Bently Nevada 3500/46M Data sheet

3500/46M Hydro Monitor
Datasheet
Bently Nevada Machinery Condition Monitoring

Description

The 3500/46M Hydro Monitor is a four-channel instrument that accepts input from proximity, seismic, dynamic pressure and air gap sensors. The monitor conditions the signal to provide vibration, position and both static and dynamic pressure measurements. It then compares the conditioned signals with user-programmable alarms. Hydro Radial Vibration channels combine the shaft gap movement with the NX amplitude to provide a measurement to alarm on shear-pin failure.
Using the 3500 Rack Configuration Software, you can configure the 3500/46M Hydro Monitor to perform the following functions:
l Hydro Radial Vibration l Hydro Air Gap l Hydro Velocity l Hydro Acceleration l Hydro Thrust l Multimode Hydro RV l Multimode Air Gap l Multimode Hydro Velocity l Multimode Thrust l Multimode Acceleration l Multimode Hydro Dynamic Pressure l Hydro Stator End Winding (SEW)
144408 Rev. Y
The monitor channels are programmed in pairs. Each channel may have separate or identical configurations.
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
The primary purpose of the 3500/46M Hydro Monitor is to provide the following:
l Machinery protection by continuously
comparing monitored parameters against configured alarm setpoints to drive alarms
l Essential machine information for
operations and maintenance personnel
Hydro Velocity channels provide early warning of pending machinery problems and assist in diagnosing them. Due to the nature of high amplitude, low frequency velocity events, the Hydro Velocity channel type cannot be used for automated machinery protection.
Each channel, depending on configuration, typically conditions its input signal to generate various parameters called static values. You can configure alert setpoints for each active static value and danger setpoints for any two of the active static values.
You can configure multimode channels to have up to eight sets of alarm parameters including alert and danger set points and alarm time delays. Each set may be configured for a specific machine mode.
As the machine changes modes, the monitor can switch to a specific set using contacts on multimode I/O modules or software commands through a communications gateway.
2/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Hydro SEW 10.19 mV/m/s2 (100 mV/g)

Specifications

Inputs
Signal
Accepts 1 to 4 proximity, air gap, velocity or acceleration sensor signals
Multimode Hydro Dynamic Pressure
Outputs
Refer to the Bently Nevada 350300 Dynamic Pressure Sensor datasheet, document 110M4613
Power consumption
Multimode positive input I/O
Input Impedance
Prox/Velom I/O and Multimode Prox/Velom I/O
Sensitivity
Hydro Radial Vibration and Multimode Hydro RV
Hydro Air Gap and Multimode Air Gap
Hydro Velocity and Multimode Hydro Velocity
Hydro Thrust and Multimode Thrust
Hydro Acceleration and Multimode Acceleration
0.79 mV/μm (20 mV/mil),
3.94 mV/μm (100 mV/mil) or
7.87 mV/μm (200 mV/mil)
0.20 mV/μm (5 mV/mil),
0.22 mV/μm (5.6 mV/mil),
0.49 mV/μm (12.5 mV/mil) or
0.55 mV/μm (14 mV/mil)
20 mV/mm/s (508 mV/in/s)
3.94 mV/μm (100 mV/mil),
7.87 mV/μm (200 mV/mil) or
11.22 mV/μm (285 mV/mil)
1.02 mV/m/s2 (10 mV/g) or
2.55 mV/m/s2 (25 mV/g)
7.7 watts, typical
50 kΩ
10 kΩ for Prox/Accel
3.5 MΩ for Velomitor
Front Panel LEDs
OK LED Indicates when the 3500/46M Hydro
Monitoris operating properly
TX/RX LED
Bypass LED
Buffered Transducer Outputs
Output Impedance
Transducer Power Supply
Prox/Velom I/O and Multimode Prox/Velom I/O
Multimode Positive Input I/O
Recorder
Indicates when the 3500/46M Hydro Monitor is communicating with other modules in the 3500 Rack.
Indicates when the 3500/46M Hydro Monitor is in Bypass Mode.
The front of each monitor has one coaxial connector for each channel.
Each connector is short-circuit protected.
550 Ω
-23 Vdc nominal at 43 mA max
+23 Vdc nominal at 23 mA max
+4 to +20 mA. Output is proportional to monitor full­scale.
One output is provided for each channel.
3/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Monitor operation is unaffected by short circuits on recorder outputs.
Voltage Compliance (current output)
Resolution
0 to +12 Vdc range across load
Load resistance is 0 to 600 Ω.
0.3662 µA per bit ±0.25% error at room temperature
±0.7% error over temperature range
Update rate 100 ms or less
Signal Conditioning
Specified at +25 ºC (+77 ºF) unless otherwise noted.
Hydro and Multimode Hydro Radial Vibration
Frequency Response
Direct filter
Gap filter -3 dB at 0.05 Hz
0.104 Hz to 500 Hz
Rotor speed is 25 to 1,500 cpm.
Composite NX amplitude multiplied by the
percent change in gap from its zero position Specific for detecting Shear Pin failure
Accuracy
Direct and Gap
1X and NX Within ±0.33% of full-scale
Not 1X ±1% of full-scale typical
Composite ±1% of full-scale typical
Within ±0.33% of full-scale typical ±1% maximum
typical ±1% 1X maximum ±3% NX maximum
±3% maximum
Hydro Air Gap and Multimode Air Gap
Instantaneous Air Gap
Average Air Gap
Provides instantaneous gap measurements when the pole-passing rate slows to less than one pole/second
The monitor measures each pole gap and averages the values for all poles together over one revolution.
Not 1X filter 0.25 to 128 times rotor speed
Constant Q notch filter Minimum rejection in stopband of -50 dB
1X and NX vector filter
Constant Q Filter Minimum rejection in stopband of –50 dB
The N value in NX is selectable between 2 and 20 (for machine speeds of 25 cpm to 1,500cpm) or 2 to 50 (for machine speeds of 25 cpm to 600 cpm). 1X and NX vector, Not 1X and composite parameters are valid for machine speeds per selected NX value range.
Minimum Air Gap
Maximum Air Gap
Min Air Gap Pole Number
Max Air Gap Pole Number
4/16
The minimum pole gap value in a revolution
The maximum pole gap value in a revolution
The pole number detected with the minimum gap value in a revolution
The pole number detected with the maximum gap value in a revolution
All values except instantaneous Air Gap are valid when the poles passing rate is between 1 and 200 poles/second.
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Accuracy
Average Air Gap
Minimum Air Gap
Maximum Air Gap
Within ±0.33% of full scale typical ±1% maximum
Within ±0.33% of full scale typical ±1% maximum
Within ±0.33% of full scale typical ±1% maximum
Hydro Velocity and Multimode Hydro Velocity
Frequency Response
Bias
Direct Low Mode: 0.1875 to 343.75 Hz,
1X and 2X vector filter
Filter Quality
High-pass 4-pole (80 dB per decade, 24
Low-pass 2-pole (40 dB per decade,
Accuracy
Direct Within ±1% of full-scale
Low-pass filter
Low Mode: -3dB at 0.02 Hz High Mode: -3dB at 0.07 Hz
-3dB High Mode: 0. 75 to 1375 Hz, ­3dB
Constant Q Filter Minimum rejection in stopband of –51 dB
Low Mode: Valid for machine speeds of 60 to 6,000 cpm High Mode: Valid for machine speeds of 60 to 24,600 cpm
dB per octave)
12dB per octave)
typical ±2% maximum Exclusive of filters
1X Amplitude Within ±1% of full-scale
typical ±2% maximum Exclusive of filters
2X Amplitude Within ±1% of full-scale
typical ±2% maximum Exclusive of filters
Hydro Thrust and Multimode Thrust
Frequency Response
Direct filter -3dB at 1.2 Hz
Gap filter -3dB at 0.4 1 Hz
Accuracy
Direct Within ±0.33% of full-scale
typical ±1% maximum
Hydro Acceleration and Multimode Acceleration
Frequency Response
Bias filter Low-pass filter
-3dB at 0.01 Hz
Not OKfilter Low-pass filter
-3dB at 2400 Hz
1X and 2X vector filter
Filter Quality
High pass 4-pole (80 dB per decade,
Low pass 4-pole (80 dB per decade,
Constant Q Filter Minimum rejection in stopband of –51 dB Valid for machine speeds of 60 cpm to 60,000 cpm
See Frequency Ranges - Multimode Acceleration Channel on the next page.
24dB per octave)
24dB per octave)
5/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Direct Within ±0.33% of full scale
typical ±1% maximum Exclusive of filters
Direct Resultant
Pole Pass Resultant
±1% of full-scale typical ±2% maximum
±2% of full-scale typical ±3% maximum
1X Amplitude Within ±0.33% of full scale
typical ±1% maximum Exclusive of filters
2X Amplitude Within ±0.33% of full scale
typical ±1% maximum Exclusive of filters
Hydro Stator End Winding (SEW)
Frequency Response
Direct 5.0 Hz to 800 Hz (-3dB
corners)
Bias voltage DC to 0.05 Hz (-3dB)
Pole Pass Amplitude
Direct Resultant
Pole Pass Resultant
2x line frequency (100 Hz or 120 Hz) Constant Q filter (Q=20) Minimum rejection in stop band of -60 dB
5.0 Hz to 800 Hz (-3dB corners) Resultant of both X and Y axis inputs
2x line frequency (100 Hz or 120 Hz) Constant Q filter (Q=20) Minimum rejection in stop band of -60 dB Resultant of both X and Y axis inputs
Multimode Hydro Dynamic Pressure
Frequency Response
Low mode 0.1875 Hz to 343.7500 Hz
High mode 0.75 Hz to 1375.00 Hz
Filter Quality
High pass 4-pole
(80 dB per decade, 24 dB per octave)
Low pass 4-pole
(80 dB per decade, 24 dB per octave)
Accuracy
Peak Direct amplitud
RMS Direct amplitude
Static Pressure ±0.87% of Full Scale
±1% of Full Scale maximum
±2% of Full Scale maximum
maximum
Frequency Ranges - Multimode Acceleration Channel
The following table lists the frequency ranges for the monitor under different options using the Multimode Acceleration Channel type:
Accuracy
Direct ±1% of Full Scale maximum
Bias voltage ±1% of Full Scale maximum
Pole Pass Amplitude
±2% of full-scale typical ±3% maximum
Output Type
RMS 10 to 30,000 10 to 20,000
Peak 3 to 30,000 3 to 20,000
6/16
Non-Integrated
(Hz)
Integrated
(Hz)
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Physical
Monitor Module (Main Board)
Dimensions (Height x Width x Depth)
Weight
I/O Modules
Dimensions (Height x Width x Depth)
Weight 0.20 kg (0.44 lb)
241.3 mm x 24.4 mm x
241.8 mm (9.50 in x 0.96 in x 9.52 in)
0.91 kg (2.0 lb)
241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
Rack Space Requirements
Monitor Module
I/O Modules 1 full-height rear slot
1 full-height front slot
Alarms
Alarm setpoints
Use Rack Configuration Software to set alert levels for each value measured by the monitor and danger setpoints for any two of the values measured by the monitor.
Alarms are adjustable from 0 to 100% of full-scale for each measured value except when the full-scale range exceeds the range of the transducer. In this case, the range of the transducer will limit the setpoint.
Multimode Hydro RV
Hydro Air Gap and Multimode Air Gap
Hydro Velocity and Multimode Hydro Velocity
Hydro Thrust and Multimode Thrust
Hydro Acceleration and Multimode Acceleration
Hydro Stator End Winding (SEW)
Multimode Hydro Dynamic Pressure
NX Amplitude Composite 1X Phase Lag NX Phase Lag
Direct Gap Not 1X Amplitude 1X Amplitude NX Amplitude Composite 1X Phase Lag
Average Air Gap Minimum Air Gap
Direct 1X Amplitude 2X Amplitude 1X Phase Lag 2X Phase Lag
Direct Gap
Direct 1X Amplitude 2X Amplitude 1X Phase Lag 2X Phase Lag
Direct Pole Pass Amplitude Direct Resultant Pole Pass Resultant
Direct Static Pressure 1X Amplitude 2X Amplitude 1X Phase Lag 2X Phase Lag
Alarm accuracy
Hydro Radial Vibration
Within 0.13% of the desired value
Direct Gap Not 1X Amplitude 1X Amplitude
Alarm Time Delays
You can program alarm delays using
Rack Configuration Software.
Alert From 1 to 400 seconds in one
7/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
second intervals
Danger From 1 to 400 seconds in one
second intervals
Multimode channels
Standard channels
You can set delays for each measured value that has alarm set points.
You can set one alert and danger delay for the channel.
8/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
3500/46M Hydro Monitor Measured Variables
Measured variables are used to monitor the machine. The 3500/46M provides the following measured variables:
Hydro Radial Vibration
Multimode Hydro RV
Hydro Air Gap Average Air Gap
Multimode Air Gap
Direct Gap 1X Amplitude 1X Phase Lag NX Amplitude NX Phase Lag Not 1X Amplitude Composite Amplitude
Direct Gap 1X Amplitude 1X Phase Lag NX Amplitude Not 1X Amplitude Composite Amplitude Mode
Instantaneous Air Gap Minimum Air Gap Maximum Air Gap Minimum Air Gap Pole Number Maximum Air Gap Pole Number
Average Air Gap Instantaneous Air Gap Minimum Air Gap Maximum Air Gap Minimum Air Gap Pole Number Maximum Air Gap Pole Number Mode
Hydro Velocity Bias
1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag Mode
Hydro Thrust Direct
Gap
Multimode Thrust
Hydro Acceleration
Multimode Acceleration
Hydro Stator End Winding (SEW)
Multimode Hydro Dynamic Pressure
Direct Gap Mode
Direct Bias 1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag
Direct Bias 1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag Mode
Direct Bias Voltage Pole Pass Amplitude Direct Resultant Pole Pass Resultant
Direct Static Pressure 1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag Mode
Hydro Velocity Direct
Bias 1X Amplitude 1X Phase Lag 2X Amplitude 2X Phase Lag
Multimode Direct
9/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y

Compliance and Certifications

FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including interference that may cause undesired operation.
EMC
European Community Directive:
EMC Directive 2014/30/EU
Standards:
EN 61000-6-2 Immunity for
Industrial Environments
EN 61000-6-4 Emissions for
Industrial Environments
Electrical Safety
European Community Directive:
LV Directive 2014/35/EU

Hazardous Area Approvals

For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from Bently.com.
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, and D;  T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing 149243 or 149244.
ATEX/IECEx
II 3 G
Ex nA nC ic IIC T4 Gc Ex ec nC ic IIC T4/T5 Gc  T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F) When installed per drawing 149243 or 149244. 
Standards:
EN 61010-1
RoHS
European Community Directive:
RoHS Directive 2011/65/EU
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships, Offshore Units, and High Speed and Light Craft
10/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y

Ordering Considerations

The 3500/46M Hydro Monitor requires the following or later revisions of these firmware and software products:
Application
3500/46M
Firmware
Version
3500/01
Software
Version
3500/02
Software
Version
3500/03
Software
Hydro Radial Vibration 2.02 2.70 2.21 1.22
Hydro Air Gap 2.09 3.40 2.30 1.30
Hydro Velocity 2.10 3.70 2.50 1.50
Hydro Acceleration 2.40 4.40
Hydro Thrust 2.40 4.40
Multimode Hydro RV 2.40 3.80 2.51 1.51
Multimode Air Gap 2.40 3.80 2.51 1.51
Multimode Hydro Velocity 2.40 3.80 2.51 1.51
Multimode Thrust 2.40 3.80 2.51 1.51
Multimode Acceleration 2.40 3.80 2.51 1.51
Hydro Stator End Winding (SEW) 4.10 3.93 2.52 1.52
Multimode Hydro Dynamic Pressure 4.21 5.20
Version
Application
Multimode applications using hardware contacts to change monitor modes
Multimode applications using software commands to change monitor modes
Multimode applications incorporating the 3500/94 display
Applications requiring full multimode support from System 1 software
3500/46M
Hardware
Revision S Multimode
3500/22
Firmware
3500/92
Firmware
System
I/O Modules
1.32 1.16
1.60 2.30
1.32 6.0
1
11/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Other Requirements and Restrictions
A multimode recorder ET block must be used with an external termination multimode I/O module. To connect these components, you must use a signal cable, part number 129525. The ET block provides recorder outputs and mode inputs.
External Termination Blocks cannot be used with Internal Termination I/O Modules.
When ordering I/O modules with External Terminations, the External Termination Blocks and cables must be ordered separately.
12/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
125808-13 Multimode Recorder Output

Ordering Information

For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from Bently.com.
128702-01 Recorder External
and Mode Input External Termination Block Euro Style connectors
Termination Block Euro Style connectors
Hydro Monitor 3500/46 - AA-BB
A: I/O Module Type
01
02 Prox/Velom I/O Module with External
03 Multimode Prox/Velom I/O Module with
04 Multimode Prox/Velom I/O Module with
05 Multimode Positive Input I/O Module
06 Multimode Positive Input I/O Module
B: Hazardous Area Approval Option
00 None
Prox/Velom I/O Module with Internal Terminations
Terminations
Internal Terminations
External Terminations
with Internal Terminations
with External Terminations
128015-08
128015-11
128015-12 Multimode Positive Input
128015-13
128710-01
Prox/Velom External Termination Block Terminal Strip Connectors
Multimode Prox/Velom External Termination Block Terminal Strip connectors
External Termination Block Terminal Strip connectors
Multimode Recorder Output and Mode Input External Termination Block Terminal Strip connectors
Recorder External ET Block Terminal Strip connectors
Cables
3500 Transducer (XDCR) to External Termination (ET) Block Cable 129525 - AAAA-BB
01
02
CSA/NRTL/C (Class 1, Division 2)
ATEX/IECEx/CSA (Class 1, Zone 2)

External Termination Blocks

125808-08 Prox/Velom External
Termination Block Euro Style connectors
125808-11 Multimode Prox/Velom
External Termination Block Euro Style connectors
125808-12 Multimode Positive Input
External Termination Block Euro Style connectors
A: I/O Cable Length
0005
0007 7 feet (2.1 metres)
0010 10 feet (3.0 metres)
0025 25 feet (7.6 metres)
0050 50 feet (15.2 metres) 0100
B: Assembly Instructions
01 Not Assembled
02
13/16
5 feet (1.5 metres)
100 feet (30.5 metres)
Assembled
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
3500 Recorder Output to External Termination (ET) Block Cable (Non­Multimode) 129529 - AAAA-BB
A: I/O Cable Length
0005
0007 7 feet (2.1 metres)
0010 10 feet (3.0 metres)
0025 25 feet (7.6 metres)
0050 50 feet (15.2 metres) 0100
B: Assembly Instructions
01 Not Assembled 02 Assembled
5 feet (1.5 metres)
100 feet (30.5 metres)
Terminations
00561941 Prox/Velom and Multimode
Prox/Velom I/O Module ten-pin connector shunt
00580434 Euro Style connector header
8 pin For use on I/O modules with internal terminations
00580432 Euro Style connector header
10 pin For use on I/O modules with internal terminations
Spares
176449-06 3500/46M Hydro Monitor
144403-01 3500/46M Hydro Monitor User
Guide
140471-01 Prox/Velom I/O Module with
Internal Terminations
140482-01 Prox/Velom I/O Module with
External Terminations
169459-01 Multimode Prox/Velom I/O
Module with Internal Terminations
169459-02 Multimode Prox/Velom I/O
Module with External Terminations
169715-01 Multimode Positive Input I/O
Module with Internal Terminations
169715-02 Multimode Positive Input I/O
Module with External
14/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y

Graphs and Figures

1. Status LEDs 2. Buffered Transducer Outputs 3. Prox/Velom I/O Module with Internal Terminations 4. Prox/Velom I/O Module with External Terminations 5. Multimode Prox/Velom I/O Module with Internal
Terminations
6. Multimode Prox/Velom I/O Module with External
Terminations
7. Multimode Positive Input I/O Module with Internal
Terminations
8. Multimode Positive Input I/O Module with External
Terminations
Figure 1: Front and Rear Views of the 3500/46M Hydro Monitor
15/16
3500/46M Hydro Monitor Datasheet 144408 Rev. Y
Copyright 2020 Baker Hughes Company. All rights reserved.
Bently Nevada and Orbit Logo are registered trademarks of Bently Nevada, a Baker Hughes Business, in the United States and other countries. The Baker Hughes logo is a trademark of Baker Hughes Company. All other product and company names are trademarks of their respective holders. Use of the trademarks does not imply any affiliation with or endorsement by the respective holders.
Baker Hughes provides this information on an “as is” basis for general information purposes. Baker Hughes does not make any representation as to the accuracy or completeness of the information and makes no warranties of any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and fitness for a particular purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect, consequential or special damages, claims for lost profits, or third party claims arising from the use of the information, whether a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make changes in specifications and features shown herein, or discontinue the product described at any time without notice or obligation. Contact your Baker Hughes representative for the most current information.
The information contained in this document is the property of BakerHughes and its affiliates; and is subject to change without prior notice. It is being supplied as a service to our customers and may not be altered or its content repackaged without the express written consent of Baker Hughes. This product or associated products may be covered by one or more patents. See Bently.com/legal.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 or 1.800.227.5514 (US only)
Bently.com
16/16
Loading...