B&G Network Depth User Manual

Page 1

CONTENTS

GENERAL INTRODUCTION TO B&G NETWORK 2 INTRODUCTION TO NETWORK DEPTH 3 EXAMPLE SYSTEMS USING NETWORK DEPTH 4 SELECTING THE DISPLAY MODE 5
USING THE DEPTH KEY 6
SETTING THE DEPTH UNITS 7 THE DEPTH DATUM - D CAL 8 SETTING THE DEPTH DATUM 9
USING THE SIGNAL KEY 10
USING THE ALARM KEY 11
DEPTH ALARMS 11 ENABLING/DISABLING THE SHALLOW ALARM 12 ADJUSTING THE SHALLOW ALARM VALUE 12 ENABLING/DISABLING THE DEEP ALARM 13 ADJUSTING THE DEEP ALARM VALUE 13 THE ANCHOR ALARM 14 ENABLING/DISABLING THE ANCHOR ALARM 15 ADJUSTING THE ANCHOR ALARM LOW LIMIT 16 ADJUSTING THE ANCHOR ALARM HI LIMIT 16
USING THE LIGHTS KEY 17
SETTING THE DISPLAY LANGUAGE 18
NETWORK ALARMS 19
FAULT AND ERROR MESSAGES 20
INSTALLATION 21
SITING THE UNIT 21 MOUNTING THE UNIT 21
SPECIFICATION 23
CONDITIONS OF WARRANTY
610-HB-0501-04
1
Page 2

GENERAL INTRODUCTION TO B&G NETWORK

The B&G Network range of instruments are designed to be used as individual units or connected together to form an integrated navigational system. A single network cable is used to carry data and power between units. The latest technology and screened cables throughout the Network System ensure the ultimate protection from interference between units and other systems.
All Network instruments can be linked to Network PILOT, Network CHART, Network GPS or Network LORAN receivers or via NMEA 0183 (v1.5) to other navigational equipment.
INSTRUMENTS
Network SPEED Network DEPTH Network QUAD Network WIND Network TACK Network DATA
NAVIGATIONAL AIDS
Network NAV Network GPS Network LORAN LCD CHART
AUTOPILOTS
Network PILOT
610-HB-0501-04
2
Page 3

INTRODUCTION TO NETWORK DEPTH NETWORK DEPTH DISPLAY UNIT

The Network DEPTH unit measures and displays Depth information on a large Liquid Crystal Display (LCD). The five keys allow selection of the displayed information and setting of the units mode, calibration factors and alarms.
It can operate as the main Network DEPTH unit either alone or as part of an Integrated Network Instrument System taking inputs directly from a Depth Sensor that plugs directly into the rear of the display. It will also operate as a repeater of depth information received via the two Network cable tails.
The Network Depth unit has three adjustable alarms:
1. Shallow water alarm
2. Deep water alarm
3. Anchor alarm
An internal alarm buzzer will sound when an alarm condition is met and the display will flash. The alarm is broadcast to all other Network Instruments in an integrated system, they will also sound their alarms and flash their displays (except Network WIND). The Network DEPTH unit will also indicated Network PILOT alarms and fault conditions.
610-HB-0501-04
3
Page 4

EXAMPLE SYSTEMS USING NETWORK DEPTH

Only one Network DEPTH unit should have a depth sensor connected to it and set to transducer mode. Up to three more Network DEPTH units can be connected on to the system network, these must be set to repeater mode. See SELECTING THE DISPLAY MODE.
When in repeater mode, if the data is not being received from the system network, the display will show OFF when a key is pressed.
rEP Repeater mode, the unit operates as a depth repeater using data from the system network.
610-HB-0501-04
4
Page 5

SELECTING THE DISPLAY MODE

The Network DEPTH unit has two operating modes. The correct mode must be selected for your network system to operate properly.
trA
data from a depth sensor connected directly into the display unit.
rEP
repeater using data from the system network.
Transducer mode, the unit uses and displays depth
Repeater mode, the unit operates as a depth
Press
SIGNAL
key.
610-HB-0501-04
Press
SETUP
key to display the current mode.
Press
ENTER
if the mode needs to be changed.
key
Use S or T to change mode.
Press
ENTER
memorise the new mode.
to
Press
SIGNAL
key to complete the change.
5
Page 6
USING THE DEPTH KEY
Press the DEPTH key to cycle through the following options:
DEPTH M
The current water depth in metres M, can also be displayed in feet FT or fathoms FA. The unit is factory set to metres. The depth displayed is from the depth datum, see below.
D CAL M
The Depth Datum can be adjusted so the displayed water depth is from the water- line, the depth sensor (transducer) or the keel/outdrive depth. The unit is factory set to display water depth from the transducer.
The Network DEPTH unit can measure and display water depth in the following ranges:
0.7 to 180 metres
2'4" to 590'
0.37 to 98.4 fathoms
Accuracy ± 2% or ± 0.2m (± 8")
If the Network DEPTH unit losses valid depth data, due either the actual depth being outside the working range, or to extreme turbulence in the water the LCD will show 3 "floating" bars. This shows that the unit is attempting to calculate the depth and is still functioning.
610-HB-0501-04
6
Page 7
SETTING THE DEPTH UNITS
The Network DEPTH unit can be set to display depth in Metres M, Feet FT or Fathoms FA. The selected units are used for displayed depth information on all Network instruments on the entire network system.
Press to display the current depth.
DEPTH
key
Press key. The depth display will go blank.
SETUP
Press if the units are to be changed.
ENTER
key
Use S or T to change the units.
Press to memorise the change.
ENTER
key
Press display current depth.
DEPTH
to
610-HB-0501-04
7
Page 8
THE DEPTH DATUM - D CAL
The depth datum to determine the displayed information reference point. It is added to the actual measured water depth to display the depth from the waterline, the depth sensor (transducer) or the keel/outdrive depth.
The Network DEPTH unit has factory set i.e. the depth is displayed from the transducer. The value is displayed in the same units as the depth.
D CAL
is an offset calibration value used
D CAL
of zero,
D CAL
610-HB-0501-04
8
Page 9
SETTING THE DEPTH DATUM
D CAL D CAL D CAL
NOTE:
be changed.
zero, depth from transducer positive, depth from waterline negative, depth from keel
If the CAL LOCK is set then the D CAL value cannot
CAL TRA.
CAL W/L.
CAL KEEL.
Press
DEPTH
key to display depth datum
D CAL M
610-HB-0501-04
Press
SETUP
key
to display current
.
datum value.
Press
ENTER
adjust the datum value.
to
Use S or T to adjust the value.
Press
ENTER
to memorise the new value.
Press
DEPTH
to display the depth datum.
9
Page 10
USING THE SIGNAL KEY
Press the this is an indication of the return echo strength. A is excellent,
is poor.
F
The sea bed can have an effect on the quality of the return echo strength, i.e. very good echoes are returned from rock, shale and sand, however poor echoes are returned from mud. Therefore the merit letter could be A or B for rocks but C or D for mud.
SIGNAL
key to display a letter of merit from A to F,
610-HB-0501-04
10
Page 11
USING THE ALARM KEY
Press the options:
SHA A M
Shallow Alarm, when enabled it will sound if
DEP A M
Deep Alarm, when enabled it will sound if
ANC A M
Anchor Alarm, when enabled it will sound if
ALARM
the water depth is less than the alarm value.
the water depth is more than the alarm value.
the water depth is outside two alarm limits.
key to cycle through the following
DEPTH ALARMS
The display will show
if the alarm is disabled or the
OFF
alarm value when enabled. The value will be displayed in metres M, feet FT or fathoms FA depending on the selected depth units.
When the alarm condition is met the unit will sound its internal alarm buzzer and flash
DEPTH M
. Silence the
alarm by pressing any key.
Shallow Alarm
Factory set to 1.0m, (3.2ft, 0.5 fathoms). Range 0 - 180m, 0 - 590ft, 0 - 98.4 fathoms.
Deep Alarm
Factory set to 10.0m, (32.8ft, 5.4 fathoms). Range 0 - 180m, 0 - 590 ft, 0 - 98.4 fathoms.
Anchor Alarm
Factory set
LOW
0.5m HI 1.0m, (1.6/3.2ft, 0.2/.5 fathoms). Range 0 -180m, 0 - 590 ft, 0 - 98.4 fathoms.
6
10-HB-0501-04
11
Page 12
ENABLING/DISABLING THE SHALLOW ALARM
Press
ALARM
key to display shallow alarm
SHA A M.
Press
SETUP
key, the alarm state will be displayed.
Press
ENTER
the display will flash.
ADJUSTING THE SHALLOW ALARM VALUE
key,
Use S or T to enable/disable the alarm.
Press
ENTER
memorise the change.
to
Press
ALARM
key, the value is displayed.
Press
ALARM
key to display shallow alarm
SHA A M
.
610-HB-0501-04
Press
SETUP
key twice, the value is displayed.
Press
ENTER
the display will flash.
key,
Use S or T to adjust the value.
Press
ENTER
key to memorise the new value.
Press
ALARM
key, the alarm is displayed.
12
Page 13
ENABLING/DISABLING THE DEEP ALARM
Press
ALARM
to display deep alarm
DEP A M.
key
Press
SETUP
key, the alarm state will be displayed.
Press
ENTER
the display will flash.
ADJUSTING THE DEEP ALARM VALUE
key,
Use S or T to enable/disable the alarm.
Press
ENTER
memorise the change.
to
Press
ALAR
M
key, the value is displayed.
Press
ALARM
key to display shallow alarm
DEP A M
610-HB-0501-04
Press
SETUP
key twice, the value is displayed.
Press
ENTER
the display will flash.
key,
Use S or T to adjust the value.
Press
ENTER
key to memorise the new value.
Press
ALARM
key, the alarm is displayed.
13
Page 14
USING THE ANCHOR ALARM
The Anchor Alarm uses two adjustable alarm limits. The alarm will sound if the water is deeper or shallower, by the amount set, than the original depth when the alarm was enabled. This allows you to adjust your anchor chain according to the rise and fall of the tides. The Network DEPTH unit has a factory set low limit of 0.5m and a high limit of 1.0m.
In the following example the original water depth was 3m when the alarm was enabled. Using the factory set values, the water depth could increase to 4m (3m + 1m) and decrease to 2.5m (3m - 0.5m) before the alarm would sound.
The anchor alarm depth limits are shown alternatively when they are enabled and displayed using the
ALARM
key.
3.0m depth
6 10-HB-0501-04
ANCH HI limit
1.0m
0.5m
ANCH LOW limit
ANCH HI Alarm
at 4.0m
ANCH LOW Alarm
at 2.5m
14
Page 15
ENABLING/DISABLING THE ANCHOR ALARM
Press key to display anchor alarm
ANC A M
ALARM
Press key, the alarm state will be displayed.
SETUP
Press key, the display will flash.
ENTER
Use S or T to enable/disable the alarm.
Press memorise the change.
ENTER
to
Press key, to display the anchor alarm.
ALARM
610-HB-0501-04
15
Page 16
ADJUSTING THE ANCHOR ALARM LOW LIMIT
Press to display anchor alarm
ALARM
ANC A M.
key
Press twice to display
ANCH LOW
value.
SETUP
key
Press the display will flash.
ENTER
ADJUSTING THE ANCHOR ALARM HI LIMIT
key,
Use S or T to adjust the displayed value.
Press memorise the new value.
ENTER
to
Press to display the anchor alarm.
ALARM
key
Press to display anchor alarm
ALARM
ANC A M.
610-HB-0501-04
key
Press 3 times to display
ANCH HI
SETUP
key
value.
Press the display will flash.
ENTER
key,
Use S or T to adjust the displayed value.
Press to memorise the new value.
ENTER
key
Press to display the anchor alarm.
ALARM
key
16
Page 17
USING THE LIGHTS KEY
The Network DEPTH Display unit has 3 levels of illumination and off, controlled by the
LIGHTS
changes the illumination level of the key legends.
The
LIGHTS
key is always illuminated so even in complete
darkness the key can be located.
key. It also
LIGHTS 0
LIGHTS 3
LIGHTS 2
LIGHTS 1
610-HB-0501-04
OFF High Medium
Low
17
Page 18
SETTING THE DISPLAY LANGUAGE
The Network DEPTH unit can show LCD text in English or French. To change the display language procede as follows.
Press
SIGNAL
key.
610-HB-0501-04
Press
SETUP
key twice to display the language
Press
ENTER
key if the language needs to be changed.
Use S or T to change the language.
setting.
Press
ENTER
to memorise the new setting.
Press
SIGNAL
key to complete the change. The LCD now shows French text.
18
Page 19
NETWORK ALARMS
y
The Network DEPTH unit has an internal buzzer that willsound when an alarm condition is met on a Network unitthat has alarm functions ie. Network DEPTH and NetworkQUAD for depth alarms and Network PILOT for WatchAlarm and Off Course alarms. The unit will also displaywhich alarm is activated.
To silence the internal alarm and return the display to normal operation press any of the five keys.
DEPTH ALARM DISPLAY
Depth alarms can be set for the following:
Shallow water
NETWORK PILOT ALARM DISPLAYS
The Watch Alarm is a count-down timer with is activated at the end of the preset count-down period. The displa alternates between the messages below.
The Off Course alarm is activated when the boat deviates off course by a preset amount. The display alternates between the messages below:
Deep water
Anchor Watch
Check your Network DEPTH or QUAD unit to see which alarm is activated.
610-HB-0501-04
19
Page 20
w
y
r
FAULT AND ERROR MESSAGES
NETWORK PILOT FAULT DISPLAY
If Network PILOT should have a fault the autopilot computer unit will send a message to all other Network Display Units. The Network DEPTH unit will alternately display the follow message, the actual fault will have to read from the Network PILOT Display unit.
UNIT INTERNAL ERRORS
In the unlikely event that your Network DEPTH unit should develop an internal error, the unit will sound it's alarm continuously and the display will show an error number.
Press any of the keys to reset the error condition and silence this alarm. In some cases the fault can be cleared by switching off the instruments at the supply, waiting a fe moments and then switching on again. If either of these methods do not clear the fault the error number should be recorded. Switch off the supply and disconnect the fault unit. Return it with the error number to your dealer fo servicing.
610-HB-0501-04
20
Page 21
INSTALLATION
The display heads are supplied with a clip-in mounting bracket which allows for easy installation, access from behind is not necessary to secure the unit in place. However to prevent theft and permanently fix the unit in position, locking studs and thumb nuts are supplied.
SITING THE UNIT
All Network Instruments are designed for mounting on or below deck. A mounting position should be selected where they are:
Easy to read by the helmsman
On a smooth and flat surface
At least 100mm (4") from a compass
Accessible from behind for fitting locking studs if
required.
MOUNTING THE UNIT
Use the cutting template supplied to mark the centres of the holes for the self-tapping screw, the fixing stud holes and the mounting bracket.
The template allows 4mm (5/32") between adjacent units
for the suncover, increase this distance if required to maximum of 60mm (2 3/8") between units or 180mm (3 1/8") between centres. For greater distances between units extension cables are available. Use a 70mm (2 3/4") diameter hole-cutter for the
mounting bracket hole. Use a 2.9mm for the self-tapping screw holes. Use a
5mm (3/32") drill for the locking stud holes. Secure the mounting bracket to the bulkhead with the
self-tapping screws supplied Fit the rubber sealing gasket around the mounting
bracket. Screw the locking studs into the back of the display head
(if required). Carefully pass the cable tails through the mounting
bracket hole, connect the cables to the main units. Clip the display head into the mounting bracket.
Secure the instrument with the thumb nuts supplied.
610-HB-0501-04
21
Page 22
INSTALLATION DATA
110.0mm
110.0mm
25.0mm 65.0mm
Mounting Bracket Rubber Gasket
82.0mm
Fit the gasket
around the bracket
Locking stud fixings
Network connector Network and Power connector
Gasket
70.0mm hole
Display
Sun cover
82.0mm
610-HB-0501-04
Bulkhead
Gasket
Mounting Bracket
Self-tapping screws
22
Page 23
SPECIFICATION
PHYSICAL PARAMETERS
Construction Window Display
Large Digits: 28.6mm 1.12" Small Digits: 11.5mm 0.45"
Dimensions
Requires 65mm 2.6" depth behind bulkhead for display barrel
Weight:
ENVIRONMENTAL
Operating Temp
@ 93%RH
Storage Temp
@ 95%RH
Humidity Sealing
bulkhead cockpit mounting. Vented barrel to prevent condensation.
Acrylic
Back-lit Liquid Crystal Display:
0,3 Kg 0.66lbs
Fully sealed front, suitable for
High impact ABS plastic
: 110 x 110 x 25.4mm 4 x 4 x 1"
-10 à+55°C, +14 to +1310F
-25 à+70°C, -25 to +700C
Up to 95%RH
ELECTRICAL
Power Supply Operating Current Protection
breaker.
CABLES AND CONNECTIONS
Connection to adjacent units is via cable tails fitted with either a plug or a socket. Extension cables are available from your dealer. The cable tails carry power and NMEA data between units.
ALARM
Internal audible alarm. Control output for external alarm unit.
NMEA OUTPUT SENTENCES
There is no NMEA output from the Network DEPTH unit.
12V DC nominal (10 to 16V)
40mA typical, 100mA illuminated
Connect via external fuse or circuit
610-HB-0501-04
23
Loading...