Temperature Calibration24...........................................
Belt Speed Calibration26............................................
Introduction
Pre-Startup Requirements
OWNER’S RESPONSIBILITIES
A minimum of 5 to 7 working days are needed
to schedule a start-up procedure.
Before a factory representative, or a factory
trained representative, arrives to perform a start up procedure, the owner MUST ALREADY have
satisfied the following requirements:
1. Gas Models: Installation of an adequate mechanically driven ventilation system for the unit.
The ventilation system should replace 80% of
the exhaust volume with fresh make up air. The
table below can be used as a guideline.
2. Electric supplies installed by a certified professional.
NOTE: Refer to the Owner’s manual provided
with the oven for electrical specifications.
3. Gas Models: Gassuppliesinstalledbyacertified professional.
NOTE: Refer to the Owner’s manual provided
with the oven for gas specifications.
Be sure to size the meter for all gas models as
follows:
U.S. installations
a.) Add the total BTU’s/hr of all the gas ap-
pliances on the line.
b.) Convert BTU’s to cubic ft/hr using the for-
mula Cu Ft/Hr = 1000 BTU/Hr.
c.) Size the meter accordingly.
General export and Canadian installations
a.) Add the total M
on the line.
b.) Sizethemeteraccordingly.
NOTE: Refer to the Owner’s manual provided with
the oven for additional information on utility installation requirements.
SERVICE AGENCY’S RESPONSIBILITIES
Before performing a start-up procedure, the service agency MUST ALREADY have satisfied the
following requirements:
1. Assembly of the oven(s).
NOTE: Refer to the Owner’s manual provided
with the oven for assembly.
2. Conversion of ovens to other types of gas
when required.
The following instructions are for the standard manual control. See Figure 1 for control identification.
COOK TIME
ONOFF
CONVEYOR
ACTUALSETPOINTHEAT
TEMPERATURE
Figure 1
ONOFF
HEAT
ONOFF
BLOWER
3
Manual Control Startup
Gas Pressure Adjustments
THE FOLLOWING STARTUP PROCEDURES MUST
BE PERFORMED BY A QUALIFIED TECHNICIAN
ONLY.
REGULATED GAS PRESSURE
NOTE: Gas models only.
Incoming static gas pressure to the unit, with all the
gas appliances drawing from the supply, should be
a minimum of 5.5” W .C. (13.7 mbar) for natural gas
and 11” W .C. (28 mbar) for propane gas.
The manifold pressure, if measured after the regulator located inside the control box, must be 3.5”
W.C. (9 mbar) for natural gas and 10” W.C. (25
mbar) for propane gas.
The pressure can be checked at the tap on either
the dual regulated gas valve or the solenoid valve.
Turn the adjusting screw on the left front side of the
dual regulated valve to adjust the gas pressure.
Turn the screw clockwise to raise the gas pressure
and counter-clockwise to lower it.
PRIMARY AIR ADJUSTMENT
NOTE: Gas models only.
The air shutter disc on the burner blower motor, located inside the control box at the top of the assembly, is factory adjusted to provide the most efficient blue flame possible at sea level.
1. Visually examine the quality of the flame.
2. If it needs adjusting, increase or decrease the
air mixture to attain the best flame quality.
Pressure Tap
Regulator
Cap
Regulator
Adjustment
Figure 2
4
Manual Control Startup
Temperature Control Configuration
CONFIGURATION PROCEDURES
NOTE: Follow these configuration procedures to
change the factory settings.
To enter the Configuration Menus
1. Press and hold the actual temperature key for
approximately 10 seconds. When the menu
system has been accessed, the display toggles
between dEF and either SP or Act.
Setting the Default Display
The default display determines whether the controller displays the actual or setpoint temperature.
1. Use the arrow keys to select the desired display default.
NOTE: We recommend using the setpoint
display default.
2. Press the actual temperature k ey to enter the
selected display default. The display toggles
between HYS and a numerical value.
Setting the Control Hysteresis
The control hysteresis, or burner cycle is used to
prevent rapid cycling around the setpoint. The
hysteresis is adjustable from 2_F to 252_F(1_Cto
122_C).
1. Use the arrow keys to select the desired control hysteresis.
NOTE: We recommend 5_F(3_C) initially.
2. Press the actual temperature k ey to enter the
selected hysteresis value. The display toggles
between OFF and a numerical value.
Setting the Display Offset
Setting the Deviation Band Alarm
The deviation band alarm causes the display to
flash when the actual temperature varies (in either
direction) from the setpoint. The deviation band
alarm is adjustable to off or values from 1_Fto
252_F (0.5_C to 122_C).
1. Use the arrow keys to select the desired deviation band alarm.
NOTE: We recommend 20_F(11_C).
2. Press the actual temperature k ey to enter the
selected alarm value.
To exit the Configuration Menus
1. Push and hold the actual temperature key for
approximately 3 seconds.
NOTE: The unit exits the configuration menus if
the controller is not touched for 1 minute
at any time during programming.
SETTING THE DISPLAY UNITS
1. Press and hold the actual temperature key for
approximately 10 seconds until the display
reads unt and flashes F or c.Presstheupor
down arrow key to toggle between _Fand_C.
2. Press and hold the actual temperature key until the control exits the programming mode.
The display offset adjusts the displayed t emperature if the actual temperature differs from the temperature seen by the thermocouple. If the actual
temperature is lower a positive offset is needed. If
the actual temperature is higher a negative offset
is needed. The display offset is adjustable from
-126_F to +126_F(-87_Cto+52_C).
1. Use the arrow keys to select the desired display offset.
2. Press the actual temperature k ey to enter the
selected offset value. The display toggles between ALr and a numerical value.
ACTUALSETPOINTHEAT
Figure 3
5
Manual Control Startup
Temperature Calibration
Low Limit Adjustment
1. Bring the oven to 200_F(93_C).
2. Turn the blower and heat switches to OFF. The
blower should continue to run.
3. Monitor the digital temperature control display. The blower motors should shut off within
the range of 170-135_F(77-57_C).
4. To adjust the temperature, turn the low-limit
potentiometer. A clockwise rotation increases
the setting, counter-clockwise decreases it.
SeeFigure4.
P1
INCREASE
INCREASEDECREASE
DECREASE
LOW LIMITP2HI LIMIT
INCREASE
DECREASE
T1
High Limit Adjustment
NOTE: Refer to the wiring diagram shipped with
the oven for terminal locations.
1. Remove the wires from the common and N.O.
terminals. Touch the wires together to energize the heat circuit. This enables the oven to
heat above the highest temperature allowed
by the controller.
2. When the display reads 600_F (316_C), the
burner blower motor should shut off. If the
temperature rises above 600_F (316_C), adjust the hi-limit pot (Figure 4) so the burner
shuts off at 600_F (316_C). A clockwise rotation of the high-limit pot increases the temperature, counter-clockwise decreases it.
P3
910
T/C
+
RED
ACTUALSETPOINTHEAT
INCREASE
HI LIMIT
12 3 45 6 78
230 115 NC C NO NO C
United Electric Board
DECREASE
LOW LIMIT
ZYTRON
SERIES 300
13 265
230
NO C NC
115
OUTPUT 1
Zytron Board
Figure 4
Athena Temperature Controller
478
NO C
OUTPUT 2
6
Manual Control Startup
Motor Control Board Adjustment
High/low speed motor control board adjustment for 180 and 130 VDC motors
NOTE: This procedure does not apply to Dart Mi-
crodrive systems or cooking computers.
NOTE: The motor control board is located on the
slide out control panel.
High Speed Motor Adjustment:
1. Turn the cook time control knob on the front
panel fully clockwise to decrease the cook
time and turn the conveyor belt on.
2. With the motor connected (make no open circuit voltage readings) measure the voltage at
the motor leads (A1 & A2 in Figure 5) on the
DC control board. If the voltage is not within 3
VDC of the specified voltage continue with
step 3.
3. Turn the MAX trim pot counter-clockwise to
lower and clockwise to raise the voltage until
it is within 3 VDC of the specified voltage.
Minimum Speed Pot
Maximum Speed Pot
Low Speed Motor Adjustment:
1. Turn the cook time control knob on the front
panel fully counter-clockwise to increase the
cook time.
2. With the motor connected (make no open circuit voltage readings) measure the voltage at
the motor leads on the DC control board (A1
& A2 in Figure 5). If the voltage is not within 1
VDC of the specified voltage, continue with
step 3.
3. Turn the MIN SPEED pot clockwise to lower
the voltage and counter-clockwise to raise the
voltage.
130 Volt System 180 Volt System
ModelLowHighLowHigh
MT21362013026180
MT32552613026180
MT32702613026180
MG327026130N/AN/A
Torque (current) limiting adjustment
(DO NOT ADJUST)
Yellow or Violet (pin 12)
Orange or Gray (pin 10)
Blue (pin 8)
Gray
Blue
Violet
Speed Pot
Line Hot (VAC)
Line Neutral (VAC)
REMOVE RED PLUG FROM TOP OF DC MOTOR PRIOR TO OPERATING!
Warning: Circuit components are not at ground potential! Use only a non-metallic or insulated adjustment tool.
Shock hazards may occur with conducting tools!
ACC MAXMINTORQ
J1
FL
TB1
LNA1A2
PM Motor Armature
TP1
TP2
+
-
Barrier Terminal Block TB1
Power Line and Motor Ground
ON
REG
FA
Figure 5
7
Manual Control Startup
Belt Speed Calibration
CLOSED LOOP -- DART MICRODRIVE MDP
1. Remove the top cover. The internal dip switch
is located next to the transformer.
Dip Switch Detail
O
123456 78
N
Figure 6
PROGRAMMING THE MDP CONTROL
NOTE: Anyvariable can be changed WITHOUT re-
setting the others.
To En t e r t h e Pr o g r a m M o d e
1. Set DIP switches 1, 2, 3, 4, 5, 6 and 8 to OFF.
Set DIP switch 7 to ON. The motor stops.
2. The display reads PROG.
NOTE: In rate mode the current decimal point
is also displayed.
Time or Rate Mode (Displayed Decimal Place)
This allows settings to be made in the proper units.
1. Set DIP switch 4 to ON.
2. The current decimal point (if any) will be lit.
The display gives the current value of the decimal place variable. To change press the up or
down arrow keys. Use 0-4 for the rate mode.
Use5forthetimemode.
NOTE: The decimal point will not be lit if the
unit is currently in the time mode.
3. When finished, flip DIP switch 4 to OFF.
4. The display reads PROG.
KConstant
1. Flip DIP sw itch 1 to ON.
2. The display gives the current value for the
constant. To change press the up or down arrow keys.
NOTE: For ovens with a 70” (178 cm) tunnel
the preset constant is 5:20. For ovens
with a 55” (140 cm) tunnel the preset
constant is 4:08.
3. When finished, set DIP switch 1 to OFF.
4. The display reads PROG.
NOTE: If you change the constant, the display set-
ting will be set to the slowest speed when
you exit the programming mode.
Minimum Setting
1. Flip DIP sw itch 2 to ON.
2. The display gives the current value for the low er limit. To change press the up or down arrow
keys.
3. When finished flip DIP sw itch 2 to OFF.
4. The display reads PROG.
Maximum Setting
1. Flip DIP sw itch 3 to ON.
2. The display gives the current value for the upperlimit.Tochangepresstheupordownarrow keys.
3. When finished flip DIP sw itch 3 to OFF.
4. The display reads PROG.
To Ex i t th e P ro g r a m M o d e
1. Make sure DIP switch 5 (Master/Follower
Mode select) is in the desired position
(ON = Follower; OFF= Master).
NOTE: In most cases DIP switch 5 should be
set to the master position (OFF).
2. Set DIP switches 1, 2, 3, 4, 6 and 8 to OFF.
3. If satisfied with programming values, set DIP
switch 7 to OFF. The control operates using
the new programmed variables.
CHECKING THE BELT SPEED CALIBRATION
Placeapanonthebeltandstarttheconveyor.
1. Begin timing the belt’s speed when the trailing
edge of the pan enters the oven.
2. End the timing cycle when the trailing edge of
the pan exits the oven.
3. If the displayed time differs from the actual more
than 5 seconds, reprogram the K constant.
8
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.