Bently Nevada 3500/72M Data sheet

Page 1
3500/72M Recip Rod Position Monitor
Datasheet
Bently Nevada Machinery Condition Monitoring

Description

The four-channel 3500/72M Recip Rod Position Monitor accepts input from proximity transducers, conditions the signal to provide dynamic and static position measurements, and compares the conditioned signals with user­programmable alarms.
Each channel, depending on how you configure it, typically conditions its input signal to generate various parameters called measured values.
Use the 3500 Rack Configuration Software to:
l Configure alert setpoints for each active measured
value and danger setpoints for any two of the active measured values.
l Protect reciprocating compressors by continuously
comparing monitored parameters against configured alarm setpoints to display alarms and trigger relays, if needed.
l Monitor the condition of essential reciprocating
compressor machinery.
146478 Rev. H
The monitor channels are programmed in pairs and can perform up to two functions at a time. For example, channels 1 and 2 can perform one function while channels 3 and 4 perform another or the same function.
The 3500/72M Recip Rod Position Monitor meets API 618 requirements for reciprocating compressors. It measures:
l Rod position l Rod drop l Hyper-compressor
Page 2
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
Data Values
The 3500/72M Recip Rod Position Monitor

Specifications

returns the following data values from measurements used to monitor the machine:
Inputs
Signal
Input Impedance 10 kΩ
Nominal Scale Factor
Rod Position
Rod Position 2
Rod Drop
Hyper Compressor
Power Consumption
Accepts from 1 to 4 proximity probe signals
0.79 mV/µm (20 mV/mil),
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
7.7 watts, nominal
Outputs
Front Panel LEDs
Indicates when the Recip Rod
OK LED
TX/RX LED
Bypass LED
Front Buffered Outputs
Buffered Transducer Outputs
Output Impedance
Transducer Power Supply
Position Monitor is operating properly.
Indicates when the Recip Rod Position Monitor is communicating with other modules in the 3500 rack.
Indicates when the Recip Rod Position Monitor is in Bypass Mode.
The front of each monitor has one coaxial connector for each channel.
Each connector is short-circuit protected.
510 Ω
-24 Vdc
Rod Position Single Channel
Rod Position Single 2 Channel
Rod Position Pair Channel
Rod Position Pair 2 Channel
Rod Drop Channel
Hyper Channel
Position Magnitude, Position Angle, Crank Angle, Pk-Pk Amplitude, Gap, 1X Amplitude, Not 1X Amplitude, 2X Amplitude
Pk-Pk Amplitude Position Magnitude Position Angle Crank Angle Gap Average Piston Position Instantaneous Piston Position Instantaneous Probe Gap
Position Magnitude, Position Angle, Crank Angle, Pk-Pk Amplitude, Gap, 1X Amplitude, Not 1X Amplitude, 2X Amplitude
Pk-Pk Amplitude Position Magnitude Position Angle Crank Angle Gap Average Piston Position Instantaneous Piston Position Instantaneous Probe Gap
Average Piston Position, Average Probe Gap, Instantaneous Piston Position, Instantaneous Probe Gap
Pk-Pk Displacement, Gap, 1X Amplitude, Not 1X Amplitude, 2X Amplitude
2/11
Page 3
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
Signal Conditioning
Specified at +25 ºC (+77 ºF) unless otherwise noted.
Rod Position 2 (Single and Pair) Channels
Frequency Response
Peak-Peak filter Fixed 1 Hz to 600 Hz Gap filter -3 dB at 0.09 Hz Average piston
position
Accuracy
Peak-Peak Amplitude
Position magnitude
Rod Position Angle (paired only)
Position Crank Angle
Gap
Average piston position
Instantaneous piston position
Instantaneous piston gap
Rod Position Single and Pair Channels
Peak-Peak filter Fixed 1 Hz to 600 Hz Gap filter -3 dB at 0.09 Hz
Not 1X filter
1X and 2X vector filter
Fixed 1 Hz to 600 Hz
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±1° typical ±3° maximum
Within ±1° typical ±3° maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Frequency Response
Constant Q Notch filter Minimum rejection in stop-band of 34.9 dB over frequency range of 60 cpm to 15.8 times running speed
Constant Q Filter Minimum rejection in stopband
Frequency Response
of 57.7 dB
1X and 2X Vector and Not 1X parameters are valid for machine speeds of 60 cpm to 2130 cpm.
Accuracy
Position magnitude (direct)
Gap
1X Amplitude
2X Amplitude
Pk-Pk Amplitude
Not 1X Amplitude Within ±3.0% of full scale typical Position Crank
Angle Rod Position
Angle (paired only)
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±1° typical ±3° maximum
Within ±1° typical ±3° maximum
Rod Drop Channels
Frequency Response
Average piston position (direct)
Average Gap -3 dB at 0.09 Hz
Accuracy
Average piston position (direct)
Average Gap
Instantaneous piston position
Instantaneous probe Gap
Fixed 1 Hz to 600 Hz
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
3/11
Page 4
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
Hyper Channels
Frequency Response
Peak-Peak filter Fixed 1 Hz to 600 Hz Gap filter -3 dB at 0.09 Hz
Constant Q Notch filter Minimum rejection in stop-band
Not 1X filter
1X Vector filter
2X Vector filter
of 34.9 dB over frequency range of 60 cpm to 15.8 times running speed
Constant Q filter Minimum rejection in stop-band of 57.7 dB
Constant Q filter Minimum rejection in stop-band of 57.7 dB
1X and 2X Vector and Not 1X parameters are valid for machine speeds of 60 cpm to 2130 cpm.
Accuracy
Peak-Peak magnitude
Gap
1X Amplitude
2X Amplitude
Not 1X Amplitude
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical ±1% maximum
Within ±0.33% of full-scale typical
Physical
Monitor Module (Main Board)
Dimensions (Height x Width x Depth)
Weight 0.91 kg (2.0 lb)
I/O Modules (non-barrier)
Dimensions (Height x Width x Depth)
Weight 0.20 kg (0.44 lb)
241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in)
241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
Monitor Module (Main Board)
I/O Modules (barrier)
Dimensions (Height x Width x Depth)
Weight 0.46 kg (1.01 lb)
241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42 in)
Rack Space Requirements
Monitor 1 full-height front slot I/O Modules 1 full-height rear slot
Environmental Limits
When used with Internal / External Termination Proximitor / Seismic I/O Module:
-30°C to +65°C
Operating Temperature
Storage Temperature
Humidity
(-22°F to +149°F)
When used with Proximitor / Seismic Internal Barrier I/O Module (Internal Termination) 0°C to +65°C (32°F to +149°F)
-40°C to +85°C (-40°F to +185°F)
95% Non-condensing
Alarms
Use Rack Configuration Software to set alert levels for each value measured by the monitor and danger setpoints for any two of the values measured by the monitor.
Alarm Setpoints
Accuracy of alarm setpoints
Alarms are adjustable from 0 to 100% of full-scale for each measured value. However, when the full-scale range exceeds the range of the transducer, the range of the transducer will limit the setpoint.
Within 0.13% of the desired value
Alarm Time Delays
You can program alarm delays using 3500 Rack Configuration Software.
Alert
From one to 60 seconds in one second intervals
4/11
Page 5
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
0.1 seconds (nominal) or from
Danger
Timed OK Channel Defeat
one to 60 seconds in one second intervals
OK Channel defeat is disabled for all Rod Position and Rod Drop configurations.
As a hyper-compressor monitor, when both transducers are NOT OK, the monitor issues a Danger alarm immediately.

Compliance and Certifications

FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including interference that may cause undesired operation.
EMC
European Community Directive:
EMC Directive 2014/30/EU
Standards:
EN 61000-6-2 Immunity for
Industrial Environments
EN 61000-6-4 Emissions for
Industrial Environments
Electrical Safety
European Community Directive:
LV Directive 2014/35/EU
Standards:
EN 61010-1
RoHS
European Community Directive:
RoHS Directive 2011/65/EU
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships, Offshore Units, and High Speed and Light Craft
5/11
Page 6
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H

Hazardous Area Approvals

For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from
Bently.com.
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc;
When used with I/O module ordering options without internal barriers
When used with I/O module ordering options with internal barriers
Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D;  T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing 149243 or 149244.
Class I, Zone 2: AEx/Ex nA nC ic [ia Ga] IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic [ia Ga] IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D (W/ IS Output for Division
1)  T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing
138547.
ATEX/IECEx
When used with I/O module ordering options without internal barriers
When used with I/O module ordering options with internal barriers
II 3 G 
Ex nA nC ic IIC T4 Gc; Ex ec nC ic IIC T4 Gc;  T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing 149243 or 149244.
II 3(1) G
Ex nA nC ic [ia Ga] IIC T4 Gc; Ex ec nC ic [ia Ga] IIC T4 Gc;
T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing
138547.
6/11
Page 7
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H

Ordering Considerations

l For I/O Modules with External
Terminations, order the External Termination Blocks and cable separately for each I/O Module.
l For Internal Barriers, refer to the 3500
Internal Barrier Datasheet (document
141495).
l The Recip Rod Position Monitor requires
version 3.20 or higher of the 3500 Rack Configuration Software.
l Rod Position Single 2 and Rod Position
Pair 2 channel types require Rack Config release 6.0 or later.
The lower limit for machine speed is 60 RPM in the standard product. For machine speeds down to 30 RPM, modification 135M8199-01 is required.

Ordering Information

For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from
Bently.com.
Rod Position Monitor 3500/72M - AA-BB

External Termination Blocks

Part Number Description
Proximitor / Velomitor External
125808-08
128015-08
128702-01
128710-01
Cables
3500 Transducer (XDCR) to External Termination (ET) Block Cable 129525 - AAAA-BB
A: I/O Cable Length 0005 5 feet (1.5 metres) 0007 7 feet (2.1 metres) 0010 10 feet (3.0 metres) 0025 25 feet (7.6 metres) 0050 50 feet (15.2 metres) 0100 100 feet (30.5 metres) B: Assembly Instructions 01 Not Assembled 02 Assembled
Termination Block Euro Style connectors
Proximitor / Velomitor External Termination Block Terminal Strip Connectors
Recorder External Termination Block Euro Style Connectors
Recorder External Termination Block Terminal Strip Connectors
A: I/O Module Type 01 I/O Module with Internal Terminations 02 I/O Module with External Terminations
I/O Module with Internal Barriers and Internal
03
Terminations
B: Hazardous Area Approval Option 00 None 01 CSA/NRTL/C (Class 1, Division 2)
ATEX/IECEx/CSA (Class 1, Zone 2)
02
3500 Recorder Output to External Termination (ET) Block Cable 129529 - AAAA-BB
A: I/O Cable Length 0005 5 feet (1.5 metres) 0007 7 feet (2.1 metres) 0010 10 feet (3.0 metres) 0025 25 feet (7.6 metres) 0050 50 feet (15.2 metres) 0100 100 feet (30.5 metres) B: Assembly Instructions
7/11
Page 8
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
01 Not Assembled 02 Assembled
Spares
Part Number Description
176449-08
140471-01
00580434
140482-01
135489-01
00580441
00502133
146479-01
3500/72M Recip Rod Position Monitor
I/O Module with Internal Terminations
Internal I/O Module connector header Euro Style, 8-pin, green Used with I/O modules 140471-01
I/O Module with External Terminations
I/O Module with Internal Barriers and Internal Terminations
Internal I/O Module connector header Euro Style, 3-pin, green Used with I/O modules 135489­01 and 140471-01
Internal I/O Module connector header Euro Style, 12 pin, blue Used with I/O modules 135489­01
3500/72M Recip Rod Position Monitor User Manual
8/11
Page 9
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H

Graphs and Figures

Figure 1: Legacy Front and Rear Views of 3500/72M Recip Rod Position Monitor
1. 3500/72M Front View 2. Status LEDs 3. Buffered Transducer Outputs 4. I/O Modules Rear Views 5. Barrier I/O Module, Internal Termination 6. I/O Module, Internal Termination
7. I/O Module, External Termination
9/11
Page 10
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
Figure 2: Updated Rear View of 3500/72M I/O Modules
The I/O modules with internal or external terminations have the same jumpers.
10/11
Page 11
3500/72M Recip Rod Position Monitor Datasheet 146478 Rev. H
Copyright 2020 Baker Hughes Company. All rights reserved.
Bently Nevada, Orbit Logo, Velomitor and Proximitor are registered trademarks of Bently Nevada, a Baker Hughes Business, in the United States and other countries. The Baker Hughes logo is a trademark of Baker Hughes Company. All other product and company names are trademarks of their respective holders. Use of the trademarks does not imply any affiliation with or endorsement by the respective holders.
Baker Hughes provides this information on an “as is” basis for general information purposes. Baker Hughes does not make any representation as to the accuracy or completeness of the information and makes no warranties of any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and fitness for a particular purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect, consequential or special damages, claims for lost profits, or third party claims arising from the use of the information, whether a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make changes in specifications and features shown herein, or discontinue the product described at any time without notice or obligation. Contact your Baker Hughes representative for the most current information.
The information contained in this document is the property of BakerHughes and its affiliates; and is subject to change without prior notice. It is being supplied as a service to our customers and may not be altered or its content repackaged without the express written consent of Baker Hughes. This product or associated products may be covered by one or more patents. See Bently.com/legal.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 or 1.800.227.5514 (US only)
Bently.com
11/11