Bently Nevada 3500/82 Data sheet

Stator Insulation Monitoring System
Bently Nevada* Asset Condition Monitoring
Description
The Bently Nevada* Stator Insulation Monitoring System uses state of the art technologies to measure the leakage current of motors sized up to 7.5 kV and 1000 Amps. The measurements are made while the motor is online and the system processes the measured data in real time to determine the condition of the stator insulation in the motor. The system consists of a 9-channel 3500/82 monitor that accepts inputs from the 350820 High Sensitivity Current Transformer (HSCT), 350822 High Voltage Sensors (HVS), and 4-20 mA process signals corresponding to motor temperature measurements. The 3500/82 processed data and results can be displayed on the 3500/94 Display. The user can configure the 3500/82 using the 3500 Rack Configuration Software to perform the following functions:
Display instantaneous stator leakage current on each phase of the
motor.
Display compensated dissipation factor and change in dissipation factor
Note: The 3500/82 monitor should not be used for machine protection.
The 3500/82 can accept 3 HSCT, 3 HVS, and 3 4-20mA process inputs from stator RTD temperature measurements. Since the interface modules are capable of driving long field cables, the monitor can be situated in a control or instrumentation room up to 330 meters (1,000 feet) away from the motor or the interface modules.
The 3500/82 is featured with measurement trending by comparing the current measurements to any historical data taken in the last 10 years (if the historical data is available). The time window for comparison is user configurable.
The 3500/82 monitor has eight buffered outputs for diagnostic purposes, 3 each HVS and HSCT values for each of those corresponding inputs, an average temperature from the temperature inputs, and a synchronization phase pulse reference signal.
from a given reference point.
Display motor stator temperature and average temperature. Display line voltage and frequency data values. Retrieve historic data stored on board the monitor for data analysis. Set alarm levels for annunciation. Configure the temperature range and time period for learn and extend
modes for temperature learning, and view the current learning state.
View the number of temperature samples, vs. operating temperatures,
that builds the learning curve used for temperature compensation.
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 1 of 13
Monitor Specifications
Parameters are specified from +20 °C to +30 °C (+68 °F to +86 °F) and at 50/60 Hz unless otherwise indicated.
Note: Operation outside these specified limits may result in a larger variation in readings from what is listed below, or a loss of machine monitoring all together.
Inputs
Input Signals
Accepts 3 HSCT, 3 HVS, and 3 4­20mA temperature inputs.
Input Impedance
150 k // 1nF (for HSCT & HVS) 200 (for 4-20 mA temperature)
Input Frequency Range
40 to 70 Hz
Power Consumption (not including external power supply)
15 watts, typical
HSCT External Power Required
+24V ± 2% @ 0.75 A Nominal Over temperature
Outputs
Front Panel LEDS
OK LED
Indicates when the system is operating properly.
TX/RX LED
Indicates when the 3500/82 is communicating with other modules in the 3500 rack.
Bypass LED
Indicates when the 3500/82 is in Bypass Mode.
Buffered Outputs
The front of the monitor has eight coaxial BNC connectors for each of the HVS and HSCT outputs and average temperature output, and a phase reference pulse (Sync). Each connector is short-circuit protected. The output from all 8 BNCs is voltage proportional to the input signals.
Output Impedance
499 ±1%
Output Range HVS and HSCT Channels (6 BNCs)
Dynamic: 1.6 to 10.4V, ±5%. Bias: 6V ±5%.
Output Range Average Temperature Channel (1 BNC)
2.0 to 10.0V, ±5%, for -40 to 200 °C (default, but can be user configurable)
Output Range Sync (1 BNC)
Digital Pulse: 0 to 10.0V, ±5%.
Sensor Specifications
Parameters are specified from +20 °C to +30 °C (+68 °F to +86 °F) and at 50/60 Hz unless otherwise indicated.
Note: Operation outside these specified limits may result in a larger variation in readings from what is listed below, or a loss of machine monitoring all together.
Sensitivity
HSCT Output Sensitivity
3.3mV / mA nominal, each unit marked with its specific sensitivity ±1% Linearity: ±0.25%
Phase
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 2 of 13
6° nominal, each unit marked with specific phase shift for that unit, ±0.5°. Linearity: ±0.5° Temperature impact on phase: +2° at minimum operating temperature,
-1° at maximum operating temperature.
Current
1.4 A peak to peak (sine wave) full­scale.
HVS Output
0.76mV / V ±5% 8 kVrms full-scale (line to neutral)
Interface Module Outputs
HSCT Interface Module Output
Gain: 3V/V
HVS Interface Module Output
Gain: 0.625V/V with 77 k source impedance
Temperature Interface Module Output
66.6 µA / °C ±2%. (default)
-40 to 200
°C full-scale (user
configurable)
Signal Conditioning in 3500/82 Monitor
HVS and HSCT
Overall Frequency Response
Direct
1 Hz to 8.5 kHz ±3.0 dB User configurable
1X Filter
50 or 60 Hz User configurable
Overall Accuracy Amplitude
±1% of full-scale, Typical
±2% of full-scale, Maximum
Phase
±1°, Typical ±2°, Maximum
Filter Quality High-Pass
2-pole (40 dB per decade)
Low-Pass
2-pole (40 dB per decade
Overall Accuracy
±1% of full-scale, Typical ±2% of full-scale, Maximum
Temperature
Overall Frequency Response
3 Hz -3.0 dB
Overall Accuracy
±1% of full-scale, Typical. ±2% of full-scale, Maximum.
Filter Quality Low-Pass
2-pole (40 dB per decade)
Overall Accuracy
±1% of full-scale, Typical. ±3% of full-scale, Maximum.
System Alert/Alarm Setting
Alarm Setpoints
The user can use software configuration to set Alert levels for each value measured by the monitor and Alarm setpoints for any values measured by the monitor. Alarms are adjustable from 0 to 100% of full-scale for each measured value.
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 3 of 13
Alarm Time Delays
The user can program alarm delays using software as follows:
Alert & Danger
From 1 to 60 seconds in 1 second Intervals.
Note: Applies to temperature, voltage and current measurements. The 3500/82 system Alert/Alarms are for annunciation only and should not be used for machine protection.
Environmental Limits
Operating Temperature Range Transducers & Interface Modules
20 °C to +70 °C (-4 °F to +158 °F)
3500/82 Monitor
30 °C to +65 °C (-22 °F to +149 °F)
MTL and P+F Barriers
20 °C to +60 °C (-4 °F to +140 °F)
Storage Temperature Transducers / Interface Modules
40 °C to +85 °C (-40 °F to +185 °F)
3500/82 Monitor
40 °C to +85 °C (-40 °F to +185 °F)
MTL Barriers
40 °C to +80 °C (-22 °F to +149 °F)
P+F Barriers
25 °C to +70 °C (-13 °F to +158 °F)
Shock Survivability Transducers
100 g peak, maximum
Interface Modules
200 g peak, maximum
3500/82 Monitor
200 g peak, maximum
Relative Humidity
95% non-condensing (75% non-condensing for P+F barriers)
Magnetic Field Susceptibility
<500µV/gauss (50 gauss, 50-60Hz)
Transducers Common Mode Line Current
Up to 1,000A rms, nominal
Line Voltage
Up to 7.5kV
rms, nominal
Operating voltage less than 2kV has limitations from the HVS.
Physical
Monitor Module
Dimensions (Height x Width x Depth)
241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in)
Weight
0.97 kg (2.14 lb.)
I/O Module
Dimensions (Height x Width x Depth)
241.3 mm x 24.4 mm x 91.1 mm (9.50 in x 0.96 in x 3.90 in)
Weight
0.41 kg (0.91 lb.)
Rack Space Requirements Monitor Module
1 full-height front slot
I/O Module
1 full-height rear slot
HVS and HSCT Interface Modules Dimensions (Height x Width x Depth)
Specifications and Ordering Information
Part Number 323735-01