ATTUATORE IN BASSA TENSIONE PER CANCELLI SCORREVOLI A CREMAGLIERA
LOW-VOLTAGE ACTUATOR FOR RACK SLIDING GATES
ACTIONNEUR A BASSE TENSION POUR PORTAILS COULISSANTS A CREMAILLERE
NIEDERSPANNUNGSANTRIEB FÜR ZAHNSTANGEN-SCHIEBETORE
SERVOMOTOR DE BAJA TENSION PARA CANCELAS CORREDERAS DE CREMALLERA
LAAGSPANNINGSACTUATOR VOOR SCHUIFHEKKEN MET TANDHEUGEL
D811343 00100_03 25-01-11
ISTRUZIONI D’USO E DI INSTALLAZIONE
INSTALLATION AND USER’S MANUAL
INSTRUCTIONS D’UTILISATION ET D’INSTALLATION
INSTALLATIONS-UND GEBRAUCHSANLEITUNG
INSTRUCCIONES DE USO Y DE INSTALACION
INSTALLATIEVOORSCHRIFTEN
DEIMOS BT + QSC D MA
DEIMOS BT + QSC D MA
Attenzione! Leggere attentamente le “Avvertenze” all’interno! Caution! Read “Warnings” inside carefully! Attention! Veuillez lire attentivement les Avertissements qui se trouvent à l’intérieur! Achtung! Bitte lesen Sie
aufmerksam die „Hinweise“ im Inneren! ¡Atención¡ Leer atentamente las “Advertencias” en el interior! Let op! Lees de “Waarschuwingen” aan de binnenkant zorgvuldig!
3x1mm
2
3x1.5mm
2
2x0.75mm
2
3x1.5mm
2
RG58
3x1.5mm
2
3x1.5mm
2
5x0,75mm
2
2x1.5mm
2
Predisposizione fissaggio motore, Preparation for motor mounting,
Aménagement fixation moteur, Vorbereitung Motorbefestigung,
Disposición fijación del motor, Voorbereiding bevestiging motor.
25mm + “X”
“X”= Cremagliera, Rack,
Crémaillère, Zahnstange,
Cremallera, Tandheugel
Montaggio motore, Mounting the motor, Montage moteur,
Montage Motor, Montaje del motor, Montage motor.
Fissaggio staffe finecorsa (dx e sx), Fastening limit switch brackets (RH/LH),
Fixation étriers fin de course (drt et gch), Befestigung Bügel Anschläge (rechts und links),
Fijación abrazaderas final de carrera (der. e izq.),
Bevestiging stangen aanslag (rechts en links).
Y
Y
Collegamento morsettiera, Terminal board wiring,
Connexion plaque à bornes, Anschluss Klemmleiste,
Conexión tablero de bornes, Aansluiting aansluitkast.
> 10mm
> 25mm
A
C
E
B
D
F
D1
PREDISPOSIZIONE TUBI, TUBE ARRANGEMENT,
PRÉDISPOSITION DES TUYAUX, VORBEREITUNG DER LEITUNGEN,
DISPOSICIÓN DE TUBOS, VOORBEREIDING LEIDINGEN.
INSTALLAZIONE VELOCE-QUICK INSTALLATION-INSTALLATION RAPIDE
Anschluss von einem Paar nicht überprüften Fotozellen
Conexión de 1 par fotocélulas no comprobadas
Aansluiting van 1 paar fotocellen anders dan “trusted device”
LOGICA test fotocellule OFF / Photocell test LOGIC OFF
LOGIQUE essai photocellules Désactivée / LOGIK Test Fotozellen OFF
LÓGICA prueba fotocélulas OFF / LOGICA test fotocellen OFF
N
L
1234567891011121314151617181920212223242526
31323334
JP2
JP3
24V
~
230V
~
F
G
M
NO
NO
FAULT
COM
PED
COM
NC
SWC
NC
SWO
24V
~
0V
ANT
Grigio-Grey-Gris-Grau-Gris-Grijs
Grigio-Grey-Gris-Grau-Gris-Grijs
A
B
C
D
E
SCA/2°CH
COM
NO
NC
NO
NC
NC
START
CLOSE
STOP
PHOT
BAR
OPEN
Connettore programmatore palmare,
Palmtop programmer connector,
Connecteur programmateur de poche,
Steckverbinder Palmtop-Programmierer,
Conector del programador de bolsillo,
activated
CLOSE input activated
OPEN input activated
opening limit switch input
activated
closing limit switch input activated
high torque during slow-down in
AUTOSET mode
Use a lower slow-down and check mo-
vement and smooth operation of leaf
software thermal cutout activated allow automated device to cool
reverse due to obstaclemake sure movement is not hindered
photocell test anomaly
safety edge test anomaly
check photocell connection and/or
parameter/logic settings
check safety edge connection and/or
parameter/logic settings
hardware anomalycheck connections to motor
check connection with accessory
Er5X *
communication anomaly
devices and/or expansion boards or
serial-connected devices
* X = 0,1,…,9,A,B,C,D,E,F
35.40
Set torque threshold
Maximum instantaneous motor torque
INSTALLATION MANUAL
DEIMOS BT-MA - 13
D811343 00100_03
WARNING! Important safety instructions. Carefully read and comply with the
Warnings booklet and Instruction booklet that come with the product as incorrect
installation can cause injury to people and animals and damage to property. They
contain important information regarding safety, installation, use and maintenance.
Keep hold of instructions so that you can attach them to the technical le and
keep them handy for future reference.
1) GENERAL SAFETY
WARNING! An incorrect installation or improper use of the product can
cause damage to persons, animals or things.
- The units making up the machine and its installation must meet the requirements
of the following European Directives: 2004/108/EEC, 2006/95/EEC, 98/37/
EEC, 89/106/EEC and later amendments. For all countries outside the EEC, it is
advisable to comply with the above-mentioned standards, in addition to any
national standards in force, to achieve a good level of safety.
- The Firm disclaims all responsibility resulting from improper use or any use
other than that for which the product has been designed, as indicated herein, as well as for failure to apply Good Practice in the construction of entry
systems (doors, gates, etc.) and for deformation that could occur during use.
- Make sure the stated temperature range is compatible with the site in which
the automated system is due to be installed.
- Before performing installation, remove any cables or chains that are not nee-
ded and disable any equipment that is not required for installation purposes.
Also check that the door/gate is in a good state of mechanical repair, is correctly balanced and opens and closes as it should do.
- Do not install the product in an explosive atmosphere.
- Disconnect the electricity supply before performing any work on the system.
Also disconnect buer batteries, if any are connected.
- Have the automated system’s mains power supply tted with a switch or omnipolar thermal-magnetic circuit breaker with a contact separation of at least
3.5 mm.
- Make sure that upline from the mains power supply there is a residual current
circuit breaker that trips at 0.03A.
- Make sure the earth system has been installed correctly: earth all the metal
parts belonging to the entry system (doors, gates, etc.) and all parts of the
system featuring an earth terminal.
- Installation must be carried out using safety devices and controls that meet
standard EN 12978.
- Apply all safety devices (photocells, safety edges, etc.) required to keep the
area free of crushing, dragging and shearing hazards.
- The motor cannot be installed on panels incorporating doors (unless the motor can be activated when the door is open)
- If the automated device is installed at a height of less than 2.5 m or is accessible, the electrical and mechanical parts must be suitably protected.
- Any xed controls must be installed within sight of the door but away from
moving parts. Unless the control is key operated, it must be installed at a
height of at least 1.5 m and in a place where it cannot be reached by the
public
- Apply at least one warning light (ashing light) in a visible position, and also
attach a Warning sign to the structure.
- If there are no instructions already, attach a label near the operating device,
in a permanent fashion, with information on how to operate the manual release.
- Make sure that nothing can be crushed between the guided part and surrounding xed parts during the door’s operation
- Once installation is complete, make sure the motor has the right settings and
that the safety and release systems are working properly.
- Only use original spare parts for any maintenance or repair work. The Firm
disclaims all responsibility for the correct operation and safety of the automated system if parts from other manufacturers are used.
- Do not make any modications to the automated system’s components unless explicitly authorized by the Firm.
- Dispose of packaging materials (plastic, cardboard, polystyrene, etc.) in accordance with the provisions of the laws in force. Keep nylon bags and polystyrene out of reach of children.
-
Anything which is not expressly provided for in the present instructions, is not
allowed
- Instruct the product user about the control systems provided and the manual
Warning! For connection to the mains power supply, use a multicore cable
with a cross-section of at least 4x1.5mm2 of the kind provided for by the
regulations mentioned above (by way of example, type H05 VV-F cable can
be used with a cross-section of 4x1.5mm2). To connect auxiliary equipment,
use wires with a cross-section of at least 0,75 mm2.
Have an omnipolar circuit breaker installed with a contact separation of
at least 3 mm and featuring overload protection, suitable for cutting the
automated device o from the mains.
Only use pushbuttons with a capacity of 10A-250V or more.
.
opening operation in case of emergency.
wires must be left as short as possible. The earthing wire must be the last to
stretch in the case where the cable xing device becomes loose.
WARNING: extremely low safety voltage cables must be phisically
separated from low voltage cables.
Access to the electrical compartment or to limit switches must be allowed
to skilled personnel only.
Setting sensitivity incorrectly can result in damage to property and
injury to people and animals.
Compliance with current safety rules with regard to people, animals and property
must be assured at all times and, more specically, measures must be taken to avoid
risks of injury due to crushing, in the area where the pinion and rack mesh, and
any other mechanical hazards. All critical points must be protected by safety
devices in accordance with the provisions of the regulations in force.
CHECKING THE AUTOMATED DEVICE
Before the automated device is nally put into operation, perform the following
checks meticulously:
• Make sure all components are fastened securely.
• Check the correct functioning of all safety devices (limit microswitches, pho-
tocells, sensitive edges etc.).
• Make sure that the anti-crush system stops the door within the limits provided
for by the standards in force.
• Check the emergency operation control device.
•
Check the opening and closing operations with the control devices in use.
• Check the standard and customised electronic functioning logic.
MAINTENANCE
WARNING: before opening the door, the spring must be unloaded (vertical
boom). WARNING: Before carrying out any maintenance to the installation,
disconnect the mains power supply. The following points need checking and
maintenance:
- Photocell optics. Clean occasionally.
- Electric edge. Carry out a periodical manual check to ensure that the edge
stops the bar in case of obstacles.
- Dismantle the gearmotor and replace the lubricating grease every two
years.
- When any operational malfunction is found, and not resolved, disconnect the
mains power supply and request the assistance of a specialised technician
(installer). When the operator is out of order, activate the emergency release
(see Fig. 2), if necessary, so as to release the manual boom opening and closing
operations.
SCRAPPING
Materials must be disposed of in conformity with the current regulations.
In case of scrapping, the automation devices do not entail any particular risks
or danger. In case of recovered materials, these should be sorted out by type
When the automation system is disassembled to be reassembled on another
site, proceed as follows:
- Disconnect the power supply and the entire electrical installation.
- Remove the actuator from its xing base.
- Disassemble all the installation components.
- In the case where some of the components cannot be removed or are dama-
ged, they must be replaced.
Correct controller operation is only ensured when the data contained in
the present manual are observed. The Company is not to be held responsible for any damage resulting from failure to observe the installation
standards and the instructions contained in the present manual.
The descriptions and illustrations contained in the present manual are
not binding. The Company reserves the right to make any alterations
deemed appropriate for the technical, manufacturing and commercial
improvement of the product, while leaving the essential product features unchanged, at any time and without undertaking to update the
present publication.
ENGLISH
The cables must be held in position using an extra xing device in the proximity of the terminals, e.g. with cable clamps.
Also add more clips to the limit device wires, to the transformer primary or
secondary wires, and to the wires connected to the printed circuit.
During installation, the power supply cable must be stripped in order for the
earthing wire to be connected to the appropriate terminal, but the active
INSTALLATION MANUAL
14 - DEIMOS BT-MA
D811343 00100_03
1) FOREWORD
The DEIMOS BT-MA actuator is highly versatile in terms of installation options
due to the extremely low position of the pinion, the actuator’s compact nature
and the height and depth adjustment features it oers. The adjustable electronic
torque limiter provides anti-crush safety. Manual emergency operation is extremely
easy to perform using just a knob.
Stopping at end of travel is controlled by electromechanical microswitches.
The built-in control panel controls the start relays and safety devices (photocells,
safety edge) each time before performing any operation.
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
3) TUBE ARRANGEMENT Fig.A
Install the electrical system referring to the standards in force for electrical
systems CEI 64-8, IEC 364, harmonization document HD 384 and other national
standards.
4) PREPARATION FOR MOTOR MOUNTING FIG.B
• Make a hole in the ground to accommodate the concrete pad, with anchors
embedded in the base plate for fastening the gearbox assembly, keeping to
the distances featured in FIG.B.
• To keep the base plate in the right position during installation, it may be
useful to weld two iron plates under the track to which the anchors can then
be welded (FIG.M).
5) MOUNTING THE MOTOR FIG.C
6) MOUNTING DRIVE ACCESSORIES FIG.D-D1
7) RACK CENTRING WITH RESPECT TO PINION FIG.N-O1-P
DANGER - Welding must be performed by a competent person issued
with the necessary personal protective equipment as prescribed by the
safety rules in force FIG.O.
8) FASTENING LIMIT SWITCH BRACKETS FIG.E
0,5A (230V~) - 1A (110V~)
Universal handheld programmer/
LCD display
63
9) STOPS FIG.Q
DANGER - The gate must be tted with mechanical stops to halt its
travel both when opening and closing, thus preventing the gate from
coming o the top guide. Said stops must be fastened rmly to the ground,
a few centimetres beyond the electric stop point.
10) MANUAL RELEASE (See USER GUIDE -FIG.2-).
Warning Do not JERK the gate open and closed, instead push it GENTLY to
the end of its travel.
11) TERMINAL BOARD WIRING Fig. F-G
Once suitable electric cables have been run through the raceways and the automated device’s various components have been fastened at the predetermined
points, the next step is to connect them as directed and illustrated in the diagrams
contained in the relevant instruction manuals. Connect the live, neutral and earth
wire (compulsory). The mains cable must be clamped in the relevant cable gland
(FIG.R-ref.P1), and the accessories’ wires in the cable gland (FIG.R-ref.P2), while
the earth wire with the yellow/green-coloured sheath must be connected in the
relevant terminal (FIG.R-ref.S).
TERMINAL
1-2
3-424V transformer secondary winding.
5-6
5-7
8-9Flashing light 24V max. 25W.
10-11
12-13
14-15
16-17
18-19F A U LT safety devices input.
19-20
21-22
21-23
21-24PHOT photocell input. If not used, leave jumpered.
21-25
21-26OPEN control button (NO).
31-32230V~ transformer primary winding.
33-34Single-phase power supply 230V, 50-60Hz (33N - 34L).
12)CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD
PROGRAMMER (Fig.T)
Refer to specic manual.
13 OPPOSITE SLIDING LEAVES FIG.U
14 SAFETY DEVICES
NOTE: ONLY USE RECEIVING SAFETY DEVICES WITH FREE CHANGEOVER
CONTACT.
Motor connection. WARNING - If opening direction is not
correct, swap wires over.
Closing limit switch SWC (5 Black common - 6 Red).
WARNING - If opening direction is not correct, swap opening
and closing limit switch wires over.
Opening limit switch SWO (5 Black common -7 Brown).
WARNING - If opening direction is not correct, swap opening
and closing limit switch wires over.
Antenna (10 signal - 11 braiding).
Use an antenna tuned to 433MHz.
Use RG58 coax cable to connect the Antenna and Receiver.
Metal bodies close to the antenna can interfere with radio reception. If the transmitter’s range is limited, move the antenna to a
more suitable position.
Accessories power supply:
24 V operation with mains power on.
24 V (12-,13+) operation with no mains power and optional
buer battery kit. Mod. SB BAT.
Free contact (NO).
Gate Open Light SCA (24V max. 3W) or 2nd radio channel output
(FIG.G-ref.1).
This option can be set via the “logic menu”.
Safety device power supply output (photocell transmitter and
safety edge transmitter).
N.B.: output active only during operating cycle.
24 V Vsafe operation with mains power on.
24 V (16 -,17+) Vsafe operation with no mains power and optional
buer battery kit. Mod. SB BAT.
Pedestrian control button PED (NO) Opens the gate for a period of
5 seconds with the set logic modes
(3 or 4 steps).
START/CLOSE control button and key-operated selector (NO).
This option can be set via the “logic menu”.
STOP control button (NC). Whatever the case, stops the automated device until a new start command is given. If not used, leave
jumpered.
Safety edge contact input BAR (NC). When tripped, the gate stops
and reverses for approx. 3 secs.
If not used, leave jumpered.
INSTALLATION MANUAL
DEIMOS BT-MA - 15
D811343 00100_03
14.1 TESTED DEVICES FIG.V
14.2 NONTESTED DEVICES FIG.H
15 CALLING UP MENUS: FIG. 1
15.1) PARAMETERS MENU PARAM PARAMETERS TABLE “A”
15.2) LOGIC MENU LOGIC LOGIC TABLE “B”
15.3) RADIO MENU radio RADIO TABLE “C”
- IMPORTANT NOTE: THE FIRST TRANSMITTER MEMORIZED MUST BE
IDENTIFIED BY ATTACHING THE KEY LABEL (MASTER).
In the event of manual programming, the rst transmitter assigns the RECEIVER’S
KEY CODE: this code is required to subsequently clone the radio transmitters.
The Clonix built-in on-board receiver also has a number of important advanced
features:
• Cloning of master transmitter (rolling code or xed code).
• Cloning to replace transmitters already entered in receiver.
• Transmitter database management.
• Receiver community management.
To use these advanced features, refer to the universal handheld programmer’s
instructions and to the general receiver programming guide.
15.4 LANGUAGE MENU lingua
Used to set the programmer’s language on the display.
15.5 DEFAULT MENU default
Restores the controller’s DEFAULT factory settings. Following this reset, you will
need to run the AUTOSET function again.
0 sec. 120 sec.10Automatic Closing TimePause time before automatic closing.
1%99%80Opening motor torqueSets motor’s operating force during opening at normal speed.
1%99%80Closing motor torque Sets motor’s operating force during closing at normal speed.
1%99%25
1%99%25
1 sec.2 min.25Fast Time during OpeningLength of normal speed stage during opening.
1 sec.2 min.25Fast Time during ClosingLength of normal speed stage during closing.
030Slow-down speed
01280Zone
Opening motor torque
during slow-down
Closing motor torque
during slow-down
15.6 AUTOSET MENU AUTOset
Used for automatic setting of motor torque and fast time during opening and
closing.
Before running the AUTOSET function, adjust slow-down speed (Fig. J).
WARNING! The AUTOSET operation must be performed starting from the
closing limit switch position. If you attempt to run the AUTOSET function
in any other position, the following error message will appear: “nsvc” and the
operation will not be performed.
WARNING!! The AUTOSET operation must be performed only once you have
checked that the leaf is moving accurately (opening/closing) and that the
limit switches are tripping correctly.
WARNING: if slow-down speed is edited after the AUTOSET operation,
the AUTOSET function will need to be run again.
During this stage, it is important to avoid breaking the photocells’ beams and not
to use the START, STOP, PED, CLOS and OPEN commands or the display.
WARNING! While the AUTOSET function is running, the obstacle detection
function is not active. Consequently, the installer must monitor the automated system’s movements and keep people and property out of range of the
automated system.
When using buer batteries, the AUTOSET function must be run with the control
panel running o mains power.
WARNING! DIAGNOSTICS
Use a lower slow-down and check movement and smooth operation of leaf.
Sets motor’s operating force during opening at slowed speed.
Sets motor’s operating force during closing at slowed speed.
Serial connection address.
Set the Zone number in the range 0 to 127. The zone number
allows you to create groups of automated devices, each of which
answers to the Zone Master. Each zone can have only one Master.
The Master of zone 0 also controls the Masters and Slaves of the
other zones.
Zone 128: Opposite Sliding Leaves Fig. U.
FIG. J1
or: high torque during slow-down in AUTOSET mode.
ENGLISH
15.2 TABLE B: LOGIC MENU logic
LogicDefault Denition
Automatic
TCA
3 step
Ibl open
Photoc.open
OFF
Closing Time
OFF3 step
OFFBlock Pulses
Photocells
OFF
during opening
Cross out
setting
used
ONSwitches automatic closing on.
OFFSwitches automatic closing o.
ON
OFF
ONThe start pulse has no eect during opening.
OFFThe start pulse has eect during opening or closing.
ON
OFF
Description
Switches to 3-step logic. A start pulse has the following eects:
door closed: opens
during opening: stops and switches on TCA (if congured).
door open: closes
during closing: stops and opens again
Switches to 4-step logic. A start pulse has the following eects:
door closed: opens
during opening: stops and switches on TCA (if congured)
door open: closes
during closing: stops and does not switch on tca (stop)
after stop: opens
When beam is broken, operation of the photocell is switched o during opening. During closing,
movement is reversed immediately.
When beam is broken, photocells are active during both opening and closing. When beam is broken
during closing, movement is reversed only once the photocell is cleared.
INSTALLATION MANUAL
16 - DEIMOS BT-MA
D811343 00100_03
LogicDefault Denition
test phot
test bar
fault phot
SCA 2Ch
preal
hold to
tun
start close
fixed code
radio prog
ster
ice
OFFPhotocell test
Safety edge
OFF
testing
ONFault Phot
Gate open light
OFF
or 2nd radio
channel
OFFPre-alarm
OFFDeadman
START - CLOSE
OFF
setting
OFFFixed code
Remote control
ON
programming
OFFMaster/slave
OFFICE
Cross out
setting
used
OFF
OFF
OFF
OFFThe output between terminals 14-15 is set as 2nd radio channel.
OFFThe ashing light comes on at the same time as the motors start.
OFFPulse operation, according to 3- or 4-step logic.
OFFInput between terminals 21-22 works as START.
OFFReceiver is congured for operation in rolling-code mode.
OFF
OFF
OFF
Description
ONSwitches photocell testing on
Switches photocell testing o
If disabled (OFF), it inhibits the photocell testing function, enabling connection of devices not
equipped with supplementary test contacts.
ONSwitches safety edge testing on.
Switches safety edge testing o
If disabled (OFF), it inhibits the safety edge testing function, enabling connection of devices not
equipped with supplementary test contacts.
ON
ON
ONThe ashing light comes on approx. 3 seconds before the motors start.
ON
ONInput between terminals 21-22 works as CLOSE.
ONReceiver is congured for operation in xed-code mode.
ON
ON
ON
The fault input is associated with the photocell test circuit,
up to 4 pairs of tested photocells and one tested safety edge can be connected (Fig. V)
The fault input is associated with the safety edge test circuit,
up to 4 tested safety edges and one pair of tested photocells can be connected (Fig. V).
The output between terminals 14-15 is set as Gate open light:
in this case, the 2nd radio channel controls pedestrian opening.
Deadman mode: operation continues as long as the control key is held down.
(OPEN terminal 21-26, CLOSE terminal 21-22).
Enables wireless memorizing of transmitters:
1- Press in sequence the hidden key (P1) and normal key (T1-T2-T3-T4) of a transmitter that has already
been memorized in standard mode via the radio menu.
2- Press within 10 secs. the hidden key (P1) and normal key (T1-T2-T3-T4) of a transmitter to be
memorized.
The receiver exits programming mode after 10 secs.: you can use this time to enter other new tran-
smitters.
This mode does not require access to the control panel.
Disables wireless memorizing of transmitters.
Transmitters are memorized only using the relevant Radio menu.
Control panel is set up as the Master unit in a centralized serial connection system.
WARNING: the control panel set as the master must be the rst in the series.
Control panel is set up as a Slave unit in a centralized serial connection system.
The controller automatically adjusts the Amperostop safety trip threshold at each start up. This feature is useful when dealing with installations running at low temperatures.
WARNING: once this feature has been activated, you will need to perform an autoset opening
and closing cycle.
The Amperostop safety trip threshold stays at the same set value.
15.3 TABLE C: RADIO MENU RADIO
Description
Add start
add 2ch
read
erase 64
Add Start Key
associates the desired key with the Start command.
Add 2ch Key
associates the desired key with the 2nd radio channel command.
Read
Checks a key of a receiver and, if memorized, returns the position of the remote control in the memory (from 01 to 63) and number of the key
(T1-T2-T3 or T4).
Erase List
WARNING! Erases all memorized remote controls from the receiver’s memory.
Read receiver code
Displays receiver code required for cloning remote controls.
ON = Enables remote programming of cards via a previously memorized W LINK transmitter. It remains enabled for 3 minutes from the time
Thank you for choosing this product. The Firm is condent that its performance will
meet your operating needs. This product meets recognized technical standards
and complies with safety provisions. We hereby conrm that it is in conformity
with the following European directives: 2004/108/EEC, 2006/95/EEC, 98/37/EEC,
99/05/EEC (and later amendments).
1) GENERAL SAFETY
WARNING Important safety instructions. Carefully read and comply with the
Warnings booklet and Instruction booklet that come with the product as improper use can cause injury to people and animals and damage to property.
Keep hold of instructions for future reference. This product has been designed
and built solely for the purpose indicated herein. Uses not contemplated herein
might result in the product being damaged and could be a source of danger
- The Firm disclaims all responsibility resulting from improper use or any use
other than that for which the product has been designed, as indicated herein,
as well as for failure to apply Good Practice in the construction of entry systems
(doors, gates, etc.) and for deformation that could occur during use.
If installed and used correctly, the automated system will meet the required level
of safety. Nonetheless, it is advisable to observe certain rules of behaviour so that
accidental problems can be avoided:
- Keep adults, children and property out of range of the automated system,
especially while it is operating.
- This application is not meant for use by people (including children) with
impaired mental, physical or sensory capacities, or people who do not have
suitable knowledge, unless they are supervised or have been instructed by
people who are responsible for their safety.
- Children must be supervised to ensure they do not play with the application.
Keep remote controls or other control devices out of reach of children in order
to avoid the automated system being operated inadvertently.
- The manual release’s activation could result in uncontrolled door movements
if there are mechanical faults or loss of balance.
- Do not deliberately hinder the door’s movement and do not attempt to open
the door manually unless the actuator has been released with the relevant
release knob.
- Check the system frequently, especially cables, springs or supports, to detect
any loss of balance and signs of wear or damage.
- When cleaning the outside or performing other maintenance work, always
cut o mains power.
- Keep the photocells’ optics and illuminating indicator devices clean. Check
that no branches or shrubs interfere with the safety devices (photocells).
- Do not use the automated system if it is in need of repair. In the event of a
malfunction, cut o the power, activate the emergency release to allow access
and call in qualied technical personnel (professional installer).
- If the automated system requires work of any kind, employ the services of
qualied personnel (professional installer).
- Have the automated system checked by qualied personnel once a year.
- Anything that is not explicitly provided for in these instructions is not
allowed.
-
The operator’s proper operation can only be guaranteed if the information given
herein is complied with. The Firm shall not be answerable for damage caused by
failure to comply with the installation rules and instructions featured herein.
- Descriptions and illustrations herein are not binding. While we will not alter the
product’s essential features, the Firm reserves the right, at any time, to make
those changes deemed opportune to improve the product from a technical,