The 3500/65 monitor provides 16 channels of temperature
monitoring and accepts both resistance temperature
detector (RTD) and isolated tip thermocouple (TC)
temperature inputs. The monitor conditions these inputs and
compares them against user-programmable alarm
setpoints.
The monitor is programmed using the 3500 Rack
Configuration Software. You can configure the 16-Channel
Temperature Monitor to accept isolated tip thermocouples,
3-wire RTD, 4-wire RTD, or a combination of TC and RTD inputs.
In Triple Modular Redundant (TMR) configurations, you must
install temperature monitors in groups of 3 adjacent
monitors. In this configuration the monitor uses 2 types of
voting to ensure accurate operation and to avoid singlepoint failures.
172930 Rev. J
Page 2
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Platinum RTDs with α = 0.00385 are the
Specifications
Inputs
worldwide industrial standard and are
the recommended RTDs for all
applications.
Power
Consumption
Signal Accepts from 1 to 16 RTD or
Input
Impedance
3 watts nominal
isolated tip TC transducer
signals.
Greater than 1 MΩ for each
lead input.
Transducers
TCs
Type E
Type J
Type K
Type T
-100°C to +1000°C,
(-148°F to +1832°F)
0°C to +760 °C
(32°F to +1400 °F)
0°C to +1370°C
(32°F to +2498°F)
-160°C to +400°C,
( -256°F to +752°F)
Outputs
Front Panel LEDs
OK LEDIndicates when the 3500/65 is
operating properly.
TX/RX LEDIndicates when the 3500/65 is
communicating with other
modules in the 3500 rack.
Bypass LED Indicates when the 3500/65
monitor is in Bypass Mode.
RTD
CurrentSource
Value
913 ± 7 µA @ 25°C per transducer
(1 supply for the 4-wire RTD and
2 supplies for the 3-wire).
Signal Conditioning
Specified at +25°C (+77° F). Full-scale
range for each channel is set in the field
via 3500 Configuration Software. No
calibration is required
RTDs
100 Ω 3-wire and
4-wire platinum
RTD (α =
0.00385)
100 Ω 3-wire and
4-wire platinum
RTD (α =
0.00392)
120 Ω 3-wire and
4-wire nickel
RTD
10 Ω 3-wire and
4-wire copper
RTD
-200°C to +850°C
(-328°F to +1562°F)
-200°C to +700°C
(-328°F to +1292°F)
-80°C to +260°C
(-112°F to +500°F)
-100°C to +260°C,
(-148°F to +500°F)
RTDs and TCs
Resolution 1°C or 1 °F.
Accuracy
Internal
Termination
External
Termination
Bulkhead Rack: ±3°C at +25°C
(±5.4°F at +77°F).
Standard Rack: ±3°C at +25°C
(±5.4°F at +77°F).
Bulkhead Rack: ±3°C at +25°C
(±5.4°F at +77°F)
Standard Rack: ±3°C at +25°C
(±5.4°F at +77°F)
Cold Junction Compensation
Sensor (used for TC
measurements) ±2°C at +25°C
(±3.6°F at +77°F).
2/8
Page 3
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Alarms
Alarm
Setpoints
Alarm
Time
Delays
Alert
Delay
Danger
Delay
You can use software
configuration to set Alert and
Danger setpoints for the value
measured by the monitor. Alarms
are adjustable from 0 to 100% of
full-scale for each measured
value. The exception is when the
full-scale range exceeds the range
of the sensor. In this case,
software will limit the setpoint to
the range of the sensor. Accuracy
of alarms are to within 0.13% of the
desired value. The 3500/65 16channel temperature monitor has
both under- and over-alarm
setpoints.
You can use software to program
alarm delays as follows:
From 1 to 60 seconds in 1-second
increments.
From 1 to 60 seconds in 0.5second increments or set to the
minimum alarm delay of 225 mS.
Proportional Values
Proportional values are temperature
measurements used to monitor the machine.
The 16-channel temperature monitor returns
temperature proportional values.
Environmental Limits
Operating
Temperature:
Storage
Temperature:
-30°C to +65°C (-22°F to
+150°F)
-40°C to +85°C (-40°F to
+185°F)
Physical
Main Module
Dimensions
(Height x
Width x
Depth)
Weight0.91 kg (2.0 lbs.).
I/O Modules
Dimensions
(Height x
Width x
Depth)
241.3 mm x 24.4 mm x 241.8 mm
(9.50 in x 0.96 in x 9.52 in)
241.3 mm x 24.4 mm x 99.1 mm
(9.50 in x 0.96 in x 3.90 in)
Weight0.45kg (1.0 lb.).
Rack Space Requirements
Main
Module
I/O Modules 1 full-height rear slot
1 full-height front slot
3/8
Page 4
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Hazardous Area Approvals
Compliance and
Certifications
FCC
This device complies with part 15 of the
FCC Rules. Operation is subject to the
following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including
interference that may cause
undesired operation.
EMC
European Community Directive:
EMC Directive 2014/30/EU
Standards:
EN 61000-6-2 Immunity for
Industrial Environments
EN 61000-6-4 Emissions for
Industrial Environments
Electrical Safety
European Community Directive:
For the detailed listing of country and
product specific approvals, refer to the
Approvals Quick Reference Guide
(108M1756) available from Bently.com.
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC T4
Gc;
Class I, Zone 2: AEx/Ex ec nC ic IIC T4
Gc;
Class I, Division 2, Groups A, B, C,
and D;
T4 @ Ta= -20˚C to +65˚C (-4˚F to
+149˚F)
When installed per drawing 149243
or 149244.
ATEX/IECEx
II 3 G
Ex nA nC ic IIC T4 Gc
Ex ec nC ic IIC T4/T5 Gc
T4 @ Ta= -20˚C to +65˚C
(-4˚F to +149˚F)
When installed per drawing 149243
or 149244.
LV Directive 2014/35/EU
Standards:
EN 61010-1
RoHS
European Community Directive:
RoHS Directive 2011/65/EU
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships,
Offshore Units, and High Speed and Light
Craft
4/8
Page 5
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Ordering Considerations
If you add the 3500/65 to an existing 3500
System your system will require the following or
later firmware and software versions:
3500/22 Module FirmwareRevision 1.50
3500/01 SoftwareVersion 3.85
3500/02 SoftwareNot supported*
3500/03 SoftwareNot supported*
3500/93 Module Firmware
System 1 SoftwareRevision 5.2
*Attempting to use the 3500/65 with
3500/02 or 3500/03 software may
prevent proper operation of the
software.
You cannot use external termination blocks
with internal termination I/O modules.
When ordering I/O Modules with external
terminations, you must order the external
termination blocks and cables separately.
When ordering I/O Modules for use with 4-Wire
RTDs, order with Modification 179952-01. For
further information, see the 3500/65 User Guide.
This will result in an I/O Module Mismatch
and 562 ADC Failure in the System Event
List.
Revision 2.02
with Service
Pack 2 or later
Ordering Information
For the detailed listing of country and
product specific approvals, refer to the
Approvals Quick Reference Guide
(108M1756) available from Bently.com.
3500/65-AA-BB
A: I/O Module Type
01
02RTD/Isolated Tip TC with External
B: Agency Approval Option
00
01CSA/NRTL/C
02CSA/ATEX
RTD/Isolated Tip TC with Internal
Terminations
Terminations
None
Agency Approval Option B 02 is only
available with Ordering Option A 01.
External Termination Block
172115-01RTD/Isolated Tip TC External
Termination Block (Euro Style
connectors).
5/8
Page 6
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Cables
Spares
3500/65 Transducer (XDCR) Signal to
External Termination (ET) Block Cable
134544-AAAA-BB
A: Cable Length
Part
Number
172931
145988-02
Description
3500/65 User Guide
3500/65 Monitor
00055 feet (1.5 metres)
00077 feet (2.1 metres)
001010 feet (3 metres)
002525 feet (7.5 metres)
005050 feet (15 metres)
0100
B: Assembly Instructions
01Not Assembled
02Assembled
100 feet (30.5 metres)
172103-01
173005
172109-01
172115-01
When replacing an older I/O module
with a newer one,172109-01 Rev D, 17210301 Rev F, 172115-01 Rev E, or future
revisions; it is necessary to upgrade the
firmware to the monitor with the latest
released version. You must remove the
I/O module before upgrading the
monitor to the latest firmware. Failure to
do this will result in an I/O Module
Mismatch and 562 ADC Failure in the
System Event List.
3500/65 RTD/Isolated Tip TC I/O
Module, Internal Terminations
Connector Header, Internal
Termination, 20-position, Black
3500/65 RTD/ Isolated Tip TC I/O
Module, External Terminations
RTD/Isolated Tip TC External
Termination Block (Euro Style
Connectors) Specifications
6/8
Page 7
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Graphs and Figures
1. Status LEDs.
2. 3500/65 16 Channel Temperature Monitor
3. Ethernet 10BASE-T/100BASE-TX I/O Module
4. Ethernet 100BASE-FX I/O Module
Figure 1: Front and rear views of the 3500/65 16 Channel Temperature Monitor
7/8
Page 8
3500/65 Channel Temperature Monitor
Datasheet172930 Rev. J
Copyright 2020 Baker Hughes Company. All rights reserved.
Bently Nevada and Orbit Logo are registered trademarks of Bently Nevada, a Baker Hughes Business, in the United
States and other countries. The Baker Hughes logo is a trademark of Baker Hughes Company. All other product and
company names are trademarks of their respective holders. Use of the trademarks does not imply any affiliation
with or endorsement by the respective holders.
Baker Hughes provides this information on an “as is” basis for general information purposes. Baker Hughes does
not make any representation as to the accuracy or completeness of the information and makes no warranties of
any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and
fitness for a particular purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect,
consequential or special damages, claims for lost profits, or third party claims arising from the use of the
information, whether a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make
changes in specifications and features shown herein, or discontinue the product described at any time without
notice or obligation. Contact your Baker Hughes representative for the most current information.
The information contained in this document is the property of BakerHughes and its affiliates; and is subject to
change without prior notice. It is being supplied as a service to our customers and may not be altered or its content
repackaged without the express written consent of Baker Hughes. This product or associated products may be
covered by one or more patents. See Bently.com/legal.