solenoid
2
MT1828
GAS SPECIFICATIONS
GAS CONNECTIONS
Domestic and General Export installations
The gas line should be large enough to accommoĆ
date the peak demand of all the gas appliances.
TABLE 2 reflects a straight line, 50 foot run with no
coupling restrictions and no other appliances
drawing service. Gas line installations MUST conĆ
form to National Fuel Gas Code NFPA 54/ANSI
Z223.1 Sec. 1.4 (Latest Edition). TABLE 2 should
be used as a guideline only.
NOTE: For any pipe runs over 50 feet (15 m), conĆ
sult the factory.
CE approved installations
1. Connect the oven to the gas line with the propĆ
er type of gas according to Local and National
Installation Standards. See TABLE 2.
DOMESTIC AND GENERAL EXPORT
Natural GasPropane Gas
Gas Line Sizing
GAS REQUIREMENTS
The firing rate for the MT1828G is 33,000 BTU/Hr.
(9.7 kW/Hr.)
NOTE: For natural gas meter sizing, consult your
local gas company to ensure that your meĆ
ter will provide the proper supply.
Installations within the U.S.
1. Add the total BTU's/hr of all the gas
appliances.
2. Convert BTU's to cubic ft/hr using the formula
Cu Ft/Hr = 1000 BTU/Hr for natural gas.
3. Size the meter accordingly.
Installations outside the U.S.
1. Add the total M3/min of all the appliances.
2. Size the meter accordingly.
Single
Double
Triple
Orifice Size#34 MTD#49 MTD
Incoming Gas PressureW.C.kPambarW.C.kPambar
Static
Operational
Manifold Gas Pressure3.5"0.87910"2.4925
CE APPROVED UNITS
Type of
Gas
G252583,122,39,8 Nat. Gas
G202082,722,39,8 Nat. Gas
G20/G2520/25Totally Inscrewed
G3030/50241,5522,39,8 Butane
G3130/37/50241,722,39,8 Propane
Inlet
Pressure
mbars
Burner Pressure
Pressure Regulator
7"
5.5"
mbars
3/4" line
3/4" line
3/4" line
1.74
1.36
Injector
Diameter
3/4" line
3/4" line
3/4" line
17.4
13.7
Opening
mm
2,322,39,8 Nat. Gas
Air
mm
12.5"
11"
3.11
2.73
Standard Delivery
Value kW (HS)
31.1
27.4
TABLE 2
3
CHAPTER 2
OPERATION
MT1828
COMPUTER CONTROLLER
9
1
2
3
45678
FIGURE 1
CONTROL DESCRIPTION
1. DIGITAL DISPLAY - Displays the time, temĆ
perature and controller related information.
2. OVEN ON/OFF - Controls power to the oven.
3. NUMERIC KEYS - Used to enter numerical
data in the programming mode.
4. CLEAR KEY - Used to clear the display if an
error is made in the programming mode.
5. SET TEMP KEY - Used to view or program the
temperature setpoint.
6. ACT TEMP KEY - Used to view the current
oven temperature.
7. TIME KEY - Used to view or program the cook
time.
8. PROG/ENTER KEY - Used to enter and exit
the programming mode. Also used to lock in
programmed settings.
9. STATUS LAMPS - When lit indicate that the
fan or burners are operating.
This oven, supplied with remote control, is
equipped with an emergency shut down
switch. Should you need to stop the belt,
fans, or heat press the emergency switch.
Do not use the emergency switch as a
GENERAL on/off switch!
CONTROL OPERATION
To turn the oven on:
1. Press and hold the ON/OFF key (2). The disĆ
play reads OFF when the oven is idle.
2. The display flashes WAIT LOW SET TIME
mmss.
3. The FAN and HEAT status lamps (9) light. The
fans begin to run. The heat rises to the proĆ
grammed temperature. The conveyor belt
travels at the programmed speed.
To view the cook time setting:
1. Press the TIME key (7). The LED on the key
lights and the display flashes SET TIME
mmss.
To display the actual oven temperature:
1. Press the ACT TEMP key (6). The LED on the
key lights and the display reads ACTUAL
nnnnF.
To view the temperature set point:
1. Press the SET TEMP key (5). The LED on the
key lights and the display flashes SET TEMP
nnnnF.
To turn the oven off:
1. Press the ON/OFF key (2). The blower moĆ
tor(s) continue to run regardless of the controlĆ
ler status until the temperature drops below
180F (82C).
2-1
OPERATION
PROGRAMMING PROCEDURES
Programming the Cook Time:
1. Press the PROGRAM/ENTER key (8).
2. Press the TIME key (7). The display reads
PROGĆ? SET TIMEĆ? _ _ _ _.
3. Use the NUMERIC keys (3) to enter the desired
cook time. The display will read the numbers
as they are entered. If an error is made, press
the CLEAR key (4) and reĆenter the number.
4. Press the PROGRAM/ENTER key (8) a second
time to lockĆin the new time. The new cook time
will be stored in the computer's memory.
Programming the Temperature:
1. Press the PROGRAM/ENTER key (8).
2. Press the SET TEMP key (5). The display reads
PROGĆ? SET TEMPĆ? _ _ _ _F.
3. Use the NUMERIC keys (3) to enter the desired
temperature set point. The control displays the
numbers as they are entered. If an error is
made, press the CLEAR key (4) and reĆenter
the number.
4. Press the PROGRAM/ENTER key (8) a second
time to lockĆin the new temperature. The new
temperature setpoint will be stored in the comĆ
puter's memory.
Operation at the Programmed Settings:
1. Press and hold the ON/OFF key (2).
DISPLAY INFORMATION
WAIT LOW - indicates that the present oven
temperature is lower than the set point temperĆ
ature. When the oven reaches the set point
temperature the display changes to READY.
READY - indicates that the oven is ready to acĆ
cept product.
SET TIME mmss - indicates the current
cook time setting.
HIGH TIME - indicates that the temperature
is well above the set point. This usually occurs
when moving from a higher āto a lower temperaĆ
ture. Wait until the display reads ready before
loading product.
HIGH TEMP LIMIT - indicates that the oven
temperature exceeds the high limit from the
2nd level program. The Over Temperature
Alarm buzzer will sound. Shut the oven off and
wait for the unit to cool down.
MTR SPD - indicates speed of the motor
does not match the set point.
MOTOR - indicates the computer is not reĆ
ceiving the signal back from the pickup.
HI TEMP MOTOR - N.A.
PROBE OPEN PROBE SHORT - indicates
that the temperature sensor has failed. The
Alarm buzzer sounds. Shut the oven off and
contact a service representative.
2. The FAN and HEAT status lamps (9) light. The
fans begin to run. The heat rises to the temperĆ
ature setting stored in the computer's memory.
The conveyor belt begins to travel at the timed
speed stored in memory.
3. The display will flash WAIT LOW SET TIME
mmss until the programmed bake temperaĆ
ture is reached. The HEAT lamp (9) will remain
lit until the oven reaches the temperature set
point.
4. The display reads READY and the HEAT lamp
(9) goes out.
5. The oven is now ready to accept product.
6. Press and hold the ON/OFF key (2) to turn the
oven off. The fans continue to run while the
oven cools to a safe temperature.
2-2
MT1828
SEQUENCE OF OPERATION
MT1828G DOMESTIC AND GENERAL EXPORT OVENS INTERNAL MOUNT - M7296
REV B
COMPONENT REFERENCE
NOTE: Refer to FIGURE 2 for component locaĆ
tions.
1. BLOWER RELAY
2. BELT STOP RELAY
3. HEAT RELAY
4. MOTOR CONTACTOR
5. SINGLE POLE DOUBLE THROW THERMAL
SWITCH
6. MOTOR CONTROL BOARD
7. SINGLE POLE SINGLE THROW THERMAL
SWITCH
8. RESETABLE HI LIMIT
9. 115/24 VOLT TRANSFORMER
10. FLAME BLOWER
11. IGNITION CONTROL MODULE
12. COOKING COMPUTER
13. PRESSURE SWITCH
14. H.S.I.
15. BURNER VALVE
16. PROOF OF FLAME ROD
17. SINGLE POLE DOUBLE THROW THERMAL
SWITCH
18. CONVECTION BLOWERS
19. COOLING FANS
OPERATION
1. Apply power to the oven. Program time and
temperature into the computer (12). The blowĆ
er relay (1), belt stop relay (2) and heat relay (3)
close.
2. When the blower relay (1) closes, 110 V.A.C.
are sent to the coil of the motor contactor (4)
starting the convection blowers (18) and N.C.
terminal of a single pole double throw thermal
switch (5).
3. When the belt stop relay (2) closes, 110 V.A .C.
are sent to the motor control board (6) and the
single pole single throw thermal switch (7). If
this switch is closed, power goes to the resetĆ
able hi limit switch (8).
4. If the resetable hi limit switch is closed power
goes to the 115/24 volt transformer (9) located
in the box mounted on the flame blower (10).
The flame blower starts.
5. The secondary side of the transformer (9)
sends 24 volts to L1 of the ignition control modĆ
ule (11) and one side of the heat relay (3). If the
computer (12) closes the heat relay, the 24
volts will go to the pressure switch (13).
6. If the pressure switch is closed, a circuit will be
completed back to the ignition module (11).
7. The ignition module initiates its firing sequence
by sending power to the H.S.I. (14). After a
warm up period both solenoids on the burner
valve (15) open allowing gas to enter for igniĆ
tion. If no flame is sensed by the proof of flame
rod (16) the system shuts down.
NOTE: Some ignition control modules may try
to refire up to 3 times. However, there
will be a longer warm up period beĆ
tween each attempt at ignition.
8. The thermal switches (5 and 17) toggle from
common to N.O. only when they reach the temĆ
perature stated on the back of the switch.
9. The convection blowers (18) receive their powĆ
er from the motor contactor (4) only.
10. The cooling fans (19) come on only when the
motor contactor (4) is energized or if the therĆ
mal switches (5 and 17) have toggled.
2-3
OPERATION
9
8
7
13
10
16
14
15
18
18
4
11
6
17
19
5
19
19
19
19
123
12
FIGURE 2
2-4
MT1828
MT1828G DOMESTIC AND GENERAL EXPORT OVENS EXTERNAL MOUNT - M9776
REV B
COMPONENT REFERENCE
NOTE: Refer to FIGURE 2 for component locaĆ
tions.
1. BLOWER RELAY
2. BELT STOP RELAY
3. HEAT RELAY
4. MOTOR CONTACTOR
5. SINGLE POLE DOUBLE THROW THERMAL
SWITCH
6. MOTOR CONTROL BOARD
7. SINGLE POLE SINGLE THROW THERMAL
SWITCH
8. RESETABLE HI LIMIT
9. 115/24 VOLT TRANSFORMER
10. FLAME BLOWER
11. IGNITION CONTROL MODULE
12. COOKING COMPUTER
13. PRESSURE SWITCH
14. H.S.I.
15. BURNER VALVE
16. PROOF OF FLAME ROD
17. SINGLE POLE DOUBLE THROW THERMAL
SWITCH
18. CONVECTION BLOWERS
19. COOLING FANS
OPERATION
1. Apply power to the oven. Program time and
temperature into the computer (12). The blowĆ
er relay (1), belt stop relay (2) and heat relay (3)
close.
2. When the blower relay (1) closes, 110 V.A.C.
are sent to the coil of the motor contactor (4)
starting the convection blowers (18). When the
motor contactor closes, power is also applied
to the NIC terminal of a single pole double
throw thermal switch (5).
3. When the belt stop relay (2) closes, 110 V.A .C.
are sent to the motor control board (6) and a
single pole single throw thermal switch (7). If
this switch is closed, power goes to the resetĆ
able hi limit switch (8).
4. If the resetable hi limit switch is closed power
goes to the 115/24 volt transformer (9) located
in the box mounted on the flame blower (10).
The flame blower starts.
5. The secondary side of the transformer (9)
sends 24 volts to one side of the heat relay (3).
If the computer (12) closes the heat relay, the
24 volts will go to the pressure switch (13).
6. If the pressure switch is closed, a circuit will be
completed to the ignition module (11).
7. The ignition module initiates its firing sequence
by starting to spark at the spark electrode (14)
and opening both solenoid valves on the burnĆ
er valve (15) allowing gas to enter for ignition.
If no flame is sensed by the proof of flame rod
(16) the system shuts down.
NOTE: Some ignition control modules may try
to refire up to 3 times. However, there
will be a longer interpurge period beĆ
tween each attempt at ignition.
8. The thermal switch (17) toggles from common
to N.O. only when it reaches the temperature
stated on the back of the switch.
9. The convection blowers (18) receive their powĆ
er from the motor contactor (4) only.
10. The cooling fans (19) come on only when the
motor contactor (4) is energized or if the therĆ
mal switch (17) has toggled.
2-5
OPERATION
9
8
7
13
3
10
16
14
18
11
4
6
2
17
1
19
12
FIGURE 3
2-6
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.