Bently Nevada 3500/60 Data sheet

3500/60 and 3500/61 Temperature Modules
Datasheet
Bently Nevada Machinery Condition Monitoring

Description

The 3500/60 & 61 modules provide six channels of temperature monitoring and accept both Resistance Temperature Detector (RTD) and Thermocouple (TC) temperature inputs. The modules condition these inputs and compare them against user-programmable alarm setpoints. The 3500/60 and 3500/61 provide identical functionality except that the 3500/61 provides recorder outputs for each of its six channels while the 3500/60 does not.
The user programs the modules to perform either RTD or TC temperature measurements using the 3500 Rack Configuration Software. Different I/O modules are available in RTD/TC non-isolated or TC isolated versions. The user can configure the RTD/TC non-isolated version to accept either TC or RTD, or a mixture of TC and RTD inputs. The TC isolated version provides 250 Vdc of channel-to-channel isolation to protect against external interference.
When used in a Triple Modular Redundant (TMR) configuration, temperature monitors must be installed adjacent to each other in groups of three. When used in this configuration, the system employs two types of voting to ensure accurate operation and to avoid single-point failures.
141540 Rev. L
3500/60 and 3500/61 Temperature Modules Datasheet 141540 Rev. L

Specifications

Inputs
Signal Accepts from 1 to 6 RTD or TC
transducer signals.
Input Impedance
Power Consumption
3500/60 Nominal consumption of 7
3500/61 Nominal consumption of 9
Tranducers
TCs
Type E -100 °C to +1000 °C, (-148 °F to
When using any of the isolated thermocouple I/O modules (-03 or -04 I/O ordering option) with Type E thermocouples, the available full-scale range will be reduced if the 3500 system is operated in an ambient temperature above +35C. The reduced range will be -60C to +1000C (-76F to +1832F). Rack configuration software will allow the user to configure a channel down to -100C but the system will not function properly in this scenario and therefore should not be configured to operate with these settings.
Type J -18 °C to +760 °C, (+0 °F to +1400
Type K -18 °C to +1370 °C, (+0 °F to
10 MΩ for each lead input.
watts.
watts.
+1832 °F).
°F).
+2498 °F)
100Ω 3-wire & 4-wire platinum RTD (alpha = 0.00385)
100Ω 3-wire & 4-wire platinum RTD (alpha = 0.00392)
120Ω 3-wire & 4-wire nickel RTD
10Ω 3-wire & 4-wire copper RTD
I/O Modules
Isolated I/O Module
-200° C to +850° C
(-328 °F to +1562 °F).
With external barriers:
-50 °C to +850 °C
(-122 °F to +1562 °F).
-200 °C to +700 °C
(-328 °F to +1292 °F).
With external barriers:
-50 °C to +260 °C
(-122 °F to + 1292 °F).
-80 °C to +260 °C
(-112 °F to +500 °F).
With external barriers:
-50 °C to +260 °C
(-122 °F to + 500 °F).
-100 °C to +260 °C,
(-148 °F to +500 °F).
With external barriers:
-50 °C to +260 °C
(-122 °F to +500 °F).
Platinum RTD's with
0.00385 alphas are the worldwide industrial standard and are recommended for all applications
System Isolation: 500Vdc Channel to Channel Isolation: 250 Vdc
.Type T -160 °C to +400 °C, (-256 °F to
+752 °F).
RTDs
Isolation is only required for fault scenarios and these voltages will not be present on
2/13
3500/60 and 3500/61 Temperature Modules Datasheet 141540 Rev. L
the I/O module inputs when a wiring or field fault occurs.
Outputs
Front Panel LEDs
OK LED Indicates when the
Temperature Monitor is operating properly.
TX/RX LED Indicates then the Temperature
Monitor is communicating with other modules in the 3500 rack.
Bypass LED Indicates when the
Temperature Monitor is in Bypass Mode.
RTD Current Source Value
925 ±15 µA @ 25° C per transducer (single supply for the 4-wire RTD and two supplies for the 3-wire).
Recorder
+4 to +20 mA. Values are proportional to monitor full-scale. Individual recorder values are provided for each channel. Monitor operation is unaffected by short circuits on recorder outputs.
RTDs and TCs (except for 10Ω Copper RTDs)
Resolution 1 °C or 1 °F
Accuracy
Internal Termination Non­Isolated
Bulkhead Rack
Standard Rack
±3 °C at 25 °C
(±5.4 °F at 77 °F).
±3 °C at 25 °C
(±5.4 °F at 77 °F).
External Termination Non-Isolated
Bulkhead Rack
Standard Rack
±3 °C at 25 °C
(±5.4 °F at 77 °F).
±1 °C at 25 °C
(±1.8 °F at 77 °F).
Internal Termination Isolated
Bulkhead Rack
±2 °C at 25 °C
(±3.6 °F at 77 °F).
Voltage Compliance (current output)
0 to +12 Vdc range across load. Load resistance is 0 to 600 Ω.
Resolution
0.3662 µA per bit ±0.15% error at room temperature ±0.4% error over temperature range.
Signal Conditioning
Specified at +25 °C (+77 °F) unless otherwise noted.
Full-scale range for each
channel is set in the field via 3500 Configuration Software. No calibration is required.
±3 °C at 25 °C
±5.4 °F at 77 °F).
Standard Rack
±3 °C at 25 °C
±5.4 °F at 77 °F).
External Termination Isolated
Bulkhead Rack
Standard Rack
±1 °C at 25 °C
(±1.8 °F at 77 °F).
°C at 25 °C (±1.8 °F at 77 °F)
10 Ω Copper RTDs
Resolution 1°C or 1 °F
Accuracy ±3 °C at 25 °C
3/13
3500/60 and 3500/61 Temperature Modules Datasheet 141540 Rev. L
(±5.4 °F at 77 °F).
Cold Junction Compensation Sensor (used for TC measurements)
Accuracy
±1° C at 25 °C
(±1.8 °F at 77 °F).
Alarms
Alarm Setpoints
Alarm Time Delays
The user can program alarm delays using software as follows:
Alert From 1 to 60 seconds in 1 second
The user can set Alert and Danger setpoints for the value measured by the monitor using software configuration. Alarms are adjustable from 0 to 100% of full-scale for each measured value. The exception is when the full-scale range exceeds the range of the sensor. In this case, the range of the sensor will limit the setpoint. Accuracy of alarms are to within 0.13% of the desired value. The Temperature Monitors have both under and over alarm setpoints.
intervals.
Danger From 1 to 60 seconds in 0.5
second intervals
Measured Values
Measured values are temperature measurements used to monitor the machine. The Temperature Monitors return temperature measured values.