Bently Nevada 3500/82 Data sheet

Page 1
Stator Insulation Monitoring System
Bently Nevada* Asset Condition Monitoring
Description
The Bently Nevada* Stator Insulation Monitoring System uses state of the art technologies to measure the leakage current of motors sized up to 7.5 kV and 1000 Amps. The measurements are made while the motor is online and the system processes the measured data in real time to determine the condition of the stator insulation in the motor. The system consists of a 9-channel 3500/82 monitor that accepts inputs from the 350820 High Sensitivity Current Transformer (HSCT), 350822 High Voltage Sensors (HVS), and 4-20 mA process signals corresponding to motor temperature measurements. The 3500/82 processed data and results can be displayed on the 3500/94 Display. The user can configure the 3500/82 using the 3500 Rack Configuration Software to perform the following functions:
Display instantaneous stator leakage current on each phase of the
motor.
Display compensated dissipation factor and change in dissipation factor
Note: The 3500/82 monitor should not be used for machine protection.
The 3500/82 can accept 3 HSCT, 3 HVS, and 3 4-20mA process inputs from stator RTD temperature measurements. Since the interface modules are capable of driving long field cables, the monitor can be situated in a control or instrumentation room up to 330 meters (1,000 feet) away from the motor or the interface modules.
The 3500/82 is featured with measurement trending by comparing the current measurements to any historical data taken in the last 10 years (if the historical data is available). The time window for comparison is user configurable.
The 3500/82 monitor has eight buffered outputs for diagnostic purposes, 3 each HVS and HSCT values for each of those corresponding inputs, an average temperature from the temperature inputs, and a synchronization phase pulse reference signal.
from a given reference point.
Display motor stator temperature and average temperature. Display line voltage and frequency data values. Retrieve historic data stored on board the monitor for data analysis. Set alarm levels for annunciation. Configure the temperature range and time period for learn and extend
modes for temperature learning, and view the current learning state.
View the number of temperature samples, vs. operating temperatures,
that builds the learning curve used for temperature compensation.
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 1 of 13
Page 2
Monitor Specifications
Parameters are specified from +20 °C to +30 °C (+68 °F to +86 °F) and at 50/60 Hz unless otherwise indicated.
Note: Operation outside these specified limits may result in a larger variation in readings from what is listed below, or a loss of machine monitoring all together.
Inputs
Input Signals
Accepts 3 HSCT, 3 HVS, and 3 4­20mA temperature inputs.
Input Impedance
150 k // 1nF (for HSCT & HVS) 200 (for 4-20 mA temperature)
Input Frequency Range
40 to 70 Hz
Power Consumption (not including external power supply)
15 watts, typical
HSCT External Power Required
+24V ± 2% @ 0.75 A Nominal Over temperature
Outputs
Front Panel LEDS
OK LED
Indicates when the system is operating properly.
TX/RX LED
Indicates when the 3500/82 is communicating with other modules in the 3500 rack.
Bypass LED
Indicates when the 3500/82 is in Bypass Mode.
Buffered Outputs
The front of the monitor has eight coaxial BNC connectors for each of the HVS and HSCT outputs and average temperature output, and a phase reference pulse (Sync). Each connector is short-circuit protected. The output from all 8 BNCs is voltage proportional to the input signals.
Output Impedance
499 ±1%
Output Range HVS and HSCT Channels (6 BNCs)
Dynamic: 1.6 to 10.4V, ±5%. Bias: 6V ±5%.
Output Range Average Temperature Channel (1 BNC)
2.0 to 10.0V, ±5%, for -40 to 200 °C (default, but can be user configurable)
Output Range Sync (1 BNC)
Digital Pulse: 0 to 10.0V, ±5%.
Sensor Specifications
Parameters are specified from +20 °C to +30 °C (+68 °F to +86 °F) and at 50/60 Hz unless otherwise indicated.
Note: Operation outside these specified limits may result in a larger variation in readings from what is listed below, or a loss of machine monitoring all together.
Sensitivity
HSCT Output Sensitivity
3.3mV / mA nominal, each unit marked with its specific sensitivity ±1% Linearity: ±0.25%
Phase
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 2 of 13
Page 3
6° nominal, each unit marked with specific phase shift for that unit, ±0.5°. Linearity: ±0.5° Temperature impact on phase: +2° at minimum operating temperature,
-1° at maximum operating temperature.
Current
1.4 A peak to peak (sine wave) full­scale.
HVS Output
0.76mV / V ±5% 8 kVrms full-scale (line to neutral)
Interface Module Outputs
HSCT Interface Module Output
Gain: 3V/V
HVS Interface Module Output
Gain: 0.625V/V with 77 k source impedance
Temperature Interface Module Output
66.6 µA / °C ±2%. (default)
-40 to 200
°C full-scale (user
configurable)
Signal Conditioning in 3500/82 Monitor
HVS and HSCT
Overall Frequency Response
Direct
1 Hz to 8.5 kHz ±3.0 dB User configurable
1X Filter
50 or 60 Hz User configurable
Overall Accuracy Amplitude
±1% of full-scale, Typical
±2% of full-scale, Maximum
Phase
±1°, Typical ±2°, Maximum
Filter Quality High-Pass
2-pole (40 dB per decade)
Low-Pass
2-pole (40 dB per decade
Overall Accuracy
±1% of full-scale, Typical ±2% of full-scale, Maximum
Temperature
Overall Frequency Response
3 Hz -3.0 dB
Overall Accuracy
±1% of full-scale, Typical. ±2% of full-scale, Maximum.
Filter Quality Low-Pass
2-pole (40 dB per decade)
Overall Accuracy
±1% of full-scale, Typical. ±3% of full-scale, Maximum.
System Alert/Alarm Setting
Alarm Setpoints
The user can use software configuration to set Alert levels for each value measured by the monitor and Alarm setpoints for any values measured by the monitor. Alarms are adjustable from 0 to 100% of full-scale for each measured value.
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 3 of 13
Page 4
Alarm Time Delays
The user can program alarm delays using software as follows:
Alert & Danger
From 1 to 60 seconds in 1 second Intervals.
Note: Applies to temperature, voltage and current measurements. The 3500/82 system Alert/Alarms are for annunciation only and should not be used for machine protection.
Environmental Limits
Operating Temperature Range Transducers & Interface Modules
20 °C to +70 °C (-4 °F to +158 °F)
3500/82 Monitor
30 °C to +65 °C (-22 °F to +149 °F)
MTL and P+F Barriers
20 °C to +60 °C (-4 °F to +140 °F)
Storage Temperature Transducers / Interface Modules
40 °C to +85 °C (-40 °F to +185 °F)
3500/82 Monitor
40 °C to +85 °C (-40 °F to +185 °F)
MTL Barriers
40 °C to +80 °C (-22 °F to +149 °F)
P+F Barriers
25 °C to +70 °C (-13 °F to +158 °F)
Shock Survivability Transducers
100 g peak, maximum
Interface Modules
200 g peak, maximum
3500/82 Monitor
200 g peak, maximum
Relative Humidity
95% non-condensing (75% non-condensing for P+F barriers)
Magnetic Field Susceptibility
<500µV/gauss (50 gauss, 50-60Hz)
Transducers Common Mode Line Current
Up to 1,000A rms, nominal
Line Voltage
Up to 7.5kV
rms, nominal
Operating voltage less than 2kV has limitations from the HVS.
Physical
Monitor Module
Dimensions (Height x Width x Depth)
241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in)
Weight
0.97 kg (2.14 lb.)
I/O Module
Dimensions (Height x Width x Depth)
241.3 mm x 24.4 mm x 91.1 mm (9.50 in x 0.96 in x 3.90 in)
Weight
0.41 kg (0.91 lb.)
Rack Space Requirements Monitor Module
1 full-height front slot
I/O Module
1 full-height rear slot
HVS and HSCT Interface Modules Dimensions (Height x Width x Depth)
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 4 of 13
Page 5
See Figures 2 & 3
Weight
0.21 kg (0.46 lb.)
Signal Input Connector
2-pin circular Lemo (HVS) 3-pin circular Lemo (HSCT)
Power/Sig out Connector
5-pin spring compression
HSCT Overall Diameter
See Figure 4
Height
See Figure 4
Weight
4.2 kg (9.25 lb.)
Case Material
Aluminum
Connector
2-pin Mil-C- 26482
Polarity
Pin A = Positive Signal Pin B = Negative Signal
Mounting
Bracket Mount
HVS Dimensions (Height x Width x Depth)
See Figure 6
Weight
1.7kg (3.7lbs)
Integral Cable
22 AWG twisted shielded pair
Case Material
Epoxy
Polarity
Pin A = Positive Signal Pin B = Negative Signal
Mounting
Bracket Mount
Temperature Interface Module Dimensions (Height x Width x Depth)
See Figure 7
Weight
0.13 kg (0.28 lb.)
Mounting
DIN rail mount
Entity Parameters
The following parameters apply for both CSA-NRTL/C and ATEX approvals.
HVS and HSCT Channel Approval Parameters
MSIM Circuit Parameters
(PWR) = 28 V
V
max
= 60 mA
I
max
= 12 V
V
+/-SIG
= 10 mA
I
+/-SIG
(PWR) = 253
R
min
= 253
R
+/-SIG
Channel Parameters (entity)
(PWR) = 28 V
V
max
= 119 mA
I
max
(PWR) = 253
R
min
= 253
R
+/-SIG
Interface Module Circuit Parameters
(PWR) = 15 V
V
max
= 50 mA
I
max
= 12 V
V
+/-SIG
= 10 mA
I
+/-SIG
= 253
R
+/-SIG
Temperature Interface Module Approval Parameters
MSIM Circuit Parameters
= 15 V
V
SIG
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 5 of 13
Page 6
I
= 20 mA
SIG
= 100
R
SIG
Channel Parameters (entity)
= 15 V
V
sig
= 20 mA
I
sig
= 100
R
SIG
Interface Module Circuit Parameters
(PWR) = 35 V
V
max
= 200 mA
I
max
= 12 V
V
SIG
= 20 mA
I
SIG
Compliance and Certifications
EMC
Standards: EN 61000-6-2 Immunity for Industrial Environments EN 55011/CISPR 11 ISM Equipment EN 61000-6-4 Emissions for Industrial Environments
European Community Directives: EMC Directive 2004/108/EC
Electrical Safety
Standards: EN 61010-1
European Community Directives: 2006/95/EC Low Voltage
Hazardous Area Approvals (Sensors and Interface Modules)
North America
CSA Zone 2 / Class I, Division 2 CSA Zone 0 / Class I, Division 1 (when installed with barriers)
European/ATEX
ATEX Zone 0 (when installed with barriers)
For further certification and approvals information please visit the following website:
www.ge-mcs.com/bently
Ordering Considerations
General
The 3500/82 monitor requires 50% more power than other 3500 monitors. To prevent overloading the 3500 systems power budget on a full size rack, a blank slot is recommended for each 3500/82 monitor installed. 3500/82 Stator Insulation Monitors added to an existing 3500 Monitoring System, require the following (or later) firmware and software versions:
3500/82 Firmware
Version 1.00, or later, for approvals certification
3500/22M RIM Firmware
Revision 1.70 or later
3500 Rack Configuration Software
Version 4.9 or later
Hazardous Area Approvals (3500/82 Monitor)
North America
CSA Zone 2 / Class I, Division 2
European/ATEX
No approvals, must be installed in a non-
hazardous area.
3500/93 System Display Firmware
Version 3.0 or later
3500/94 VGA Display Firmware
Version 3.0 or later
System 1™ Software
Version 6.0 or later
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 6 of 13
Page 7
3500/91 & 3500/92
All Versions Supported
System Components
The following hardware components are required for a successful installation:
Three (3) 350820 High Sensitivity Current
Transformers (HSCTs)
Three (3) 350821 HSCT Interface Modules Three (3) 350825 HSCT Interface Cables A minimum of Two (2) 350822 High Voltage
Sensors (HVSs). Three (3) are recommended.
One (1) 350823 High Voltage Sensor Interface
Module for each 350822 ordered.
Three (3) barriers for each HSCT and HVS to be
installed. Applicable to Hazardous Area installations only.
One (1) 350824 RTD temperature convertor.
Three (3) are recommended.
One (1) 3500/82 Stator Insulation Monitor with
corresponding I/O module.
One (1) 181945 24 VDC 3.5A external power
supply for each 3500/82 monitor. Larger power supplies can be used to power multiple 3500/82 monitors. Consult the input power requirements when selecting a different power supply.
Ordering Information
Monitor
3500/82–AXX–BXX-CXX
A: I/O Module Type
0 1 MSIM I/O Module with Internal
Terminations
B: External Power Supply Option
0 0 Not Provided 0 1 24Vdc, 3.5A DIN Rail Mount
C: Agency Approval Option
0 0 None 0 1 CSA (Class 1, Zone 2 / Div 2)
HSCT
350820–AXX-BXX
A: Inner Diameter
0 1 Up to 7.5 kV*
Operating voltage less than 2kV has limitations from the HVS.
*
B: Agency Approval Option
0 0 No Approvals 0 4 CSA C/US Zone 2 / Div 2 0 5 Multi-Approvals Zone 0 / Div 1
HSCT Interface Module
350821–AXX-BXX
A: Mount configuration
0 0 Panel Mount 0 1 DIN Mount
B: Agency Approval Option
0 0 No Approvals 0 4 CSA C/US Zone 2 / Div 2 0 5 Multi-Approvals Zone 0 / Div 1
HSCT Cable
350825-AXX
A: Cable Length
0 5 5 meters
HVS
350822–AXX-BXX
A: Voltage Divider
0 1 15 kV Full Scale Range
B: Agency Approval Option
0 4 CSA C/US Zone 2 / Div 2 0 5 Multi-Approvals Zone 0 / Div 1
HVS Interface Module
350823-AXX-BXX
A: Mount configuration
0 0 Panel Mount 0 1 DIN Mount
B: Agency Approval Option
0 0 No Approvals 0 4 CSA C/US Zone 2 / Div 2 0 5 Multi-Approvals Zone 0 / Div 1
Temperature Interface Module
350824–AXX
A: Preconfigured Temperature Range & Sensor Type
0 1 -40 °C to +200 °C
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 7 of 13
Page 8
(-40 °F to +392 °F) 3-wire 100 PT RTD
Barriers
Barriers are required to protect the HSCT and HVS when installing them in Zone 0 hazardous areas. Barriers are installed between the 3500/82 monitor and the HSCT/HVS interface modules. There are 3 barriers required for each sensor, 1 barrier for power, and 2 for signal (SIG + and SIG -).
MTL Barriers
100M1770
MTL 7715+ safety barrier for signal
100M1771
MTL 7728P+ safety barrier for power
For further information on these MTL barriers, please visit the following website:
http://www.mtl-inst.com/product/mtl7700_series_barriers/
Pepperl+Fuchs Barriers
100M5332
P+F Z715+ safety barrier for signal
100M5333
P+F Z779.H safety barrier for power
For further information on these P+F barriers, please visit the following website:
http://www.pepperl-fuchs.com/global/en/classid_2414.htm
Spares
100M2907-01
3500/82 Stator Insulation Monitor
324197-01
MSIM I/O Module
181945
28 Vdc 3.5A Power Supply (Din Rail Mount)
100M1761
Base unconfigured MTL5575 temperature isolator. Requires 143324-01 to configure.
102M0274-01
3500/82 Stator Insulation Monitor Manual
Field Wiring Considerations
4 wire shielded 18 AWG shielded cable.
02171490
Belden 89418
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 8 of 13
Page 9
Graphs and Figures
1
6
7
2
8
3
9
4
5
1. 3500/82 Monitor (front view)
2. Status LEDs
3. Buffered Transducer Outputs (HSCT & HVS)
4. Buffered Transducer Output (Average Temperature)
5. Buffered Transducer Output (Phase Synchronization)
6. MSIM I/O Module
7. External 28 Vdc Power Input
8. HVS Inputs
9. HSCT Inputs
10. Temperature Inputs (4-20 mA)
10
Figure 1: 3500/82 Stator Insulation Monitor and I/O Module
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 9 of 13
Page 10
1. 350821/350823 Mounting Option AXX = 00
Figure 2: Panel Mount HSCT/HVS Interface Module
1. 350821/350823 Mounting Option AXX = 01
2. 35mm DIN rail (Not Included)
3. Additional 3 mm [0.120 in] required to remove from DIN rail.
Figure 3: DIN Rail Mount HSCT/HVS Interface Module
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 10 of 13
Page 11
7.5 kV HIGH SENSITIVITY CURRENT TRANSFORMER
Figure 4: High Sensitivity Current Transformer
Note: Dimensions above represents AXX option = 01.
3
1
2
350825-05 REV -
4
5
1. 300V, 105°C, 22 AWG twisted shielded pair PVC cable
2. 5.5 mm [0.216 in] maximum diameter
3. MIL-C-26482 circular connector (connects to HSCT)
4. LEMO 3-pin circular connector (connects to the HSCT interface module)
5. Cable Length = 5 +/- 0.2 meters
Figure 5: HSCT Interface Cable
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 11 of 13
Page 12
4
3
2
11 kV RMS HIGH VOLTAGE SENSOR (HVS)
EARTH (GROUND) TERMINAL
HIGH VOLTAGE TERMINAL
1
1. ¼-20 High Voltage Terminal
2. 3/8-16 Earth Ground Terminal
3. 300V, 105°C, 22 AWG twisted shielded pair PVC cable (4.5 meters)
4. LEMO 2-pin circular connector (connects to the HVS interface module)
Figure 6: High Voltage Sensor
This terminal is an electrically isolated mounting terminal on the intrinsically safe HVS. Consult field wiring drawing
100M5071 for important grounding requirements for hazardous area installations.
1. Top of DIN rail
2. 35mm DIN rail (Not Included)
Figure 7: Temperature Interface Module
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 12 of 13
Page 13
*Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Company.
© 2012 - 2014 Bently Nevada, Inc. All rights reserved.
Printed in USA. Uncontrolled when transmitted electronically.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1-775.782.3611 Fax: 1-775.215.2873
www.ge-mcs.com/bently
Specifications and Ordering Information
Part Number 323735-01
Rev. C (07/14)
Page 13 of 13